17 conditions · 5 needing a document upload
Financial Eligibility Criteria: (Ref: RB letter No. 2022/CE-I/CT/GCC- 2022/POLICY : Advance Correction Slip No.-1 dt 14.07.2022) The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-I, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
The intending tenderers should possess a valid electrical contractor license at the time of opening of tender, issued by any state government & same should be submitted along with tender documents by all bidders including working contractors of this unit otherwise offer shall be summarily rejected....... IT SHOULD BE NOTED BY THE TENDERER THAT ELECTRICAL LICENSE UNDER RENEWAL AT THE TIME OF TENDER OPENING WILL NOT BE CONSIDERED AND OFFER WILL BE SUMMARILY REJECTED. IT IS THE RESPONSIBILITY OF TENDERER TO UPLOAD VALID ELECTRICAL CONTRACTOR LICENSE ON THE DATE OF TENDER OPENING.
All requisite documents mentioned in clause 3.7 of the tender document attached pertaining to constitution of firm/concern. (As applicable).
36 conditions · 4 needing a document upload
The rate to be quoted by tenderer shall be inclusive of all state/central taxes including GST. THE TENDERER SHOULD UPLOAD VALID GST REGISTRATION CERTIFICATE ALONG WITH THE OFFER.
The tender shall comply with General Condition of contract (GCC),2022 of Indian Railways (file attached). and its latest amendment, if any. The tenderer shall submit the offer after duly satisfying himself/herself with the GCC,2022 in general.
Tenderers are required to upload the Bank details as per Annexure-XII (Real Time Gross Saving (RTGS)/National Electronic Fund Transfer (NEFT) Model Mandate Form)of tender document.
Tenderers are required to upload requisite details as per Annexure-VIIB (DETAILS OF CONTRACTUAL PAYMENT RECEIVED IN LAST THREE FINANCIAL YEARS AND CURRENT FINANCIAL YEAR) without which the offer is liable to be rejected.
Tenderers are compulsorily required to upload Affidavit as per Annexure-XXIV along with tender document, without which the offer will be considered incomplete and will be rejected summarily.
All requisite documents/credentials mentioned in clause 3.5 of the tender document attached pertaining to his/their technical and financial eligibility. (As applicable).
All requisite documents mentioned in clause 3.7 of the tender document attached pertaining to constitution of firm/concern. (As applicable).
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
No post tender correspondence for submission of additional documents shall be entertained after opening of the Technical & Commercial offers. Even suo-moto post tender letters of the tenderer/s shall be treated as Null & Void.
Defective parts shall only be replaced with OEM's spares. Proper invoices/delivery challan /warranty certificate etc. shall be provided by the firm to prove genuineness of spare parts.
This tender complies with Public Procurement Policy (Make in India) Order 2017, dated 15/06/2017, issued by Department of Industrial Promotion and Policy, Ministry of Commerce, circulated vide Railway Board letter no. 2015/RS(G)/779/5 dated 03/08/2017 and 27/12/2017.
IF ANY DISCREPANCY IS FOUND IN THE TENDER DOCUMENT, NAMELY SOR ITEM DESCRIPTION, SPECIAL TENDER CONDITION ETC., CLARIFICATION CAN BE SOUGHT FROM THE OFFICE OF SRDEE/G/DLI, DRM OFFICE, STATE ENTRY ROAD, NEW DELHI.
This tender complies with Railway Board instructions for Startups (recognized by Department of Industrial Policy and Promotion, Ministry of Commerce and Industry) for exemption from payment of Bid Security as detailed in GCC 2022 as amended from time to time. Such Startup firms may note that no other exemption is applicable to them in this particular tender.
On account payment, contractor shall submitted indemnity bond with validity up to the completion/extended period in the prescribed format (please refer Annexure-XXVIII) at the contractor's cost, vesting the ownership of such material with the railways.
This tender shall also complies with "Indian Railways Standard General Conditions of Contract, April 2022 (Advance Correction Slip No. 11)" vide Railway Board letter No. 2022/CE-I/CT/GCC- 2022/POLICY/Pt.I (E-3320424), dated:13.03.2026 (attached)
The issues not covered under the tender document shall be governed by General conditions of Contract (GCC) 2022 or its latest amendments if any during entire period of contract. If any contradiction in Tender Document and GCC is observed then GCC shall prevail.
All disputes or differences of any kind whatsoever arising out of or in connection with this contract, whether during its execution or after completion, termination, or breach thereof, shall be subject to the exclusive jurisdiction of the competent courts at New Delhi only.
Electrical work in connection with "Provision of booster pump with associated electrical work for watering facilities at TKJ in c/w train shifting from NDLS to TKJ station".
79-SRDEE-G-DLI-2026-27
79-SRDEE-G-DLI-2026-27
Open
Works - General
6 Months
Delhi, Delhi
₹0
₹1.2 L
10 Jun 2026
19 May 2026
27 May 2026
107 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 5931279.00 Below/P | ||
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of Pump & allied fittings Pump sets 40 HP. 1 set=3 Nos (Pump set of 40 HP each along with Electric motor)., total head-35 Mtrs, discharge-200 Cu.m/hr. Pump should be of standard manufacture such as M/s Kirloskar Brothers and Motors, M/s Crompton Greaves Limited or equivalent & as per explanatory note. | — | — | — | 8,08,704 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of Pump & allied fittings Common skid Mounting for pumps sets & as per explanatory note. | — | — | — | 57,294 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of Pump & allied fittings Basket type in Line strainer 200 mm. for pumps sets & as per explanatory note. | — | — | — | 69,870 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of Pump & allied fittings Suction manifold with fittings & fitment work & as per explanatory note. | — | — | — | 65,607 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of Pump & allied fittings Delivery manifold with fittings & fitment work & as per explanatory note. | — | — | — | 65,607 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of Pump & allied fittings Butter Fly valve 150 mm & as per explanatory note. | — | — | — | 15,946 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of Pump & allied fittings Non return valve 150 mm & as per explanatory note. | — | — | — | 14,237 | |
| — | 3.00 | — | — | ||
| Pump & allied fittings Flow meter 150 MB & as per explanatory note. | — | — | — | 5,43,309 | |
| — | 3.00 | — | — | ||
| Pump & allied fittings Electrical Operated valve 150 MB (Main Bore) with fittings 150 mm & as per explanatory note. | — | — | — | 5,43,309 | |
| — | 600.00 | — | — | ||
| Supply, fixing, testing and commissioning of Pump & allied fittings 1.5 Sq mm 6 core copper cable & as per explanatory note. | — | — | — | 40,800 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of Pump & allied fittings hydro pneumatic Tank & as per explanatory note. | — | — | — | 64,353 | |
| — | 150.00 | — | — | ||
| Supply, fixing, testing and commissioning of Pump & allied fittings Cable for pumps to panel 16 sq. mm copper 3.5 core & as per explanatory note. | — | — | — | 42,600 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of Electrical & Control Items Control panel inclusion of the following (i) to (ix) (i) Design, fabrication, transportation, supply, erection and commissioning of LT cubical panel 3 phase and neutral 415 V., 4 wire, free standing floor mounted, LT panel made up of 14 SWG CRCA (Cold Rolled Carbon Annealed) sheet after seven tank process and painting with EPOXY powder coating. The panel shall consist of suitable rating TPN (Triple Pole Neutral) tinned copper bus bar supported with DMC/AMC barriers and colour coded with heat shrinkable sleeves. The metering shall be provided as specified. The panel shall have short circuit with standing capacity of minimum 50 KA(RMS) power frequency test and consist of the switch gear as mentioned below. The panel shall be mounted on channels including supply and fixing as per specification. The complete work has to be carried out by the contractor including masonry work. After execution, all the feeder cables have to be connected to new panel with suitable cable glands as per the requirement of the Engineer at site. Air condition provision is to be made for entire control panel. The panel consists. (ii) 1 No. of 400 A., 4 Pole, 36 KA, MCCB (Molded case circuit Breaker) & 400 A Change over for incoming. (iii)4 No. of 100 A., 10 KA 4 Pole MCCB out going. (iv)1 No. of 36 A., 10 KA 4 pole MCB (Miniature Circuit Breaker) out going. (v)1 No. of 32 A., 10 KA 4 pole MCB out going. (vi)Along with multi functional digital meter similar to model No. EM-VIFPE of M/s HPL make with suitable ratio CTs (Current Transformer) along with selector switches, LED phase indication pilot lamps (3 No's), and tinned copper bus bar of 1000 V along with rubber chequered sheets of size 1 m x length of panel of 12 mm thick as per IS 5424-1 No., complete. (vii) Suitable set of capacitor 40 KVAR with auto manual APF Relay. (viii) VFD (Variable Frequency Drive) 1 No. PLC 1 No. HMI, with pressure treasures. (ix)Suitable 40 HP star delta starter with auto manual selection mode. And same starter will work on VFD and command will be to VFD by PLC (Programmed Logic Control) & as per explanatory note. | — | — | — | 13,66,823 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing & commissioning of 2 KVA on line UPS with battery 72 volt, 42AH should have input, output protection complete with trolley as per relevant IS/IEC standard & as per explanatory note. | — | — | — | 27,892 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of LT distribution board recessed mounting double door type made up of CRCA sheet sheet with anti corrosion treatment, IP 54 phosphatised powder painted complete with neutral link, earth point, Din rail and prewired confirming to IEC: 61439 or latest of make ABB, Siemens, L&T, Schneider, Legrand or equivalent with following items of matching make to be fixed in distribution board, confirming to IEC:60947 or latest, IE rules and site requirement. It should be rodent entry proof. It should also include well dressing and coding of circuit. 40A 2P RCBO 30/100 mA= 01 No. (Incoming) 6-32A MCB SP "C" Series =18 Nos. (Outgoing) It should be rodent entry proof. It should also include well dressing and coding of circuit IP2X terminal, reversible door with 180 degree opening, cement spill protection, detachable gland at top and bottom and short link for MCBs. It should also include proper tagging on electrical wires/cables which clearly indicate the incoming point or source and outgoing point of wires/cables & as per explanatory note. | — | — | — | 8,926 | |
| — | 2.00 | — | — | ||
| Design, Supply, fixing, testing and commissioning of front operated double door type weather proof feeder pillar body made of CRCA sheet sheet with anti corrosion treatment and suitable having IP 65 protection (MCCB - Incoming & MCCB - Outgoing) comprising with the following MCCB's fixed in it of make: Siemens, L&T, Schneider, Legrand or equivalent conforming to IEC 60947 or latest with digital measuring instrument & bus-bar arrangement and as per IS, IE rules and site requirement. It should be dust and vermin proof, conforming to IEC:60947 and powder coating as per latest relevant IS. 4P MCCB 630Amps on load change over switch (COS)= 01 No. (Incoming) 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release = 02 No. (outgoing) 4P MCCB 125Amps 36 kA with adjustable thermal & fixed magnetic release = 04 No. (outgoing) | — | — | — | 3,00,530 | |
| — | 100.00 | — | — | ||
| Supply and recessing/fixing of PVC conduit pipe of 25mm size conforming to IS:9537 Part-III:1987 (or Latest version) with accessories junction box, bends etc. including making chase, plastering/clamping etc. as per site requirement conforming to IS 9537 (Part 3) latest & as per explanatory Note. | — | — | — | 3,100 | |
| — | 200.00 | — | — | ||
| Supply, Fixing, testing & commissioning of following sizes FRLSH PVC insulated multi stranded copper (annealed) conductor single core cable conforming to IS 694 (or Latest Version), and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of point wiring / circuit wiring / sub main / main as required as per technical specification including connections, testing and commissioning & as per Explanatory Note. Size = 1x1.5 sq.mm. | — | — | — | 4,800 | |
| — | 200.00 | — | — | ||
| Supply, Fixing, testing & commissioning of following sizes FRLSH PVC insulated multi stranded copper (annealed) conductor single core cable conforming to IS 694 (or Latest Version), and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of point wiring / circuit wiring / sub main / main as required as per technical specification including connections, testing and commissioning & as per Explanatory Note. Size = 1x2.5 sq.mm | — | — | — | 8,000 | |
| — | 100.00 | — | — | ||
| Supply, Fixing, testing & commissioning of following sizes FRLSH PVC insulated multi stranded copper (annealed) conductor single core cable conforming to IS 694 (or Latest Version), and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of point wiring / circuit wiring / sub main / main as required as per technical specification including connections, testing and commissioning & as per Explanatory Note. Size = 1x4.0 sq.mm | — | — | — | 5,300 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of following modules, GI box alongwith modular base and cover plate for modular switches/ sockets in recess etc as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per Explanatory Note. Size= 6 Module | — | — | — | 100 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of following modules, GI box alongwith modular base and cover plate for modular switches/ sockets in recess etc as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per Explanatory Note. Size= 08 module | — | — | — | 126 | |
| — | 20.00 | — | — | ||
| Supply, fixing, testing and commissioning of 6A modular type switch complete including connections etc. as required as per IS, IE rules and site requirement and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per explanatory Note. | — | — | — | 1,080 | |
| — | 5.00 | — | — | ||
| Supply, fixing, testing and commissioning of 16A modular type switch complete including connections etc. as required as per IS, IE rules and site requirement and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per explanatory Note. | — | — | — | 445 | |
| — | 5.00 | — | — | ||
| Supply, fixing, testing and commissioning of modular type socket 5/15A multi pin complete including connections etc. as required as per IS, IE rules and site requirement and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per explanatory Note. | — | — | — | 655 | |
| — | 5.00 | — | — | ||
| Supply, fixing, testing and commissioning of modular type 3 pin socket 5/6A complete including connections etc. as required as per IS, IE rules and site requirement and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per explanatory Note. | — | — | — | 495 | |
| — | 4.00 | — | — | ||
| Supply, fixing, testing and commissioning of 4-feet long surface mounting 36-40watt, 5700K,CRI>80, LED Luminaire as per CEE/NR's spec. No. CEE/NR/121 Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121 Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest, IS, IE rules and site requirement. Fitting shall be environmentally friendly, long life, corrosion resistant, impact proof IP 66 with PC housing & opal finish cover suitable for wet location similar to Make - Havells Model No. MAGNUM NEO or equivalent. Fitting shall be suitable for operation on single phase 240Volt, 50 Hz AC supply complete & as per explanatory Note. | — | — | — | 12,400 | |
| — | 2.00 | — | — | ||
| Supply, fixing, testing and commissioning of 45-50 watt LED based street light luminary with cool white light, pressure die cast aluminum housing, IP 66 or better having system complete confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 5,930 | |
| — | 2.00 | — | — | ||
| Supply, fixing, testing and commissioning of 380mm sweep, 1400 rpm (approx) propeller type exhaust fan complete in all respect as specification and as per site requirement, including grouting of nut, bolts, washer and with the suitable fasteners conforming to IS 2312 & IS 302 or latest and other relevant IS/IEC standards. Make Bajaj, Usha, Havells, Orient or equivalent and as per explanatory note | — | — | — | 5,548 | |
| — | 2.00 | — | — | ||
| Supply, fixing, testing and commissioning of 400 mm sweep wall mounted fan complete conforming to relevant IS/IEC standards & as per Explanatory Note. | — | — | — | 4,482 | |
| — | 2.00 | — | — | ||
| Supply, fixing, testing and commissioning of 25A/32A, 30mA DP RCCB AC type confirming to IS12640-1 & IEC 61008-1 with 10KA short circuit with stand capacity complete with enclosure conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 & as per Explanatory Note. | — | — | — | 5,530 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of Float type mercury level switch with 12 mtr cable for On/Off as per level and as per IS & IE rule & as per explanatory note. | — | — | — | 2,263 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning of suction and delivery transducers fittings with pressure gauge as per site requirement and as per IS & IE rule & as per explanatory note. | — | — | — | 27,829 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing, commissioning of control panel for electrically operated through GSM based/ mobile for 4 or 5 nos. of valves with auto manual selection valve and as per site requirement. SIM to be supplied by Indian Railway along with Recharge & as per explanatory note. | — | — | — | 2,29,750 | |
| — | 1.00 | — | — | ||
| Supply of one computer table, two chairs and one steel almirah size 1500 x 900 x 600 mm. (One set = one table + 02 chairs + one almirah) & as per explanatory note. | — | — | — | 39,265 | |
| — | 100.00 | — | — | ||
| Supply, fixing and commissioning of 3 core flat PVC insulation and sheathed with multistrand flexible copper conductor 1100 volts suitable for submersible pump (for maximum conductor temperature 70 deg. C to 85 deg. C approx, water proof, confirming to IS-694 latest as per IS/IE rules and site requirement) & as per explanatory note. Make: Finolex, Havells, Polycab, KEI or equivalent. 3Cx6 sqmm | — | — | — | 14,700 | |
| — | 2.00 | — | — | ||
| Supply, fixing, testing and commissioning of Elbow of following size, 100 mm & as per explanatory note. | — | — | — | 980 | |
| — | 2.00 | — | — | ||
| Supply, Fixing, Testing and Commissioning of GI nipple of 1' long of the size 100mm & as per explanatory note. | — | — | — | 1,372 | |
| — | 2.00 | — | — | ||
| Supply, Fixing, Testing and Commissioning of MS Flange of size 4" suitable for 100 mm NRV & Gateway complete & as per explanatory note. | — | — | — | 784 | |
| — | 2.00 | — | — | ||
| Supply, fixing, testing and commissioning of CI NRV of make Zoloto, Kartar, Karan or equivalent as per site requirement of following size 100 mm | — | — | — | 16,660 | |
| — | 2.00 | — | — | ||
| Supply, fixing, testing and commissioning of ISI marked water cooled vertical type monoblock submersible pumps of capacity 20 HP, 2 stage, 1450 LPM, 42 meter head, SS impellar and copper rotar and sutaible size ISI marked cable & as per explanatory note, Make Falcon, KSB, Crompton, Kirloskar or equivalent. | — | — | — | 1,52,116 | |
| — | 2.00 | — | — | ||
| Supply & testing of ISI marked water cooled vertical type monoblock submersible pumps of capacity 20 HP, 2 stage, 1450 LPM, 42 meter head, SS impellar and copper rotar and suitable size ISI marked cable & as per explanatory note, Make Falcon, KSB, Crompton, Kirloskar or equivalent. | — | — | — | 1,45,078 | |
| — | 2.00 | — | — | ||
| Supply, fixing, testing and Commissioning of 20 HP fully automatic star-delta starter for submersible pump with overload current range 20-32amp, with single phase protection, Dry run, over voltage and under voltage, phase reversal. Make L&T MUG 20H with IADSM, Subtech, Havells, Rockwell or equivalent with all accessories and site requirement conforming to relevant IS/IEC standard & as per explanatory note. | — | — | — | 32,054 | |
| — | 2.00 | — | — | ||
| Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 or latest fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1400mm, service value >= 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) conforming to CPWD DSR(E&M) 2025 & as per Explanatory Note. | — | — | — | 5,474 | |
| — | 600.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation((upto 75-100 cm depth and not less than 35 cm wide ), sand cushioning, protective covering and refilling the trench etc. as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest & as per explanatory Note. Above 35 sq. mm and upto 95 sq. mm | — | — | — | 2,52,600 | |
| — | 1200.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation((upto 75-100 cm depth and not less than 35 cm wide ), sand cushioning, protective covering and refilling the trench etc. as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest & as per explanatory Note. Above 95 sq. mm and upto 185 sq. mm | — | — | — | 5,60,400 | |
| — | 200.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation(upto 75-100 cm depth and not less than 55 cm wide & maintaining gap not less than 20 cm between the cables), sand cushioning, protective covering and refilling the trench etc as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest and explanatory note. Above 35 sq. mm and upto 95 sq. mm | — | — | — | 62,200 | |
| — | 400.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation(upto 75-100 cm depth and not less than 55 cm wide & maintaining gap not less than 20 cm between the cables), sand cushioning, protective covering and refilling the trench etc as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest and explanatory note. Above 95 sq. mm and upto 185 sq. mm | — | — | — | 1,32,400 | |
| — | 200.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative conforming to IS 1255 (Reviewed in 2016) or latest & as per explanatory Note. Above 35 sq. mm and upto 95 sq.mm (clamped with 25x3mm MS flat clamp) | — | — | — | 28,200 | |
| — | 400.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative conforming to IS 1255 (Reviewed in 2016) or latest & as per explanatory Note. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) | — | — | — | 66,400 | |
| — | 6.00 | — | — | ||
| Earthing with 40 mm dia GI pipe class 'B' 4.5 meter long earth electrode as per IS:3043 (latest version)to achieve earth resistance less than 5 ohms including construction of masonry enclosures with hinged cover plate of cast iron with locking arrangement (approx. size 400 mmx 400 mm) on top, provision of earth plate, connections from earth electrode to switch gear/pole as per drawing & as per explanatory Note. | — | — | — | 34,506 | |
| — | 30.00 | — | — | ||
| Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required as per IS:3043 (Latest version) and as per explanatory Note | — | — | — | 1,650 | |
| — | 200.00 | — | — | ||
| Supplying and laying 25 mm X 5 mm G.I strip confirming to relevant IS as per IS:3043 (Latest version), fixing on surface or as per site condition, clamping or fixing with suitable arrangement as per site requirement, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm) & as per explanatory Note. | — | — | — | 30,800 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC-2022-ACS10_merged.pdf
ATTACHMENT
TECHSPEC-IRev.3.pdf
ATTACHMENT
TECHSPEC-IIRev.4.pdf
ATTACHMENT
GCCAdvanceCorrectionSlipNo-11.pdf
ATTACHMENT
ExplanatoryNote-79.pdf
ATTACHMENT
TenderDocument-79.pdf
ATTACHMENT
ModifiedSpecialConditionsofContract.pdf SPECIAL CONDITIONS
ATTACHMENT
ModifiedSpecialConditionsofContract.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .