| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹2.1 CrAccepted-AOC 606 80 FEET ROAD 7TH BLOCK 2ND PHASE BANASHANKARI 3RD STAGE BANGALORE 560 085 | BENGALURU URBAN | KARNATAKA | 560085 | ₹2.1 Cr | 1 | Accepted-AOC Being L1 |
| 2 | 2₹2.2 Cr+₹5.1 L (2.39%)Rejected-AOC | ₹2.2 Cr+₹5.1 L (2.39%) | 2 | Rejected-AOC Since not L1 |
| 3 | 3₹2.5 Cr+₹32.2 L (15.1%)Rejected-AOC | ₹2.5 Cr+₹32.2 L (15.1%) | 3 | Rejected-AOC Since not L1 |
Tender Value
₹1.9 Cr
EMD Value
₹2.7 L
Closing Date
26 Jan 2022, 6:00 pmClosed
Chief Engineer R n D Secunderabad
ChiefEngineer RnD Picket Secunderabad 500003
ADDITION ALTERATION TO BUILDING NO P 147 FOR SETTING UP STATE OF THE ART HIGH PERFORMANCE COMPUTING FACILITY AT GTRE BANGALORE
2021_MES_479885_2
CERD/BAN/ TOKEN/ 15 of 2021- 2022
Open Tender
Civil Works - Others
Item Rate
365 days
GTRE, Bangalore
Class B
Category a i b ii
7 documents required · 7 mandatory
₹1,000
Yes
Garrison Engineer I RnD East
₹2.7 L
Yes
4 Mar 2022
22 Dec 2021
2 Feb 2022
22 Dec 2021
26 Jan 2022
12 Jan 2022
Amount
Demolition of cement Concrete in ground floors and pavings exc 15 cm thickness (below or above ground level)
Demolition of brick work or precast cement concrete blocks work, built in cement mortar including all quoins, arches, pillars, etc, but excluding ashlar facings, dressed stone work and precast concrete articles all as directed.
Taking down chowkhat with shutter [without taking off shutter from the frame] exceeding 1.5 Sqm but not exceeding 4.0 Sq.m each complete all as specified and as directed.
Dismantling of Structural Steel work including Doors, Gates etc but excluding framed trusses complete all as specified and as directed.
M & L for PCC 1:4:8, Type D-2, using 40mm graded stone aggregate as in Foundation, Fillings, Mass concrete, Footings etc complete all as specified and as directed.
M & L for 75mm thich, PCC 1:4:8, Type D-2, using 40mm graded stone aggregate as in sub base to floors etc complete all as specified and as directed.
M & L for PCC 1:3:6, Type B-1 [using 20 mm graded granite stone aggregate] in surface channels and drains including forming fair finished drain or channel of any inner girth using extra cement including forms, moulds, mitred / stooped ends complete all as specified and as directed.
M & L for PCC 1:2:4, Type B-1 [using 20 mm graded granite stone aggregate] in benching/surface channels along the wall and roof junction to a required shape and size complete all as specified and as directed.
M & L for RCC M-25 (Design Mix) using 20mm graded stone aggregate as in foundations, rafts, footings, plinth beams, basement slabs etc complete all as specified and directed.
M & L for RCC M-25 (Design Mix) using 20mm graded stone aggregate as in columns, pillars, piers, posts and struts complete all as specified and directed.
M & L for RCC M-25 (Design Mix) using 20mm graded stone aggregate as in beams, bands, cantilevers, lintels over 1.5M span complete all as specified and directed.
M & L for RCC M-25 (Design Mix) using 20mm graded stone aggregate as in chajja etc complete all as specified and directed.
M & L for RCC M-25 (Design Mix) using 20mm graded stone aggregate as in slabs supported on walls, beams, roofs, landings, balconies, canopies, deck slabs and in shelves and the like etc., complete all as specified and directed.
M & L for RCC of Design Mix M-25 as in basementslab and the like; any thickness; complete all as specified and directed.
M & L for RCC of Design Mix M-30 as in walls, sump walls, basement walls and the like; any thickness; above top of footings; including attached pilasters and buttresses complete all as specified and directed.
M & L for RCC of Design Mix M-30 as in raft slabs for sumps complete all as specified and directed.
M & L for RCC M-30 (Design Mix) using 20mm graded stone aggregate as in roof slabs for sumps, beams, roofs, landings, balconies, canopies, deck slabs and in shelves and the like etc., complete all as specified and directed.
S & F Reinforcement using High Strength Corrosion Resistant Deformed TMT Bars of Grade Fe–500D of 10mm dia and over, cut to length, bent to shape required including cranking, bending, spirally for hooping, hooking ends and binding with annealed mild steel wire not less than 0.9mm dia or securing with clips or welded complete all as specified and as directed.
S & F Reinforcement using High Strength Corrosion Resistant Deformed TMT Bars of Grade Fe–500D of 6 to 8mm dia and over, cut to length, bent to shape required including cranking, bending, spirally for hooping, hooking ends and binding with annealed mild steel wire not less than 0.9mm dia or securing with clips or welded complete all as specified and as directed.
S & F Reinforcement using High Strength Corrosion Resistant Deformed TMT Bars of Grade Fe–500D of 5mm dia and over upto and including 10mm dia in stirrups, spacers and binders, cut to length, bent to shape required including cranking, bending, spirally for hooping, hooking ends and binding with annealed mild steel wire not less than 0.9mm dia or securing with clips or welded complete all as specified and as directed.
Use and waste of formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits of plinth beams and similar work for fair finished surfaces of concrete flat complete all as specified and directed.
Preparation of newly plastered surfaces of walls and applying three coats of white wash, complete all as specified and directed.
Use and waste of formwork to sides of pillars, posts, columns and similar work for fair finished surfaces of concrete square, rectangular or polygonal complete all as specified and directed.
Use and waste of formwork to sides of walls of sumps and similar work for fair finished surfaces of concrete flat complete all as specified and directed.
Use and waste formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work not exceeding 200mm thick [horizontal or sloping] including rough finished surfaces complete all as specified and directed.
Use and removal of steel formwork to sides and soffits of floor or roof beams, beam launchings, girders, bressummers, lintels, cantilevers, shelves including supports, overhangs, etc, splays between floors and beams and similar works for fair finished surfaces of concrete complete all as specified and as directed.
Use and waste formwork to Edges of Concrete Flats, Treads, Breaks in Floors, Window Cills, Concrete Railings, Ppenings in Concrete Walls, Floor and Roofs not exceeding 20cm wide and sides of RCC / PCC Bands in Walls, horizontal or sloping and similar work for rough finished surface of concrete complete all as specified and as directed
Use and waste formwork to soffits of slabs of sumps and similar work not exceeding 200mm thick [horizontal or sloping] including fair finished surfaces complete all as specified and directed.
Excavation over areas not exceeding 1.50 m in depth and getting out in Hard / dense soil complete all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 10 Sq.m on plan area and not exceeding 1.5m deepfor foundations, shafts, wells, cesspits, manholes, pier holes etc getting out in Hard / Dence soil complete all as specified and as directed.
M & L for Earth Filling under floors including watering and consolidation complete all as specified and as directed. [Note : Earth free from vegetation, pebbels/foreign materials obtained from excavation shall be reused]
M & L for Hardcore of gauge not exceeding 63mm of broken stones or boulders, deposited, spread and levelled in layers not exceeding 15 cm thick watered and rolled/rammed to a true surface and consolidated to required gradient and camber complete all as specified.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick of excavated soil complete all as specified and as directed. Note: A deduction of 10% shall be made from total computed volume of filling to cater in bulk irrespective of machinery used for ramming.
Removal of excavated material [Soil] to a distance exceeding1.50 km and not exceeding 5.0 km and depositing where directed complete all as specified and as directed.
M & L for 40mm thick, PCC 1:2:4, type B-1, using 20mm graded stone aggregate as in floors/paving finishing the surface even and smooth without using extra cement complete all as specified and directed.
M & L for 50mm thick, PCC 1:3:6, Type C-1, using 20mm graded aggregate as in Plinth protection etc. surface finished fair and even with out using extra cement complete all as specified and as Note: Plinth protection shall be laid in panels and length of each panel shall not be more than 2.00Meter leaving 6mm joints. Joints shall be filled with 85/25 grade bitumen and sand in the ratio of 1:3
M & L for providing Precast RCC 1:2:4, Type B-1 using 20mm graded stone aggregate as in landings, cover slabs [for manholes etc], Chullah hoods, Chajjas, water troughs, mangers, Shelves and similar articles with plain faces set in cement mortar 1:6 complete all as specified and as directed.
M & L for Brick work with Sub class 'B' bricks, straight or curved on plan exceeding 6 m mean radius built in Cement Mortar 1:6 complete all as specified and as directed.
M & L for Vitrified Tiles, Double Charged, light shade, First Quality, area of each tile exceeding 0.42 Sqm and not exceeding 1.0 Sqm, 9 to 10 mm thick as in Floors, set and jointed in neat cement slurry and pointed in epoxy grout to match including screed bed or bedding layer of mortar 15 mm thick in Cement Mortar 1:4 complete all as specified and as directed. Note: The colour / shade / design of tiles shall be as approved by GE.
M & L for Vitrified Tiles, Double Charged, light shade and matching with adjacent floor tile, First Quality, area of each tile exceeding 0.36 Sqm and not exceeding 0.42 Sqm, 9 to 10 mm thick as in skirting , set and jointed in neat cement slurry and pointed in epoxy grout to match including platring with 10 mm thick in Cement Mortar 1:4 complete all as specified and as directed. Note: The colour / shade / design of tiles shall be as approved by GE.
M & L for providing Pre- cast cement concrete block masonry 1:3:6, Type C1 withsolid blocks, exceeding10cm in width and setting in motar, complete set in CM 1:6 complete all as specified and directed.
S & F Powder Coated Aluminium (minimum thickness of powder coating 50 micron) frame for doors, windows, ventilators, partitions with one or more rebates including jointing cleat, rubber beading for fixing, locking arrangement etc complete all as specified and as directed.
S & F powder coated aluminium grill of approved design/pattern, with approved standard section and fixed to existing window frame with CP brass/ stainless steel screws at 200mm centre to centre including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening complete all as specified and as directed.
S & F Aluminium Powder Coated [Minimum 50 Micron thick] Sections as in door shutters, Aluminium section weighing 0.55 KG / RM including necessary Joining Cleats, Glazing Clips, Neoprene Rubber Packing, Powder Coated Aluminium Snap Beading, Screws, Powder Coated Aluminium Fittings such as Locking Arrangement [1 No], Suitable Handle [2 Nos] per Shutter complete all as specified and as directed. Note: Unit rate quoted shall be deemed to include for cost of rubber beading, glazing clips, neoprene packing, fittings such as Handles, Locking Arrangement and fixing only of Panel inserts such as Glass / Gauge / Grills etc.
S & F Aluminium Powder Coated [Minimum 50 Micron thick] Sections as in Window and Ventilator Shutters, Sliding Type, without Sash Bar, Aluminium section weighing 0.55 KG / RM including necessary Joining Cleats, Glazing Clips, Neoprene Rubber Packing, Powder Coated Aluminium Snap Beading, Screws, Powder Coated Aluminium Fittings such as peg stays 150mm [1 No], hinges type B-21 100mm long[2 nos] Suitable Handle [1 No] per Shutter complete all as specified and as directed. Note: [a] Supply only panel inserts such as Glass / Gauge / Grills will be measured and paid separately. [b] Unit rate quoted shall be deemed to include for cost of rubber beading, glazing clips, neoprene packing, fittings such as Handles,Peg stays, Hinges etc.
M & L for 5.50 mm thick sheet glass ordinary quality in square exceeding 0.50 Sq.m each pane glazing with aluminium beads with solar control film 25 micron reflective type sticked to glass panes as per manufacturers instructions complete all as specified and as directed.
S & F 12mm thick, Prelaminated Particle Board, prelaminated on one side with decorative choice lamination and other side balancing white lamination, interior Grade fixed with screws to timber frame work complete all as specified and as directed.
S & F Aluminium extruded body section Door Closer Hydraulically Regulated, Designation No. 3 universal type, suitable for door shutters of 851 mm to 1000 mm in width and of weight between 61 to 80 Kg complete all as specified and as directed.
M & L for 1.60mm thick Plain, Black Sheet, mild steel sheeting as in in wall cladding, steel gates and similar work, cut to size, holes punched including round headed screws, clout nails or rivets and fixed to wood or steel framing with plain 40 mm lap joints with riveted or welded seams, including bending or turning up, mitred angles, etc. complete all as specified and as directed.
M & L for cutting openings, through brick walls for door, window and other openings or enlarging existing openings, converting into window into door openings etc. or cutting out defective brick work for under pinning, including providing, fixing and removing shoring, cleaning and stacking bricks, removing surplus serviceable bricks, hard core etc to store and rubbish not exceeding 50M distance complete all as specified and as directed.
S & F Rolled Mild Steel work confirming to Fe 410-W, Grade-E- 250, Quality-A as in Framed work as in doors or gates of angle or other sections with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering, Doors etc., to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive or steel sheeting or other covering, running rails and guides) and hanging also fastening and fixing complete all as specified and as directed.
Taking down Cement Plaster of any description on brick or stone walls or concrete surfaces including raking out joints, hacking for key, scrubbing down with water etc complete all as specified and as directed.
M&L for rendering 15mm thick cement plaster on brick masonry surface in two layers, base layer 10mm thick in CM (1:4) and top layer 5mm thick in CM (1:4) (with river sand) mixed with WPC as per manufacture' s instructions, finished even and fair without using extra cement complete all as specified and directed by Engineer-in-Charge. Note: WPC shall be measured and paid seperatly
M & L for rendering 5 mm thick in Cement Mortar 1:4 on fair faces of concrete surface of ceiling surfaces finished even and smooth without using extra cement including complete all as specified and as directed.
M & L for rendering to brick / concrete surfaces, 10 mm thick in Cement Mortar 1:4, surfaces finished even and smooth without using extra cement complete all as specified and as directed.
M & L for preparation of plastered or decorated or undecorated Wall, chajja, balcony, facia tec by brooming down or steel wire brushing, scrapping down smoke soots, moulds, moss, efflorescent salts, treading oil and greasy spots and applying two or more coats of Cement based Wall Care Putty of 2mm on walls including rubbing with sand paper to obtain a smooth surface and making good any undulations on the surfaces and applying two coats of plastic emulsion paint over one of alkali resistant primer on Wall surfaces complete all as specified and as directed. Make : Royal in Asian or its eqavalent in Berger/ Johnson & Nicholson
M & L for two coats of Synthetic Enamel paint over one coat of Red Oxide / Zinc Chrome Primer on new steel surfaces over 10cm width or girth including preparation of new steel surfaces complete all as specified and as directed.
M & L for two coats of Synthetic Enamel paint on old steel surfaces over 10cm width or girth including preparation of old steel surfaces complete all as specified and as directed.
M & L for two coats of synthetic enamel paint to old wooden surfaces over 10cm width or girth including preparation of surfaces complete all as specified and as directed.
Removal of entire existing water proofing treatment in any position including tarfelt, plaster and removing the debirs out side MD land all as specified and directed.
M & L for preparation of surfaces, brushing neat cement slurry with 3 KG of cement per Sq.m, screed bed 10mm thick in cement mortar 1:4 on concrete surfaces finished even and smooth without using extra cement including mixing of water proofing compound @3% by weight of cement for levelling the surface smooth and applying APP based polymeric membrane minimum weighing 3.5Kg/Sqm and minimum 3.0mm thick reinforced with polyster non woven fabric (weight not less than 150grams/Sqm) laid over primed surface including bituminous primer conforming to IS-3384 and applied 0.3Litre/Sqm by forced application complete all as specified and directed. The complete roof treatment shall be consisting of as under after laying levelling coarse as described above :- (i) Applying one coat of bituminous primer confirming to IS-3384 @ 0.3 Litre/Sqm. (ii) Laying APP based membrane of specified thickness and weight (iii) Applying two coat of aluminium paint @100ml/Sqm Note: Water proofing compound will be measured and paid separately as " Supply only"
Supply only Integral Water Proofing compound
S & F Aluminium anodised barrel Tower Bolt of size 125 mm size of extruded section complete all as specified and as directed.
S & F 100mm Mortice Latch with two levers (vertical type), brass body complete all as specified and as directed.
S & F Stainless steel wire cloth / mesh with average aperture not exceeding 1.40 mm and dia of wire 0.36 mm and fixed with tinned tacks or stainless steel wire staples complete all as specified and as directed.
S & F PVC 4mm sheets, laminated plain coloured, marbled, mosaic or mottled finish laid with approved rubber based adhesive in floors complete all as specified and as directed.
S & F in repairs Collapsible Steel Gates, Top Hung, consisting of Channel Pickets, Pivoted Flat Bars, Top and Bottom Runners, Brass Handles etc. as specified, erected in position and securing runners with holdfasts and brackets, complete all as specified and as directed.
S & F in repairs Steel rolling shutters, thickness of laths of 1.25 mm, with ball bearing, as specified including top cover, anchoring rod, hasp and staple and one shop coat of primer, erected in position as indicated, Gear Operated Type withchain wheel and hand chain complete all as specified and as directed.
M & L for Hacking out old brocken glass from wooden/steel frames and fixing 4mm thick sheet glass ordinary quality and glazing with oil putty in square n. exc 0.5 Sqm each pane complete all as specified and as directed.
M & L for Hacking out old brocken glass from wooden/steel frames and fixing 4mm thick sheet glass ordinary quality and glazing with oil putty in square exc 0.5 Sqm each pane complete all as specified and as directed.
M & L for Forming Expansion Joint, 20mm thick, filled with Preformed Bituminous Filler and top 30mm Primed and sealed with approved Polyurethane sealing compound for 75mm thick flooring complete all as specified and directed
S & F for pre-painted Galvalume zinc coating GI based corrugated steel sheets of Trapezoidal profile having pitch 190mm, depth 29mm and thickness 0.50mm base metal tickness[Galvalume base-PPGL trapezoidal profile sheets], having tensile strength of 550 Mpa, fixed with aluminium self tapping screws, neoprene and EPDM washers of suitable size in roof covering complete all as specified and as directed. Note: 1. Overlap shall be provided as specified by the manufacturer. 2. Height upto 15M and rate quoted deemed to include for necessary scaffolding
M & L Pre-painted galavalume aluminium zinc coating GI based plain sheet 0.71mm thick, of an Alloy 31000 H4 in ridges, hips, valley gutter, drip and straight flashing complete all as specified and directed by the Engineer-in-Charge
S & F for Joist, Channel, angle or tee sections fixed independently without connecting plates etc., complete all as specified confirming to FE-410W(Gde E-250) Quality B complete all as specified and as directed.
S & F for venetian blinds verical type 100 mm width with approved fabric and powder coated aluminium fittings such as top rails, metal weight, nylon button loops etc complete all as specified including dismantling unserveable one.
S&F horizontal level suspended ceiling comprising of Armstrong Aluminium clip-in PlainTile 600mm x 600mm (norminal size) tiles made of AA-3003-H14(Tempered) grade Aluminium suitable for Architectural finishes in 0.7mm thickness as per IS:2676(1981) in Global white colour with concealed suspension system having a bevelled edge of 3x3mm and height of 33 mm on one side and 18mm on the other side. Tiles shall be flattened by precision leveller to minimize sag to less than 1/400 mm. Tiles shall have double rounded pip of dia 2mm and dia 6mm for secure engagement and levelling respectively, along with swing down feature and special tabs to allow removal of tile to enable plenum access. The Tile shall be electrostatically polyester powder coated using RoHS compliant powder having coating thickness ranging from 60-80 microns, The powder coating shall pass salt spray test for 750 Hours as per ASTM B117, QUV-A Test for 1000 hours as per ASTM G-154(Cycle-1) and humidity test for 1000 hours as per DIN 50017. (The powder coating shall have an adhesion of GTO as per ENISO 2409. The shade vriation across batches shall be delta E-1 using Excite / BYK Gardner instrument and gloss level of 2409. The shall variation across batches shall be delta E<1 using Excite /BYK Garner instrument and gloss level of 25+_5% at 60 as per ASTM D523.M The tile shakk have a light Reflectance of Excite/BYK Gardner instrument and gloss level of 25+_5% at 60 as per ASTM D523M) The tiles shall have a light Reflectance of >63% in accordance to ASTM 1477 -98 and Fire performance of class0/1 as per BS 476 Part 6&7 in module size of 600 x 600 mm.
Item No. 76 (Contd...) The Grid shall comprise of 3000 mm long Ç' channels of 38 h x 12w mm and 1mm thick spaced at 1200mm centre securly fixed to the structural soffit using threaded rod connected to C Channel hanger of 109x18.50x16.5mm at 1200mm c/c and anchor fastener . The last hanger at the end of each C- channel shall not be greater than 600mm from adjacent wall, use a C-channel connector of 99.6x35x9mm for splicing together two pieces of C-Channels, 4000mm DP-12 main carriers (Clip-in bar) of 16wx40H mm and 0.6mm thick made of Galvanized steel of 140gsm as IS 277(2003) and shall be spaced at 600 mm c/c in a direction perpendicular to the C--channels and secured at every intersection with C-channel using a DP-12 hanger (clip-in bar hanger) of 54x18x20mm use DP-12 conncter) to splice two pieces of DP-12 main carrier (clip-in bar). Tiles shall be clipped in between two DP-12 carriers (clip-in bar) from bel;ow, optionally security clip to be installed to ensure the pannels are positively engaged with DP-12 (clip-in bar channel).installation shall be carried out as per manufacturers recommended procedure. Perimer to be finished using angle of size 3000x19x32xmm in white colour secured to walls using screws at 450mm c/c cut tiles to secured to the wall angle using a spring clamp. The Tile & Grid system used together shall carry a 10Years warranty against Manufacturing defect and manufacturer shall provide a warranty certificate. The Tile & Grid shall have the manufacturers names embossed / printed on it . The manufacturer shall submit test certificate for the entire sustem Make: Arm strong / Saint Gobain
S&F Metal wall cladding cladding shall be of rectangular system W-H 1000 lock on with panels of length 3000 mm and width 275mm with horizontal grid frame work with C- shape wall profile fixed with wall anchors to wall panel plain shall be with woodgrain colour powder coated Galvanised plain steel sheet of 1mm thick, Joint shall be square edged with break gasket and plastic spacers on one short side and longer side complete all as specified and directed. Make: Armstrong Metal wall system Cat Part No.W-H 1000 wall cladding or techno commercially equivalent in Saint Gobin or other makes.
S&F 46mm thick fire proof metalic Door Shutter made out of 1.25mm thick Galvanized sheet with rock wool fillar material and fixed to frame with suitable stainless steel hinges of size 102mm x 76mm x 3mm with ball bearing, door frame of 143mm x 58mm cross section along with Mortice sash lock, profile cylinder, lever handle etc and surface finished with power coating of Polyurethane paint sutable for fire proof doors complete all as specified and directed. Standard NFPA-80 and IS:4020 Part - I : 12 &16 Note: The Door Frame also to be of same standared as per Door Shutter Make: Tata pravesh or Equivalent.
S/F Raised Access False Flooring suitable for heavy load of 2.5 ton. The floor panel shall be of core calcium sulphate with backing coat of hard plastic laminate sheet and ceramic finishing on top and shall comprises of the following:- (a) Pannel of size 600 x 600 mm and 30mm thick. (b) Bottom pedestal plate 100 mm square x 3mm thick. (c) Top pedestal plate 90 mm diameter x 3mm thick with panel locators. (d) Threaded rod assembly to be adjasted upto 600mm. (e) 50mm long counter sunk-head mechnical fastener for all corner fixed and rigid-grid stringer systems. (f) Pedstal galvanized heavy duty stainless steel leg. (g) glavanised steel stringers with standard OEM specifications and fixtures.
M & L for Preparation of newly plastred surfaces of wall/ceiling by scrapping down with wire brushes and washing down and removing existing loose particles and applying Two coats of 100% Acrylic premium Weather Proof Exterior Emulsion Paint having VOC less than 50gm/litre and UV resistance as per IS 15489:2004, Alkali & Fungal resistance, dirt resistance of required shade over and including a Coat of Weather Proof Exterior Primer of same manufacturer as that of paint complete all as specified and as directed.
M & L for complete removal of existing treatment on wall/ceiling surface including preparation by scrapping down with wire brushes and washing down and removing existing loose particles, scrapping down smoke soots, moulds, moss, efflorescent salts, treading oil and greasy spots and applying Two coats of 100% Acrylic premium Weather Proof Exterior Emulsion Paint having VOC less than 50gm/litre and UV resistance as per IS 15489:2004, Alkali & Fungal resistance, dirt resistance of required shade over and including a Coat of Weather Proof Exterior Primer of same manufacturer as that of paint complete all as specified and as directed.
M & L for preparation of newly plastered surfaces of Wall and applying two coats of plastic emulsion paint over one of alkali resistant primer complete all as specified and as directed. Make : Royal in Asian or its eqavalent in Berger/ Johnson & Nicholson
M & L for preparation of newly plastered surfaces of walls to receive Putty and applying two or more coats of Cement based Wall Care Putty of 2mm including rubbing with sand paper to obtain a smooth surface and making good any undulations on the surfaces complete all as specified and as directed.
Taking down carefully copper / aluminium point wiring [light, fan, socket or power] complete including fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings etc. and making good the disturbed surfaces all as per existing complete all as specified and as directed.
M & L for Point Wiring complete with 1100 Volts, FRLS Grade, 1.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor Cable, confirming to IS - 694 drawn through and including Stove enameled metallic conduit of suitable dia including all accessories on Walls / Roofs / Floors / Ceiling etc. and Modular Type Pressed Metal Flush Box made out of 2mm thick MS Sheet of suitable size and including Modular type Base / Grid Frame & Cover Frame for housing Modular Type Switches, Sockets and Regulators etc. concealed in walls, including 1100 Volts, FRLS Grade, 1.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable as earth continuity conductor with colour coding and connecting to Earth Dolly for One Light / Fan Point controlled by One Switch complete all as specified.
All as per Item No. 85 here- in- above, but for 3 pin 16amps socket outlet independently, with 1100 Volts, FRLS Grade, 4 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor Cable, conforming to IS - 694 and including 1100 Volts, FRLS Grade, 4 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor Cable, conforming to IS - 694 as earth continuity conductor and connecting to earth dolly complete all as specified and as directed.
S & F Modular switch one way, 6 Amp, one module, (ISI marked), complete all as specified and directed.
S & F Switch, Modular Type, One Module, Single Pole, One Way, 16 Amps, 230 Volts complete all as specified and as directed.
S & F Socket Outlet, 2/3 pin, 6/16 Amps and combained Modular Type, Two Modules, Multipurpose, 230 Volts complete all as specified and as directed.
S & F Exhaust fan with louvers shutters, heavy duty, single phase suitable for 230volts, 1400 RPM, 50HZ of 300mm sweep complete including provision of 3 core flexible copper cable ofsuitable size from ceiling rose to fan and fixing arrangement including grouting of bolts in wall, etc complete all as specified and directed.
S & F Wall mounting air circulators 450mm sweep, single phase suitable for 230volts, complete with built in regulator including provision of 3 core flexible copper cable ofsuitable size from ceiling rose to fan and fixing arrangement including grouting of bolts in wall, etc complete all as specified and directed.
M & L for Sub main wiring with 2 runs of single core 4 Sq.mm Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable, 1100 Volts, FRLS Grade, ISI Marked, drawn through and including stove enamelled metallic conduit of suitable dia with accessories fixed on Walls / Roofs / Floors / Ceiling etc. and connecting terminal ends including One run of 4 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable, green in colour, 1100 Volts, FRLS Grade as earth continuity conductor complete all as specified and as directed. Note: 3 runs of 4 Sq.mm copper conductor & one run of stove enamelled metallic conduit of suitable dia with accessories will be measured as one RM.
M & L for Sub main wiring with 2 runs of single core 6 Sq.mm Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable, 1100 Volts, FRLS Grade, ISI Marked, drawn through and including stove enamelled metallic conduit of sitable dia with accessories fixed on Walls / Roofs / Floors / Ceiling etc. and connecting terminal ends including One run of 6 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable, green in colour, 1100 Volts, FRLS Grade as earth continuity conductor complete all as specified and as directed. Note: 3 runs of 6 Sq.mm copper conductor & one run of stove enamelled metallic conduit of suitable dia with accessories will be measured as one RM.
M & L for Sub main wiring with 4 runs of single core 16 Sq.mm Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable, 1100 Volts, FRLS Grade, ISI Marked, drawn through and including suitable stove enamelled metallic conduit of siutable dia with accessories fixed on Walls / Roofs / Floors / Ceiling etc. and connecting terminal ends including Two runs of 16 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable, green in colour, 1100 Volts, FRLS Grade as earth continuity conductor complete all as specified and as directed. Note: 4 runs of 16 Sq.mm & 02 Runs of 16Sq.mm copper conductor one run of stove enamelled metallic conduit of suitable dia with accessories will be measured as one RM.
Supply and fixing Distribution board Power line Vertical TPN MCCB DBs with IP 54 Protection metal door 415 volts,8 way with double door fixed on flush to the wall including making the hole in th wall and fixing the DB including cement work and plastering complete including comprising the following all as specified and as directed (a) MCCB with thermal magnetic release 415 volts 3 pole 125 Amps capacity and breaking capacity 25 KA - 01 No
S&F SPN MCBs distribution board of sheet metal enclosure factory made double door powder coated single pole and neutral with 200 amps rated bus bar 8 way 240 Volts all as specified and directed
S&F of MCB SPN 240 Volts, 'C' series, breaking capacity 10 KA of rating 63Amps complete all as specified and as directed.
S&F of MCB SP 240 Volts, 'C' series, breaking capacity 10 KA of rating 6 to 32 Amps complete all as specified and as directed.
Supply and fix Recess mounted full panel LED luminaire 36 watt fitting 2' x2' with White powder coated housing & frame in CRCA sheet, High efficiency LED grade diffuser, electronic driver duly wired upto terminal block, CRI>80, Colour temperature-5700K, IP20, 50000 burning hours as per L70 Criteria, Ambient temperature-0 to 50DegC, Driver Efficiency>85%, THD<10%, Powerfactor>0.95, Surge protection in CM-3KV, Multistage isolated Constant current-Constant voltage operated driver with range 150-270V AC and Safety extra low voltage safe level<60V DC as per IEC Standard. Make:- Havells /Bajaj/CG/Wipro
S&F High efficient LED Street light fitting 25 watt, with Aluminium pressure Die cast housing parts for long life, High purity PC Fresnel diffuser with silicon gaskets for IP65 Protection, in-built electronic driver pre- wired up to terminal block,Suitable for external pole dia. Up to 35 mm, CRI >70,Temperature range- 0 to 45DegC, Driver efficiency>85%, Power factor>0.95, THD<10%, Colour Temperature- 5700K, Surge protection in CM-3.5KV, 50000 burning hours as per L70 Criteria, Multistage Isolated Constant Current- Constant Voltage Operated driver with range 150-270V AC and Safety Extra Low Voltage Safe level<60V DC as per IEC standard in and including 1.5 Mtr length GI tubing medium grade 25mm dia bent to shape with necessary CI clamps, bolts etc for fixing and connecting from ceiling rose to filling with 3 core 5 Sqmm insulated copper cable.
Supply and Fixing MCCB with thermal magnetic release 415 Volts, 4 pole 350 Amps capacity and breaking capacity 35 KA wiwth enclosure made our of 2 mm thick CRCA sheet duly powder coated suitable for mounting on wall including provision of cable entry for both incoming and out going complete all as specified and as directed.
Supply and Fixing MCCB with thermal magnetic release 415 Volts, 4 pole 160 Amps capacity and breaking capacity 36KA with enclosure made our of 2 mm thick CRCA sheet duly powder coated suitable for mounting on wall including provision of cable entry for both incoming and out going complete all as specified and as directed.
Supply and Fixing MCCB with thermal magnetic release 415 Volts, 4 pole 63 Amps capacity and breaking capacity 25 KA wiwth enclosure made our of 2 mm thick CRCA sheet duly powder coated suitable for mounting on wall including provision of cable entry for both incoming and out going complete all as specified and as directed.
M & L for chemical earthing complete with copper earth plate electrode 90cm x 60cm x 5mm thick buried directly in ground (earth pit not less than 3 mtr deep below ground level) with top edge of the plate not less than 2.10 mtr below normal ground level, connected to and including copper earth strip of 32x6 mm by means of rivetting and brazing and protected by GI pipe light grade of suitable size up to the test point i.e. up to 7.5 mtr, including providing alternate layers up to full volume of pit by charcoal dust and common salt, magnesium sulphate & vegetable soil all around the plate 15 cm depth and width minimum including PCC pit chamber, watering pipe of 50mm dia medium grade GI pipe up to the top of the plate having funnel complete and RCC cover, connecting to the test point and testing on ground complete and including excavation and earth work in any type of strata and cleaning of site all as specified in MES SSR Part-I and directed by Engineer-in-charge. Note :- Extra length of main earthing lead shall be measured beyond 7.5 mtrs under respective item of schedule
Earth continuity conductor or main earthing lead ixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any ther indicated situation for loop earthing etc. as required 32 x 6 mm copper strip
Supply, install, testing and commissioning of five star rated hi-wall split units indoor/outdoor with cordless remote control unit and with in built air ioniser and plasma filter for better indoor air quality with latest inverter technology having eco friendly refrigerent gas, copper condenser coil, EER 3.2 of capacity 2.0 TR including taking down old AC units and hand over to MES store yard omplete all as specified and directed by the Enginer-in-Charge. [Make: BLUE STAR / HITACHI / DAIKIN / CARRIER]
Supply, install, testing and commissioning of five star rated hi-wall split units indoor/outdoor with cordless remote control unit and with in built air ioniser and plasma filter for better indoor air quality with latest inverter technology having eco friendly refrigerent gas, copper condenser coil, EER 3.2 of capacity 1.5 TR including taking down old AC units and hand over to MES store yard complete all as specified and directed by the Enginer-in-Charge. [Make: BLUE STAR / HITACHI / DAIKIN / CARRIER]
S & F voltage stabiliser for automatic operation, single phase naturally air cooled, copper wounded as per IS 8448-1989 with digital display, wall mounted, indoor type & designed for input variation between 170 Volts to 250 Volts with output voltage stabilsed at 230 Volts with time delay and of capacity 5 KVA complete all as spcified and directed. [Make: V-GUARD / UNISTAB / VOLINA / VOLTAMP / VINTEK]
S & F voltage stabiliser for automatic operation, single phase naturally air cooled, copper wounded as per IS 8448-1989 with digital display, wall mounted, indoor type & designed for input variation between 170 Volts to 250 Volts with output voltage stabilsed at 230 Volts with time delay and of capacity 4 KVA complete all as spcified and directed. [Make: V-GUARD / UNISTAB / VOLINA / VOLTAMP / VINTEK]
S & F mild steel work as in brackets (stands) for fixing of outdoor units of 1.5 TR & 2 TR Split AC units including applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed by Engineer-in-Charge
S & F HDPE drain pipe of 20mm bore fixed to wall/roof complete all as specified and directed by Engineer-in-Charge. [Make: KISAN / JAIN IRRIGATION / FINOLEX / SUPREME / PRINCE]
Making opening/drilling of size 65 mm dia, using heavy duty stone driller/cutter machine in the stone machinry wall for installing spilit type air conditioners and for passing suction and discharge refrigerant pipe lines, drain pipe, cable etc and making good the disturbed surface all as directed.
Supply, install, testing and commissioning and testing of Automatic Air curtain unit of 5 fit/1490mm complete with door switch with controller for prevention of dust and conditioned air losses, single phase, 220 V, 50 HZ, Alumiium powder coated chasis with CRC plates, 5 feet long Air curtain with necessay fixing arrangement , Aluminium alloy fans and single phase electric motor, nozzles etc, complete with fittings and accessories so as to produce 21 m/sec air velocity at floor level for door opening as specified.
M & L for 120 / 180 Ltrs. PESO/CCOE Approved Cylinder with Valve all as specifed and directed
M & L for 80 Ltrs. PESO/CCOE Approved Cylinder with Valve all as specified and directed.
M & L UL Listed FK-5-1-12 agent for filling in cylinder all as specified and directed.
CE Approved Master Cylinder Accessories a. Electric Control Head, 24 V DC with Manual Actuator & Contact Pressure Gauge b. Discharge Hose c. Vent Valve Kit d. Warning Sign - HFC 227EA
Supply and fix Discharge Pressure Switch in the fire fighting system all as specified and directed.
Supply and fix Discharge Nozzle as pe suitable size into the fire fighting system all as specified and directed.
M & L for Cylinder Bracket suitable for fixing the 120/180 ltrs and 80 ltr cylinder all as specified and directed.
M & L for 2 Zone Gas Release Panel with battery back up including testing and commissioning all as specified and directed.
M &L for Conventional Smoke Detector with base complete with making connection all as specified and directed.
M & L for Manual Abort Switch including making all connection all as specified and directed
M & L for Manual Release Switch including making all connection all as specified and directed.
M & L for Hooter with strobe including makin all connection all as specifi
M & L for Remote response Indicator including making connection wit system all as specified and directed.
S & F copper conductor of size 2 x 1.5 Sqmm PVC round sheathed copper conductor FRLS cable, 1100V grade conforming to IS 694 multistanded, run on duct/concealed complete all spacified and directed.
Supply of MS seamless Pipe Network for 120 / 180 Ltrs including making all connection , testing and commisioning all as specified and directed .
Supply of Pipe Network for 80 Ltrs including making all connection , testing and commisioning all as specified and directed .
Installation of all MS seamless pipe Network for 80 and 120/180 cylinder including making all connections, testing and commissioning all as specified and directed
Installation of FAS ncluding making all connections, testing and commissioning all as specified and directed
Supply, installing, testing and commissioning of indoor type step down transformer of capacity 500 KVA, 11KV/433V, 3 phase, 50 HZ, ONAN cooled oil immersed copper wound (at no load), AC , 3 phase 50 Hz capacity step down, outdoor copper wound type complete with first filling of IS : 335 ISI marked and dehydrated transformer oil with standard fittings , HT 11 KV 3 phase , LT 433 volts, 3 phase 4 wire with off load tapings on HT side to vary secondary voltage within limit, all as per IS: 1180 part-I of capacity 500 KVA core type copper wound, oil immersed, naturally cooled, oil nature, air nature(ONAN) with external cooling tubes/fins delta connected on primary side (HV) and star connected on secondary side(LV) in accordance with vector symbol DYN-11(Vector group)with neutral brought out on secondary side (LV side ) and 7 position OFF circuit tap changer having tapping range at ±7.5% in steps of 2.5% each on HV side to be changed by means of hand operated off load tap changer gear. the maximum temperature rise should not exceed 45 degree Celsius in oil and 55 degree Celsius in HV/LV winding when measured by resistance method after continuous full load run on an ambient temperature of 40 degree Celsius. The transformer shall be IS 1180:2014 marked and shall comprise of the following :- (a) 3 Nos porcelain bushing with arcing horn on HV side suitable for 11 KV complete with bushing, copper rods, nut and washers. (b) one cable box on LT side (secondary side ) consisting with porcelain bushing with copper rod , complete with nuts and washers with two numbers cable glands suitable for connecting LT XLPE insulated heavy duty armored cable including glands, joints and jointing material complete.
Item No. 133 (Contd...) (c) Oil conservator with filter type drain valve and oil level gauge (d) Dehydrating breather with first fills dehydrating agents (Silca gel) (e) one cable box on HT side (Primary side ) consisting of 03 No of porcelain bushing with copper rod , complete with nuts and washers for connecting HT XLPE insulated heavy duty armored cable including glands, joints and jointing material complete. (f) explosive vent (g) thermometer pocket on tank cover (h) one number 100 mm dia, dial type thermometer, vapour pressure type having range 0-120 degree Celsius with metal guard having max perimeter reading temperature indicator with resisting device for transformer (j) Two earthing terminal on tank cover to facilitate fixing of 32x6 mm GI earth strip for earhting of neutral and body. (k) Rating plate and terminal marking plate. (l) Oil level gauge (m) Oil drain filter valve (n) lifting legs (p) Oil filling holes with cap/plug with connecting plate complete (q) Air release valve plug (r) Four plain solid cost steel detachable rollers (s) Extra bushing for neutral, outside LT cable box for proving independent earthing for neutral (t) First filling new and unused transformer oil IS-335/93(fourth version) marked (make -Savita/power oil) filtered and tested upto 60 KV dia-electric strength . Note : Certificate of die electric strength shall be submitted by the contractor after filling the oil.
Supply, installation, commissioning and testing silent diesel engine driven Generating Set 500 KVA (400 KW at 0.8 PF) capacity 415 Volts, 3 phase, 4 wire & with including acoustic weather proof enclosure as per latest CPCB II norms and noise level shall not be exceeding 75 db at a distance of 1 metre from all sides, complete in all respects & comprising the following components. Make : Kirloskar Green/Kirloskar Cummins (A) Diesel Engine developing suitable BHP at 1500 RPM conforming to BS 5514/ISO0346 series inclusive of the following accessories:- (i) Radiator and Radiator fan (ii) Spider coupling guard (iii) Fly wheel (iv) Fly wheel housing complete with starter gear ring and coupling as per manufacturer design. (v) Air cleaner dry type. (vi) Fuel and lubricant oil filter. (vii) By-pass filter (viii) Coolant inhibitor (ix) Fuel pump DTR type/in line mono block fuel injecting pump. (x) Water pump (xi) Lub oil pump and inclusive of first filling of lubricant oil & coolant. (xii) Electric starter 24 Volts DC as manufacturer's design. (xiii) Battery charging generator (DC alternator) (xiv) Industrial silencer (xvi) Flexible pipe for silencer
Item No. 134 (Contd...) (xvii) DC volt meter (xviii) Water temperatures gauge, lub oil pressure gauge (xix) Speedo meter and Engine running hours meter xx) Display for fault (xxi) Suitable size of turbo-charger (xxii) Shut off coil with safeties for LLOP/HWT. (xxiii)Electronic Governor. (xxiv) Maintenance free secondary batteries 180 AH 12 Volts as per manufacture design. (xxv) Safeties and indications against Low Lube Oil Pressure & High Coolant Temperature. (xxvi) Fuel Injection Pump with Electronic Governor and fuel feed pump. (xxviii)Engine mounting supports. (xxix)Engine control panel consisting of OFF/ON/START keys, Lube Oil Pressure Gauge, (xxx)Ammeter, Electric Hour meter. (xxxi)Engine Operator/Maintenance & Spare parts Manual. (xxxii)Engine Spare parts Manual. (xxxiii)Engine Warranty Certificate. (xxxiv)Engine test certificate. (B) Alternator:- Synchronous alternator 500 KVA,1500rpm, 415 Volts,50Hz, 3 phase system, brushless type,screen protected revolving filled self excited, self regulated, confirming to IS 4772 of 1992/BS 500.
Item No. 134 (Contd...) (xvi) Suitable type of ACB for main supply/DG Supply adjustable over load and adjustable short circuit . (xvii) The AMF panel shall have by pass arrangement in case failure of bypass AMF panel (xviii) Acoustic enclosure with natural air curculation without loss of any power to ventilation fan. The enclosure shall be modular in construction with hinged bolted structure to provide easy dismantling and shall be made out of high quallity CRCA steel sheet of 1.6mm thick with sufficient accessories for maintenance work openable and lockable door air tight gasket interior lightening arangement of 20 W fitting with On/Off switch to meet latest emission norms. (xix) Fuel tank of suitable capacity with inlet and outlet connectiions and fuel level indicator as per OEM recommendations. (xx) Base frame made out of suitable channel duly reinforced and provided with adequate numbers of anti vibration pads to ensure minimum vibration as recommended by manufacturer.
Supply install testing and commissioning ISOLATION TRANSFORMER Indoor type- suitable for IP 23 enclosure, input 400V/440V and output400Volts at no load AC 3 phase 50 Hz capacity 200 KVA, core type double copper wound ONAN cooled Oil immersed delta connected on primary side and star connected on secondary side in accordance with vector symbol DYN-II (vector group) with neutral brought out on secondary side (LV side) and having tapping at +5% in steps of 2.5% by means of off circuit tap link board. The maximum temperature reise 115 degree calsius by winding resistance method after continuous full load on an ambient temp of 50 degree celsius. The transformer shall be confirming to IS: 1180: 2014 and shall comprise of the following :- (a) Rating and diagram plate. (b) Two earthing terminals in two side. (c) Lifting lugs . (d) Off circuit link board. (e) Base channel with Bi- directional Rollers. (f) Danger board (g) 100 mm dial type thermometer. (h) Cable entry boxes etc on both sides
Supply, laying, jointing and testing, XLPE insulated, armoured, heavy duty, electric HT UG cable 120 Sqmm 3 Core with multi stranded aluminium conductor, 11000 Volts grade, earthed laid in trenches or in duct/passed through pipes or fixed to walls/poles etc complete as specified
Supply and fixing cable joiniting kit for 11 KV (earthed) grade cable for indoor termination cold shrink type joint complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 Sqmm complete all as specified and directed by Engr- in charge.
Supply, laying, jointing and testing, XLPE insulated, armoured, heavy duty, electric LT UG cable 400 Sqmm 3.5 Core with multi stranded aluminium conductor, 1100 Volts grade laid in trenches or in duct/passed through pipes or fixed to walls/poles etc complete (AVR Sub Stn transformer to to proposed LT Panel and LT panel to Chiller unit MCCB
Supply, laying, jointing and testing, XLPE insulated, armoured, heavy duty, electric LT UG cable 95 Sqmm 3.5 Core with multi stranded aluminium conductor, 1100 Volts grade laid in trenches or in duct/passed through pipes or fixed to walls/poles etc complete all as specified and directed. (LT Panel to UPS battery/ fire figthing room)
Supply, laying, jointing and testing, XLPE insulated, armoured, heavy duty, electric LT UG cable 70 Sqmm 3.5 Core with multi stranded aluminium conductor, 1100 Volts grade, cross sectional area of sizes laid in trenches or in duct/passed through pipes or fixed to walls/poles etc complete all as specified and directed. (LT Panel toVertical TPN DB)
Supply, laying, jointing and testing, XLPE insulated, armoured, heavy duty, electric LT UG cable 50 Sqmm 3.5 Core with multi stranded aluminium conductor, 1100 Volts grade laid in trenches or in duct/passed through pipes or fixed to walls/poles etc complete all as specified and directed. (LT Panel toVertical TPN DB)
Supply, laying, jointing and testing, XLPE insulated, armoured, heavy duty, electric LT UG cable 25 Sqmm 4 Core with multi stranded aluminium conductor, 1100 Volts grade laid in trenches or in duct/passed through pipes or fixed to walls/poles etc complete all as specified and directed. (LT Panel to technical discussion Room)
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deep for foundation etc for laying of cables, erection of poles, struts/stays etc not exceeding 10 sqm in hard /dense soil complete all as specified.
M&L for river washed sand, sreened dry for filling in the trenches below and around the UG cable for cushioning of cable including punning down complete all as specified and directed.
M & L for Un- reinforced pre cast concrete covers class LV type 250x 150x 40 size factory made for cable protection complete all as specified and directed.
M & L for Un- reinforced pre cast concrete covers class HV type 300mmx 180mm x 40mm size factory made for cable protection complete all as specified and directed.
Supply and fixing GI pipe light grade 100 mm dia for protection of HT/LT cable under road or on wall all as specified and directed .
M & L for earthing complete with GI earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to and including GI earth strip of 32 x 6mmm by means of rivetting and brazing and protected by GI pipe light grade of suitable size up to the test point i.e. up to 7.5 mtr, including providing alternate layers up to full volume of pit by charcoal dust and common salt, magnesium sulphate & vegetable soil all around the plate 15 cm depth and width minimum including PCC pit chamber, watering pipe of 50mm dia medium grade GI pipe up to the top of the plate having funnel complete and RCC cover, connecting to the test point and testing on ground complete and including excavation and earth work in any type of strata and cleaning of site all as specified in MES SSR Part-I and directed by Engineer-in-charge.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/GI pipe or fixed to poles or any other indicated situation for loop earthing etc as required of GI strip 32 x 6 mm complete all as specified and as directed
"Supply & install, testing and commissioning outdoor type LT electric panel weather proof , vermining proof consisting separate compartment for each out going feeders with locking arrangement for each feeder fabricated out of 3 mm thick MS sheet floor mounting type suitable size base frame/channel, painted with powder coated and including necessary PCC 1:3:6 type C2 foundation of panel boad and earth work including comprising the following :- (a) Bus bar chamber of 3 phase and neutral 4 strip 415 volts with 1200 Amps Aluminiun strip - 1 set (b) ACB 4 POLE, 415V, MANUAL DRAWOUT TYPE WITH MICROPROCESSOR RELEASE OF CAPACITY 800 AMPS CAPACITY - 1 No (In coming) (c) 4 POLE MCCB 250 TO 320 AMPS 50 Hz,415 V with rupturing capacity 35 KA (outgoing) 1 No (d 4 POLE MCCB 125 TO 160 AMPS 50 Hz,415 V with rupturing capacity 35 KA (outgoing) 1 No (e 4 POLE MCCB 100 TO 125 AMPS 50 Hz,415 V with rupturing capacity 35 KA (outgoing) 1 No (f) 4 POLE MCCB 100 TO 125 AMPS 50 Hz,415 V with rupturing capacity 35 KA (outgoing) 1 No (g) 4 POLE MCCB 63 TO 100 AMPS 50 Hz,415 V with rupturing capacity 25 KA (outgoing) 1 No (h) Three phase volt meter digital type 0 - 500 Volts - 1.0 (j) Three phase Ammeter with suitable ratings CTs- 1.0 (k) LED Indicator lamp Red, Yellow, Blue - 01 Set (l) Complete internal wiring with suitable copper condutor wires - 1 Lot (m) Provision of extra space for two more out going feeders suitable 160Amps & 125 Amps ( with out MCCB ) Note : (i) All termination of existing cable should be provided with copper lugs/thimbles and suitable size of glands & rate for the same is deemed to be included in the item
M&L for cutting of black top cover of existing road up to 1 mtr depth and 60 cm wide for laying of UG cable and pipe line, refilling and making good after laying UG cable and pipe line with PCC 1:3:6 uptp 30 cm from top of the road surface comple all as directed by EIC.
M/S J J ENTERPRISES
Sai Ram Builders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .