Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.2 LAccepted-Finance 1ST FLOOR FLAT NO 103 SCHEME NO 51 234 AVANTIKA NAGAR INDORE INDORE MADHYA PRADESH 452006 | INDORE | MADHYA PRADESH | 452006 | L1 | Accepted-Finance Accepted | |
| 2 | L2₹5.9 L+₹69,156.54 (13.4%)Accepted-Finance | L2 | Accepted-Finance Accepted | |
| 3 | L3₹7.4 L+₹2.2 L (42.7%)Accepted-Finance | L3 | Accepted-Finance Accepted |
Tender Value
₹5.6 L
EMD Value
₹11,154
Closing Date
19 Aug 2026, 3:00 pmClosed
Executive Engineer(E)
Judiciary Electrical Division-I, PWD, Yamuna Western Bank, Lok Nayak Setu, New Delhi-110002
RMO of EI and Fans installed at Rouse Avenue District Court Complex, New Delhi (Sh Replacement of AHU at auditorium)
2026_PWD_296845_1
107/EE(E)/JED-1/PWD/2026-27
Open Tender
Electrical Works
Percentage
30 days
Rouse Avenue Court DDU Marg New Delhi
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹11,154
24 Aug 2026
11 Aug 2026
19 Aug 2026
11 Aug 2026
19 Aug 2026
11 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supplying, Installation, Testing and commissioning of factory built in confirmation to IS 18794 : 2024 floor mounted chilled water double skin type horizontal/vertical air handling units made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 4 row deep, filter section having filters suitable for achieving air quality as per CPWD HVAC Specification 2024 belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for variable frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities including dismantling of existing AHU . (Total static pressure considered is max. 50 mm wg) | |||||
| 1.01 | 15300 CMH* | 1 | No. | 2,53,573 | ₹2,53,573 |
| 1.02 | 20400 CMH* | 1 | No. | 3,16,621 | ₹3,16,621 |
| 2Supplying, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, bends, transitions, reducers, end caps, collars etc as required complete in all respect in confirmation with IS : 655 and approved drawings and specifications of following sheet thickness complete as required. | |||||
| 2.01 | Thickness 0.63 mm sheet | 15 | Sqm | 1,213 | ₹18,195 |
| 2.02 | Thickness 0.80 mm sheet | 15 | Sqm | 1,415 | ₹21,225 |
| 3Supplying and fixing of following thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.. | |||||
| 3.01 | a) 19mm | 10 | Sqm | 810 | ₹8,100 |
| 4 | Less Credit for dismantled AHU i/c of removing all the materials of site and cleaning etc. of AHU rooms complete as required.. | 2 | Job | -30,000 | - |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.74 MB
BOQ_395279.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .