Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.4 LAccepted-Finance | L1 | Accepted-Finance ACCEPTED BEING L1 | |
| 2 | L2₹20.2 L+₹1.8 L (9.72%)Rejected-Finance | L2 | Rejected-Finance REJECTED BEING L2 | |
| 3 | L3₹21.8 L+₹3.4 L (18.4%)Rejected-Finance | L3 | Rejected-Finance REJECTED BEING L3 | |
| 4 | L4₹23.2 L+₹4.8 L (25.9%)Rejected-Finance H 13 GEETANJALI PARK WEST SAGARPUR NEW DELHI 110046 | NEW DELHI | DELHI | 110046 | L4 | Rejected-Finance REJECTED BEING L4 |
Tender Value
₹42.5 L
EMD Value
₹85,000
Closing Date
3 Mar 2020, 6:00 pmClosed
GE AF SUBROTO PARK
GE AF SUBROTO PARK
REPAIR MAINT AND REPLACEMENT OF LT DISTRIBUTION ELECT SUPPLY UG CABELS LT PANEL BOARDS MCCBS SECURITY LIGHTS STREET LIGHTS GATE LIGHTS HIGH MAST LIGHTS LIGHTENING CONDUCTORS EARTHING AND MAINT OF DG SETS AMF PANEL AND OTHER MISC EM ITEMS
2020_MES_322484_1
GE/SP/TOKEN-70/2019-20
Open Tender
Electrical and Maintenance Works
Works
270 days
GE AF SUBROTO PARK
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
Yes
GE AF SUBROTO PARK
₹85,000
Yes
6 Mar 2020
6 Feb 2020
4 Mar 2020
7 Feb 2020
3 Mar 2020
19 Feb 2020
7 Feb 2020 - 18 Feb 2020
Amount
Excavating in trenches not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out in soft / loose soil including forming of bottom for laying cable complete all as specified and as directed by Engineer-in-Charge.
All as per item No. 1 above but not exceeding 1.5 mtr wide and exc 1.5 mtr depth and not exc 3.0 Mtr depth complete all as specified and as directed by Engineer-in-Charge.
Excavation in hard and dense soil Iincluding Road cutting etc not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out including forming of bottom for laying cable complete all as specified and as directed by Engineer-in-Charge.
Returning filling soft & loose/hard & dense soil including spreading levelling, watering and well ramming in layers n exc 25 cms complete all as specified and as directed by Engineer-in-Charge.
Removal of excavated material n.exc 50 mtrs and depositing where directed at a level n.exc 1.5 mtrs above the starting point complete all as specified and as directed by Engineer-in-Charge.
Supply and fix in replacement on-load changeover switch 415 V, 4 pole,250 A. open execution complete all as specified and as directed by Engineer-in-Charge. Make : Havells / L&T / Legrand
Supply and fix in replacement on-load changeover switch 415 V, 4 pole, open execution , 320 A complete all as specified and as directed by Engineer-in-Charge. Make : Havells / L&T / Legrand
Supply and fix in replacement on-load changeover switch 415 V, 4 pole, open execution 400 A complete all as specified and as directed by Engineer-in-Charge. Make : Havells / L&T / Legrand
Supply and install in repair integral LED aviation light comprising of aluminium housing with polycarbonate enclosure, 302 Nos. LEDs complete including necessary fixing arrangement, installed on top of hangars/OH tanks etc. complete all as specified and as directed by Engineer-in-Charge. Make : BAJAJ / PHILIPS / CG
Supply and fix in replacement MCCB, 415 volts, 3 pole adjustable thermal setting type 16 KA, 63 Amps complete all as specified and as directed by Engineer-in-Charge. Make : Havells / L&T / Legrand
Supply and fix in replacement MCCB, 415 volts, 3 pole adjustable thermal setting type 25 KA, 100 Amps complete all as specified and as directed by Engineer-in-Charge. Make : Havells / L&T / Legrand
Supply and fix in replacement MCCB, 415 volts, 3 pole adjustable thermal setting type 25 KA, 125 Amps complete all as specified and as directed by Engineer-in-Charge. Make : Havells / L&T / Legrand
Supply and fix in replacement MCCB, 415 volts, 3 pole adjustable thermal setting type 25 KA, 160 Amps complete all as specified and as directed by Engineer-in-Charge. Make : Havells / L&T / Legrand
Supply and fix in replacement MCCB ,3 pole,415V,36KA, 200 Amps with adjustable thermal setting complete all as specified and as directed by Engineer-in-Charge. Make : Havells / L&T / Legrand
Supply and fix in replacement MCCB ,3 pole,415V,36KA,250 Amps with adjustable thermal setting.250 complete all as specified and as directed by Engineer-in-Charge. Make : Havells / L&T / Legrand
Supply and fix in replacement MCCB ,3 pole,415V,36KA,315 Amps with adjustable thermal setting complete all as specified and as directed by Engineer-in-Charge. Make : Havells / L&T / Legrand
Supply and fix in replacement MCCB ,3 pole,415V,50KA,400 Amps with adjustable thermal setting complete all as specified and as directed by Engineer-in-Charge. Make : Havells / L&T / Legrand
Supply and jointing Straight through joint epoxy type for LT cable PVC/XLPE insulated armoured aluminium conductor of sizes up to 16 sqmm 3.5/4 core ,1100 volts grade complete with jointing kit complete all as specified and as directed by Engineer-in-Charge. Make: 3 M / Denson / yamuna
Supply and jointing Straight through joint epoxy type for LT cable PVC/XLPE insulated armoured aluminium conductor of sizes from 25 sqmm 3.5/4 core to 50 Sq mm x 3.5 core,1100 volts grade complete with jointing kit. Make : 3 M / Denson / yamuna
Supply and jointing Straight through joint epoxy type for LT cable PVC/XLPE insulated armoured aluminium conductor of sizes from 70 sqmm 3.5 core to 120 Sq mm x 3.5 core,1100 volts grade complete with jointing kit complete all as specified and as directed by Engineer-in-Charge. Make: 3 M / Denson / yamuna
Supply and jointing Straight through joint epoxy type for LT cable PVC/XLPE insulated armoured aluminium conductor of sizes from 150 sqmm 3.5 core to 185 Sq mm x 3.5 core,1100 volts grade complete with jointing kit complete all as specified and as directed by Engineer-in-Charge. Make : 3 M / Denson / yamuna.
Supply and jointing Straight through joint epoxy type for LT cable PVC/XLPE insulated armoured aluminium conductor of size 240 sqmm 3.5 core to 300 sqmm 3.5 core 1100 volts grade complete with jointing kit complete all as specified and as directed by Engineer-in-Charge. Make : 3 M / Denson / yamuna
Supply and jointing Straight through joint epoxy type for LT cable PVC/XLPE insulated armoured aluminium conductor of size 400 sqmm 3.5 core to 500 sqmm 3.5 core 1100 volts grade complete with jointing kit complete all as specified and as directed by Engineer-in-Charge. Make : 3 M / Denson / yamuna
Supplying and laying in repairs (in trenches / duct / fixing to pole / wall or in such similar position ) GI tubing medium grade for cable protection of following sizes : Make : Bansal / TATA / Jindal Note : Excavation & earthwork shall be measured and paid seperately under respective item of BOQ.
80 mm dia
50 mm dia
40 mm dia
Supply & fix in replacement aluminium strip 25x3.15mm with saddles and fixing screws etc.for roof conductors and down conductors above ground complete all as specified and as directed by Engineer-in-Charge.
Supply & fix in replacement galvanised iron strip 32 x 6 mm burried in ground all as specified and directed.
Supply & fix in replacement air termination single pointed aluminium rod 12mm dia and 300mm long all as specified and directed.
Supply & fix in replacement test point terminal block made of gun metal or phosphorous bronze size 75x75x25mm drilled and screwed includind 3 nos 8mm dia 25mm long hex.head screw complete all as specified and as directed by Engineer-in-Charge.
Taking up or down LT UG cables from trench/poles/wall etc of following size complete all as specified and as directed by Engineer-in-Charge.
10 Sqmm 2 core
10 Sqmm 4 core
16 Sqmm 4 core
25 Sqmm 3.5 core
35 Sqmm 3.5 core
50 Sqmm 3.5 core
95 Sqmm 3.5 core
120 Sqmm 3.5 core
185 Sqmm 3.5 core
240 Sqmm 3.5 core
300 Sqmm 3.5 core
Supply and lay UG cable XLPE insulated armoured and PVC sheathed LT 1100 volts grade with aluminium conductor stranded of sizes : Make : Havells / polycab / Gloster / Bharath electrical cables
10 Sqmm 2 core
10 Sqmm 4 core
16 Sqmm 4 core
25 Sqmm 3.5 core
35 Sqmm 3.5 core
50 Sqmm 3.5 core
95 Sqmm 3.5 core
120 Sqmm 3.5 core
185 Sqmm 3.5 core
240 Sqmm 3.5 core
300 Sqmm 3.5 core Note of BOQ item No. 29 & 30: - (i) Excavation and earth work shall be measured and paid seperately under respective item of BOQ. (ii) Sand cushioning and brick protection shall be measured and paid seperately under respective item of BOQ
M&L for Sand cushioning of cables provided with a layer of sand 8 cm deep before laying the cable and provide 15 cm depth after laying of cable. This is then gently punned down to a depeth of 10 cm complete all as specified and as directed by Engineer-in-Charge.
Supply and laying well burnt sub class ‘B’ bricks old size as mechanical protection to under ground cables laying across the cable complete all as specified and as directed by Engineer-in-Charge.
M & L for earthing complete with GI earth electride of size 60cmx60cmx6mm buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level wuith top edge of earth plate at a depth not less than 1.5 metre below normal ground surrounded from all sides by 15cm thick and packed layer of charcoal dust and conmmon salt filling in alternate layers cleaned connected to and including GI earth strip 32 x 6mm size upto 7.5 mtr by means of bolts, nuts, check nuts and washers made of galvanised iron and protected light grade 50mm dia 5 mtr long GI pipe connected to main control board and GI pipe light grade 20mm bore for watering and including funnel wire mesh, RCC pit cover 50mm thick with 10mm dia reinforcement 100mm c/c and PCC chamber pit with pcc 1:2:4 Type C2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 metre) and testing after completion all as specified and shown on plate No 3 of SSR Part -I 2009
Material and labour for earthing complete with galvanised iron plate 60x60 cm x 6 mm thick electrode buried directly in ground (earth pit no less than 2.25 Mtrs deep below ground level) with top edge of the plate not less than 1.5 Mtrs below normal ground level connected to glavnasied earth strip of size 25X4 mm mm dia by means of bolts, nuts, check nuts and washers all as shown in electrical plate no. 5 connected to earth test point and provn of GI pipe 20 mm dia medium grade for watering, GI pipe 40 mm dia light grade for earth strip protection all as specified and including excavation, earth work provn of earth pit, pit cover, CI funnel, wire mesh etc complete all as specified and as directed by Engineer-in-Charge.
M&L for taking down serviceable/ unserviceable street/ security /Flood lights/gate lights/ high mast lights of any type/size/rating including GI pipe bracket from the existing pole/ wall of road / building stacking at site here-in-before duly repaired including replacement of unserviceable spares / parts and refixing in the original position all as specified and directed by Engineer-in-Charge. Note :- All the unserviceable spares/parts shall be measured and paid separately as supply only under respective items of this Schedule here-in-after.
Supply & fixing in replacement SSL Neo Solar street light fitting with in built SCC suitable for LED type 28 to 36 Watts Capacity Lumen 2520 System voltage 12 V Solar charge controller PWM including necessary electrical connection aerodynamically designed with better thermal management complete fittings fixed on wall/pole up to 11 mtr hight complete all as specified and as directed by Engr-in-Charge. Make:- Havells / Cat part No : LHKTBJU7PA6J028 or equivalent Philips / Luker
Supply only in replacement of LED driver up to 48 Watt for street light/flood light/high bay/ security light/ gate light/ high mast light/ post top light all as specified and directed. Make : Philips / Havells / CG
Supply only in replacement of LED driver 60 to 72 Watt for street light/flood light/high bay/ security light/ gate light/ high mast light/ post top light al as specified and directed. Make : Philips / Havells / CG
Supply only in replacement of LED driver 100 to 150 Watt for street light/flood light/high bay/ security light/ gate light/ high mast light/ post top light al as specified and directed. Make : Philips / Havells / CG
Supply and fix in replacement Surge protection device (SPDs) for street light/flood light fixing in before place driver in street light surger protection rating up to 2 KV all as specified and directed : Make ; Philips/bajaj/ Havells
Supply & fixing in replacement GI bracket for fixing street/ security light fitting made out of GI pipe medium grade 50 mm dia 1.50 Mtr long bent to required angle/ shape complete with MS flat iron clamp of size 50x5 mm, nut, bolt, washer of suitable size as per site requirement etc and fixed on pole/wall including two coats of aiuminium paint over a coat of redoxide primer to MS clamps , nut ,bolts etc complete all as specified and directed by Engineer-in-Charge.
Supply & fixing in replacement GI bracket for fixing street/ security light fitting made out of GI pipe medium grade 40 mm dia 1.50 Mtr long bent to required angle/ shape complete with MS flat iron clamp of size 50x5 mm, nut, bolt, washer of suitable size as per site requirement etc and fixed on pole/wall including two coats of aiuminium paint over a coat of redoxide primer to MS clamps , nut ,bolts etc complete all as specified and directed by Engineer-in-Charge.
Supply & fixing in replacement GI bracket for fixing street/ security light fitting made out of GI pipe medium grade 25 mm dia 1.50 Mtr long bent to required angle/ shape complete with MS flat iron clamp of size 50x5 mm, nut, bolt, washer of suitable size as per site requirement etc and fixed on pole/wall including two coats of aiuminium paint over a coat of redoxide primer to MS clamps , nut ,bolts etc complete all as specified and directed by Engineer-in-Charge.
Dismantling unserviceable/damaged street light steel tubuler / RCC pole of any type/size for replacement all as specified and directed by Engineer-in-Charge. ( Excavation/earth work etc shall be measured and paid for separately under respective item of this Schedule)
Supply & fixing in replacement Steel tubuler swaged Poles complete with cast iron base plate,finial taper plug,bolts,nuts & screws as specified type SP-31 (9.0 Mtrs long) with single curve at the top for fixing of street light fitting all as specified and directed by Engineer-in-charge.
Supply & fixing in replacement of FRP boxes with 4 connectors heavy duty, and clamps made out of FI 32 x 6mm and GI nuts, bolts , busbar chamber size 30x20 cm including provn of Aluminium Busbar SPN 20 Amps capacity fixed on porcelain insulator, 01 No MCB SP 6 Amps Capacity complete all as specified and directed by Engineer-in-Charge. Make : Sintex model GSJB-3020 / HAVELLS / STANDARD
S & F integrated model 3 phase timer switch with enclosure 12 KW 40 Amps phase including incoming and out going MCBs, power contactors, and complete 3 phase circuits for controlling of security light fitting with proper connection and testing schedule operation all as directed. Make : sintex or L&T / Havells / IndoAsian
S & F in replacement for two single core PVC insulated unsheathed , 1100 Volts grade, copper cable 1.5 sqmm multistranded conductor and drawn through and including rigid PVC non metalic surface conduit of suitable size but not less than 20mm dia with conduit accessories etc. including continuous earth wire PVC insulated unsheathed 1100 volts grade, cable 1.5sqmm copper conductor fixed to poles with saddles and screws and all as specified and as directed by Engr-in-Charge. Note : One run of PVC conduit, two runs of cable1.5 sqmm and one run of earth wire 1.5sqmm shall be measured and paid as one unit.
Supply and fix in replacement of Street light fitting LED type, 60 Watts 240 Volts luminous energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection and impact resistance of IK07 with 10KV Built-in Surge Protection Device., mounted on wall/pole/building,connection complete all as specified and as directed Make : Havells cat part No : ENDURA PEARLPLUSSL60WLED757SASYTOPC or equivalent of / Philips / CG
Supply and fix in replacement of Street light fitting LED type, 70 Watts 240 Volts luminous energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection and impact resistance of IK07 with 10KV Built-in Surge Protection Device., mounted on wall/pole/building,connection complete all as specified and as directed Make : Havells cat part No: ENDURA PEARLPLUSSL70WLED757SASYTOPC or equivalent of / Philips / CG
Supply and fix in replacement of Street light fitting LED type, 90 Watts 240 Volts luminous energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection and impact resistance of IK07 with 10KV Built-in Surge Protection Device., mounted on wall/pole/building,connection complete all as specified and as directed Make : Havells cat part No: ENDURA PEARLPLUSSL90WLED757SASYTOPC or equivalent of / Philips / CG
Supply and fix in replacement of smart bright Flood light fitting LED type, 100 Watts 240 Volts luminous Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP66 flood light fixing on pole/wall of any hight suitable for highlighting architectural facade and general purpose lighting.connection complete including taking down old unserviceable light fitting all as specified and as directed Make : Havells Cat part No: ETAIRISFLS 100WLED757ASYMLT G or equivalent of Philips / CG
Supply and fix in replacement of high bay light fitting LED type, 100 Watts 240 Volts luminous shall be more than >80 lumen/watt lumen, efficiency not less than 100 lm/Watt , Energy saving, environment friendly & robust Highbay/Mediumbay LED IP65 luminaire with high efficacy mounting on pole/wall/ roof including connection complete including taking down old unserviceable light fitting all as specified and as directed Make : Havells cat part No : SAUCERNEOP100WLED75790DLT G or equivalent of Philips / CG
Supply and fix in replacement of high mast light fitting LED type, 180 Watts 240 Volts Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium non integral IP66 flood light, suitable for high mast application, highlighting architectural facade and general purpose lighting. mounting on pole/wall/ roof on any hight including connection complete including taking down old unserviceable light fitting all as specified and as directed Make : Havells cat part No : JETA VALOURFLS180WLED757MODSYMLT G or equivalent of Philips / CG
S& fix energy efficient pedestal light/bollard light 8 watt fitting on wall/gate high quality Cone series acts as a imposing street furniture.The elegant yet minimalsitic design acts a silent observer and giving light, diffuser at the upper portion acts a beacon of path guidance in a landsacpe environment. LED bulb , clamps, nut and bolts mounting acessories etc all as specified and directed. Make : Havells Cat Part No: CONEBL8WLED857SSYMTOPC or Philips / CG
S& fix energy efficient post top light 25 Watt New generation, post-top, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source.. including all necessary wiring LED bulb , clamps, nut and bolts mounting acessories etc all as specified and directed. Make : Havells Cat Part No:CORALPT25WLED757PSYMTOPC or Equivalent of CG / Philips
S& fix energy efficient post top light 135 Watt Endura Spring 6 New generation, post-top, energy saving, environmental friendly, long life aesthetically designed with good indirect symmetrical light distribution, die-cast aluminium landscape IP65 luminaire with high power COB LED as light source. including all necessary wiring LED bulb , clamps, nut and bolts mounting acessories etc all as specified and directed. Make : Havells Cat Part No:ENDURASPRING6PT35WLED740PSYMTOTG or Equivalent of CG / Philips
S& fix energy efficient post top light 135 Watt Victoria - IP65 Design from the renaissance era yet with a modern look using new generation technology in LED to enliven your outdoor areas in perfect synchronisation with functionality and aesthetics. Family of post top lantern designed to complement the geometry of the area. including all necessary wiring LED bulb , clamps, nut and bolts mounting acessories etc all as specified and directed. Make : Havells Cat Part No:VICTORIAPT35WLED730PSYMTOTG or Equivalent of CG / Philips
M&L for painting of steel tubular 9 mtr long poles but for 7.5 mtr above the ground after preparing old paint surfaces with two coat of Aluminium paint and two coats of zebra marking with enamel paint of approved make from ground level & upto 1 mtr high including white washing the coping including numbering and painting the pole terminal box all as directed by Engineer - in - Charge. Note : (i) PCC coping shall be painted with cement based white colour snowcem. (ii) Marking of pole No. shall be with black colour on yellow rectangular surface of minimum 150 mm x100 mm. (iii) Radium based reflector tape of yellow colour 50mm wide in three nos of circles above 1.5 mtr height on pole shall be provided.
Same as item No 59 above but RCC poles 7.5 mtr long with two coats of exterior emulsion paint of approved make all as directed by Engineer - in - Charge.
Supply and fix in replacement of MCB SPN 6 Amps,240V, 10KA rupturing capacity complete all as specified and as directed by Engineer-in-Charge. Make: L&T / C&S / Legrand
Dfismantling old unserviceable LT panel and design, Supply, installing testing and commissioning factory fabricated outdoor type totally enclosed LT cubical panel board suitable size with aluminum bus bar of suitable current rating, conforming to relevant IS and protection class IP-65 ,dust, vermin and weather proof fabricated out of 3.15mm thick CRCA sheet duly powder coated ,mounted on 50x50x6mm MS angle iron frame, duly welded in shape including necessary grouting of legs 300mm deep in ground in PCC 1:4:8 type D2 using 20mm graded stone aggregate ,panel base to be 500mm above ground level with suitable compartments for controls and Monitors including cable glands for incoming and outgoing cables, locking arrangement, including accommodating, supply and fixing the following accessories/items including necessary internal panel wiring with suitable size of Copper wire PVC insulated & sheathed multi stranded complete all as specified and as directed by Engr-in-charge. including Supply and fixing the following:- a) MCCB, 415 volts, 4 pole adjustable thermal setting type 36 KA, 250 Amps - 01 No (in Coming) Make: Havells/L&T/Legrand.
b) MCCB, 415 volts, 4 pole adjustable thermal setting type 25 KA, 100 Amps - 02 Nos (Out going) Make: Havells/L&T/Legrand. c) MCCB, 415 volts, 4 pole adjustable thermal setting type 25 KA, 63 Amps - 02No (Out Going) Make: Havells/L&T/Legrand. d) Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable. (d) Interconnection of MCCBs with aluminium bus bar and with suitable size PVC insulated, unsheathed , multi stranded copper conductor cable, 1100 volts grade. h) Indicators RYB , LED type - set of three. J) Digital Volt meter & ameter - 01 set Make : L&T.
Cutting and trimming of tree branches to clear the over head lines enroute of LT over head lines/feeders (including repairing and jointing of ACSR Conductor if damaged during cutting of trees) and removal of the trimmed branches of tree and deposit the same in waste bins inside the campus complete all as directed by Engineer-in-Charge.
S&F in Replacement of ACSR conductor steel re-inforced of any size on pole including binding wire and line taps of appropriate size & type complete all as directed by Engineer-in-Charge.
Supply & errect in replacement of Aesthetically designed decorative hot dipped galvanised mild steel step pole with grey powder finish.Compatible for all Havells post top range.3.5 mtr long, not less then 75 mm dia suitable for fixing spring serious & emperor luminiare post top lantern fittings complete all as specified and directed by engineer - in- charge. Make : Havells cat no 7308 and its equivalent CG / PHILIPS. Note : Quoted rate shall be deemed to be included for excavation in any type of soil and cement concrete 1 : 3 : 6 type C1 required for fixing of pole.
Supply and fixing in replacement of aluminium thimble stud type suitable for size of cable 300 sq mm all as specified and directed by engineer-in-charge.
Supply and fixing in replacement of aluminium thimble stud type suitable for size of cable 240 sq mm all as specified and directed by engineer-in-charge.
Supply and fixing in replacement of aluminium thimble stud type suitable for size of cable 120 sq mm all as specified and directed by engineer-in-charge.
Supply and fixing in replacement of aluminium thimble stud type suitable for size of cable 95 sq mm all as specified and directed by engineer-in-charge.
Supply and fixing in replacement of aluminium thimble stud type suitable for size of cable 35 sq mm all as specified and directed by engineer-in-charge.
M&L for repair and painting of LT panel of any size, any type by welding, screewing, replacement of nut bolt and hinges after repair preparing old paint surfaces with two coat synthetic enamel spray paint and red oxide before painting internal and external approved make from ground level & upto including white washing the coping all as directed by Engineer - in - Charge.
M&L for plain cement concreate ( PCC) 1:4:8 type D-2 with 40 mm graded aggregate in foundation filling and mass concrete for foundation of pole
Maintenance and general servicing 'B' Check of following capacities DG set of any make including replacing oil filter, fuel filter, air cleaner, hose for air cleaner and topping up of coolant etc. complete including general cleaning including cleaning of accoustic enclosures of DG set with the help of air blowers complete all as specified and as directed by the Engineer-In- Charge..
320 KVA DG set
200 KVA DG set
125 KVA DG set
Disconnecting all electrical cable connections from the dynamo assembly and taking down the dynamo assembly for carrying out repairs and complete overhauling the system including replacing the unserviceable parts like Carbon brushes, Bearings, Armature. Burnt out coils etc. reassembling and re-fixing the dynamo assembly to its original position and reconnect all disconnected the cable connections including testing complete of the following capacities of DGs all as specified and directed by Engineer - in - charge.
320 KVA DG set
200 KVA DG set
125 KVA DG set
Supply & Fix in replacement of 24 Volts 30 Amps Battery Charger panel mounting type including removing of the unsv from the existing position complete all specified and directed by Engr- in- charge.
Supply and fix in replacement of lead acid Maintenance free batteries 180 AH, 12 V, 25 plates complete all as specified and directed. Make : Exide / Amarron / SF sonic
Supply and connect maintenance free lead acid battery 12 Volt, 150 AH. complete all as specified and directed. Make : Exide / Amarron / SF sonic
Draining out the fuel from the fuel tank of DG Set of various capacity and keeping it in separate container, disconnecting all the fuel lines and other mechanical connections and taking out the fuel tank for cleaning, cleaning the fuel tank both internally and externally by removing all the accumulated dust / sediments, leak testing the tank and welding / brazing and re-fixing the tank to its original position, replacing the drain plug and PVC pipe protected with steel flexible pipe, calibrating the fuel tank, refilling the drain out fuel back into the tank and provision of locking arrangements complete all specified and directed by Engineer- in- charge.
M & L for de-scaling / servicing of radiator of copper/aluminium any type taking out by disconnecting from DG set locating the leaking places, soldering / brazing complete in cleaning with acid and refixing in position complete all as direcetd incl replacement of hoses with new one for DG set of capacity 125/200 KVA complete all as specified and as directed by Engr-in-Charge.
M & L for de-scaling / servicing of radiator of copper/aluminium all type taking out by disconnecting from DG set locating the leaking places, soldering / brazing complete in cleanibg with acid and refixing in position complete all as direcetd incl replacement of hoses with new one for DG set of capacity 320 KVA complete all as specified and as directed by Engr-in-Charge.
Disconnecting and taking down the defective / unserviceable DC wiring and M & L for rewiring with same size of cable including supply and replacing of complete wire with flexible pipe, control cable including testing complete for following capacities of DG Set complete all specified and directed by engineer- in- charge :-
320 KVA DG set
200 KVA DG Set
125 KVA DG Set
Supply and fill distilled water of best quality sealed packing complete all as specified and as directed by Engineer-in-Charge.
M&L for servicing of AMF panel of DG set of capacity 125 KVA to 320 KVA cleaning of AMF panel, rectification of defect rewiring replacement of D/S indicator with new indicator of complete AMF panel and replacement of unserviceable relays under respective item of this schedule complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement of Auto voltage regulator relay 415V AC as exists complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement under voltage relay 300-400V as exists complete all as specified and as directed by Engineer-in-Charge.
Suppy and fixing in replacement Electronic timer 240V AC, adjustment time 6-60Sec as exists complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement Engine start relay, 12V DC as exists complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement reverse power relay, 415V AC as exists complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement of copper terminal end suitable for batteries of capacity 12V 180AH complete all as specified and as directed by Engineer-in-Charge.
Supply & Fix in replacement of Earth leakage relay, 240V AC complete all specified and as directed by Engineer- in- charge.
Supply & Fix in replacement of digital multi function meter to read voltage current and power factor including set of CT-1 each complete all as specified and as directed by engineer- in- charge.
Supply & Fix in replacement of 3 pole power contactor ML-6, 125 A complete all as specified and as directed by Engineer- in- charge.
Supply & Fix in replacement of 3 pole power contactor ML-10, 250 A complete all as specified and as directed by engineer- in- charge.
Supply & Fix in replacement of 3 pole power contactor ML-10, 400 A complete all as specified and as directed by Engineer- in- charge.
Supply & Fix in replacement power contractors in built 1 No + INC No auxiliary 3 pole AC 220 Volts type MNX – 12, 30 A complete all as specified and as directed by engineer- in- charge.
Supply & Fix in replacement of 3 pole power contactor MNX 18, 30 A complete all as specified and as directed by Engineer- in- charge.
Supply & Fix in replacement of solenoid switch suitable including all necessary arrangement complete all as specified and as directed by Engineer- in- charge
Supply and replace engine oil from engine oil sump with suitable grade oil SAE-20W40 complete all as specified and as directed by Engineer-in-Charge. Make : I O C Servo / Volvaline / Shell
Supply & Fixing in replacement self starter for suitable of 125 KVA DG set capcity complete all as specified and as directed by Engineer-in-Charge. Make : Greeves / Cummins / Kirloskar
Supply & Fixing in replacement self starter for suitable of 200 KVA DG set capcity complete all as specified and as directed by Engineer-in-Charge. Make : Greeves / Cummins / Kirloskar
Supply & Fixing in replacement self starter for suitable of 320 KVA DG set capcity complete all as specified and as directed by Engineer-in-Charge. Make : Greeves / Cummins / Kirloskar
S & F in replacement of unserviceable fan belt with provided new fan belt DG set pf capacity 125- 200 KVA complete all as specified and as directed by Engineer-in-Charge.
S & F in replacement of unserviceable fan belt with provided new fan belt DG set pf capacity 320 KVA complete all as specified and as directed by Engineer-in-Charge.
M & L for fixing in replacment of belt water pump ( set ) in 125/200 KVA DG set for greevs complete all as specified and as directed by Engineer-in-Charge.
M & L for fixing in replacment of belt water pump ( set ) in 320 KVA DG set cummins complete all as specified and as directed by Engineer-in-Charge.
Maintenance & servicing of DG Set of capacities 125 KVA to 200 KVA any make complete for ‘C’ as follows :- 'C' CHECK (i) Change Oil (ii) Check oil filter, fuel filter, by pass filter. (iii) Change Air Filter (iv) Change water Separator (v) Radiator cleaning with chamical (vi) Check All Electrical terminal & thimbles (vii) Check polution level of DG Set capacity 125 KVA to 200 KVA complete all as directed by Engr-in-Charge
Maintenance & servicing of DG Set of capacities 320 KVA any make complete for ‘C’ as follows :- 'C' CHECK (i) Change Oil (ii) Check oil filter, fuel filter, by pass filter. (iii) Change Air Filter (iv) Change water Separator (v) Radiator cleaning with chamical (vi) Check All Electrical terminal & thimbles (vii) Check polution level of DG Set capacity 125 KVA to 320 KVA complete all as directed by Engr-in-Charge
Supply and fixing in replacement aluminium Tube terminal ( thimbles) of size 50 to120 Sqmm XLPE Cable complete all as specified and as directed by Engineer-in-Charge. Make : Dowells / KI / Kirloskar
Supply and fixing in replacement aluminium Tube terminal ( thimbles) of size 150 to 240 Sqmm XLPE Cable.
M/L servicing, repair ,caliberation including replacement of spare parts as required of PT pump on test bench of DG set capacity 125 KVA complete all as required and as directed by Engineer-in Charge.
All as per item No. 111 above but of capacity 200 KVA complete all as specified and as directed by Engineer-in-Charge.
All as per item No. 111 above but of capacity 320 KVA complete all as specified and as directed by Engineer-in-Charge.
M/L for repair to turbo charger of DG set capacity 200 KVA from authorized vendor including testing on test bench complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing oil safety switch to engine of 200 KVA DG set as per existing complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing oil safety switch to engine of 125 KVA DG set as per existing complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement the corrosion resistor as per existing to the Engine of DG set capacity 125 and 200 KVA complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement gear tachometer for DG set of capacity 125 & 200 KVA as per existing complete all as specified and as directed by Engineer-in-Charge.
S/F in replacement Hub and spider unit for fuel pump of DG set of capacity 200 KVA as per existing complete all as specified and as directed by Engineer-in-Charge.
M/L for caliberation of injector on test bench of DG set capacity 125 to 200 KVA complete all as specified and as directed by Engineer-in-Charge
Supply and fix in replacement exhaust manifold set of three piecescomplete with gaskets , studd mountings, nuts etc complete ( centre , rear and front) in 200 KVA / 125 KVA DG set complete all as specified and as directed by Engineer-in-Charge.
M/L for repair including replacement of coils , bush/ bearings and other spares as required to alternator/dynamo unit of DG set of capacity 125/200 KVA complete all as specified and as directed by Engineer-in-Charge.
S/F in replacement manifold fuel supply to DG set capacity 125 KVA complete all as specified and as directed by Engineer-in-Charge.
M/L for carry out the tappet setting after opening the top cover to DG set capacity 125 KVA including replacement of gasket and minor spares as required complete all as specified and as directed by Engineer-in-charge.
M/L for carry out the tappet setting after opening the top cover to DG set capacity 200 KVA including replacement of gasket and minor spares as required complete all as specified and as directed by Engineer-in-charge.
M/L for carry out the cylinder head servicing including servicing of valves intake, valve exhaust, guide valve, insert valve seat, pin guide, collet valve, lapping, replacement of gasket for 125 KVA DG set complete all as specified and as directed by Engineer-in-Charge.
All as per item No.126 above above but capacity 200 VA complete all as specified and as directed by Engineer-in-Charge.
M/L for repair water pump of DG set 125 KVA including replacement of impeller, ball bearing, shaft, spacer, plug and seal complete all as specified and as directed by Engineer-in-Charge.
S/F timer unit to AMF panel of DG set as per existing and providing control connections complete all as specified and as directed by Engineer-in-Charge.
M & L for supply & providing asbestos rope 12 mm dia for wrapping the exhaust pipe of DG set complete all as specified and as directed by Engineer-in-Charge.
M & L for fixing in replacement of Air filter of 125/200/ KVA DG set complete all as specified and as directed by Engineer-in-Charge.
M & L for fixing in replacement of Air filter of 320 KVA DG set complete all as specified and as directed by Engineer-in-Charge.
M & L for repair and reconditioning the starting motor of kirloskar / cummins / Greaves make including taking out the defective starter from 125 KVA / 200 KVA / capacity DG set , complete dismantling and repair and replacing the carbun brushes with holder, solenoid switch assly, bush, commutator unit, starting coil, etc refixing the same in the DG set and connecting with the circuit including all required items, starting and testing complete all as specified and as directed by Engineer-in-Charge. Note : Rate quoted shall be for removing , refixing incl overhauling of starter & spares reqd will be measured and paid separately,
Supply of following Items carbon brush set with holder
Solenoid switch assembly with bush
commutator unit
stator starting coil unit complete
stator running coil unit complete
M & L for repair and reconditioning the starting motor of kirloskar / cummins / Greaves make including taking out the defective starter from 320 KVA / capacity DG set , complete dismantling and repair and replacing the carbun brushes with holder, solenoid switch assly, bush, commutator unit, starting coil, etc refixing the same in the DG set and connecting with the circuit including all required items, starting and testing all as specified and directed by Engineer-in-charge (Note- rate quoted shall be for removing , refixing incl overhauling of starter & spares reqd will be measured and paid separately,
Supply of following Items carbon brush set with holder
Solenoid switch assembly with bush
commutator unit
stator starting coil unit complete
stator running coil unit complete
Supply and fix in replacement coil suitable for contactor ML-4 with coil voltage 240/415 V complete all as specified and as directed by Engineer-in-Charge. Make : L & T / C & S / Havells
Charges for attending and rectifying the DG set ( Engine and Alternator), Breaker all electrical complaint as and when required for smooth operation of DG set complete all as specified and as directed by Engineer-in-Charge.
S & Fixing in repairs of PT fuel pump by dismantling, transporting, repairing and calibration, testing and commissioning of PT fuel pump for 125 / 200 KVA DG set including the replacement of all service kits, pulsvation damper, tacho drive shaft and seal, gear drive shaft , bearing, weight carriers, etc complete all as specified and as directed by Engineer-in-Charge.
M & L for taking down stator assembly of alternator by disconnecting electrically and mechanically taking to work shop for rewinding incl removing burnt coils, insulating material complete cleaning with CTC and rewinding with same gauge ISI marked winding wire complete with ISI marked insulating paper and Dr Beck varnish baking / heating and bringing back to installatin refixing , connecting elecrtically and mechanically and testing on completion of work complete all as directed for DG set of capacity 200 KVA/ 125 KVA complete all as specified and as directed by Engineer-in-Charge.
S & fixing in repair solid state potentiometer under cummins part no. 3877372 in 200 KVA and testing complete all as specified and as directed by Engineer-in-Charge.
S & Fixing Push button ( 2 nos ) for ON / Off to 200 KVA AMF panel at ATC Power house and connecting with control circuit connection and testing complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing coolant hose set 1 no and set of clamps complete all as specified and as directed by Engineer-in-Charge.
Supply only coolant for radiator suitable for DG set 125/160/200/ Make- Cummins/ Cotton greave/ Kirloskar under part no. 3167215 complete all as specified and as directed by Engineer-in-Charge.
S & F start and stop relay 12 V/24 V DC suitable for AMF Panel capacity of 200 KVA complete all as specified and as directed by Engineer-in-Charge.
NOTE FOR ITEM NO. 73 TO 144: - (i) The contractor shall have MOU for providing service and material with OEM of DG Set of Make : M/s ThyssenKrupp. (ii) Thetenderer shall have to replace the unserviceable materials within the OEM materials only. Necessary paid vouchers shall be submitted from OEM for the materials like ARD, drive etc. Contractor is responsible for renewal of licence fee. The charges for Annual Government inspection is deemed to be included in the quoted rate. (iii) The work will be carried out under authorised dealer for comprehensive maintenance of DG Set all as specified in BOQ
M&L for locating fault in LT/HT (1.1/11 KV grade) underground cable laid in trenches by locating fault with the help of electronic fault locator machine comprising of surge generator pulse ECHP fault location with high frequency distance calculator etc. Excavation in any type of soil strata exposing the cable fault removal of deteriorated position of cable treating of cable and keeping the same ready for jointing work for cables of size upto 400 Sqmm 3.5 core/ 300 sq mm 3 core. The fault locating equipment will be brought to site with 02 hours of instruction received from Engineer-in-Charge complete all as specified and as directed.
M/S MG GROUP
M/S LADPURIA ENTERPRISES
J.P. Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .