Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.4 CrAccepted-AOC | ₹25.4 Cr | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹26.8 CrRejected-Finance | ₹26.8 Cr | L2 | Rejected-Finance Other than lowest |
| 3 | L3₹27.3 CrRejected-Finance | ₹27.3 Cr | L3 | Rejected-Finance Other than lowest |
| 4 | L4₹30.1 CrRejected-Finance | ₹30.1 Cr | L4 | Rejected-Finance Other than lowest |
| Sl No | Description | Qty | Unit | SOM BUILDERS L4 | BANSI BUILDER AND CONTRACTORS PVT LTD L1 | Kartik Builders L3 | Sood Enterprises L2 |
|---|---|---|---|---|---|---|---|
| 0.00NOTE:- (Applicable for all parts/items/):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates. | |||||||
| 1.00 | Lump sum price worked out by the tenderer for BUILDING WORKS as listed in Schedule ‘A’ Part-I(Ref pre-priced schedule attached separately) | 1 | Lump Sum | 19,84,61,958 ₹19.8 Cr | 15,50,26,495 ₹15.5 Cr | 16,81,88,100 ₹16.8 Cr | 16,31,42,457 ₹16.3 Cr |
| 2.00 | Lump sum price worked out by the tenderer for INTERNAL ELECTRIFICATION WORKS as listed in Schedule ‘A’ Part-II(Ref pre-priced schedule attached separately) | 1 | Lump Sum | 30,00,000 ₹30 L | 32,50,000 ₹32.5 L | 27,57,645.29 ₹27.6 L | 30,05,109.28 ₹30.1 L |
| 3.00 | Lump sum price worked out by the tenderer for INTERNAL WATER SUPPLY WORKS as listed in Schedule ‘A’ Part-III(Ref pre-priced schedule attached separately) | 1 | Lump Sum | 8,00,000 ₹8 L | 6,50,000 ₹6.5 L | 7,97,048.45 ₹8.0 L | 7,65,166.51 ₹7.7 L |
| 4.00 | Lump sum price worked out by the tenderer for ROAD, PATH AND CULVERT WORKS as listed in Schedule ‘A’ Part-IV(Ref pre-priced schedule attached separately) | 1 | Lump Sum | 3,20,00,000 ₹3.2 Cr | 2,90,00,000 ₹2.9 Cr | 3,70,65,014.25 ₹3.7 Cr | 3,17,09,016.84 ₹3.2 Cr |
| 5.00 | Lump sum price worked out by the tenderer for AREA DRAINAGE WORKS as listed in Schedule ‘A’ Part-V(Ref pre-priced schedule attached separately) | 1 | Lump Sum | 39,00,000 ₹39 L | 37,00,000 ₹37 L | 35,69,258.75 ₹35.7 L | 40,66,244.15 ₹40.7 L |
| 6.00 | Lump sum price worked out by the tenderer for SEWAGE DISPOSAL WORKS as listed in Schedule ‘A’ Part-VI(Ref pre-priced schedule attached separately) | 1 | Lump Sum | 25,00,000 ₹25 L | 24,50,000 ₹24.5 L | 24,83,166.73 ₹24.8 L | 24,83,166.73 ₹24.8 L |
| 7.00 | Lump sum price worked out by the tenderer for COMPOUND WALL, FENCING AND GATE WORKS as listed in Schedule ‘A’ Part-VII(Ref pre-priced schedule attached separately) | 1 | Lump Sum | 70,00,000 ₹70 L | 68,25,000 ₹68.3 L | 79,28,452 ₹79.3 L | 77,61,537.71 ₹77.6 L |
| 8.00 | Lump sum price worked out by the tenderer for EXTERNAL WATER SUPPLY WORKS as listed in Schedule ‘A’ Part-VIII(Ref pre-priced schedule attached separately) | 1 | Lump Sum | 7,00,000 ₹7 L | 8,15,000 ₹8.2 L | 6,59,062 ₹6.6 L | 6,99,178.68 ₹7.0 L |
| 9.00 | Lump sum price worked out by the tenderer for EXTERNAL ELECTRIFICATION as listed in Schedule ‘A’ Part-IX(Ref pre-priced schedule attached separately) | 1 | Lump Sum | 33,92,898.45 ₹33.9 L | 30,50,000 ₹30.5 L | 29,85,750.02 ₹29.9 L | 37,32,188.3 ₹37.3 L |
Tender Value
₹23.9 Cr
EMD Value
₹15 L
Closing Date
19 Jul 2025, 6:00 pmClosed
Chief Engineer Bathinda Zone
Headquarters Chief Engineer Bathinda Zone Military Engineer Services PIN- 900484 C/o 56 APO
PROVN OF OTM ACCN FOR FD HOSPITAL AT BATHINDA MIL STN
2025_MES_711593_1
84CE BTZ/BTD/TOKEN-14 OF 2025-26 84484
Open Tender
Civil Works
548 days
Bathinda
As per Notice Inviting Tender (NIT)
8 documents required · 8 mandatory
₹3,000
GE (P) Bathinda
₹15 L
Yes
Chief Engineer Bathinda Zone
27 Aug 2025
30 May 2025
21 Jul 2025
30 May 2025
19 Jul 2025
7 Jul 2025
30 May 2025 - 12 Jul 2025
13 Jun 2025
Amount
NOTE:- (Applicable for all parts/items/):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates.
Lump sum price worked out by the tenderer for BUILDING WORKS as listed in Schedule ‘A’ Part-I(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for INTERNAL ELECTRIFICATION WORKS as listed in Schedule ‘A’ Part-II(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for INTERNAL WATER SUPPLY WORKS as listed in Schedule ‘A’ Part-III(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for ROAD, PATH AND CULVERT WORKS as listed in Schedule ‘A’ Part-IV(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for AREA DRAINAGE WORKS as listed in Schedule ‘A’ Part-V(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for SEWAGE DISPOSAL WORKS as listed in Schedule ‘A’ Part-VI(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for COMPOUND WALL, FENCING AND GATE WORKS as listed in Schedule ‘A’ Part-VII(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for EXTERNAL WATER SUPPLY WORKS as listed in Schedule ‘A’ Part-VIII(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for EXTERNAL ELECTRIFICATION as listed in Schedule ‘A’ Part-IX(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for SUMMER COOLING APPLIANCES, AIR CONDITIONING AND HOT WATER SUPPLY as listed in Schedule ‘A’ Part-X(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for LIGHTENING PROTECTION as listed in Schedule ‘A’ Part-XI(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for LANDSCAPING as listed in Schedule ‘A’ Part-XII(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for DEMOLITION as listed in Schedule ‘A’ Part-XIII(Ref pre-priced schedule attached separately)
Lump sum price worked out by the tenderer for SITE CLEARANCE, EXCAVATION AND EARTH WORKS as listed in Schedule ‘A’ Part-XIV(Ref pre-priced schedule attached separately)
Schedule 'A' Part-XV(FURNITURE)
Almirah large steel as per drawing No. FD-1031 sheet No. 1/1
Almirah small steel as per drawing No. FD-1032 sheet No. 1/1
Stool revolving (adjustable) (steel) as per drawing No. FD-354 sheet No. 1/1
Bath Mat (PVC) as per drawing No. FD/E6/MAP/07 sheet No. 1/1
Bed Hard as per drawing No. FD/E6/MAP/08(R) sheet No. 1/1
Bed Stead Iron Hospital as per drawing No. HFD/ 2001 sheet Nos 1/2 & 2/2
Work bench workshop (1800 mm X 900 mm X 760 mm) (steel) as per drawing No. FD-1024 sheet No. 1/1
Board Notice as per drawing No. FD-1(M) sheet No. 1/1
Book shelf open (small) steel as per drawing No. FD-69(M) sheet No. 1/1
Barber Chair with adjustable Headrest as per Model No. IK-2687 of Ikonic Furniture/ Professional or equivalent of Marc Salon Furniture
Chair CB (Office) with arms (steel) as per drawing No. FD-75(M) sheet No. 1/1
Visitor Chair, PP Cushion Arm, Powder Coated Pipe Stand, Leatherette Tapestry as per Model No. GM-226 A of Geeken or equivalent of Godrej, Methodex as approved by the GE
Chair CB'A' special with hand rest as per drawing No. FD-120(M) sheet No. 1/1
Chair Computer as per drawing No. FD/E6/MAP/01 sheet No. 1/1
Table typing (steel) as per drawing No. FD-1005 sheet No. 1/1
Chair dining with long back as per drawing No. FD-357 sheet No. 1/1
Chair easy per drawing No. FD-229 sheet No. 1/1
Chair easy as per drawing No. FD-358 sheet No. 1/1
Chair Writing as per drawing No. FD/E6/MAP/12 sheet No. 1/1
Chair verandah as per drawing No. FD/MAP-II/06 sheet No. 1/1
Chair writing as per drawing No. FD-280 sheet No. 1/1
Charpoy with hard top as per drawing No. FD/MAP-II/01 sheet No. 1/1
Examination Couch as per drawing No. HFD/ 2019 sheet No 1/1
Desk with Dias Wooden as per drawing No. FD-399 sheet Nos 1/2 and 2/2
Board Notice (2440 mm X 1220 mm) as per drawing No. FD-99(M) sheet No. 1/1
Drugget of variety No. Wollen, 60 tex X 12 warp, size 3000 mm X 2000 mm as per IS 697: 2005
Form with back (1800 mm long) as per drawing No. FD-78(M) sheet No. 1/1
Form without back(1900 mm long) (steel) as per FD-1027 sheet No. 1/1
Hat stand (small) as per drawing No. FD-361 sheet No. 1/1
Hot case small as per drawing No. FD-363 sheet No. 1/1
Ladder aluminium as per drawing No. FD-1025 sheet No. 1/1
Locker (steel) as per drawing No. FD-1029 sheet Nos 1/2 & 2/2
Magazine rack medium as per drawing No. FD-365 sheet No. 1/1
Mattress of size 1980 mm X 900 mm X 100 mm of Make:- Sleepwell/Kurl-on/Coir-fom as approved by the GE
Board notice (900 mm X 600 mm) as per drawing No. FD-366 sheet No. 1/1
Pegs (set of three) as per drawing No. FD-80(M) sheet No. 1/1
Polyester fibre filled pillows and outer protective cover as per IS IS 18930: 2024
S & F Kitchen stainless steel plate rack of size 31" X 30" X 10" as per catalogue No. P-346 of Prayag or equivalent of Make mentioned under Appendix ‘B’ to Particular Specification including necessary fixing / fittings & making good the existing surfaces complete all as specified and as directed.
Pointer long 1525 mm as per drawing No. FD-1041 sheet No. 1/1
Pointer medium 1220 mm as per drawing No. FD-1041 sheet No. 1/1
Pointer short 900 mm as per drawing No. FD-1041 sheet No. 1/1
Rack pigeon hole (steel) as per drawing No. FD-1037 sheet No. 1/1
Rack for 20 rifles as per drawing No. BTD 96 of HQ CE Bathinda Zone.
Rack six tiers (dimension as 1905 mm X 915 mm X 610 mm) (steel) as per drawing No. FD-1038 sheet No. 1/1
Receptacle as per drawing No. FD/E6/MAP/13 sheet No. 1/1
Receptacle (small) with bin per drawing NO. FD-1045 sheet No. 1/1
Meat safe (large) as per drawing No. FD-370 sheet No. 1/1
Screen Movable 3 Fold Steel as per drawing No. HFD/ 2015 sheet No 1/1
Side Board as per drawing No. FD-371 sheet No. 1/1
Side rack with tray four spaces (steel) as per FD-1023 Sheet No. 1/1
Sofa set single seater as per drawing No. FD-373 sheet Nos 1/2 & 2/2
Sofa set to seat 5 as per drawing No FD-373 sheet Nos 1/2 & 2/2
Stool revolving (adjustable) as per drawing No. FD-103(M) sheet No. 1/1
Stool dressing as per drawing No. FD/E6/MAP/14 sheet No 1/1
Stool steel (510 mm high) as per drawing No. FD-409 sheet No. 1/1
Table (600 mm X 600 mm X 760 mm) as per drawing No. FD-293 sheet No. 1/1
Table for Havs & Ors (steel) as drawing No. FD-1007 sheet No. 1/1
Table with drawer (900 mm X 600 mm X 760 mm) (steel) as per drawing No. FD-1008 sheet Nos 1/2 & 2/2
Table bed Side as per drawing No. FD/E6/MAP/15(R) sheet No. 1/1
Table card (900 mm X 900 mm X 760 mm) as per drawing No. FD-352 sheet No. 1/1
Table centre two tier (900 mm X 450 mm X 400 mm) as per drawing No. FD-274 sheet No. 1/1
Table centre as per drawing No. FD-375 sheet No. 1/1
Table conference as per drawing No. FD-287 sheet Nos 1/2 & 2/2
Table cook as per drawing No. FD-297 sheet No. 1/1
Table dining for six persons (1500 mm X 900 mm X 760 mm) as per drawing No. FD-273 sheet Nos 1/2 & 2/2
Table dining for eight persons (1800 mm X 900 mm X 760 mm) as per drawing No. FD-273 sheet Nos 1/2 & 2/2
Dining table for OR's as per drawing No. FD-165(M) sheet No. 1/1
Table dressing (gents) as per drawing No. FD-379 sheet Nos 1/2 & 2/2
Dressing table (ladies) as per drawing No. FD-378 sheet No. 1/1
Table clerks (steel) as per drawing No. FD-1004 sheet No. 1/1
Table officers (steel) as per drawing No. FD-1003 sheet Nos 1/2 & 2/2
Table pantry (steel) as per drawing No. FD-1020 sheet No. 1/1
Peg table (450 mm X 300 mm X 380 mm) as per drawing No. FD-384 sheet No. 1/1
Table writing (1145 mm X 600 mm X 760 mm) as per drawing No. FD-275 sheet No. 1/1
Table conference/ library (steel) as per drawing No. FD-1001 sheet Nos 1/2 & 2/2
Teapoy Verandah as per drawing No. FD/E6/MAP/17 sheet No. 1/1
Teapoy as per drawing No. FD-278 sheet No. 1/1
Trestle store room (steel) as per drawing No. FD-1043 sheet No. 1/1
Schedule 'A' Part-XVI(ARBORICULTURE)
M & L for trenching in ordinary soil up to a depth of 60 cm including removal and stacking of serviceable materials and then disposing of surplus soil, by spreading and neatly leveling within a lead of 50 m and making up the trenched area to proper levels by filling with earth or earth mixed with sludge or / and manure before and after flooding trench with water (excluding cost of imported earth, sludge or manure) complete all as specified and as directed.
Supplying and stacking at site dump manure screened through sieve of IS. designation 20 mm from approved source, including carriage from outside MD land complete all as specified and as directed. Note: Manure measured in stacks will be reduced by 8% for payment.
M & L for rough dressing the trenched ground including breaking clods complete all as specified and as directed.
M & L for uprooting weeds from the trenched area after 10 to 15 days of its flooding with water including disposal of uprooted vegetation complete all as specified and as directed.
M & L for fine dressing of the ground complete all as specified and as directed.
M & L for spreading of sludge, dump manure and/or good earth in required thickness complete all as specified and as directed. Note: Cost of sludge, dump manure and/ or good earth to be paid separately.
M & L for preparation of beds for hedging and shrubbery by excavating 60 cm deep and trenching the excavated base to a further depth of 30 cm, refilling the excavated earth after breaking clods and mixing with sludge or manure in the ratio of 8:1 (8 parts of stacked volume of earth after reduction by 20% : one part of stacked volume of sludge or manure after reduction by 8%), flooding with water, filling with earth if necessary, watering and finally fine dressing, leveling etc. including stacking and disposal of materials declared unserviceable and surplus earth by spreading and leveling as directed, within a lead of 50 m, lift up to 1.5 m complete all as specified and as directed. Note: Cost of sludge, manure or extra earth to be paid for separately.
M& L for plantation of shrubs, hedge etc. at the site including watering and removal of unserviceable material including shrub/ hedge plants of any type and of height 60-75 cm in earthen pots of size 20 cm complete all as specified and as directed.
Complete maintenance after physical completion of plants/Hedge/grass by weeding hosing, saucer making once in every week for plants/Hedge once in every 10 days for carpet grass/country grass/doob grass, burmuda grass, prunning dried branches once in every week, depositing the material at place as directed by Engr-In-Charge and planting the new plants in place of dead plants of same species and height tuning with dods wherever required by replacing the dead patches of grass with the same grass as required without extra cost to the deptt and all as directed by Engr-In-Charge. Note:(i) Manure and pesticide required for maintenance of plant under this items shall be arranged by the contractor at his own cost and rate of the same shall be deemed to be included in the unit rate quoted against this items (ii) Scope of maintenance shall be as specified in Ph-II. (iii) Work against this item will be commenced only after completion of plantation of trees, plantation of grass and plantation of hedge & shrubbery.
Schedule 'A' Part-XVII(MISCELLANEOUS PARTS)
Supply, installing, commissioning and testing frost free refrigerator electric driven single phase 220 volts, AC 50 Hz, 180 litres or next higher capacity with BEE approved, minimum 5 star rating single door, stabilizer free operation, Inverter Technology, R600a Refrigerant, tempered glass self, deodorizer and with fruit & vegetables drawer complete all as specified and as directed. Note (a) Contractor shall submit original purchase voucher and warranty card as recommended by manufacturer.
Supply, installing, commissioning and testing frost free refrigerator electric driven single phase 220 volts, AC 50 Hz, 300 litres or next higher capacity with BEE approved, minimum 5 star rating single door, stabilizer free operation, Inverter Technology, R600a Refrigerant, tempered glass self, deodorizer and with fruit & vegetables drawer complete all as specified and as directed. Note (a) Contractor shall submit original purchase voucher and warranty card as recommended by manufacturer.
Supply, installing, commissioning and testing frost free refrigerator electric driven single phase 220 volts, AC 50 Hz, 415 litres or next higher capacity with BEE approved, minimum 5 star rating single door, stabilizer free operation, Inverter Technology, R600a Refrigerant, tempered glass self, deodorizer and with fruit & vegetables drawer complete all as specified and as directed. Note (a) Contractor shall submit original purchase voucher and warranty card as recommended by manufacturer.
Supplying, fixing, testing and commissioning Industrial cooler (evaporative cooling unit), minimum dia 900 mm, minimum airflow 25000 cum per hour, Axial fan type, Noise maximum 70 decibel, coverage area 100 to 200 sqm, water consumption 65 to 90 liter, UV protected cooler body including 36-liter water tank, standard duct with auto swing grills with all fixing arrangements complete all as specified and as directed. Note: - Industrial sockets and three phase control copper wires shall be measured and paid separately.
S & F evaporative air coolers (desert coolers) as per IS 3315: 2019, minimum air capacities 6000 cum per hour, sump tank capacity 120 litres, cooling efficiency not less than 65%, maximum power consumption 400 watts, plastic body, noise level not more than 65 dBA at 1 m distance including connecting up with three core flexible copper conductor cable of suitable size including numbering of coolers using two coats of synthetic enamel paint complete all as specified and as directed.
Supply and fixing Air grills of any size, made of ABS materials with auto swing and rust free, specially engineered grill for 2 X longer air flow & wider angle coverage and upto 50 % less sound complete all as specified and as directed.
S & F XLPE insulation sheet with one side aluminium foil, 9 mm thick, thermal conductivity 0.0382 W/m0K at mean air temperature of complete all as specified and directed.
S & F in integrated type Heat Pump water heater with following components including installation testing and commissioning Outdoor Air cooled Integrated or split type Heat Pump with recirculation mode having minimum compressor capacity 3 HP, hermetically sealed with environment friendly refrigerant. At Rated heating Capacity, the heat pump must be able to deliver hot water at 65˚C (outlet temperature), at the rate not less than 120 litre per hour at minimum water inlet temperature of 4˚C and outlet temperature of 60˚C, and minimum 300 litre per hour in hybrid mode. At Rated heating Capacity, the heat pump must be able to deliver hot water at 65˚C (outlet temperature), at the rate not less than 120 litre per hour at minimum water inlet temperature of 4˚C and outlet temperature of 60˚C, and minimum 300 litre per hour in hybrid mode. The ratio of Rated output heating capacity to Rated Input Power should be such that COP of the machine is not less than 3.0 and must have Back-up heater power of not less than 12 kW and rated power input of not more than 2.5 kW. The heat pump shall have water storage tank of capacity (having internal glass lining) not less than 450 litre. NOTE: (a) Heat pump should have all the safety protections like high/low voltage, high temperature, refrigerant leak, compressor overheat protection with operational noise level not more than 60 dbA. (b) Heat pump should have a user friendly control panel to set the desired temperature with display of the actual temp also with flexibility of installing the same 15-30 m away from the heat pump.
S & F stainless steel braided flexible connection pipe for hot and cold water supply for geyser, 15 mm bore, 450 mm length, 12 bar working pressure complete all as specified and as directed.
Supplying, installing, testing and commissioning inverter type air cooled split unit air conditioner hot and cold type with indoor unit (IDU), outdoor unit (ODU) of capacity 1.50 TR, single phase, input voltage 170 to 270 V AC, 50 Hz, surface / concealed copper Refrigerant piping with insulation (EP Foam pipe section) up to 5 metre (IDU to ODU), copper power cable up to 4 metre, PVC Insulation, FR-LSH copper wire, complete with inverter, twin rotary compressor, cordless remote control unit and with inbuilt air ioniser and Plasma filter for better indoor air quality with BEE 3 star rating having ISEER value not less than 3.8 complete all as specified and as directed.
Supplying, installing, testing and commissioning inverter type air cooled split unit air conditioner hot and cold type with indoor unit (IDU), outdoor unit (ODU) of capacity 2.0 TR, single phase, input voltage 170 to 270 V AC, 50 Hz, surface / concealed copper Refrigerant piping with insulation (EP Foam pipe section) up to 5 metre (IDU to ODU), copper power cable up to 4 metre, PVC Insulation, FR-LSH copper wire, complete with inverter, twin rotary compressor, cordless remote control unit and with inbuilt air ioniser and Plasma filter for better indoor air quality with BEE 3 star rating having ISEER value not less than 3.8 complete all as specified and as directed.
Supplying, installing, testing and commissioning automatic, servo controlled, indoor type, voltage stabilizer of capacity 4 kVA, single phase, IP55 protection, copper wound, naturally air cooled type, insulation class H, designed for input voltage of 160 V to 270 V and output voltage of 230 V ± 1%, voltage correction rate of 15 V per second, metallic body with lifting hook duly power coated, LCD display for Input and Output Voltage, frequency, current, Time Delay and Mains ON with under and over voltage protection, short circuit protection, surge protection all as per IS 8448: 1989 complete all as specified and as directed.
Supplying, installing, testing and commissioning automatic, servo controlled, indoor type, voltage stabilizer of capacity 5 kVA, single phase, IP55 protection, copper wound, naturally air cooled type, insulation class H, designed for input voltage of 160 V to 270 V and output voltage of 230 V ± 1%, voltage correction rate of 15 V per second, metallic body with lifting hook duly power coated, LCD display for Input and Output Voltage, frequency, current, Time Delay and Mains ON with under and over voltage protection, short circuit protection, surge protection all as per IS 8448: 1989 complete all as specified and as directed.
Supply, installing, commissioning and testing of washing machine with washer extractor of capacity 28 kg to 30 kg (dry weight per washing cycle) front loading electrically driven including water connection from PVC tank to washing machine as per requirement and drain out pipe from machine to drain complete all as specified and as directed and comprising of following specifications/ accessories/capacity/size and material shall be as per OEM/Manufacturer recommendations: - (i) Industrial washer extractor. (ii)Outer drum/ Inner basket/ outer basket made out of high grade stainless steel sheet of SS304 grade with perforation. (iii) Front loading and unloading open pocket. (iv) Forward and reverse basket rotation. (v) 01 No Heavy duty high spin single phase motor, variable frequency drive type of suitable capacity and 01 Nos driver motor three phase 415 volts variable frequency drive type of suitable capacity. (vi) Suspension with shock absorber and springs. (vii) Fully programmable microprocessor and auto balance while extraction. (viii) Manual dosage of powder detergent. (ix) Door limits electric inter locking and emergency stop for safety and trouble free and operation both manual and auto lock. (x) Aluminium casted pulley and belt. (xi) Main body of full stainless steel 304 grade. (xii) Heater of suitable KW. (xiii) PCC foundation as required shall be as per manufacturers recommendation NOTE: - (a) Contractor shall submit necessary company test certificate and purchase voucher and warranty cards as per recommendation by vender. (b) Testing and commissioning shall be carried out by authorized rep of the firm/company for which no extra payment shall be made.
Supply, installing, commissioning and testing of drying tumbler electrically heated suitable for washing machine as per above item having loading capacity of 28 KG to 30 KG per charge Fin type Electric Heater of 24 Kw made out of SS pipe, front loading type, Auto Timed, Auto reveres, Microprocessor controlled with electric motor and electric panel complete. Fully die pressed door, inner basket stainless steel basket of min 503 litre volume, outer body mild steel sheet insulated with glass wool complete all as specified and directed. Note: - (a) The Contractor shall submit necessary company test certificate and purchase voucher and warranty cards as per recommended by vender. (b) Testing and commissioning shall be carried out by authorized rep of the firm/ company for which no extra payment shall be made.
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed.
Supplying, installing, testing and commissioning 2.0 Ton Cassette type with BEE 3-star rating having ISEER value not less than 3.8 with heating and cooling function & digital inverter units indoor/outdoor complete with cordless remote control units and with inbuilt heating and cooling arrangements and digital inverter twin rotary compressor, single phase units 220V -240V 50 Hz of capacity all as specified and directed
Supply, installing, commissioning and testing frost free refrigerator electric driven single phase 220 volts, AC 50 Hz, 270 litres or next higher capacity with BEE approved, minimum 5 star rating single door, stabilizer free operation, Inverter Technology, R600a Refrigerant, tempered glass self, deodorizer and with fruit & vegetables drawer complete all as specified and as directed. Note (a) Contractor shall submit original purchase voucher and warranty card as recommended by manufacturer.
Supplying, installing, testing and commissioning diesel engine driven generating set 100 kVA /80 kW (prime power), 415 volt, 50 Hz, 3 phase, 4 wire, at 1500 rpm, 0.8 lagging power factor including diesel engine, alternator, coupling, common base plate, acoustic enclosure, 12 V DC battery, AMF Panel. Exhaust system, foundation etc. complete all as specified and as directed. Note: - The emission limits for diesel engine driven generating set shall be as specified in Table 1 of the Environment (Protection) Third Amendment Rules, 2022.
M & L for forming embankments using earth brought from outside MD land including raising (or lowering) earth, spreading in layers not exceeding 30 cm thick; watering, ramming/rolling and finishing to required size, shape, etc., not exceeding 1.5 m high from base complete all as specified and as directed.
Material and labour for construction and laying of kerb of size as directed directly on the road construction site with automatic kerb casting machine (kerb/divider making/laying machine), using M25 (Design Mix) grade cement concrete laid in position to the required line, level and curvature kerb stone cast continuous and making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm) at a distance as directed, including making drainage opening wherever required, including necessary excavation/earth work and making good disturbed surface complete all as specified and as directed.
Supplying, laying, connecting, jointing and testing in trenches 150 mm nominal dia ductile iron pressure pipe for water mains, centrifugally cast, spigot and socket ends (for push on joints), class K7 in any length with external protection of Metallic zinc with finishing layer of bituminous paint and internal linings of Portland cement (with or without additives) mortar with seal coat, all as per IS 8329: 2000 and including materials and jointing with rubber gasket for WA type of application and hardness class 50 for bulb and hardness class 80 for heel all as per IS 5382: 2018 and IS 12820: 2004 complete all as specified and as directed.
Supplying, laying, connecting, jointing and testing in trenches 100 mm nominal dia ductile iron pressure pipe for water mains, centrifugally cast, spigot and socket ends (for push on joints), class K7 in any length with external protection of Metallic zinc with finishing layer of bituminous paint and internal linings of Portland cement (with or without additives) mortar with seal coat, all as per IS 8329: 2000 and including materials and jointing with rubber gasket for WA type of application and hardness class 50 for bulb and hardness class 80 for heel all as per IS 5382: 2018 and IS 12820: 2004 complete all as specified and as directed.
Supplying, laying, connecting, jointing and testing in trenches ductile iron fittings (special castings) (class K12 as per IS 9523: 2000) for ductile iron pressure pipe for water mains upto 250 mm nominal dia (spigot and socket and flange ends (for push on joints and flanged joints) with external coatings of Metallic zinc with finishing layer of bituminous paint and internal linings of Portland cement (with or without additives) mortar with seal coat, all as per IS 9523: 2000 and including materials and jointing with rubber gasket for WA type of application and hardness class 50 for bulb and hardness class 80 for heel all as per IS 5382: 2018 and IS 12820: 2004 for push on joints and rubber gasket as per IS 638: 1979 for flanged joints complete all as specified and as directed.
S & F ductile iron air relief valve, type of double air valve – standard type with in-built isolating valve (DS 1), nominal size 50 mm, PN 1.6, flange end, conforming to IS 14845: 2000 complete all as specified and directed.
M & L for construction of new valve pit/chamber of size 750 mm (Length) X 750 mm (Breadth) X 750 mm (depth) including necessary earth work in any type of soil, PCC foundation M7.5(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate as in base concrete, brick work with sub class 'B' bricks, non-modular sizes as per IS 1077: 1992, straight or curved on plan exceeding 6 m mean radius built in cement mortar 1:6, cement plaster 20 mm thick internally in two coats of (15 mm and 5 mm) in cement mortar 1:4, 3 mm thick mild steel sheet of any grade and designation as per IS 513: 2008 and IS 10748: 2004 welded with angle iron (40 mm X 40 mm X 6 mm) frame of structural steel, frame welded with angle iron (50 mm X 50 mm X 6 mm) frame of structural steel, welded to flat iron of size 150 mm X 50 mm X 6 mm of structural steel, fixed with bolt of 16 mm dia anchored with plate of size 100 mm X 100 mm X 3 mm of structural steel, bolt and anchored plate embedded in 250 mm thick PCC coping in M15(Nominal Mix) using 20 mm nominal size graded crushed stone aggregate, mild steel handle, grade E165 as per IS 15911: 2010 for structural steel with necessary, welding, riveting, bolting including painting exposed steel surfaces with two coats of bituminous paint and embedded surfaces of steel with two coats of tar, finishing exposed faces of concrete surfaces and plaster surfaces with three coats of white wash and all as per drawing No. BTD-811 Sheet Nos 1/2 and 2/2 of HQ CE Bathinda Zone complete all as specified and as directed.
Supply and fix metal oxide surge arrester without gap for AC system as per IEC 60099-4: 2014, outdoor type, porcelain housing, single column and single phase construction, station class, heavy duty, nominal discharge current 20 kA, switching impulse discharge current 2 kA, repetitive charge transfer rating (Qrs) more than 2.4 C, thermal energy rating (Wth) more than 10 kJ/kV, nominal system voltage 11 kV, highest system voltage 12 kV, rated voltage of arrester 9 kV, continuous operating voltage 7.2 kV, temporary overvoltage (10.15 kV for 1 s, 9.50 kV for 10 s, 8.75 kV for 100 s), rated short circuit current 20 kA, low short circuit current 600 A, insulation withstand level (lightning impulse voltage 1.2/ 50 µs) 75 kV, lightning impulse residual voltage (8/20 µs) at nominal discharge current maximum 26 kV, switching impulse residual voltage (30/60 µs) at switching impulse discharge current maximum 21 kV, high current impulse withstand capability (4/10 µs) 100 kA, minimum creepage distance 300 mm complete all as specified and as directed.
Supply, testing, commissioning and Installation of Compact substation comprising 11 kV, 630 Amps RMU, 500 KVA copper wound oil cooled, off circuit Transformer with LT side ACB as below:- HT Section: - 11 kV three way RMU 630 Amp 21 KA for 3 sec SF-6 insulated one side extensible switchgear consisting of three Nos (02 No incoming & 01 No outgoing) of motorized VCB in SF-6 insulated SS enclosure with 24 V DC closing/opening shunt trip coils, Aux switch, Mechanical On/Off push button, mechanical operating counter with metering cubical auxiliary relay, under voltage relay, 8 window annunciator model No Sl-801, Battery power pack with 7 AH battery & in-built charger for 24V circuit. Potential Transformer – 3 Phase cast resin of ratio 11 KV/110V, Class-0.5, 100VA with HT primary fuses. Current Transformer – Cat resin Ratio: 50-25/5+5A, core 1: Cl 0.5, 15 VA, core: CI.5P10,15VA. Protection: Numerical 2OC + 1EF Relay. Micro based non-directional IDMT. Indication lamps: - VCB Off/On/Auto trip/ Trip circuit healthy/ Spring charge indication. Transformer Section: - mineral oil immersed, natural air-cooled, outdoor type, double wound (copper) distribution transformer, three phase, 500 kVA rating, non-sealed type, 50 Hz rated frequency, 11 kV high voltage and 415 V low voltage nominal system voltage, minimum 75 kVp basic insulation level, 11000 V/ 433-250 V no-load voltage ratio, connection (vector) symbol Dyn11, 30⁰ positive phase displacement, off circuit tap changing arrangement for voltage variations of +5% to -10% in steps of 2.5% for variation of HV, minimum energy efficiency level 2 (Star 2 as per the notification issued by the Central Government, in consultation with the Bureau of Energy Efficiency and including all the amendments issued up-to-date), 4.5% impedance, ONAN type cooling all as per IS-1180 (Part 1): 2014 including amendment upto and including amendment No. 4 dated 04 Mar 2021 complete with all fittings, accessories and item as specified and as directed. Note: - The energy efficiency level higher than the minimum energy efficiency level as specified here shall be provided without any extra cost in case the transformer of minimum energy efficiency level is not available. LV side Incomer: - 01 No 800 Amps 4 Pole, 50 KA MDO Air circuit breaker micro processor based with O/L,S/C & E/F protection – RYB indication lamp with all accessories.
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 4.0 mm dia galvanised mild steel wire by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 20 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed.
Supplying, installing, testing and commissioning factory made, CPRI approved, outdoor type, floor mounting LT panel board of adequate size, made of cold rolled close annealed sheet of 3 mm thick with 50 mm X 50 mm X 6 mm angle iron frame works, powder coated, dust & vermin proof, front and rear openable, double doors, compartmentalized, Form 4b construction, conforming to IS/IEC 60947 : PART 1 : 2007, locking arrangements, suitable for 3 phase 4 wire 415 V, 50 Hz with 1200 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection including wiring with single core PVC power cable of suitable size and including mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm complete all as specified and as directed. and shall be comprising the followings: - (A) 1200 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection – 4 Nos (B) Wiring with single core PVC, copper power cable of suitable size (C) Incoming: (a) Air Circuit Breaker (ACB) of rated current 800 A, Rated operational voltage 415 V, Rated insulation voltage 1000 V, 4 Pole, 50 Hz AC supply, Rated ultimate short circuit breaking capacity 50 kA, Rated service short circuit breaking capacity 50 kA, Rated short time withstand capacity 50 kA for 1 second, Rated making capacity 105 kA, Rated impulse withstand voltage of main circuit 8 kV, typical opening time 40 ms, typical closing time 60 ms, thermal magnetic release, manual draw out, overload protection, short circuit protection, earth fault protection – 1 No (D) Outgoing: (a) MCCB rated current (In): 200 A, Icu: 25 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -2 Nos
Supplying, installing, testing and commissioning factory made, CPRI approved, outdoor type, floor mounting LT panel board of adequate size, made of cold rolled close annealed sheet of 3 mm thick with 50 mm X 50 mm X 6 mm angle iron frame works, powder coated, dust & vermin proof, front and rear openable, double doors, compartmentalized, Form 4b construction, conforming to IS/IEC 60947 : PART 1 : 2007, locking arrangements, suitable for 3 phase 4 wire 415 V, 50 Hz with 150 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection including wiring with single core PVC power cable of suitable size and including mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm complete all as specified and as directed. and shall be comprising the followings: - (A) 150 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection – 4 Nos (B) Wiring with single core PVC, copper power cable of suitable size (C) Incoming: (a) MCCB rated current (In): 100 A, Icu: 16 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (D) Outgoing: (a) MCCB rated current (In): 80 A, Icu: 16 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (b) MCB, TPN, 10 kA, C-type, rated current 6 to 32 A: -2 Nos (c) MCB, DP, 10 kA, C-type, rated current 6 to 32 A: -1 No (d) On load change over switch, 4 pole, 100 Amp: - 1 No (E) Accessories:
Supplying, installing, testing and commissioning factory made, CPRI approved, outdoor type, floor mounting LT panel board of adequate size, made of cold rolled close annealed sheet of 3 mm thick with 50 mm X 50 mm X 6 mm angle iron frame works, powder coated, dust & vermin proof, front and rear openable, double doors, compartmentalized, Form 4b construction, conforming to IS/IEC 60947 : PART 1 : 2007, locking arrangements, suitable for 3 phase 4 wire 415 V, 50 Hz with 300 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection including wiring with single core PVC power cable of suitable size and including mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm complete all as specified and as directed. and shall be comprising the followings: - (A) 300 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection – 4 Nos (B) Wiring with single core PVC, copper power cable of suitable size (C) Incoming: (a) MCCB rated current (In): 200 A, Icu: 25 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (D) Outgoing: (a) MCCB rated current (In): 160 A, Icu: 25 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (b) MCB, DP, 10 kA, C-type, rated current 6 to 32 A: -4 Nos (c) On load change over switch, 4 pole, 200 Amp: - 1 No (E) Accessories:
Supplying, installing, testing and commissioning factory made, CPRI approved, outdoor type, floor mounting LT panel board of adequate size, made of cold rolled close annealed sheet of 3 mm thick with 50 mm X 50 mm X 6 mm angle iron frame works, powder coated, dust & vermin proof, front and rear openable, double doors, compartmentalized, Form 4b construction, conforming to IS/IEC 60947 : PART 1 : 2007, locking arrangements, suitable for 3 phase 4 wire 415 V, 50 Hz with 300 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection including wiring with single core PVC power cable of suitable size and including mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm complete all as specified and as directed. and shall be comprising the followings: - (A) 300 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection – 4 Nos (B) Wiring with single core PVC, copper power cable of suitable size (C) Incoming: (a) MCCB rated current (In): 200 A, Icu: 25 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (D) Outgoing: (a) MCCB rated current (In): 100 A, Icu: 16 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (b) MCCB rated current (In): 32 A, Icu: 10 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (c) MCB, TPN, 10 kA, C-type, rated current 6 to 32 A: -1 No (d) MCB, DP, 10 kA, C-type, rated current 6 to 32 A: -4 Nos
Supplying, installing, testing and commissioning factory made, CPRI approved, outdoor type, floor mounting LT panel board of adequate size, made of cold rolled close annealed sheet of 3 mm thick with 50 mm X 50 mm X 6 mm angle iron frame works, powder coated, dust & vermin proof, front and rear openable, double doors, compartmentalized, Form 4b construction, conforming to IS/IEC 60947 : PART 1 : 2007, locking arrangements, suitable for 3 phase 4 wire 415 V, 50 Hz with 300 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection including wiring with single core PVC power cable of suitable size and including mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm complete all as specified and as directed. and shall be comprising the followings: - (A) 300 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection – 4 Nos (B) Wiring with single core PVC, copper power cable of suitable size (C) Incoming: (a) MCCB rated current (In): 200 A, Icu: 25 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (D) Outgoing: (a) MCCB rated current (In): 100 A, Icu: 16 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (b) MCCB rated current (In): 63 A, Icu: 16 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No
Supplying, installing, testing and commissioning factory made, CPRI approved, outdoor type, floor mounting LT panel board of adequate size, made of cold rolled close annealed sheet of 3 mm thick with 50 mm X 50 mm X 6 mm angle iron frame works, powder coated, dust & vermin proof, front and rear openable, double doors, compartmentalized, Form 4b construction, conforming to IS/IEC 60947 : PART 1 : 2007, locking arrangements, suitable for 3 phase 4 wire 415 V, 50 Hz with 100 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection including wiring with single core PVC power cable of suitable size and including mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm complete all as specified and as directed. and shall be comprising the followings: - (A) 100 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection – 4 Nos (B) Wiring with single core PVC, copper power cable of suitable size (C) Incoming: (a) MCCB rated current (In): 63 A, Icu: 16 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (D) Outgoing: (a) MCCB rated current (In): 32 A, Icu: 10 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (b) MCB, TPN, 10 kA, C-type, rated current 6 to 32 A: -2 Nos (c) MCB, DP, 10 kA, C-type, rated current 6 to 32 A: -6 Nos (d) On load change over switch, 4 pole, 200 Amp: - 1 No (E) Accessories:
Supplying, installing, testing and commissioning factory made, CPRI approved, outdoor type, floor mounting LT panel board of adequate size, made of cold rolled close annealed sheet of 3 mm thick with 50 mm X 50 mm X 6 mm angle iron frame works, powder coated, dust & vermin proof, front and rear openable, double doors, compartmentalized, Form 4b construction, conforming to IS/IEC 60947 : PART 1 : 2007, locking arrangements, suitable for 3 phase 4 wire 415 V, 50 Hz with 200 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection including wiring with single core PVC power cable of suitable size and including mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm complete all as specified and as directed. and shall be comprising the followings: - (A) 200 Amps rated aluminium bus bar fully insulated with class F materials and nuts, bolts, washers for connection – 4 Nos (B) Wiring with single core PVC, copper power cable of suitable size (C) Incoming: (a) MCCB rated current (In): 125 A, Icu: 25 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (D) Outgoing: (a) MCCB rated current (In): 80 A, Icu: 16 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (b) MCCB rated current (In): 32 A, Icu: 10 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, for 415 V, 50 Hz AC supply: -1 No (c) MCB, TPN, 10 kA, C-type, rated current 6 to 32 A: -2 Nos (d) MCB, DP, 10 kA, C-type, rated current 6 to 32 A: -4 Nos
M & L for auguring under road, pavement, hard standing, railway lines by trenchless technology using latest boring technique and necessary machine for insertion of GI/CI/PP-R/PVC pipe of any dia/ bore/size complete all as specified and as directed.
Supply and erect factory made 7 meter long hot dip galvanized (as per relevant IS with average coating thickness 65 micron) octagonal poles conform to IS-2062/ BSEN 10025 with 155 mm dia at bottom and 70 mm dia at top A/F made up of 3 mm thick HT sheet along with foundation type base plate of size 250 mm X 250 mm X 16 mm, foundation bolt 4 Nos of M20 X 600 mm high 'J' type EN8 grade, including 1 meter long hot dip galvanized single arm (swan neck) bracket made up of 40 NB dia GI pipe and including excavation, earth work, PCC (1:2:4) type B1 for foundation and grouting the bolts as per manufacturer’s instructions including marking pole number in letters & figures of size not less than 10 cm height with red colour enamel paint complete all as specified and as directed. Note: - (i) Srl number will be issued by Engineer-in-Charge.
S & F three core flexible conductor FR-LSH cables for outdoor use, PVC insulation of type C and having PVC sheath of type ST2, 2.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor for fittings complete all as specified and as directed.
Material and labour for laying of double wall corrugated pipe (DWC), non-metallic, Resistance to Compression : Type 450, Resistance to Impact: Normal, Resistance to Bending : Pliable, Resistance to External Influence: Ingress Protection : IP 67, Resistance against Corrosion : Without Protection, Resistance to Flame Propagation : Non Flame Propagating, Nominal outside diameter 160 mm, minimum inside dia 120 mm conforming to IS 16205 (Part 24) : 2017 including boring of holes by trenchless technology using ultra sounding technique and necessary machine including all fittings complete all as specified and as directed.
Material and labour for laying of double wall corrugated pipe (DWC), non-metallic, Resistance to Compression : Type 450, Resistance to Impact: Normal, Resistance to Bending : Pliable, Resistance to External Influence: Ingress Protection : IP 67, Resistance against Corrosion : Without Protection, Resistance to Flame Propagation : Non Flame Propagating, Nominal outside diameter 90 mm, minimum inside dia 67 mm conforming to IS 16205 (Part 24) : 2017 including boring of holes by trenchless technology using ultra sounding technique and necessary machine including all fittings complete all as specified and as directed.
Material and labour for laying of double wall corrugated pipe (DWC), non-metallic, Resistance to Compression : Type 450, Resistance to Impact: Normal, Resistance to Bending : Pliable, Resistance to External Influence: Ingress Protection : IP 67, Resistance against Corrosion : Without Protection, Resistance to Flame Propagation : Non Flame Propagating, Nominal outside diameter 50 mm, minimum inside dia 37 mm conforming to IS 16205 (Part 24) : 2017 including boring of holes by trenchless technology using ultra sounding technique and necessary machine including all fittings complete all as specified and as directed.
M & L for cable route indicator made out of CI plate 100 dia, 8 mm thick, embossed with lettering "MES LT Cable", welded or bolted onto 35 mm X 35 mm X 6 mm angle iron, 500 mm long duly painted with anti-corrosive paint in brown colour & including necessary earthwork and excavation, embedded in PCC M15(Nominal Mix) using 20 nominal size graded crushed stone aggregate of size 400 mm X 400 mm X 300 mm complete all as specified and as directed.
Supply and fix precast HT cable route indicator made of PCC M15 (Nominal Mix) using 12.5 mm nominal size crushed stone aggregate of size 300 mm (Length) X 100 mm (Width) X 500 mm (Height) duly painted with cement base paint and written in white colour with lettering "MES HT Cable/ HT Straight Joint" using two coats of synthetic enamel paint in black colour & including necessary earthwork and excavation, embedded in PCC M15(Nominal Mix) using 20 nominal size graded crushed stone aggregate of size 400 mm X 400 mm X 300 mm complete all as specified and as directed.
S & F pole mounted decorative LED post top with IP-65 protection as per Bajaj luminaire type BLPTSP 25W WH LED, product code 111741 or equivalent of Philips or Crompton Greaves including necessary wirings and testing commissioning complete all as specified and as directed.
Supply & fixing 3 Phase, 5 kW automatic street light control switch using infrared sensor based twilight/ nature switch for automatic switching of streetlights, consisting of weatherproof powder coated metal box of suitable size, 1 No of twilight/ nature switch dusk to dawn, 25 Amps 3 pole contactor- 1 No, 20 Amps MCB- 6 Nos (3 Nos input and 3 Nos output) including wiring with10 sqmm copper wiring, IP54 protection grade complete all as specified and as directed.
S & F polymer pin insulator, Type B, Nominal System voltage 3.3 kV, highest system voltage 3.6 kV, visible discharge test voltage 3 kV, wet power frequency withstand voltage 21 kV, power frequency puncture withheld voltage 78 kV, impulse withstand voltage 45 kV, minimum total creepage distance 75 mm, minimum failing load 5 kN, of suitable size with galvanised steel insulator pin, nut, washers complete all as specified and as directed.
S & F class SN 8 structured wall polyethylene piping system (pipe with online coupler and elastomeric rubber ring) with hollow annular profiled outer surface and a smooth inner surface (double wall corrugated) for non-pressure underground drainage and Sewerage application, Type B, Nominal Size (DN/ID) 150, made of polyethylene (PE) material conforming to per IS 16098 (Part 2):2013 and to be transported, handled, installed and jointed as per Annex A of IS 16098 (Part 2):2013 complete all as specified and as directed.
S & F class SN 8 structured wall polyethylene piping system (pipe with online coupler and elastomeric rubber ring) with hollow annular profiled outer surface and a smooth inner surface (double wall corrugated) for non-pressure underground drainage and Sewerage application, Type B, Nominal Size (DN/ID) 200, made of polyethylene (PE) material conforming to per IS 16098 (Part 2):2013 and to be transported, handled, installed and jointed as per Annex A of IS 16098 (Part 2):2013 complete all as specified and as directed.
Supply, Installation, testing and commissioning of Non-clog Submersible pump for handling sewage water and having discharge of minimum 396 LPM and 8-19M head, 415 Volts, 50 Hz, 2840 RPM, class "F" insulation, IP68 protection, 40 degree centigrade operating temperature with Cl Impellor, Cl motor body, Cl pump housing, stainless steel shaft and delivery pipe size of 50mm including hoisting submersible sewage pump into sewage collection tank using suitable stainless steel heavy duty chain (Gde 316) and anchoring with hook on top of sewage tank with necessary nuts, bolts, washers etc. complete all as specified and directed.
Supplying, laying, connecting, jointing and testing in trenches 80 mm nominal dia ductile iron pressure pipe for water mains, centrifugally cast, spigot and socket ends (for push on joints), class K7 in any length with external protection of Metallic zinc with finishing layer of bituminous paint and internal linings of Portland cement (with or without additives) mortar with seal coat, all as per IS 8329: 2000 and including materials and jointing with rubber gasket for WA type of application and hardness class 50 for bulb and hardness class 80 for heel all as per IS 5382: 2018 and IS 12820: 2004 complete all as specified and as directed.
S & F submersible cable flat PVC insulation of type C and having PVC sheath of type ST2, flexible copper conductor, FR-LSH, 3 core of size 2.5 sqmm complete all as specified and as directed.
Supplying, installing, testing and commissioning factory made, CPRI approved, outdoor type, floor mounting LT panel board of adequate size, made of cold rolled close annealed sheet of 3 mm thick with 50 mm X 50 mm X 6 mm angle iron frame works, powder coated, dust & vermin proof, front and rear openable, double doors, compartmentalized, Form 4b construction, conforming to IS/IEC 60947 : PART 1 : 2007, locking arrangements, suitable for 3 phase 4 wire 415 V, 50 Hz with 50 Amps rated copper bus bar fully insulated with class F materials and nuts, bolts, washers for connection including wiring with single core PVC power cable of suitable size and including mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm complete all as specified and as directed. and shall be comprising the followings: - (A) 50 Amps rated copper bus bar fully insulated with class F materials and nuts, bolts, washers for connection – 4 Nos (B) Wiring with single core PVC, copper power cable of suitable size (C) Incoming: (a) MCB, TP, 10 kA, C-type, rated current 20 A: -1 No (D) Outgoing: (a) MCB, TP, 10 kA, C-type, rated current 10 A: -2 Nos (b) DOL Starter, 415 Volt, suitable for upto 3 HP motor, 4 to 6 Amps – 2 Nos (E) Accessories: (a) Rotary switch 3 Phase- 1 No (b) Push button start and stop – 2 Nos (c) Ultrasonic non-contact type water level sensor with PLC – 1 No (d) LED indicating lamps – 3 Nos (e) Single Phase preventer of suitable rating- 2 Nos (f) Multifunctional digital voltmeter and amp meter including CT coils 32/5 A – 1 No (g) Danger Notice Plate for LT
Srl Item No 17.055 Continued...... (F) The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.)
Providing and fixing stone Jalli 50 mm thick throughout, decorative, red sand stone, pattern as approved by the GE, in cement mortar 1:3 (1 cement: 3 coarse sand), including pointing in white cement mortar 1:2 (1 white cement: 2 stone dust) with an admixture of pigment, matching the stone shade, Jalli slab without any chamfers etc. complete all as specified and as directed.
S&F stainless steel 304 grade 1.6 mm thick SS sheet cascade fountain waterfall of Size 1.2 X 0.10 X 0.15 m and nozzle 1.5 inch with complete accessories all as per manufacturer’s instructions and as directed by Engineer in charge Note: The sample shall be approved by GE before placing the order
S&F stainless steel 304 grade 1.6 mm thick SS sheet cascade fountain waterfall of Size 1.5 X 0.10 X 0.15 m and nozzle 1.5 inch with complete accessories all as per manufacturer’s instructions and as directed by Engineer in charge Note: The sample shall be approved by GE before placing the order
Supply, install, testing and commissioning of openwell submersible pump of SS body, single phase, Voltage range 240 V, 50 Hz, Speed 2800 rpm, Head 12-18 meter, discharge 0.45-1.8 lps, Size 25mm X 25 mm with all necessary accessories required for fixing as directed by Engineer in charge.
Supply and fix heavy duty metal direct online starter single phase 1 Hp motor starter ideal for Open well submersible pump all as per specified and directed by Engineer in charge.
Supply and fixing of 18 watt Submersible LED(RGB) based decorative fountain light with colour changing facility, made out of die cast stainless steel (304 grade), emitter type power LEDs with all-in-one optical lens of efficiency 85%, step tempered glass of 8mm thickness with protection class of IP-68, including connection and waterproof jointing etc, as required for fixing as directed by Engr-in charge.
Supply and fixing of fountain LED light controller assembly consists of 12 V constant voltage driver ,10 A DMX controller with SMPS and power contractor, including the control circuit wiring with 1.5 Sqmm FRLS PVC insulated flexible copper wire, MCB Etc., as required for fixing as directed by Engr-in charge.
Supply and fixing of waterproof IP 67 neon flex LED strip lights ice blue, 120 high quality LEDs arrange every 3.3 ft deliver well balanced flicker free lighting over a 160-degree beam angle, the size of flexible neon light strip is 8 x 12 mm covered by high quality silicon tube, very thin, light, soft and waterproof besides it can be cut after every 1 meter, including 12 volt adapter and 2 pin connector etc, as required for fixing as directed by Engr-In-Charge.
Supply, installation, commissioning and testing of factory made (CPRI approved) LT panel feeder pillar Board of suitable size, outdoor type (double door panel including locking arrangements) 240 Volts, dust proof, vermin proof made out of CRCA sheet 3 mm thick powder coated and fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, panel shall be mounted on angle iron frame and 04 Nos legs made from angle of size 40 mm X 40 mm X 5 mm, legs shall be 750 mm long, 300 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 450 mm ground clearance, frame and legs duly spray painted with seven tank process internally and externally with two coats of synthetic enamel over a coat of red oxide primer, internal wiring of panel board with solid conductor copper cable single core of suitable size, danger notice plate for LT with conventional skull and bones duly riveted/ pasted to the panel board door, complete including all connection incoming/ outgoing all as directed and comprising of following accessories:- Incoming: (a) MCB SPN 40 Amp, 240 V, 'C ' curve - 01 No incoming (b) LED Indicating Lamps Red, yellow and blue -03 Nos Outgoing: (c) MCB SP 20 AMP 'C' curve -02 Nos (d) MCB SP 10 AMP 'C' Curve -02 Nos (e) Space for up to 2 HP DOL starter - 02 Nos (f) internal power and control wiring with suitable size PVC insulated multistranded copper wire. Note: - All type of spare such as gland, lugs, nut, bolts etc., necessary excavation and earthwork, PCC work and making good disturbed surface shall be deemed to be included in coated unit rate.
S & F LED bollard lights nominal power 10 watt, pressure die-cast aluminium alloy housing with polyester powder coated, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 800, lumen efficacy of minimum 100 lumens per watt, built-in integrated electronic LED driver, output open /short circuit protection, phase to phase protection, over voltage protection, surge voltage protection upto 2 kVs, protection grade IP 65, CRI greater than 70, CW available CCT of 5700⁰K, power factor of minimum 0.95, life span of minimum 50000 working hours including fixing at any height and including wiring using three core PVC insulated, PVC sheathed, flexible stranded copper conductor FR-LSH cables suitable for outdoor use, 1.5 sqmm as per IS 694: 2010 complete all as specified and as directed.
S & F pole mounted junction box, size 200 mm X 140 mm X 95 mm made of FRP with connector for single phase supply and arrangement to fix MCB SP 6A 10 KA complete all as specified and as directed.
Supply and fix Y Type Strainer of size 25 mm small resistance drip system pressure regulator all as specified and directed by Engr-In-Charge.
Supply and laying 3 layer PPR perforated pipe suitable for drip irrigation hole at a distance of 45 cm with end cap as required at site including all PPR palin & brass threaded polypropylene random fittings required for size 16mm dia with complete fittings as specified and directed by Engr-In-Charge.
Supply and fix Sprinkler set 2 feet height, 3.2 Kgs, L clamp with adopters, bends, tees of 25mm dia bore with all connected accessories as specified and directed by Engr-In-Charge.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2 mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 6 Way 240 V, suitable for mounting MCB/Isolator etc., conforming to IS-13032, DB shall be semi glossy finished with epoxy polyester based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessary complete all as specified and directed
S & F TPN distribution board 6 way vertical type double door made out of CRCA mild steel sheet surface with insulated material like polyester or with powder coating flush/surface mounting with copper busbar of suitable rating, with neutral bar and earth bar and cable tie for cable management, IP54 Protection and provision and including MCCB 4 pole upto 200 Amp,16KA as incomer and provision for MCBs as outgoing, dust and vermin proof complete as per IEC61439-3 complete all as specified and as directed. Note: MCBs for outgoing shall be measured and paid separately.
S & F blanking plate in DBs of MCB complete all as specified and as directed.
S & F LED bulb with battery/Invertor, System Wattage: 9 Watt, Rated Voltage: 230 Volt, Frequency: 50 Hertz, Operating Voltage Range: 170 to 270 Volt, System Current (mA): < 46, Power Factor: ≥ 0.90, System Lumen Efficacy (lumens/watt or lumens): 100, Total Harmonic Distortion (THD): ≤ 30 %, Color Rendering Index (CRI): ≥ 80, Driver Efficiency: ≥ 85 %, Ingress Protection: IP20, Correlated Color Temperature (CCT) (As per ANSI): 6500⁰ Kelvin, Emergency Light Output (Lumen %): 50, Mounting/Holder Type/Base cap: B22d, System Protections: Open & Short circuit protection, reverse polarity protection, surge protection of 2.5KV internal, Battery Type: Li-Ion, Battery Backup (in Hours): 3, Certification Standards: LM80, Conformity to Indian Standard: IS:16102 part I and Part II latest complete all as specified and as directed.
S & F LED bulb, System Wattage: 0.5 Watt, Rated Voltage: 230 Volt, Frequency: 50 Hertz, Operating Voltage Range: 170 to 270 Volt, System Current (mA): < 46, Power Factor: ≥ 0.98, System Lumen Efficacy (lumens/watt or lumens): 100, Total Harmonic Distortion (THD): ≤ 30 %, Color Rendering Index (CRI): ≥ 80, Driver Efficiency: ≥ 85 %, Ingress Protection: IP20, Correlated Color Temperature (CCT) (As per ANSI): 6500⁰ Kelvin, Mounting/Holder Type/Base cap: B22d, System Protections: Open & Short circuit protection, reverse polarity protection, surge protection of 2.5KV internal, Certification Standards: LM80, Conformity to Indian Standard: IS:16102 part I and Part II latest complete all as specified and as directed.
S & F LED light fitting 1 X 20 Watt flame proof, CIMFR certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminium hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and as directed.
Supply, fixing and testing LED batten with battery/Invertor, LED Rating (in Watts)/System Wattage/Rated Power: 20 Watt, Rated Voltage & Frequency: 230V, 50Hz, Luminaire System Efficacy (Lumen/watt): 100, Operating Voltage Range: 140-280V, Power Factor: ≥0.95, Total Harmonic Distortion: ≤30%, Colour Rendering Index(CRI): ≥80, Colour Temperature: 5000⁰-6500⁰ Kelvin, Driver Efficiency: ≥85%, Emergency Time: 3 hour, Ingress Protection: IP-20, Type of Control Gears: Electronic, Working life for LED (as per LM-80 and LM 21 reports): ≥50000 hours, Housing Material: Aluminium Extruded, Front Cover Material: Polycarbonate, Surge Protection of 3.0 kV Internal: Yes, Open & Short Circuit Protection: Yes, Reverse Polarity Protection: Yes, Battery Type: Li-Ion, Battery Backup (in Hours): 3, Emergency Light Output (Lumen %): 50, including connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
S & F 15 mm nominal size, nonrising spindle type fancy angle stop valves, two ways in double control with wall flange, made of cast brass including knob, knob components, divertor & components, nickel-chromium plated finish complete all as specified and as directed.
S & F single lever concealed divertor including bath spout and shower complete all as specified and as directed.
S & F brass chromium plated aquaguard/ RO inlet valve or diverter valve with nozzle compatible for all type of water purifier filing to steel pipe of socket of 15 mm complete all as specified and as directed.
M & L for bracket made out of GI pipe 25 mm dia medium grade, 1.2 metre long bent to shape with MS flat iron clamps made out of 40 mm X 6 mm thick mild steel nuts, bolts including taking down old unserviceable complete all as specified and as directed.
Supply, install, commissioning and testing Automatic road boom barrier (electrically operated) of length 6.0 metre complete with following major components and making functional complete all as specified and as directed (a) Drive Mechanism: Consisting of Max 1/4 HP, reversible motor, coupled through a timing belt ("V" belt) to oil filled and sealed type composite gear drive unit internal unit with internal looking feather, friction clutch, circuit controller, hand crank arrangement for manual operation at the time of electric supply failure, control switch gear with contactors motor rating MCB, electronic surveillance circuit terminals etc., system should be such to work in voltage range of 200 to 250 Volt , 50 Hz AC complete all as specified and as directed and as per OEM Recommendation.
S & F Aluminium Composite Materials (ACM) signboard, 4 mm overall thickness, sandwiched construction with a thermoplastic core of 'Low Density Polyethylene' (LDPE), aluminium skin thickness of 0.4 - 0.5 mm and 0.25 - 0.3 mm respectively on both sides, a fluorocarbon coating applied over the exposed surface of aluminium, Type-IV high intensity retro-reflective sheeting made of micro-prismatic retro-reflective element material coated with pressure sensitive adhesive on top surface with aluminium surface, digitally colour printed indicating necessary sign, text, symbol, etc. all as mentioned in IRC 67-2022 complete all as specified and as directed.
Sood Enterprises (BID ID -3364340)
Kartik Builders (BID ID -3363376)
SOM BUILDERS (BID ID -3356444)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid