Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.0 CrAccepted-AOC | ₹4.0 Cr | L1 | Accepted-AOC Due to lowest bid price |
| 2 | L2₹4.2 CrRejected-Finance 208 L MODEL TOWN LUDHIANA | LUDHIANA | PUNJAB | 141001 | ₹4.2 Cr | L2 | Rejected-Finance Due to high bid price |
| 3 | L3₹4.3 CrRejected-Finance | ₹4.3 Cr | L3 | Rejected-Finance Due to high bid price |
Tender Value
₹4.3 Cr
EMD Value
₹8.6 L
Closing Date
6 Jan 2026, 11:00 amClosed
Executive Engineer
Provincial Division PWD BandR DAC Complex Sangrur
Turnkey Works in PET/SPECT and LINAC Building in Homi Bhabha Cancer Hospital, Sangrur (Punjab)
2026_CEPW_156970_1
Bid no 79 Dt. 22-12-2025
Open Tender
Civil Works - Buildings
180 days
Sangrur
Please refer Tender documents.
6 documents required · 6 mandatory
₹20,000
₹8.6 L
Yes
2 Mar 2026
1 Jan 2026
6 Jan 2026
1 Jan 2026
6 Jan 2026
1 Jan 2026
Civil Works:- Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material within 50 meters lead as directed by Engineer-in-charge
Providing and laying resilient vinyl sheet floor covering 2 mm thick, having a vinyl plastic wear layer with backing duly fixed to the base floor using adhesive as approved by the manufacturer.
Providing and Laying Self Levelling compund for providing smooth finish for Vinyl Flooring
Providing and fixing mineral fibre false ceiling tiles ( NRC 0.55 to 0.6) at all heights of size 595X595x16 mm of approved texture, design and pattern.The tiles should have Humidity Resistance (RH) of 99%,Light Reflection>85%,Thermal Conductivity k =0.052- 0.057w/mK, Fire Performance as per (BS 476 pt- 6&7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33mm thick (galvanized @120gsm) comprising of mainT runners of 15x32mm of length 3000mm,crossTof size15x32mm of length1200mm and secondary intermediate crossTof size15x32mm of length600mm to form grid module of size600x600 mm suspended from ceiling using galvanized mildsteel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2mm, spaced at 1200mm centre to centre along main‘T’.The system should rest on peripherywalls/partitions with the help of GI perimeter wall angle of size24x24X3000mm made of 0.40mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long drywall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge.
Providing and fixing ceiling at height upto 4 mtr consisting of 12.5mm thick Gypsum Board of any size G.I. Cradling hanged from the ceiling by means of G.I. hanger complete as per drawings, specifications and to the entire satisfaction of engineer-in- charge.
Dismantling cement conglomerate floors 25mm to 50mm thick including concrete base.
Earth work in excavation in foundations trenches etc. in all kinds of soil where Pick-Jumper work is not involved and not exceeding 2.0 metres depth including dressing of bottom and sides of trenches, stacking the excavated soil clear from the edge of excavation and subsequent filling around masonry in 15 cm, layers with compaction including disposal of all surplus soil as directed within lead of 30 metres.
Providing and Supplying of Lead Sheet of 2mm thickness complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Base course of floor consisting of 100mm thick cement concrete 1:8:16 with stone aggregate 40mm gauge and 100mm sand filling using mechanical mixer for mixing of material
Cement concrete 1:2:4 with stone ballast or shingle mixing by manual means
Providing and Fixing of GI Hinge Lead Door with 2mm lead sheet complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing of 2mm Lead equivalent Glass Window of 10mm thickness with frame complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing of 4mm Acrylic inbuilt Name plates (10''x4'') complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing 5mm thick Sunboard Sign Boards with vinyl lamination print complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing of Acrylic LED Letters complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing of Acrylic Letters complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing of Acrylic Cutout Letters with self adhesive complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing of Backlit Fabric Signage complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Scraping white wash and colour wash
Preparation of plastered or concrete surface for painting (including sand papering the surface) using ready mixed cement based wall putty by applying two or more coats to get required finish
Applying priming coat with cement primer in all shade on newly plastered or concrete exterior surface
Distempering with Acrylic washable oil bound distemper (of approved manufacture) one coat over one priming coat on old distempered surface
Finishing walls with acrylic smooth exterior paint of required shade with two or more coats applied @ 1.67 litre/10Sqm over and including base coat of water proofing Cement Paint applied @ 2.20 Kg/10 Sqm
Dismantling brick work tile, masonary or tile lining In cement
First class burnt brick work laid in cement sand mortar 1:6 in first storey upto 4 metres above plinth level.
Extra for First Floor
Dismantling glazed tiles(to be carefully removed).
12.5 mm thick cement plaster 1:5
Extra Rate for First Floor
Reinforced cement concrete M-20 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in superstructure
Extra Rate for First Floor
Centering and shuttering for sides and soffits of beam, beams, launching girders, bressumers, lintels.
Extra Rate for First Floor
Cold twisted detormed (Ribbed/ Tor steel) Bars (Fe 500 grade as per IS 1786-2008) , for R.C.C works, where not including in the complete rate of RCC including bending and binding placing in position complete
Extra for First Floor
Providing and fixing aluminum work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate z sections and other sections conforming to Is: 733 and IS : 1285 of Jindal, Hindalco, Mahavir or equivalent make approved by Engineer in Charge , fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC Plug/neoprene felt etc. aluminum sections shall be smooth, rust free, straight, mitered and jointed mechanically wherever required including cleat angle, aluminum snap beading for glazing/paneling, C.P.brass/stainless steel screws, all complete as per architectural drawings and the directions of Engineer-InCharge. (Glazing and paneling to be paid for separately) : For fixed portion and chawkhats
For shutters of doors, windows & ventilators including providing and fixing hinges/pivots and labour for fixing of fittings wherever required including the cost of PVC Plug / neoprene gasket required
Providing Polyester Powder coating 50 micron any coloured specified to alumnum section of various sizes including carriage of material from market to workshop & workshop to site of work
Providing and fixing aluminum Wire Mesh including cost of necessary fittings i.e. screws,u Type Beading etc. complete
Providing and fixing glazing in aluminum door, window, ventilator shutters and partitions etc. with PVC Plug/ neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminum snap beading shall be paid in basic item). Float glass panes of 5 mm thickness
Cost of Aluminium fittings complete for doors, windows such as tower bolts, handless and screw etc. for these fittings (Excluding sliding bolt) For shutter area above 0.50 sqm
Providing and fixing aluminum grill 6.3 mm including cost of necessary fittings i.e. screws,u Type Beading etc. complete
Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in paneling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer-In-Charge. Prelaminated particle board with decorative lamination on Both side.
Providing and fixing aluminium sliding door bolts ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : 300mm x 16mm
Providing and fixing 1st quality ceramic glazed wall tiles Matt/Semi Matt/Glosy/Highly Gloss finish/Highlighter/emboss conforming to IS : 15622 (thickness to be specified by the manufacture of approved make in all colours, shades except burgundy, bottle green, black of size 600 x 300 mm as approved by Engineer-inCharge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:4 (1 cement: 4 fine sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete.
115mm thick brick wall in cement sand mortar 1:4 without reinforcement in superstructure
Extra Rate for First Floor
Reinforced cement concrete M-20 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in superstructure.
Extra Rate for First Floor
Centering and shuttering for flat surfaces such as suspended floors, roofs, landings, chajjas, shelves etc.
Extra Rate for First Floor
Cold twisted detormed (Ribbed/Tor steel) Bars (Fe 500 grade as per IS 1786-2008), for R.C.C works, where not including in the complete rate of RCC including binding,bending and placing in position complete
Extra Rate for First Floor
Coloured Granite stone tiles 15mm to 20mm thick in skirting, risers of steps,dado walls and pillars laid in 12.5mm thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with neat cement slurry mixed with pigment to match the shade of stone, including rubbing and polishing including labour for fixing dowel pins and cramps.
Extra for First Floor
Providing and fixing commercial plywood 18mm thick
Providing and fixing HDHMR Plywood 18mm thick
Providing & Fixing decorative high pressure laminated sheet 1mm thick High Class Texture with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, ISI marked complete in all respect as per the directions of Engineerin-charge.
Providing & Fixing decorative high pressure laminated sheet 1mm SF thick with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality.
Providing and Installation of Telescopy Channel upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing & fixing 6" stainless steel handles ISI marked on door & window frames complete in all respect as per the directions of Engineer-in-charge
Providing and fixing special quality bright finished brass cupboard or ward robe locks with four levers of approved quality including necessary screws etc. complete in all respect as per the directions of Engineer-in-charge. 65mm
Providing and Installation of Magnetic Catcher upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Installation of Auto Hinge upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing & fixing 6"stainless steel tower bolts ISI marked on door & window frames complete in all respect as per the directions of Engineer-in-charge.
Wrought iron and mild steel ladders, framed grills, grating etc. with ends of bars, riveted or welded or forged, framed window guards, barred iron doors, stair case, iron railing including cost of bolts & nuts or screws or welding rod, complete fixed in position.
Taking out existing CC interlocking paver blocks from footpath/ central verge/pavement, including removal of rubbish etc., disposal of unserviceable material to the dumping ground, for which payment shall be made separately and stacking of serviceable material within 50 metre lead as per direction of Engineer-in Charge.
Earth work in excavation in foundations trenches etc. in all kinds of soil where Pick-Jumper work is not involved and not exceeding 2.0 metres depth including dressing of bottom and sides of trenches, stacking the excavated soil clear from the edge of excavation and subsequent filling around masonry in 15 cm, layers with compaction including disposal of all surplus soil as directed within lead of 30 metres.
Cement Concrete 1:8:16 with stone ballast of size. 40 mm guage.mixing by mechanical means using concrete mixer volumetric type
CC 1:2:4 with stone ballast with stone ballast or shingle mixing by mechanical means using concrete mixer volumetric type
First class burnt brick work laid in cement sand mortar 1:6 in foundation and plinth.
Reinforced cement concrete M-20 mechanically batchmixed using batch type concrete mixer asper IS:1791andvibrated by needle vibrator but excluding steel reinforcement centring and shuttering in superstructure.
Centering and shuttering for flat surfaces such as suspended floors, roofs, landings, chajjas, shelves etc.
Cold twisted detormed (Ribbed/Tor steel) Bars (Fe 500 grade as per IS 1786-2008), for R.C.C works, where not including in the complete rate of RCC including binding,bending and placing in position complete
Wrought iron and mild steel ladders, framed grills, grating etc. with ends of bars, riveted or welded or forged, framed window guards, barred iron doors, stair case, iron railing including cost of bolts & nuts or screws or welding rod, complete fixed in position.
Applying priming coat with metal primer on new steel or iron work including preparation of surface.
Painting two or more coats excluding priming coat with synthetic enamel paint in all shades on wood work, metallic or plastered, concrete surface to give an even shade.
Providing & fixing wire mesh GI Chain link 10 gauge mesh size 50mm ISI 2721:1979 fixed with nut and bolt on vertical post and touch welding on horizontal member complete in all respects as per specification and as desired by engineer in charge
Construction of granular sub-base by providing material, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC, and compacting with vibratory roller to achieve the desired density, complete as per MORD technical specifications
Providing and laying 60 mm thick factory made cement concrete interlocking paver block of M-35 grade machine made rubber moulded smooth finish with strong vibratory process or with vibrohydraulic compaction machine and of approved size and design / shape laid in Ordinary Grey and pattern over and including 40 mm thick compacted bed of coarse sand, filling the joints with fine sand etc, all complete as per directions of Engineer-in-Charge for Non traffic Areas and streets having width less than 3.05 mt.( Also not to used over footoaths).
Stripping and stacking slate or tiles of a roof
Earth work excavation in ordinary soil, exclusive of compensation of earth. Earth work undressed with a combined lead upto 15 metres including breaking of clods.
Earth work in excavation in foundations, trenches etc. in all kinds of soil where pick jumper work is not involved and not exceeding 2.0 metres depth including dressing of bottom and sides of trenches, stacking the excavated soil clear from the edge of excavation
Cement concrete 1:8:16 with stone aggregates 40mm gauge mixing by mechanical means using concrete mixer volumetric type
First class burnt brick laid in cement sand mortar 1:6 in foundation and plinth
Reinforced cement concrete M-20 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in superstructure
Extra for First Floor
Extra for Third Floor
Centering and shuttering for sides and soffits of beam, beams, launching girders, bressumers, lintels.
Extra Rate for First Floor
Extra Rate for Third Floor
Centering and shuttering for flat surfaces such as suspended floors, roofs, landings, chajjas, shelves etc.
Extra Rate for First Floor
Extra Rate for Third Floor
First class burnt brick work laid in cement sand mortar 1:6 in first storey upto 4 metres above plinth level.
Extra for First Floor
Extra for Second Floor
Extra for Third Floor
Cold twisted detormed (Ribbed/ Tor steel) Bars (Fe 500 grade as per IS 1786-2008) , for R.C.C works, where not including in the complete rate of RCC including bending and binding placing in position complete
Extra for First Floor
Extra for Third Floor
12.5 mm thick cement plaster 1:4
Extra for First Floor
Extra for Second Floor
Extra for Third Floor
20mm thick cement plaster 1:4 in two coat work
Providing and applying plaster of paris (ISI marked such as JK, Kohinoor, Maharaja etc.) punning 6mm thickness over plastered surface to prepare the surface even and smooth complete in all respect as per the directions of Engineer-in-charge
Preparation of plastered or concrete surface for painting (including sand papering the surface) using ready mixed cement based wall putty by applying two or more coats to get required finish
Applying priming coat with cement primer in all shade on newly plastered or concrete exterior surface
Distempering with Acrylic washable oil bound distemper (of approved manufacture) two or more coats over one priming coat to give an even shade
Finishing walls with acrylic smooth exterior paint of required shade with two or more coats applied @ 1.67 litre/10Sqm over and including base coat of water proofing Cement Paint applied @ 2.20 Kg/10 Sqm
Terracing consiting of tiles 22.86x11.43x3.83cm laid over 25 mm mud plaster 7.5 cm mud filling on another layer of 25mm mud plaster including two coats of bitumen laid hot at 1.65 Kg. /Sqm top of R.C.C. slab including grouting with cement sand mortar 1:4 and top surface to be left clean after wire brushing
Cement concrete 1:2:4 gola 10cm x 10cm concave quadrant along junction of roofs with parapet wall finished smooth, where specially specified.
Providing and fixing 110 mm dia . U.P.V.C Rain water pipe of 4 kgf./sqm as per IS:4985 including jointing during masonary complete as per specifications and to the entire satisfaction of Engineer-in- charge U-PVC pipes (working pressure 4kgf. / sqcm) pipe 110 mm dia.
Providing and fixing 110 mm dia. U.P.V.C bend for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge UPVC 110 mm bend
Providing and fixing 110 mm dia. U.P.V.C Coupling/Sockete for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge. UPVC 110 mm bend
Top Khurra 0.6mx0.6m for rain water pipe in 25mm thick cement concrete 1:2:4 over 50.00 thick cement concrete 1:8:16
Bottom khurra on ground 1.2m 0.6m consisting of bricks on edge laid in cement mortar 1:3 over 7.5 cm cement concret 1:8:16 including 12.5mm thick cement plaster 1:3
Screed of 50mm thick cement concrete 1:8:16 with stone aggregate to be laid below the topping using mechanical mixer for mixing of material
Extra Rate for First Floor
Extra Rate for Third Floor
Conglomerate floor 50mm thick cement concrete topping 1:2:4 using mechanical mixer for mixing of material
Extra Rate for First Floor
Extra Rate for Third Floor
Providing and fixing aluminum work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate z sections and other sections conforming to Is: 733 and IS : 1285 of Jindal, Hindalco, Mahavir or equivalent make approved by Engineer in Charge , fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC Plug/neoprene felt etc. aluminum sections shall be smooth, rust free, straight, mitered and jointed mechanically wherever required including cleat angle, aluminum snap beading for glazing/paneling, C.P.brass/stainless steel screws, all complete as per architectural drawings and the directions of Engineer-InCharge. (Glazing and paneling to be paid for separately) : For fixed portion and chawkhats
For shutters of doors, windows & ventilators including providing and fixing hinges/pivots and labour for fixing of fittings wherever required including the cost of PVC Plug / neoprene gasket required
Providing Polyester Powder coating 50 micron any coloured specified to alumnum section of various sizes including carriage of material from market to workshop & workshop to site of work
Cost of Aluminium fittings complete for doors, windows such as tower bolts, handless and screw etc. for these fittings (Excluding sliding bolt) For shutter area above 0.50 sqm
Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in paneling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer-In-Charge. Prelaminated particle board with decorative lamination on Both side.
Providing and fixing aluminium sliding door bolts ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : 300mm x 16mm
Providing and fixing hydraulic door closer ISI mark with necessary screw etc. complete. ISI designation no I (Size of door up to 700mm)
CREDIT OF MATERIAL TO BE RECEIVED FROM DISMANTLING
Tile from dismantling of tile terracing
Bricks from dismantling Brick work
Brick/Tile/Bats
LINAC
Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material within 50 meters lead as directed by Engineer-in-charge
Dismantling Concrete Reinforced cement concrete
Providing and fixing mineral fibre false ceiling tiles ( NRC 0.55 to 0.6) at all heights of size 595X595x16 mm of approved texture, design and pattern.The tiles should have Humidity Resistance (RH) of 99%,Light Reflection>85%,Thermal Conductivity k =0.052- 0.057w/mK, Fire Performance as per (BS 476 pt- 6&7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33mm thick (galvanized @120gsm) comprising of mainT runners of 15x32mm of length 3000mm,crossTof size15x32mm of length1200mm and secondary intermediate crossTof size15x32mm of length600mm to form grid module of size600x600 mm suspended from ceiling using galvanized mildsteel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2mm, spaced at 1200mm centre to centre along main‘T’.The system should rest on peripherywalls/partitions with the help of GI perimeter wall angle of size24x24X3000mm made of 0.40mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long drywall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge.
Providing and fixing ceiling at height upto 4 mtr consisting of 12.5mm thick Gypsum Board of any size G.I. Cradling hanged from the ceiling by means of G.I. hanger complete as per drawings, specifications and to the entire satisfaction of engineer-in- charge.
Scraping white wash and colour wash
Preparation of plastered or concrete surface for painting (including sand papering the surface) using ready mixed cement based wall putty by applying two or more coats to get required finish
Applying priming coat with cement primer in all shade on newly plastered or concrete exterior surface
Distempering with Acrylic washable oil bound distemper (of approved manufacture) one coat over one priming coat on old distempered surface
Finishing walls with acrylic smooth exterior paint of required shade with two or more coats applied @ 1.67 litre/10Sqm over and including base coat of water proofing Cement Paint applied @ 2.20 Kg/10 Sqm
Providing and Fixing of 4mm Acrylic inbuilt Name plates (10''x4'') complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing 5mm thick Sunboard Sign Boards with vinyl lamination print complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing of Acrylic LED Letters complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing of Acrylic Letters complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing of Acrylic Cutout Letters with self adhesive complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing of Backlit Fabric Signage complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Laying Self Levelling compund for providing smooth finish for Vinyl Flooring
Providing and fixing commercial plywood 18mm thick
Providing and fixing HDHMRl plywood 18mm thick
Wrought iron and mild steel ladders, framed grills, grating etc. with ends of bars, riveted or welded or forged, framed window guards, barred iron doors, stair case, iron railing including cost of bolts & nuts or screws or welding rod, complete fixed in position.
Providing & Fixing decorative high pressure laminated sheet 1mm thick High Class Texture with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, ISI marked complete in all respect as per the directions of Engineerin-charge.
Providing & Fixing decorative high pressure laminated sheet 1mm SF thick with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality.
Providing and Installation of Telescopy Channel upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing & fixing 6" stainless steel handles ISI marked on door & window frames complete in all respect as per the directions of Engineer-in-charge
Providing and fixing special quality bright finished brass cupboard or ward robe locks with four levers of approved quality including necessary screws etc. complete in all respect as per the directions of Engineer-in-charge. 65mm
Providing and Installation of Magnetic Catcher upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Installation of Auto Hinge upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing & fixing 6"stainless steel tower bolts ISI marked on door & window frames complete in all respect as per the directions of Engineer-in-charge.
Providing and fixing ply wood, plain lining,butt jointed including PVC Plug placed at 45 cm to 65 cm centers complete with necessary nails (Frame work shall be payable extra) Providing and fixing commercial plywood 12mm thick
Providing and fixing Venier board 3.75mm thick complete including Labour for fixing
Melamine polish two or more coats to give required finish including one coat of wood filler
Providing and Fixing of PVC Sheet with labour complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Providing and Fixing of UV Sheet with labour complete in all respects upto to the entire satisfaction of the Engineer-In-Charge of the work
Regrading terracing of mud plaster covered with tiles or bricks in cement by dismantling tiles or bricks, removing mud plaster, preparing the surface of mud plaster to proper, slope, relaying mud plaster Gobri leaping and tiles or bricks grouted in cement mortar 1:3 (1 cement and 3 fine sand) including replacing unserviceable tiles, or bricks with new over and disposal of unserviceable material to the dumping ground within 50 m lead (The cost of new tiles or bricks excluded).
Earth work in excavation in foundations trenches etc. in all kinds of soil where Pick-Jumper work is not involved and not exceeding 2.0 metres depth including dressing of bottom and sides of trenches, stacking the excavated soil clear from the edge of excavation and subsequent filling around masonry in 15 cm, layers with compaction including disposal of all surplus soil as directed within lead of 30 metres.
Dismantling cement conglomerate floors 25mm to 50mm thick including concrete base.
Re-barring (Chemical Anchor) of 12mm dia bar, hole size 16mm, depth 120mm with 14 ml injectable mortar epoxy adhesive (Hybrid urethane methacrylate adhesive) rebaring chemical complete in all respect.
Providing and applying rust remover–cum–passivator of approved brand on existing reinforcement, including thorough removal of rust by mechanical/hand brushing, cleaning of surface, applying the approved rust treatment chemical as per manufacturer’s specifications, allowing adequate reaction time, wiping/rinsing (if required), and providing complete corrosion protection to the reinforcement steel, including cost of all materials , but excluding all labour, tools & tackles, plant & equipment, scaffolding, handling, safety measures and incidentals, complete as directed by the Engineer-in-Charge
Providing and applying a cement-based polymer-modified rebar corrosion protection system to the existing reinforcement, including surface preparation by cleaning the reinforcement thoroughly with wire brushing/sandpaper/mechanical methods to remove all rust, dust, scale and loose particles; mixing and applying the approved polymer-modified corrosion-inhibiting coating in two coats or as specified by the manufacturer; ensuring uniform coverage and proper bonding; curing as required; and completing the work in accordance with the manufacturer’s specifications; including only cost of all materials , but excluding all labour, tools & tackles, plant & equipment, scaffolding, handling, safety measures and incidentals, complete as directed by the Engineer-in-Charge.
Fixing shear connectors of required diameter using TOR steel bars with an epoxy-resin-based, two-part, thixotropic, high-performance anchoring adhesive, suitable for anchoring threaded rods and reinforcement bars in both cracked and uncracked concrete, and in dry or damp RCC members. The work shall include power drilling of holes to required depth and diameter, thorough cleaning of drilled holes using air/wire brush as per manufacturer’s specifications, injection/placement of the approved epoxy anchoring adhesive, inserting and positioning of shear connectors to achieve the required embedment and bond strength, and allowing curing time as recommended. All operations shall be carried out in accordance with the manufacturer’s guidelines; including only cost of all materials , but excluding all labour, tools & tackles, plant & equipment, scaffolding, handling, safety measures and incidentals, complete as directed by the Engineer-in-Charge. In cases where drilling and fixing with anchoring adhesive is not feasible, shear connectors may be welded at the L-end of reinforcement bars, with all welding work completed using approved procedures and materials.
Providing and applying a two-component epoxy resin bonding primer on prepared RCC surfaces, including mixing and application of the epoxy bonding coat strictly as per manufacturer’s specifications. The work includes surface preparation by chipping, removing all loose and unsound material, and thoroughly cleaning the substrate to achieve a sound, dust-free surface; mixing of components in the specified proportion; and uniform application of the epoxy bonding primer to ensure proper adhesion between old and new concrete; including only cost of all materials , but excluding all labour, tools & tackles, plant & equipment, scaffolding, handling, safety measures and incidentals, complete as directed by the Engineer-in-Charge. The epoxy bonding primer shall comply with ASTM C-881, Type II, Grade 2, Class B & C.
Providing, supplying and applying a ready-to-use, non-shrink, cementitious, free-flow micro-concrete for structural repair/strengthening works, to be placed in an average thickness of approximately 75 mm. The material shall be mixed and applied strictly in accordance with the manufacturer’s specifications, including preparation of the substrate, erection of leak-proof shuttering, mixing with the required quantity of clean water, and placing/pouring of micro-concrete to ensure proper compaction, flow, and void-free filling; including only cost of all materials , but excluding all labour, tools & tackles, plant & equipment, scaffolding, handling, safety measures and incidentals, complete as directed by the Engineer-in-Charge. The micro-concrete shall meet the following performance requirements: Compressive strength > 60 N/mm² at 28 days (as per ASTM C 1107-99), Bulk density of fresh mortar: approximately 1.2 kg/l.
Providing of labour only for RCC repair, rehabilitation and structural strengthening works, including all labour, tools & tackles, plant & equipment, scaffolding, handling, safety measures and incidentals, but excluding cost of all materials, comprising of cleaning and mechanical/hand brushing of existing reinforcement; application of rust remover–cum–passivator and cement-based polymer-modified rebar corrosion protection coating; fixing of shear connectors using power drilling and epoxy-resin-based chemical anchoring adhesive or by welding where required; surface preparation and application of two-component epoxy bonding primer and placing of ready-to-use non-shrink cementitious micro-concrete as directed by the Engineer-in-Charge
Centering and shuttering for faces of walls, partitions, retaining walls and the like (vertical or battering including attached pilasters buttresses etc.
Cold twisted detormed (Ribbed/Tor steel) Bars (Fe 500 grade as per IS 1786-2008), for R.C.C works, where not including in the complete rate of RCC including binding,bending and placing in position complete
Providing and fixing double scaffolding system (cup lock type) on the exterior side, upto seven story height made with 40mm dia M.S. tube 1.5m centre to centre, horizontal & vertical tubes joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S.clamps and M.S. staircase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for the required duration as approved and removing it thereafter .The scaffolding system shall be stiffened with bracings, runners, connection with the building etc wherever required for inspection of work at required locations with essential safety features for the workmen etc. complete as per directions and approval of Engineer in charge .The elevational area of the scaffolding shall be measured for payment purpose .The payment will be made once irrespective of duration of scaffolding. Note:- This item to be used for maintenance work judicially, necessary deduction for scaffolding in the existing item to be done.
Providing and laying vitrified floor tiles in different sizes in light colour shades made using Full Body Technology (thickness to be specified by the manufacturer) with water absorption’s less than 0.08% and conforming to IS : 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement: 4 fine sand), complete. ( Full body vitrified tiles have pigment in entire body / thickness of tile which makes chips and scratches less noticeable and make na ideal choice for high traffic zones.) Size 600x600 mm
Base course of floor consisting of 100mm thick cement concrete 1:8:16 with stone aggregate 40mm guage and 100mm fine sand filling using mechanical mixer for mixing of material
Stripping and stacking slate or tiles of a roof
Earth work excavation in ordinary soil, exclusive of compensation of earth. Earth work undressed with a combined lead upto 15 metres including breaking of clods.
Reinforced cement concrete M-20 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in superstructure
Extra for Second Floor
Centering and shuttering for sides and soffits of beam, beams, launching girders, bressumers, lintels.
Extra Rate for Second Floor
Centering and shuttering for flat surfaces such as suspended floors, roofs, landings, chajjas, shelves etc.
Extra Rate for Second Floor
First class burnt brick work laid in cement sand mortar 1:6 in first storey upto 4 metres above plinth level.
Extra Rate for Second Floor
Cold twisted detormed (Ribbed/ Tor steel) Bars (Fe 500 grade as per IS 1786-2008) , for R.C.C works, where not including in the complete rate of RCC including bending and binding placing in position complete
Extra for Second Floor
12.5 mm thick cement plaster 1:4
Extra for Second Floor
20mm thick cement plaster 1:4 in two coat work
Providing and applying plaster of paris (ISI marked such as JK, Kohinoor, Maharaja etc.) punning 6mm thickness over plastered surface to prepare the surface even and smooth complete in all respect as per the directions of Engineer-in-charge
Preparation of plastered or concrete surface for painting (including sand papering the surface) using ready mixed cement based wall putty by applying two or more coats to get required finish
Applying priming coat with cement primer in all shade on newly plastered or concrete exterior surface
Distempering with Acrylic washable oil bound distemper (of approved manufacture) two or more coats over one priming coat to give an even shade
Finishing walls with acrylic smooth exterior paint of required shade with two or more coats applied @ 1.67 litre/10Sqm over and including base coat of water proofing Cement Paint applied @ 2.20 Kg/10 Sqm
Terracing consiting of tiles 22.86x11.43x3.83cm laid over 25 mm mud plaster 7.5 cm mud filling on another layer of 25mm mud plaster including two coats of bitumen laid hot at 1.65 Kg. /Sqm top of R.C.C. slab including grouting with cement sand mortar 1:4 and top surface to be left clean after wire brushing
Cement concrete 1:2:4 gola 10cm x 10cm concave quadrant along junction of roofs with parapet wall finished smooth, where specially specified.
Providing and fixing 110 mm dia . U.P.V.C Rain water pipe of 4 kgf./sqm as per IS:4985 including jointing during masonary complete as per specifications and to the entire satisfaction of Engineer-in- charge U-PVC pipes (working pressure 4kgf. / sqcm) pipe 110 mm dia.
Providing and fixing 110 mm dia. U.P.V.C bend for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge. UPVC 110 mm bend
Providing and fixing 110 mm dia. U.P.V.C Coupling/Sockete for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge. UPVC 110 mm bend
Top Khurra 0.6mx0.6m for rain water pipe in 25mm thick cement concrete 1:2:4 over 50.00 thick cement concrete 1:8:16
Bottom khurra on ground 1.2m 0.6m consisting of bricks on edge laid in cement mortar 1:3 over 7.5 cm cement concret 1:8:16 including 12.5mm thick cement plaster 1:3
Screed of 50mm thick cement concrete 1:8:16 with stone aggregate to be laid below the topping using mechanical mixer for mixing of material
Conglomerate floor 50mm thick cement concrete topping 1:2:4 using mechanical mixer for mixing of material
Providing and fixing aluminum work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate z sections and other sections conforming to Is: 733 and IS : 1285 of Jindal, Hindalco, Mahavir or equivalent make approved by Engineer in Charge , fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC Plug/neoprene felt etc. aluminum sections shall be smooth, rust free, straight, mitered and jointed mechanically wherever required including cleat angle, aluminum snap beading for glazing/paneling, C.P.brass/stainless steel screws, all complete as per architectural drawings and the directions of Engineer-InCharge. (Glazing and paneling to be paid for separately) : For fixed portion and chawkhats
For shutters of doors, windows & ventilators including providing and fixing hinges/pivots and labour for fixing of fittings wherever required including the cost of PVC Plug / neoprene gasket required
Providing Polyester Powder coating 50 micron any coloured specified to alumnum section of various sizes including carriage of material from market to workshop & workshop to site of work
Cost of Aluminium fittings complete for doors, windows such as tower bolts, handless and screw etc. for these fittings (Excluding sliding bolt). For shutter area above 0.50 sqm
Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in paneling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer-In-Charge. Prelaminated particle board with decorative lamination on Both side.
Providing and fixing aluminium sliding door bolts ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : 300mm x 16mm
CREDIT OF MATERIAL TO BE RECEIVED FROM DISMANTLING
Tile from dismantling of tile terracing
Brick/Tile/Bats
PUBLIC HEALTH WORK
FIRE SUPPRESSION SYSTEM (FK-5-1-12)
PESO Approved Seamless Cylinder and Valve Assembly, 120 Ltrs. capacity
Agent - FK 5- 1- 12 (Fluoro Ketone) UL listed
Primary Cylinder Accessories Electrical Actuator, Manual Actuator & Discharge Hose Pipe
Slave Cylinder Accessories Pneumatic Actuator, Discharge Hose Pipe and slave cylinder kit
Manifold Check Valve for Multiple Bank Cylinders Nominal diameter 32 mm Thread EN 10226 Rp 1"1/4 Operating pressure max 42 bar Opening pressure 1 bar
Manifold discharge pressure switch
Cylinder mounting straps to hold the cylinders at wall
Cylinder Low Pressure Supervisory Switch
Directional Valve with Pneumatic Actuator & Handle
4 way pilot manifold with N2 cylinder & Accessories as per flow calculations for the specific hazard volume and stand to 12 hold, position and support the manifold and piping properly. M.S. Seamless pipes as per ASTM A106 Gr B, schedule 40; Pressure testing for piping with nitrogen as per NFPA 2001 of 2010 Fittings to ASTM A105 3000 Lbs Threaded / Welded Structural Support with Angle, steel plate, clamp and anchor fastetners Paint for Pipes/fittings and structurals supports
Warning board with marking as per satisfaction of EIC
UL listed Manual release station and manual abort station with DPDT relay and to be monitored by Fire alarm and BMS
2 Zone Gas Release Panel with GR Module
12v. 7/12ah Battery for fire alarm panel
2 Core X 1.5 Sq mm FRLS armored Cable including accessories (Screw , PVC Gripper , Sadels, etc )
Conventional type Horn / Strobe wall mounted type UL Listed
Multisensor Detector Note: Clean agent fire suppression system shall be installed in the Server rooms/UPS room/machine room etc area to suppress any outbreak of fire. This system shall be integrated with the fire panel. The bidder shall supply, install, test the FK 5112 (UL listed) based fire suppression system and put it in operation. The fire suppression system shall include and not be limited to gas release control panel, PESO approved seamless cylinders, discharge valve (with solenoid and pneumatic actuator) as the case may be, discharge pipe, check valve and all other accessories required to make a complete operation system meeting applicable requirements of NFPA 2001 (2022 edition) standards and installed in compliance with all applicable requirements of the local codes and standards. Generally, the key components (i.e. valves and its accessories, actuators, flexible discharge and connection hoses, check valves, pressure switch, and nozzles) etc. of the system shall be UL/FM approved.
Providing and fixing in position vitreous Chinaware white laboratory sinks of approved make (to the approval of Engineerin-charge) consisting of a pair of brackets, C.P. Brass waste 40mm complete in all respect. Size 470 mm x 470 mm x 150 mm
Providing & fixing 15 mm C.P brass laboratory cock swan neck of approved make (to the approval of Engineer-in-charge ) complete in all respect. Laboratory cock swan neck One Way
Providing and fixing in position vitreous chinaware white lavatory suites of approved make (to the approval of Engineer-in-charge) including Rack Bolt Screw Pair 115mm long without CP fittings complete in all respect. Size 550 mm x 400 mm x 815 mm
Providing and fixing in position Chinaware European type water closet P trap or S trap of approved make (to the approval of the Engineer-in-charge) consisting of 10 ltr. PVC flushing cistern ISI marked, PVC short bend 32 mm dia including cost of seat cover complete in all respect and to the entire satisfaction of Engineer-in-charge.
Providing and fixing PVC Cistern 10 Ltr. Capacity ISI marked IS 7231:1994( size 32.5x47.6x15.5 cm) of approved make(to the approval of the Engineer-in-charge) including PVC fittings complete.
Providing & placing in position on terrace (at all floor levels) HDPE water storage tanks of approved make (to the approval of Engineer -incharge) with cover with suitable locking arrangement and making necessary holes for inlet, outlet and over flo pipes but without fittings and base support for tank. Triple Layer Tanks
Providing and fixing in position automatic brass Ball Cock in tanks. Plastic Ball Cock with rod and Plastic Ball 25mm i/d
Providing and fixing in position G.I. Tank Nipple of approved make (to the approval of Engineer-incharge) in PVC Water storage tanks complete in all respect. G.I. tank nipple 25mm i/d
Providing and fixing in position G.I. Tank Nipple of approved make (to the approval of Engineer-incharge) in PVC Water storage tanks complete in all respect. G.I. tank nipple 32mm i/d
Providing and fixing in position Chinaware extended wall mounted E. W.C. type suite (size 66 x 46 x 77.5 cm ) with P trap or S trap of approved make (to the approval of the Engineer-in-charge) with or without 10 ltr. chinaware matching flushing cistern and seat cover complete in all respect and to the entire satisfaction of Engineer-in-charge. Chinaware extended wall mounted E.W.C. with matching chinaware cistern and seat cover complete in all respect.
Providing and fixing in position C.P. brass soap dish of approved make (to the approval of Engineer-in-charge ) fixed into wall with rawl plugs and C.P brass screws complete in all respect..
Providing and fixing P.V.C Waste Pipe Collapsiable 32mm complete in all respect.
Providing & Fixing in postion CP Brass Spout Operated Pillar Tap with base flange (for foot operated valve) of approved make (to the approval of Engineer-in-charge) complete in all respect.
Providing and fixing in position C.P elbow action pillar tap of approved make (to the approval of Engineer-in-charge) complete in all respect.
Providing & fixing in position 15 mm i/d C.P brass wall mixer of approved make (to the approval of Engineer-in-charge ) complete in all respect. C.P brass wall mixer with Telephonic Shower
Providing and fixing in position 15mm i/d bib cock of approved make (to the approval of Engineer-in-Charge) complete in all respect. C.P. brass Bib cock long nose/ long body foam flow without flange
Providing and fixing in position stop cock/angle valve of approved make (to the approval of Engineer-in-Charge) complete in all respect.
C.P. brass 15 mm concealed stop cock with flange.
C.P.brass 15mm Angle valve without flange
P/F in position PVC flexible tube connection of approved make (to the approval of Engineer-in- Charge) Complete in all respect. PVC tube connection of size 15mm x 450mm with CP brass nut.
Providing & Fixing in position C.P. Brass flange Dome of approved make (to the approval of Engineer-in-charge) under various fixtures complete in all respect.
Providing and Fixing in position C.P. brass extension piece 25 mm long to 50 mm long of approved make (to the approval of the Engineer- in-Charge) under various fixtures complete in all respect. (i) C.P. Brass extension piece, 25mm long to 50mm long
Providing and Fixing in position C.P. brass Hexa Nipple 15mm of approved make (to the approval of the Engineer-in-Charge) under various fixtures complete in all respect.
Providing and fixing in position Acrylic Liquid Soap container of approved make (to the approval of Engineer-in-Charge) complete in all respect.
CONCEALED IN WALL: Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes as per IS 15778 (ISI marked with the prior approval of Engineer-in-Charge), having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing including jointing of pipes & fittings, with one step CPVC solvent cement and testing of pipes complete as per direction of Engineer-in-Charge. CPVC SDR 11 Pipe & fitting 25mm o/d
CONCEALED IN WALL: Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes as per IS 15778 (ISI marked with the prior approval of Engineer-in-Charge), having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing including jointing of pipes & fittings, with one step CPVC solvent cement and testing of pipes complete as per direction of Engineer-in-Charge. CPVC SDR 11 Pipe & fitting 32mm o/d
INTERNAL - EXPOSED ON WALL : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes as per IS 15778 (ISI marked with the prior approval of Engineer-in-Charge), having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing including jointing of pipes & fittings with one step PVC solvent cement and testing of pipes complete as per direction of Engineer-in-Charge SDR 11 CPVC pipes & fittings 25mm o/d
INTERNAL - EXPOSED ON WALL : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes as per IS 15778 (ISI marked with the prior approval of Engineer-in-Charge), having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing including jointing of pipes & fittings with one step PVC solvent cement and testing of pipes complete as per direction of Engineer-in-Charge SDR 11 CPVC pipes & fittings 32mm o/d
Providing and fixing in position single socket (Single Socket Type B) SWR UPVC soil waste or antisyphonage pipes as per IS 13592 of E.D.C manufacture or of any other reputed firm including cutting, jointing, wastage, but excluding cost of jointing. Type B 110mm o/d SWR UPVC pipe lines laid complete
Providing PVC solvent cement joints to SWR Pipes and specials including cost of PVC solvent cement and tools etc of approved make (to the approval of Engineer-in-charge) 110mm o/d
Providing and fixing in position SWR UPVC special for soil waste vent or anti-syphonage pipes as per IS - 14735 of approved make (to the approval of Engineer-in-Charge) including cutting and wastage etc. cutting holes in walls roofs or floors etc. and making good to its original condition but excluding cost of lead joining. For 110mm o/d pipes
Single Tee
Coupler
Elbow 90 Degree (All side socketed)
P Trap/Floor Trap 110mm x 110mm
Nahani trap without jali 110mmx90mm
Providing, Stringing out, cutting, Jointing and testing of ISI Marked D.I. Pipe (S&S) as per IS 8329 and laying the same in trenches to correct alignment and gradients, jointed with rubber tyton joints fitted complete including all cartage, cost of rubber ring. D.I. Pipe as per IS 8329 DI-K7 100mm i/d pipe lines laid complete
Excavation manually in trenches for pipe lines with straight or open cutting in streets and lanes in builtup area where width of street / Lane from wall to wall is less than 3 meter including trimming and dressing sides levelling of beds of trenches to correct grade, cutting joint holes, refilling consolidation,watering , including the cost of dewatering of rain water, diversion for traffic, night signals. Providing & fixing caution boards, watching, fencing, etc. and removal of surplus soil from the site upto 15 meter distance complete in all respects. Earth work upto 1.5 m. Depth All classes of soil except rocky
Dismantling interlocking pavers and relaying the same in original condition complete in all respects. For 100mm dia. pipe
Providing, Installing, Testing & Commissioning of Biological ETP of capacity 3.0 KLD for Labs based on suitable technology.
Providing & installing Submersible sewage pump of capacity 5.0 BHP (1 no. as standby) complete in all respect.
FIRE UPGRADATION
Providing, laying, fixing, testing and commissioning of 'C' Class heavy duty MS Pipe conforming to Indian Standard IS : 1239/3589 including fittings like tees, bends, sockets, elbows, flanges, tapers, nuts bolts, gaskets etc. on surface and providing angle iron support or cement concrete block as support including painting with two or more coats of synthetic enamel paint of required shade complete in all respects. 100mm internal diameter
P/F Clean agent type fire extinguisher. Capacity 6 kg.
COPPER EARTHING (Upto 8 metre in Length): Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 4.50 metre (14.76 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 8metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 3metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- Earthing with 25mm x 5mm Copper Tape (upto 8Metre in Length)
COPPER EARTHING STRIP (As Additional Length): Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:- Additional Length 25mm x 5mm thick Copper Tape
EQUIPMENT Hot and Cold Inverter Ductable Acs Supply, Installation, Testing and Commissioning of Air Cooled Hot & Cold Inverter Ductable Split units with Scroll/Rotary Inverter Compressor working on R410a refrigerant. The prices should include any lifting, shifting and positioning of outdoor units including painted MS Stands. The unit shall be charged or any top-up gas/oil required should be included in the individual price quoted below. This shall include the nitrogen leak testing, oil charging,vaccumisation, TF quality Canvass Connection b/w Indoor & duct.The outdoor unit shall be a factory assembled and unit housed in a sturdy weather proof casing constructed form rust-proofed mild steel panels with powder coated finish. The heat exchanger for Outdoor shall be constructed with Copper tubes mechanically bonded to aluminium fins to form a cross fin coil. The Condenser fins must be coated with Anti-corrosive treatment. Insurance of Units ,Unloading at site, placement of Outdoor Units on the foundation,stands, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned by OEM. Note: The civil foundations reqd shall be made by the Vendor/Contractor Make :Daikin, Mtistibushi Electric, Toshiba,O General,Carrier,Blue Star
5.5 TR( Hot and Cold -3% or higher capacity as per OEM standards) or better technology
8.5 TR( Hot and Cold -3% or higher capacity as per OEM standards) or better technology
Refrigerant Piping Supply and Installation of Interconnecting Refrigerant Piping of various sizes as required for the full functionality of the VRF/VRV system etc. complete in all respects duly insulated with Class O closed cell nitrile rubber as per specifications of the manufacturer. the contractor shall submit a detailed drawing approved by the manufacturer showing the piping sizes & layout to be followed at the site with the tender document. the contractor shall also get the drawings showing outdoor units in connection with indoor units approved from the HVAC consultant/Client in original from and then the head office of the manufacturer with a certificate stating that the piping layout is as per company specifications for full functioning of the system.(Make : Rajco,Mandev,Totaline,) Insulation Make : K Flex ,Armacell
25.4 mm OD (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
22.2 mm OD (ins(Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
19.1 mm OD (Hard drawn) with tube thickness 1.2 mm with 13 mm thick insulation
15.9 mm OD (Soft drawn) with tube thickness 1.2 mm with 13 mm thick insulation
12.7 mm OD(Soft drawn) with tube thickness 1.2 mm with 13 mm thick insulation
DUCT LINE ACOUSTIC TREATMENT Supply, Installation, Testing and Commissioning of Acoustic lining inside ducts/plenum using open cell nitrile rubber foam having microban anti-microbial/ anti fungal product protection and of 160-180 kg / m³ density as per ASTM D3575, class 1 ratingn As per BS476,PART-7, cut to required sizes and to be stuck to the inside of duct surfaces with adhesive as approved by the manufacturer. (Rubber based solvent). as per specifications 10mm thick sound board for Ceiling Suspended AHU/Ductable Acs
DUCT LINE THERMAL INSULATION (Inside Conditions) SITC of Physically / Chemically crosslinked polyethylene foam, with factory reinforced alupet foil facing, ANTI MICROBIAL/ANTI FUNGAL,HFC & CFC free , Negligible VOC level with Class O fire properties,with very low fire propagation of < 5.5 and passing E-84 at < 25/50, as per technical specification, the density of the foam should be not less than 25-30kg/m3 and the maximum thermal conductivity K should be 0.032W/mK@ 23 Deg C , the permeability resistance factor u shouldn't be less than 14000. The product shall have temperature range of –20oC to 115oC 13 mm thick
CONDENSATE DRAIN PIPE Providing and fixing and in position the following PVC pipes for condensate drain duly insulated with 6mm Nitrile Insulation & vapour barrier duly secured with adhesive tape as per specification ,cut to required length and installed with all joints , including the necessary fittings. (For all the indoor units upto the main header in the shaft dor vertical risers Astral,Diplast,Supreme,Prince
40 mm dia
32 mm dia
25 mm dia
AIR SIDE WORKS Duct - GI duct factory Fabricated Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting as per IS 655:2006 complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications.GI Sheet Should be 120GSM with RoHS complaintand TDF flange should be of 35 mm only of following sheet thickness complete as required and shall also confirm to the BIS specifications.The duct shall be fabricated at site for to make Collors/bends/plenums/suit pieces Only Sheet Make : Ductofab, Rolastar,ADS,zeco ( Sheet Make Sail /Tata )
1.0 mm (20 gauge) GSS
0.8mm (22 gauge) GSS
0.63mm (24 gauge) GSS
Factory fabricated Duct-GI OVALduct SITC of Factory fabricated Powder Coated Spiral Oval Duct Pre/site Insulated from Inside with 9.0mm thick Nitrile 'O' Class Insulation (payble separately) fabricated GSS Ducting complete with hanging arrangement of fasteners, GI threaded rods of sizes:. However The duct shall be fabricated at site for to make Collors/bends/plenums/suit pieces Only 0.80mm (22 gauge) GSS Sheet Make : Ductofab, Rolastar,ADS,zeco ( Sheet Make Sail /Tata )
Grills/Diffusers Providing and fixing of Extruded aluminium supply and return air grilles/diffusers/ louvres with dampers,etc. duly powder coated as per specifications and drawings. Make : Swirl Air,Pinaire,Caryaire,Systemair
Supplying & fixing of powder coated extruded aluminium Supply/Return curved/plain Air Grills with louvers as per specifications
Supplying, fixing testing commissioning of supply air diffusers with removable core (Round/Square) of powder coated aluminium complete as rquired.
Dampers Make : Swirl Air,Pinaire,Caryaire,Systemair
Supply, installation, testing & commissioning of Al Collar dampers
Supply, installation, testing & commissioning of CBRI approved Fire duct Dampers for at least 90 min fire rating as per UL555:1955 Specifications without Sleeve
Supply, installation, testing & commissioning of Spring Return Actuator and Control Panel Complete with Heat Sensors , Complete Control wiring and Limit switch,4NM/7NM/9NM,(24VAC/220VAC)
ASSOCIATED ELECTRICAL WORKS AC Main Panel (CPRI Approved) Main Electrical Panel-1 (CPRI Approved) Design,Supply,Installation,Testing and Commissioning Electrical Main Panel weather Proof outdoor Type Powder Coated Made out of TATA/SAIL/ESSAR/JINDAL/Reputed make sheet having thickness 2.0 mm for load bearing surfaces & 1.6 mm Non bearing surfaces duly processsed powder coated having Siemens grey colour or as approved by client or department (Outdoor Type with weatherproof canopy design)as per following specifications complete in all respect . INCOMING SUPPLY 160-250Amps ,3Pole MCCB,50 KA with Microprocessor release.The MCCB shall be double break & the ICS=100% ICU = 1nos Make : Schneider/ Siemens/ABB Spreader Link with phase Barriers = 4sets Make : Schneider/ Siemens/ABB Rotary Mechanism = 1nos Make : Schneider/ Siemens/ABB Metering Section Load Manager EM6400NG with RS485 Port or Equivalent (Class 1.0, with RS485 Port, with Paramenters V, Amp, PF, % THD, F,W,WH,VA,VAH, VAR,VARH, Runhrs, ON hrs, Interupts = 1No. Make : Schneider / Secure / Siemens/ABB/Elmeasure Control MCB SP C Curve= 3nos Make : Schneider/ Siemens/ABB CT's 300/5 = 3nos Make: AE/Essma/Newtek/Selec Indication Lamps LED Type RYB = 3nos Make : ABB/ Schneider/ Siemens/L&T/Reputed Outgoing Feeders - (5 Nos + 3 Spare ) MCB TPN32- 40 Amps C Curve 10 KA -8nos ELCB 32-40 Amps 300 MA 4 Pole -8 Nos or as Required by OEM Outgoing Feeders - (5 Nos + 3 Spare )
MCB TPN 16 Amps or as per IDU rating C Curve 10 KA -8nos Multi function Meter EM 64xx 1.0 RS or equavalent for EMS/BMS compatibilty Make: Schnieder/Nippen/HPL-9 nos INDICATING LAMPS LED Type Make : ABB/ Schneider/ Siemens/L&T/Reputed Control MCB SP C Curve for control Make : Schneider/ Siemens/ABB CT's 30/5 Make: AE/Essma/Newtek/Selec Panel Fabrication of Powder Coated Enclosure made out of TATA/SAIL/ESSAAR/JINDAL/Reputed make CRCA sheet having 2 mm for load bearing surfaces & 1.6 mm for non load bearing surfaces ,duly processsed powder coated having Siemens grey colour. (Outdoor Type with weatherproof canopy design) Assembly charges of Aluminium Bus Bar 400A TPN Electrolite grade E91 having cross section 1X50X10mm for Phase & 1X50x5 mm for Neutral & Current carring capacity 1 A/Sq. mm2. inclusive of Insulators, colour coded Heat shrinkable Insulation sleeve (RYBN) Assembly of Hardware (PVC Channels/MCB Channels/Fibre-Glass/Gaskits/nuts/Bolts/washers/ Terminal blocks, etc) Complete Wiring inclusive of control wiring, power wiring, Aluminium Solid connections/interconnections including insulators, thimbles,etc Unloading at site, placement of Panel on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Panel. Panel Make : Adlec/Siemens/Tricolite/Unitech Power System/Vrindavan Electricals/International Switch Gears Pvt. Ltd
Providing & fixing control cum FRLS transmission wiring/ Control Cabling of 2 core x 1.5sq. mm copper in suitable conduits between indoor and out door unit & indoor unit & its remote controller. (Make: Havells/Ecko/Finolex/Polycab/L&T/KEI)
P/F of GSS Weatherproof Louvers with bird screen, adjustable damper for fresh air and exhaust air etc.
Electrical Cables Supply, installation, testing & commisioning of Copper conductor , PVC insulated, PVC sheathed armoured/Unarmoured cable of 1.1 KV grade (Which is Interconnecting wiring for the fire alarm system with the AHU and the smoke dampers and AHU to BMS Make : Havell's,Eko,Finolex,Polycab
4C x 10 Sqmm Armoured
4C x 06 Sqmm Armoured
4C x 04 Sqmm Armoured
4C x 2.5 Sqmm Un-armoured
4C x 1.5 Sqmm Un-armoured
Supplying and installing following size of perforated G.I. cable trays, G.I. bends with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with suitable suspenders including G.I. bolts & nuts, painting of suspenders etc. complete as required.
50 mm x 150 mm x 50mm x 1.6mm. Thickness
50 mm x 300 mm x 50mm x 1.6mm. Thickness
Under Deck Insulation Providing & Fixing Underdeck Insulation with 50 mm thick TF Quality EPS of Density 20 Kg/M3 fixed to slab with good quality Black CPRX Compound. 28Gwirenet shall be tightened arround insulation so as avoid any kind of sagging, Ends of net shall be overlapping at least 25mm. Overlaps shall be screwed with galvanized screws to avoid rusting : Make: Beardsell,Llyod
ITC OF SPLIT ACS Installation, Testing and Commissioning of Wall mounted existing split units,The scope of work also includes the dismentling of existing split AC units and re installtion of these Units as per Direction of EIC 1.0TR /1.5TR /2.0 TR
Top-up of the gas in split AC's as per requirement
ELECTRICAL WORKS
RECESSED PVC CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES: Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge PVC conduit pipe 20mm/ 25mm dia. (ISI Marked) recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulators (two module) 100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10Amp. Switches and 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), Steel Hooks, Sheet metal fan box (1.6mm thick shape hexagonal), Circular junction Boxes (Four way PVC 1½" deep for walls and CI 3" deep for ceiling), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc. including the cost of above material, cutting and filling up of chases (With finishing surface)for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site. :-
Wiring fan point (With fan box)
Wiring light point
Wiring 6Amp. wall socket point
Wiring 6Amp. Plug control comprising wall socket point
Wiring 16/20Amp. power plug control point
Wiring light point without control switch.
RECESSED COMPUTER SUPPLY TERMINAL POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES):
Wiring Computer supply terminal points recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10/16/20Amp. Switches and blanking plate etc., and covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface)for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site. :-
Wiring Computer terminal point having 2 Nos. 6Amp. 2/3 universal socket (shuttered), 1No. 16/20Amp. universal Socket (shuttered) and 2Nos. 16/20Amp. switch with indicator (Modular accessories).
RECESSED AIR CONDITIONER SUPPLY TERMINAL POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYATEM WITH MODULAR ACCESSORIES):
Wiring air conditioner supply terminal points recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 25Amp. combined/ universal Socket (shuttered) and modular motor starter 25Amp. (2Module), covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases:-
Wiring AC supply terminal points having 1No. 25Amp. universal Socket (shuttered) erected at AC height and 1No. Motor starter 25Amp. erected at switchboard height.
CABLE TRAY
Supply and erection of MS perforated cable tray (MS Sheet thickness 2mm) with DA gray paint on the existing surface with the help of MS angle iron support (to be painted with approved paint) of size 50mm x 50mm x 6mm thick to be fixed with fastners/ nut & bolts etc., complete in all respect as desired by the Engineer-in-charge and as per PWD General Specifications for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site.:-
Cable Tray Size 150mm x 50mm x 50mm (2mm thick)
Cable Tray Size 300mm x 50mm x 50mm (2mm thick)
Cable Tray Size 450mm x 50mm x 50mm (2mm thick)
PVC, HDPE PIPES & PVC FLEXIBLE PIPES:
Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, MS saddle clamps and other petty materials etc., as per PWD General Specificationsfor connections and testing complete in all respect as approved and desired by the Engineer in-charges at site. :-
Heavy Gauge PVC Conduit Pipe 25mm dia. (Flushed)
Heavy Gauge PVC Conduit Pipe 32mm dia. (Flushed)
Heavy Gauge PVC Conduit Pipe 40mm dia. (Flushed)
PVC INSULATED FR COPPER CONDUCTOR CABLES:
Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-
Overall size 1.5sq.mm (Un-sheathed)
Overall size 2.5sq.mm (Un-sheathed)
Overall size 4sq.mm (Un-sheathed)
Overall size 10sq.mm (Un-sheathed)
Overall size 16sq.mm (Un-sheathed)
Overall size 70sq.mm (Un-sheathed)
XLPE INSULATED UN-ARMOURED CABLES (LOOSE):
Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-
Overall size 240sq.mm (3½ Core) Un-armoured (Loose)
LT PANELS & MCCB's (MOULDED CASE CIRCUIT BREAKERS):
LT PANELS:
Designing, Supply, Erection, Testing & commissioning of indoor Type LT cubical panel enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, 3 phase 4 wire & earth system. The assembly manufacturer should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP 54/55). Fabrication:- Panel shall be made from 14/16 SWG CRCA sheet, conforming to IS 8623/1977-82. The sheet metal used for the fabrication of control panel will be 2mm for load bearing member’s door and fittings plates etc. the partitions and other non load bearing members will be fabricated out of 1.6mm sheet, the sheet will be of mild steel CRCA type. The base channel will be made out of 75 x 40 x 5mm rolled channel.
The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel. The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc.
The fabrication should be such that all the member i.e. vertical/horizontal should be detachable type i.e. total bolted. In case of any changes required at site. it should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B construction fully compartmentalized type i.e. bus bar chamber as well as the cable chamber should be totally isolated from the feeder chamber. Where there crossing of the wire or bus links. It should have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition.
Painting:- The sheet metal is sprayed with corrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work . Busbars:-The panel shall be provided with TPN aluminium busbar of suitable size according to the size of MCCB's. Busbar shall be of high conductivity (53% to 58%) E91-E Grade aluminium (1A/Sq.mm). All Busbar will be air insulated with codified in Red, Yellow, Blue & Black as per standard for cable termination with the help of extended busbar only with proper adjustable cable supports. The main busbar would be supported upon non-hygroscopic SMC/DMC supports.
LT Panel enclosure having space for 1No. Incomer MCCB 400Amp. and 4Nos. outgoing MCCB's 100amp. to 160amp. according to the requirement at site (Approx. size 2025 x 1100 x 400mm)
MINIATURE CIRCUIT BREAKERS/ RCBO's/ RCCB's:
MINIATURE CIRCUIT BREAKERS:
Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:-
MCB Single Pole 6-32amp. (10kA, Curve-C) (20A)
MCB Four Pole 50, 63amp. (10kA, Curve-C)
MCCB's (FOR PANELS & SHEET ENCLOSURE):
Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-
MCCB Four Pole 200amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MCCB Four Pole 250amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting
MCCB Four Pole 400amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting
MCCB's (MOULDED CASE CIRCUIT BREAKER):
Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-
MCCB Four Pole 400amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting
MS SHEET ENCLOSURE FOR MCCB's:
Supply & Erection of indoor type MCCB enclosure of suitable size having provision for MCCB with extended rotary handle. The Enclosure shall be made from 14/16 SWG CRCA sheet, confirming to IS 8623/1977-82. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The Enclosure door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. The Enclosure will be wall mounting type having provision for cable entry from bottom/top with cable glands etc. The sheet metal is sprayed with corrosion resistant etch primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work:-
MS Sheet Enclosure having provision for MCCB 200-630Amp.with extended rotary handle (Approx. Size 750mm x 300mm x 250mm)
COPPER EARTHING
COPPER EARTHING (Upto 14 metre in Length):
Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 4.50 metre (14.76 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 8metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 3metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-
Earthing with 25mm x 3mm Copper Tape (upto 14Metre in Length)
Earthing with 40mm x 5mm Copper Tape (upto 14Metre in Length)
COPPER EARTHING STRIP (As Additional Length):
Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
Additional Length 25mm x 3mm thick Copper Tape
Additional Length 40mm x 5mm thick Copper Tape
Supply and erection of Recessed Mounted 36 Watt LED 2x2 panel (including constant LED driver) with CRCA sheet having efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site.LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No:- AT/2021/GL/1410-1422 Dated:- 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited labortary.
Supply and erection of 3-Star rating AC Ceiling Fan 1200mm (48") suitable for 230 V single phase with double ball bearing, copper wound, full aluminium body, 3Nos. of blades, white in colour. The mounting type is down rod mount. The product should possess a minimum air deleivery of 218 CMM. The rated speed of the the product must be minimum of 350 revolutions per minute and 5Nos. of speeds. The approximate weight of the product should be 4Kg and 180gms.(without packing) or higher. The product should have a manufcaturer's guarantee /warranty of minimum 2 years. The product should be complete in all aspects with fan motor, bladeset, down rod, conopy set, shackle kit, twisted wire etc., including erection & testing of ceiling fan having connection with PVC insulated PVC sheathed two single core copper conductor (FR) cable 0.75 sq. mm complete in all respects as per satisfcation of the Engineer in-charge at site.
Supply and erection of Wall Fan Plastic Body 400MM, 16" including flexible wire & petty material etc. for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site.
Supply and erection of Heavy duty Exhaust Fans 300mm sweep 900RPM complete with aluminium louver shutter Canon Make, double ball bearing, longer life including flexible wire & petty material etc. for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site.
Providing CCTV System
Supply, Installation, Testing & Commissioning of Indoor STQC Approved 3 MP IP WDR IR Rugged Mini Dome Camera OPERATIONAL: Video Standard: NTSC / PAL, Scanning System: Progressive, Image Sensor: 1/2.7” CMOS, Sensor Size (H x V): 4.608 mm x 2.592 mm, Number Of Pixels (H x V): 2304 x 1296, Minimum Illumination (Color/BW): .005 Lux / F1.6 (Color, 30 IRE), 0 Lux / F1.6 (IR ON), S/N Ratio: 50 dB, Electronic Shutter Speed: 1/8 ~ 1/32,000, IR Distance: up to 40 m, IR Light Control, Smart IR ( Auto / Manual ) / OFF, IR Light Number: 2, Day/Night: Auto (ICR) / Color / BW, Backlight Compensation: WDR, BLC, HLC, White Balance: Auto/Tungsten/ Fluorescent/ Daylight/Shadow/Manual, Gain Control: 0-100%, Wide Dynamic Range: 120 dB, Noise Reduction: 2D / 3D DNR, Lens: : 2.8 mm Fixed Iris, F1.6, Angle Of View: H: H:88°°, V:47°, Privacy Masking: Off / On (4 Areas), Defog: Not supported, Local Storage: Micro SD (up to 256 GB), Alarm Inputs/Outputs: Not supported, Pan Range: 0°-330°, Tilt Range: 0°-75°, Rotation Range: 0°-337°, Video Compression:H.265 HEVC/H.264/MJPEG, Smart Codec, Resolution: 1st: 2304 x 1296 / 1920 x 1080 / 1280 x 720 2nd: 704 x 576 (PAL) / 704 x 480 (NTSC) / 640 x 480 / 352 x 288 (PAL) / 352 x 240 (NTSC) 3rd: 640 x 480 / 352 x 288 (PAL) / 352 x 240 (NTSC) / 320 x 240, Number of Video Streams: 3 (2 for encryption), Frame Rate*: MAX 30 fps, Bit Rate*: 100K ~ 6 Mbps, Audio Compression: Not supported, Audio Stream: Not supported, Audio Interface: Not supported,
NETWORK: Ethernet: 10 Base-T/100 Base-TX Ethernet (RJ-45), Supported Web Browsers: Chrome / Edge, Supported OS: Microsoft Windows 10, Protocols**: IPv4, IPv6, TCP / IP, HTTP, HTTPS, RTSP / RTP / RTCP, IGMP / Multicast, SMTP, DHCP, NTP, DNS, QoS, SNMP, 802.1X, UDP, ICMP, ARP, TLS, Interoperability: ONVIF Profile G/S/T, Maximum Users Access: 10 Users, Security: User account and password protection, HTTPS, IP Filter, Digest authentication, TLS1.2 only, Stream encryption, AES128 / 256, SSH / Telnet closed, PCI-DSS compliance, EVENTS / ANALYTICS: Built-in Video: Analytics, Motion Detection, Tampering, Event Type: Video motion detection,Recording notification, Event Linkage: Event notification using Email and MicroSD card, Region Of Interest: 8, ELECTRICAL: Power Supply: DC12V, PoE (IEEE 802.3af) (Class 0), Power Consumption (Max): MAX 3.6 W, MECHANICAL: Dimensions: Ø110.0 mm × 85.6 mm (Ø4.33” × 3.37”), Dome Diameter Ø78.2 mm (3.08”), Product Weight 0.56 kg (1.23 lb), Package Weight 0.65 kg (1.43 lb), Body Material Die-cast aluminium housing, ENVIRONMENTAL: Operating Temperature: Starting Temperature:-40°C ~ 60°C (-40°F ~ 140°F), Working Temperature: -40°C ~ 60°C (-40°F ~ 140°F), Relative Humidity Less than 90 %, non-condensing, Ingress Protection IP67, Impact Resistance IK10, REGULATORY: Emissions: FCC PART 15, CE (EN 55032), Complies with RCM and UKCA, Immunity CE(EN 50130-4), Complies with RCM and UKCA, Safety: UL LISTED TO UL/CSA 62368-1, CE(EN 62368-1), Complies with RCM and UKCA, RoHs: CE(EN 63000) Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Outdoor STQC Approved 3MP IP WDR IR MFZ Bullet Camera OPERATIONAL; Video Standard: NTSC / PAL, Scanning System: Progressive, Image Sensor: 1/2.7” CMOS, Sensor Size (H x V); 4.608 mm x 2.592 mm, Number Of Pixels(H x V): 2304 x 1296, Minimum Illumination (Color/BW); 0.005 Lux/F1.6 (Color,30 IRE), 0 Lux/F1.6 (IR ON), S/N Ratio: 50 dB, Electronic Shutter Speed: 1/8 ~ 1/32,000, IR Distance: up to 40 m, IR Light Control: Smart IR (Auto / Manual) / OFF, IR Light Number: 4, Day/Night: Auto (ICR) / Color / BW, Backlight Compensation:WDR, BLC, HLC, White Balance Auto/Tungsten/ Fluorescent/ Daylight/Shadow/Manual, Gain Control: 0-100%, Wide Dynamic Range: 120 dB, Noise Reduction: 2D/3D DNR, Lens: 2.8mm Fixed Iris F1.6, Angle Of View: H:88°, V:47°, Privacy Masking: Off / On (4 Areas), Defog: Not supported, Local Storage: Micro SD (up to 256 GB), Alarm Inputs/Outputs: Not supported, Video Compression: H.265 HEVC/H.264/MJPEG, Smart Codec, Resolution: 1st: 2304 x 1296 / 1920 x 1080 / 1280 x 720 2nd: 704 x 576(PAL) / 704 x 480(NTSC) / 640 x 480 / 352 x 288(PAL) / 352 x 240(NTSC)3rd: 640 x 480 / 352 x 288(PAL) / 352 x 240(NTSC) / 320 x 240, Number of Video Streams: 3 (2 for encryption), Frame Rate*: MAX 30 fps, Bit Rate*: 100K ~ 6 Mbps, Audio Compression: Not supported, Audio Stream: Not supported, Audio Interface: Not supported, NETWORK: Ethernet: 10 Base-T/100 Base-TX Ethernet (RJ-45), Supported Web Browsers Chrome/Edge, Supported OS: Microsoft Windows 10, Protocols**: IPv4, IPv6, TCP / IP, HTTP, HTTPS
RTSP / RTP / RTCP, IGMP / Multicast, SMTP, DHCP, NTP, DNS, QoS, SNMP, 802.1X, UDP, ICMP, ARP, TLS, Interoperability: ONVIF Profile G/S/T, Maximum Users Access: 10 Users, Security;User account and password protection, HTTPS, IP Filter, Digest authentication, TLS1.2 only, Stream encryption, AES128 / 256, SSH / Telnet closed, PCI-DSS compliance, EVENTS / ANALYTICS: Built-in Video Analytics: Motion Detection, Tampering, Event Type: Video motion detection,Recording notification, Event Linkage: Event notification using Email and MicroSD card, Region Of Interest: 8, ELECTRICAL: Power Supply: DC12V, PoE (IEEE 802.3af) (Class 0), Power Consumption (Max): MAX 5.5W, MECHANICAL; Dimensions: Ø87.0 mm × 197.3 mm Product Weight:.0.7 kg , Package Weight: 0.85 kg , Body Material Die-cast aluminium housing, ENVIRONMENTAL: Operating Temperature: Starting Temperature:-40°C ~ 60°C (-40°F ~ 140°F)Working Temperature:-40°C ~ 60°C (-40°F ~ 140°F) (IR off), Relative Humidity: Less than 90 %, non-condensing, Ingress Protection:IP67, Bullet Casing: IK10, REGULATORY: Emissions: FCC PART 15, CE (EN 55032), Complies with RCM and UKCA, Immunity: CE(EN 50130-4), Complies with RCM and UKCA, Safety: UL LISTED TO UL/CSA 62368-1, CE(EN 62368-1), Complies with RCM and UKCA, RoHs: CE (EN 63000) Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of 32 Channel NVR Embedded Linux , 4 SATA interface, Up to 32 channel Video Inputs, NVR shall have throughput of incoming bandwidth 256Mbps & outgoing 128 Mbps, 2* HDMI , 1 *VGA Video output. Supports live view, storage, and playback at 1- 8MP resolution,Shall be capable of live streaming & Storing 32 cameras, Shall support Net HDD, Storage up to 10 TB Surveillance HDD,Shall support audio, G.711A/G.711U, Shall support 1 E-sata port, 2x RJ45 10M/100M/1000M ports,Audio input 1 channel, Audio Output 1 channel output , Alarm input 16 channel, Alarm Output 4 channel output, USB2.0*1, USB3.0*1+USB2.0*1 port , RS485*1,Protocol :IPv4, IPv6, TCP/IP, HTTP, HTTPS, DDNS,RTMP, SMTP(SSL), SNMP, DHCP, PPPoE, UPnP,NTP, P2P, FTP , Simultaneously record multiple streams in any combination of H.264/H.265/H.264+/H.265+, support Start, stop, normal play, back play, frame by frame forward, full screen, Fast forward / backward (2x, 4x, 8x,16x), Slow forward (1/2x, 1/4x, 1/8x,1/16x), Add custom/ Default Tag for any events at the time of playback, digital zoom, video clip, sub stream/main-stream, playback video bar, Shall be able to take actions pre and post recording, Send email, show message, send email, FTP upload video or screenshot, Cloud upload video or screenshot, full screen, voice prompts, Alarm output trigger, PTZ linkage on events, support the display of VCA metadata on video live-view and and playback, Supports AI from camera side : Face Detection, Human Detection, Vehicle Detection, Perimeter Intrusion Detection, Line Crossing Detection, Cross Counting, Heat Map, Crowd Density Detection, Queue Length Detection, License Plate Detection, Rare Sound Detection, Stationary Object Detection, Sound Detection, Capable to show statistics and graphs of events for different interval of time search, Shall support S.M.A.R.T HDD function for HDD status,Onvif Support , Power Supply : DC12V/2A ,Consumption without HDD : 12W , Temperature : -10°C~+50°C (14°F ~ 122°F) Humidity : Less than 90%RH , 300X227X53mm (W×D×H) Dimensions ,Certificates:BIS,FCC,CE , ROHS, REACH Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Supply of 20 Port Gigabit Intelligent Standard PoE Switch, I/O Interface Power AC INPUT (100-240 V) Ethernet 16*Gigabit PoE Ports 2*Uplink ports 2*Gigabit SFP Ports Chipset EN8850DH,RTL8238B Performance Bandwidth 40Gbps Packet Forward Rate 29.76Mpps Package Cache 3Mbit MAC Address 8K Forwarding Mode Store and forward Standard Network Protocol IEEE802.3 (Ethernet) IEEE802.3u (Fast Ethernet) IEEE802.3ab (Gigabit Ethernet) IEEE802.3x (Flow Control) IEEE 802.3z (Gigabit Ethernet Fiber Standard) PoE protocol IEEE802.3af (15.4W) IEEE802.3at (30W)POE port output voltage: DC 44-57V POE power supply core: 1/2+; 3/6- Industry Standard EMS: EN61000-4-2 (ESD), IEN61000-4-5 (Surge) Network medium 10Base-T: Cat 3, 4, 5 Class or above UTP/STP (≤ 100m) 100Base-TX: Cat 5 Class or above UTP/STP (≤ 100m) 1000Base-TX: Cat 5 Class or above UTP/STP (≤ 100m) approved make hp, juniper, mountxross, hrui, cisco, should have Optical Medium Multimode optical fiber: 50/125, 62.5/125, 100/140um Single-mode optical fiber: 8/125, 8.7/125, 9/125, 10/125um Certification Safety Certificate CE/FCC/ROHS, Environment Standard Working Environment Working temperature: -10~50°C Storage temperature: -40~70°C Working humidity: 10%~90%, non-condensing Storage humidity: 5%~95%, non-condensing
Supply, Installation, Testing & Commissioning of HDD Formatted capacity 6TB surveillance ,Data transfer rate (max) Buffer to host Host to/from drive (sustained) 6 Gb/s 171 MB/s,Cache (MB) 64,Rotational speed (RPM) IntelliPower ,Load/unload cycles4 300,000,Non-recoverable read errors per bits read <1 in 1014, Operating (2 ms, read/write) 30, Operating (2 ms, read)65, Non-operating (2 ms)250, Average power requirements (W) Read/Write 5.90,Idle 4.90,Standby and Sleep 0.40 complete in all respects.Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Display : 43 inch, 4K (3,840 x 2,160), Direct LED, Professional Display with 4K Processor, Native Contrast ratio 5,000:1 or higher, Response time 12 ms or lower, Brightness 400 cd/m² or higher, 24/7, Portrait/Tilt functionality, HDMI Auto wake up, HTML5 platform, 16GB On Board Storage, HDMI*4 with HDCP 2.3 / RS232 / USB / RJ45 / Wi-Fi Direct / 20W Speakers / Android OS or similar, Viewing angle 178 degree, Apple AirPlay & Chromecast.complete in all respects.Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of 6U Rack ,Front Glass Door (tinted,Toughened) with Lock & Key,2 pairs of 19" Mounting Rails with U-Marking,Welded Side Walls With Metal Logo,1U Cable Manager (1), Hardware Packet (1 Pkt),6 Socket 5 Amp. Power Distribution Unit (1 No),Roof Mounted Fan Unit / 90 CFM /230V AC (1 No) .Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of 6 Mtr HDMI Cable for NVR, UL Listed .Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
COPPER CONDUCTOR CABLES FOR SPECIAL ELECTRICAL SERVICES:
Supply and erection of CAT 6 with 23AWG solid bare copper conductor, special grade PE insulation with star separator, 4pair Unshielded Twisted Pair (UTP) industrial cable, FR PVC sheathed, Class-E, 250 MHz of bandwidth, supporting data transfer speeds of up to 10 Gbps (10GBASE-T) for distances up to approximately 180 feet, cables are manufactured and tested to meet the ANSI/TIA 568-C.2 and ISO/IEC 11801 Class E standards left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-
CAT 6 LAN cable
PVC, HDPE PIPES & PVC FLEXIBLE PIPES:
Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:-
Heavy Gauge PVC Conduit Pipe 25mm dia. (Flushed)
Providing Fire Alarm System (Smoke, MCP, Hooter & Control Module Only)
Supply, installation, testing & Commissioning of Addressable Smoke photo-Thermal Detector and base with sensitivity range of 0.5 to 4.0% obs/ft.The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Designed to meet UL268, 7th Edition. The solution should be from single OEM including warrenty and service for one years complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Addressable Rate of Rise Heat Detector rated at 8.3 deg C/min.NFPA 72. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches.UL & FM Approved The solution should be from single OEM including warrenty and service for one years complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device complete in all respects as approved and desired by the Engineer in-charge at site. UL & FM Approved including warrenty and service for one years complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Sounder cum Strobe rated at 80 dBA @ 3m for Audible annunciation and Min.110 cd flashintg at 1 Hz for visual indication. UL & FM Approved including warrenty and service for one years complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Addressable Control Module for Sounders/ Strobes/ Sounder cum Strobes/ Telephone Jack. The control module shall provide supervised NAC output rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary / Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period)
Supply and erection of fire survival cable for fire alarm & PA system with annealed stranded copper conductor, fire resistant mica tape wrapped (at 950°C for 180 minutes), XLPE insulated, LSHZ (low smoke & zero halogen) bedding, LSZH (low smoke & zero halogen) red outer sheath, galvanized steel wire armour, 600/1000 volts grade, Fire resistant to IEC 331 & BS7846 F2/BS6387 & CWZ, Acid gas emission to BS EN 50267 (IEC60754), smoke emission to BS EN 50268 (IEC61034) and flame propagation to BS EN 50265, BS EN 50266 (IEC 60332-3) left bare in pipe or casing or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:-
Fire Survival cable 2Core x 1.5 sq.mm
Providing Silent DG Set 625-650KVA with AMF Control Panel
Supply, Erection, Testing and Commissioning of Water Cooled Silent DG Set 625-650KVA with AMF Control Panel, Three Phase, 415Volts, 50Hz, 1500 RPM Silent (Sound Proof) Diesel Generator Set. It should be Water cooled naturally aspirated/ turbo charged/ turbo charged after cool (As per manufacturer standard). DG Set should be operated/ controlled through AMF Panel as well as Manually ENGINE: The Diesel engine developing suitable BHP for giving a power rating as per ISO 8528- Part-1 (With CPCB-IV Norms) in KVA at the load terminals of alternator at 1500 rpm at actual site conditions. The engine shall confirm to IS 10000/ ISO 3046/ BS: 649/ BS 5514 amended up to date have dynamically balanced Fly wheel, air cleaner (dry/ oil bath type) as per manufacturer standard. A mechanical/ electronic governor of TYPE A1 AND A2 to maintain engine speed at all conditions of load, daily fuel service tank of minimum 8 hours running capacity as per manufacturer standard, Dry exhaust manifold with suitable exhaust residential grade silencer to reduce the noise level.suitable self-starter for 12 V/ 24 V DC ,battery charging alternator unit and voltage regulator, Lubrication oil cooler,Lubrication oil filters with replaceable elements.
ENGINE CONTROL PANEL: Engine control panel fitted and having digital display i.e Start/stop key switch/push button, Battery charging indication,Engine Hours indications, Over speed indication, High water temperature indication, Lubricant oil pressure indication,) RPM indication. ALTERNATOR: The alternator should be designed as per (IS4722 and IEC:34 ) standard. Rated Power Factor : 0.8 (lag), Rated voltage : 230/415 volt, SPDP (Screen Protected Drip Proof), Degree of protection: IP-23, Ventilation : Self ventilated air cooled
Alternator should have 40 degree maximum class H insulation, Automatic voltage regulator unit should be provided as per standard practice of manufacturer. Its voltage dip shall not exceed more than 20% of the rated voltage at any step load or transient load as per ISO 8528 (Part-1). Its efficiency at full load 0.8 power factor, 10% overload one hour in every 12 hrs of continuous use. ACOUSTIC ENCLOSURE: The enclosure shall be fabricated out the CRCA sheet of thickness not less than 1.6 mm on the outside cover with inside cover having not less than 0.6 mm thick perforated powder coated CRCA sheet. It should be IP54 Suitable for outdoor installation exposed to weather conditions, noise level up to 75 dB (A). All sheet metal parts should be processed through 7-tank pre treatment process and batteries accommodated in the battery rack .The acoustic lining should be made up of high quality insulation material i.e. Rockwool / glass/ mineral wool / PU foam of appropriate thickness & density for sound absorption.The inside of enclosure should be provided with at least one no. 28 W-T5 fluorescent tube light/ LED 10Watt luminaries controlled by a 5A switch for adequate lighting during servicing etc.
AMF PANEL: AMF control panel shall be fabricated out of 1.6 mm sheet steel, totally enclosed, dust, damp and vermin proof wall mounted/ free standing floor mounted type with IP-53 degree of protection & front operated, composite meter for digital display, HRC fuses of suitable rating. MCCB (Fixed Thermal and Adjustable Thermal protection)/ ACB (Over cuurent/ overload, shorcircuit, instantenous, earth fault protection) should be used. Battery charger complete with voltage regulator, Voltmeter and Ammeter for charging the battery from external mains. This will be in addition to the battery charging alternator or dynamo fitted on the engine.All the components in the control panel shall be properly mounted, duly wired and labeled. Suitable terminals are to be provided for panel incoming and outgoing connections. System opeartion facility provided shall afford the following operational requirements. Necessary instruments and accessories such as voltmeter, power factor meter, KW meter, KWH meter, Ammeter, Frequency meter,battery charger complete in all respect as desired by engineer at site:-
XLPE INSULATED UN-ARMOURED CABLES (LOOSE):
Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-
Overall size 400sq.mm (3½ Core) Unarmoured (Loose) (3 Runs)
DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:
Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:-
Double Walled Corrugated HDPE Pipe 160/ 136mm (Outer/ Inner dia.)
COPPER EARTHING
COPPER EARTHING (Upto 14 metre in Length):
Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 4.50 metre (14.76 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 8metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 3metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-
Earthing with 40mm x 5mm Copper Tape (upto 14Metre in Length)
COPPER EARTHING STRIP (As Additional Length):
Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
Additional Length 40mm x 5mm thick Copper Tape
Providing Power Supply for PH Services
XLPE INSULATED UN-ARMOURED CABLES (ON SURFACE):
Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid (On Surface) as per PWD General Specifications:-
Overall size 70sq.mm (3½ Core) Un-armoured (On-Surface)
XLPE INSULATED UN-ARMOURED CABLES (LOOSE):
Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-
Overall size 50sq.mm (3½ Core) Unarmoured (Loose)
DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:
Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:-
Double Walled Corrugated HDPE Pipe 63/ 51mm (Outer/ Inner dia.)
MCCB's (FOR PANELS & SHEET ENCLOSURE):
Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-
MCCB Four Pole 250amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting
MCCB's (MOULDED CASE CIRCUIT BREAKER):
Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-
MCCB Four Pole 160amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MCCB Four Pole 200amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MS SHEET ENCLOSURE FOR MCCB's:
Supply & Erection of indoor type MCCB enclosure of suitable size having provision for MCCB with extended rotary handle. The Enclosure shall be made from 14/16 SWG CRCA sheet, confirming to IS 8623/1977-82. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The Enclosure door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. The Enclosure will be wall mounting type having provision for cable entry from bottom/top with cable glands etc. The sheet metal is sprayed with corrosion resistant etch primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work:-
MS Sheet Enclosure having provision for MCCB 40-160Amp.with extended rotary handle (Approx. Size 500mm x 300mm x 200mm)
MS Sheet Enclosure having provision for MCCB 200-630Amp.with extended rotary handle (Approx. Size 750mm x 300mm x 250mm)
SHEET METAL BUS BAR CHAMBERS (COPPER STRIPS):
Supply and erection of sheet metal bus-bar chamber (factory fabricated) duly powder coated on existing surface with required 4Nos. of tin plated copper bus-bar strips of suitable length and cross-sectional area mounted on DMC/ SMC moulds at sufficient distance, enclosure made of M.S. sheet 1.6mm thick with hinged cover and lock, fitted with dust excluding gaskets and secured with sufficient no. of cadmium plated iron screws and of given overall dimensions and to be fixed with G.I. bolts and nuts/ rag bolts and nuts etc. complete with all accessories including connections with suitable size of thimbles, bonding to the existing earth and painting etc. as desired by the Engineer-in-charge at site:-
Bus Bar Chamber 200amp., 415volts Overall Dimensions (610mm x 510mm x 215mm) nominal
COPPER EARTHING
COPPER EARTHING (Upto 14 metre in Length):
Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 4.50 metre (14.76 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 8metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 3metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-
Earthing with 20mm x 3mm Copper Tape (upto 14Metre in Length)
COPPER EARTHING STRIP (As Additional Length):
Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
Additional Length 20mm x 3mm thick Copper Tape
LINAC
RECESSED PVC CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES:
Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge PVC conduit pipe 20mm/ 25mm dia. (ISI Marked) recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulators (two module) 100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10Amp. Switches and 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), Steel Hooks, Sheet metal fan box (1.6mm thick shape hexagonal), Circular junction Boxes (Four way PVC 1½" deep for walls and CI 3" deep for ceiling), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc. including the cost of above material, cutting and filling up of chases (With finishing surface)for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site. :-
Wiring fan point (With fan box)
Wiring light point
Wiring 6Amp. wall socket point
Wiring 6Amp. Plug control comprising wall socket point
Wiring 16/20Amp. power plug control point
Wiring light point without control switch.
RECESSED COMPUTER SUPPLY TERMINAL POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES):
Wiring Computer supply terminal points recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10/16/20Amp. Switches and blanking plate etc., and covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface)for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site. :-
Wiring Computer terminal point having 2 Nos. 6Amp. 2/3 universal socket (shuttered), 1No. 16/20Amp. universal Socket (shuttered) and 2Nos. 16/20Amp. switch with indicator (Modular accessories).
RECESSED AIR CONDITIONER SUPPLY TERMINAL POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYATEM WITH MODULAR ACCESSORIES):
Wiring air conditioner supply terminal points recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 25Amp. combined/ universal Socket (shuttered) and modular motor starter 25Amp. (2Module), covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases:-
Wiring AC supply terminal points having 1No. 25Amp. universal Socket (shuttered) erected at AC height and 1No. Motor starter 25Amp. erected at switchboard height.
RECESSED TV, TELEPHONE & NETWORKING SOCKETS OUTLET POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES):
Supply and erection of TV socket, Telephone socket and Networking socket points in powder coated/anodized concealed metal boxes recessed in wall required for suitable number of modules (Modular accessories) for having TV sockets, Telephone sockets RJ11 & Networking socket RJ45 (one module), covered with Frame Plate and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):-
Wiring Telephone socket point RJ11 (one module)
Wiring Networking socket point RJ45 (one module)
CABLE TRAY
Supply and erection of MS perforated cable tray (MS Sheet thickness 2mm) with DA gray paint on the existing surface with the help of MS angle iron support (to be painted with approved paint) of size 50mm x 50mm x 6mm thick to be fixed with fastners/ nut & bolts etc., complete in all respect as desired by the Engineer-in-charge and as per PWD General Specifications for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site.:-
Cable Tray Size 150mm x 50mm x 50mm (2mm thick)
Cable Tray Size 300mm x 50mm x 50mm (2mm thick)
Cable Tray Size 450mm x 50mm x 50mm (2mm thick)
PVC, HDPE PIPES & PVC FLEXIBLE PIPES:
Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, MS saddle clamps and other petty materials etc., as per PWD General Specificationsfor connections and testing complete in all respect as approved and desired by the Engineer in-charges at site. :-
Heavy Gauge PVC Conduit Pipe 25mm dia. (Flushed)
Heavy Gauge PVC Conduit Pipe 32mm dia. (Flushed)
Heavy Gauge PVC Conduit Pipe 40mm dia. (Flushed)
PVC INSULATED FR COPPER CONDUCTOR CABLES:
Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-
Overall size 1.5sq.mm (Un-sheathed)
Overall size 2.5sq.mm (Un-sheathed)
Overall size 4sq.mm (Un-sheathed)
Overall size 10sq.mm (Un-sheathed)
Overall size 16sq.mm (Un-sheathed)
Overall size 70sq.mm (Un-sheathed)
XLPE INSULATED UN-ARMOURED CABLES (LOOSE):
Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-
Overall size 240sq.mm (3½ Core) Un-armoured (Loose)
LT PANELS & MCCB's (MOULDED CASE CIRCUIT BREAKERS):
LT PANELS:
Designing, Supply, Erection, Testing & commissioning of indoor Type LT cubical panel enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, 3 phase 4 wire & earth system. The assembly manufacturer should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP 54/55). Fabrication:- Panel shall be made from 14/16 SWG CRCA sheet, conforming to IS 8623/1977-82. The sheet metal used for the fabrication of control panel will be 2mm for load bearing member’s door and fittings plates etc. the partitions and other non load bearing members will be fabricated out of 1.6mm sheet, the sheet will be of mild steel CRCA type. The base channel will be made out of 75 x 40 x 5mm rolled channel.
The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel. The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc.
The fabrication should be such that all the member i.e. vertical/horizontal should be detachable type i.e. total bolted. In case of any changes required at site. it should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B construction fully compartmentalized type i.e. bus bar chamber as well as the cable chamber should be totally isolated from the feeder chamber. Where there crossing of the wire or bus links. It should have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition.
Painting:- The sheet metal is sprayed with corrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work . Busbars:-The panel shall be provided with TPN aluminium busbar of suitable size according to the size of MCCB's. Busbar shall be of high conductivity (53% to 58%) E91-E Grade aluminium (1A/Sq.mm). All Busbar will be air insulated with codified in Red, Yellow, Blue & Black as per standard for cable termination with the help of extended busbar only with proper adjustable cable supports. The main busbar would be supported upon non-hygroscopic SMC/DMC supports.
LT Panel enclosure having space for 1No. Incomer MCCB 400Amp. and 4Nos. outgoing MCCB's 100amp. to 160amp. according to the requirement at site (Approx. size 2025 x 1100 x 400mm)
MINIATURE CIRCUIT BREAKERS/ RCBO's/ RCCB's:
MINIATURE CIRCUIT BREAKERS:
Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:-
MCB Single Pole 6-32amp. (10kA, Curve-C) (20A)
MCB Four Pole 50, 63amp. (10kA, Curve-C)
MCCB's (FOR PANELS & SHEET ENCLOSURE):
Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-
MCCB Four Pole 200amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MCCB Four Pole 250amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting
MCCB Four Pole 400amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting
MCCB's (MOULDED CASE CIRCUIT BREAKER):
Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-
MCCB Four Pole 400amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting
MS SHEET ENCLOSURE FOR MCCB's:
Supply & Erection of indoor type MCCB enclosure of suitable size having provision for MCCB with extended rotary handle. The Enclosure shall be made from 14/16 SWG CRCA sheet, confirming to IS 8623/1977-82. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The Enclosure door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. The Enclosure will be wall mounting type having provision for cable entry from bottom/top with cable glands etc. The sheet metal is sprayed with corrosion resistant etch primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work:-
MS Sheet Enclosure having provision for MCCB 200-630Amp.with extended rotary handle (Approx. Size 750mm x 300mm x 250mm)
COPPER EARTHING
COPPER EARTHING (Upto 14 metre in Length):
Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 4.50 metre (14.76 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 8metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 3metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-
Earthing with 25mm x 3mm Copper Tape (upto 14Metre in Length)
Earthing with 40mm x 5mm Copper Tape (upto 14Metre in Length)
COPPER EARTHING STRIP (As Additional Length):
Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
Additional Length 25mm x 3mm thick Copper Tape
Additional Length 40mm x 5mm thick Copper Tape
Supply and erection of Recessed Mounted 36 Watt LED 2x2 panel (including constant LED driver) with CRCA sheet having efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site.LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No:- AT/2021/GL/1410-1422 Dated:- 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited labortary.
Supply and erection of 3-Star rating AC Ceiling Fan 1200mm (48") suitable for 230 V single phase with double ball bearing, copper wound, full aluminium body, 3Nos. of blades, white in colour. The mounting type is down rod mount. The product should possess a minimum air deleivery of 218 CMM. The rated speed of the the product must be minimum of 350 revolutions per minute and 5Nos. of speeds. The approximate weight of the product should be 4Kg and 180gms.(without packing) or higher. The product should have a manufcaturer's guarantee /warranty of minimum 2 years. The product should be complete in all aspects with fan motor, bladeset, down rod, conopy set, shackle kit, twisted wire etc., including erection & testing of ceiling fan having connection with PVC insulated PVC sheathed two single core copper conductor (FR) cable 0.75 sq. mm complete in all respects as per satisfcation of the Engineer in-charge at site.
Supply and erection of Wall Fan Plastic Body 400MM, 16" including flexible wire & petty material etc. for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site.
Supply and erection of CAT 6 with 23AWG solid bare copper conductor, special grade PE insulation with star separator, 4pair Unshielded Twisted Pair (UTP) industrial cable, FR PVC sheathed, Class-E, 250 MHz of bandwidth, supporting data transfer speeds of up to 10 Gbps (10GBASE-T) for distances up to approximately 180 feet, cables are manufactured and tested to meet the ANSI/TIA 568-C.2 and ISO/IEC 11801 Class E standards left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-
CAT 6 LAN cable
Providing CCTV System
Supply, Installation, Testing & Commissioning of Indoor STQC Approved 3 MP IP WDR IR Rugged Mini Dome Camera OPERATIONAL: Video Standard: NTSC / PAL, Scanning System: Progressive, Image Sensor: 1/2.7” CMOS, Sensor Size (H x V): 4.608 mm x 2.592 mm, Number Of Pixels (H x V): 2304 x 1296, Minimum Illumination (Color/BW): .005 Lux / F1.6 (Color, 30 IRE), 0 Lux / F1.6 (IR ON), S/N Ratio: 50 dB, Electronic Shutter Speed: 1/8 ~ 1/32,000, IR Distance: up to 40 m, IR Light Control, Smart IR ( Auto / Manual ) / OFF, IR Light Number: 2, Day/Night: Auto (ICR) / Color / BW, Backlight Compensation: WDR, BLC, HLC, White Balance: Auto/Tungsten/ Fluorescent/ Daylight/Shadow/Manual, Gain Control: 0-100%, Wide Dynamic Range: 120 dB, Noise Reduction: 2D / 3D DNR, Lens: : 2.8 mm Fixed Iris, F1.6, Angle Of View: H: H:88°°, V:47°, Privacy Masking: Off / On (4 Areas), Defog: Not supported, Local Storage: Micro SD (up to 256 GB), Alarm Inputs/Outputs: Not supported, Pan Range: 0°-330°, Tilt Range: 0°-75°, Rotation Range: 0°-337°, Video Compression:H.265 HEVC/H.264/MJPEG, Smart Codec, Resolution: 1st: 2304 x 1296 / 1920 x 1080 / 1280 x 720 2nd: 704 x 576 (PAL) / 704 x 480 (NTSC) / 640 x 480 / 352 x 288 (PAL) / 352 x 240 (NTSC) 3rd: 640 x 480 / 352 x 288 (PAL) / 352 x 240 (NTSC) / 320 x 240, Number of Video Streams: 3 (2 for encryption), Frame Rate*: MAX 30 fps, Bit Rate*: 100K ~ 6 Mbps, Audio Compression: Not supported, Audio Stream: Not supported, Audio Interface: Not supported,
NETWORK: Ethernet: 10 Base-T/100 Base-TX Ethernet (RJ-45), Supported Web Browsers: Chrome / Edge, Supported OS: Microsoft Windows 10, Protocols**: IPv4, IPv6, TCP / IP, HTTP, HTTPS, RTSP / RTP / RTCP, IGMP / Multicast, SMTP, DHCP, NTP, DNS, QoS, SNMP, 802.1X, UDP, ICMP, ARP, TLS, Interoperability: ONVIF Profile G/S/T, Maximum Users Access: 10 Users, Security: User account and password protection, HTTPS, IP Filter, Digest authentication, TLS1.2 only, Stream encryption, AES128 / 256, SSH / Telnet closed, PCI-DSS compliance, EVENTS / ANALYTICS: Built-in Video: Analytics, Motion Detection, Tampering, Event Type: Video motion detection,Recording notification, Event Linkage: Event notification using Email and MicroSD card, Region Of Interest: 8, ELECTRICAL: Power Supply: DC12V, PoE (IEEE 802.3af) (Class 0), Power Consumption (Max): MAX 3.6 W, MECHANICAL: Dimensions: Ø110.0 mm × 85.6 mm (Ø4.33” × 3.37”), Dome Diameter Ø78.2 mm (3.08”), Product Weight 0.56 kg (1.23 lb), Package Weight 0.65 kg (1.43 lb), Body Material Die-cast aluminium housing, ENVIRONMENTAL: Operating Temperature: Starting Temperature:-40°C ~ 60°C (-40°F ~ 140°F), Working Temperature: -40°C ~ 60°C (-40°F ~ 140°F), Relative Humidity Less than 90 %, non-condensing, Ingress Protection IP67, Impact Resistance IK10, REGULATORY: Emissions: FCC PART 15, CE (EN 55032), Complies with RCM and UKCA, Immunity CE(EN 50130-4), Complies with RCM and UKCA, Safety: UL LISTED TO UL/CSA 62368-1, CE(EN 62368-1), Complies with RCM and UKCA, RoHs: CE(EN 63000) Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Outdoor STQC Approved 3MP IP WDR IR MFZ Bullet Camera OPERATIONAL; Video Standard: NTSC / PAL, Scanning System: Progressive, Image Sensor: 1/2.7” CMOS, Sensor Size (H x V); 4.608 mm x 2.592 mm, Number Of Pixels(H x V): 2304 x 1296, Minimum Illumination (Color/BW); 0.005 Lux/F1.6 (Color,30 IRE), 0 Lux/F1.6 (IR ON), S/N Ratio: 50 dB, Electronic Shutter Speed: 1/8 ~ 1/32,000, IR Distance: up to 40 m, IR Light Control: Smart IR (Auto / Manual) / OFF, IR Light Number: 4, Day/Night: Auto (ICR) / Color / BW, Backlight Compensation:WDR, BLC, HLC, White Balance Auto/Tungsten/ Fluorescent/ Daylight/Shadow/Manual, Gain Control: 0-100%, Wide Dynamic Range: 120 dB, Noise Reduction: 2D/3D DNR, Lens: 2.8mm Fixed Iris F1.6, Angle Of View: H:88°, V:47°, Privacy Masking: Off / On (4 Areas), Defog: Not supported, Local Storage: Micro SD (up to 256 GB), Alarm Inputs/Outputs: Not supported, Video Compression: H.265 HEVC/H.264/MJPEG, Smart Codec, Resolution: 1st: 2304 x 1296 / 1920 x 1080 / 1280 x 720 2nd: 704 x 576(PAL) / 704 x 480(NTSC) / 640 x 480 / 352 x 288(PAL) / 352 x 240(NTSC)3rd: 640 x 480 / 352 x 288(PAL) / 352 x 240(NTSC) / 320 x 240, Number of Video Streams: 3 (2 for encryption), Frame Rate*: MAX 30 fps, Bit Rate*: 100K ~ 6 Mbps, Audio Compression: Not supported, Audio Stream: Not supported, Audio Interface: Not supported, NETWORK: Ethernet: 10 Base-T/100 Base-TX Ethernet (RJ-45), Supported Web Browsers Chrome/Edge, Supported OS: Microsoft Windows 10, Protocols**: IPv4, IPv6, TCP / IP, HTTP, HTTPS
RTSP / RTP / RTCP, IGMP / Multicast, SMTP, DHCP, NTP, DNS, QoS, SNMP, 802.1X, UDP, ICMP, ARP, TLS, Interoperability: ONVIF Profile G/S/T, Maximum Users Access: 10 Users, Security;User account and password protection, HTTPS, IP Filter, Digest authentication, TLS1.2 only, Stream encryption, AES128 / 256, SSH / Telnet closed, PCI-DSS compliance, EVENTS / ANALYTICS: Built-in Video Analytics: Motion Detection, Tampering, Event Type: Video motion detection,Recording notification, Event Linkage: Event notification using Email and MicroSD card, Region Of Interest: 8, ELECTRICAL: Power Supply: DC12V, PoE (IEEE 802.3af) (Class 0), Power Consumption (Max): MAX 5.5W, MECHANICAL; Dimensions: Ø87.0 mm × 197.3 mm Product Weight:.0.7 kg , Package Weight: 0.85 kg , Body Material Die-cast aluminium housing, ENVIRONMENTAL: Operating Temperature: Starting Temperature:-40°C ~ 60°C (-40°F ~ 140°F)Working Temperature:-40°C ~ 60°C (-40°F ~ 140°F) (IR off), Relative Humidity: Less than 90 %, non-condensing, Ingress Protection:IP67, Bullet Casing: IK10, REGULATORY: Emissions: FCC PART 15, CE (EN 55032), Complies with RCM and UKCA, Immunity: CE(EN 50130-4), Complies with RCM and UKCA, Safety: UL LISTED TO UL/CSA 62368-1, CE(EN 62368-1), Complies with RCM and UKCA, RoHs: CE (EN 63000) Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
SITC of NVR shall have 16-channel video input. NVR shall be Embedded Linux. NVR shall support the following bandwidth - Incoming 112 Mbps and outgoing 96 Mbps. NVR shall support Video Output: HDMI (1 1024*768, 1280*720, 1280*1024, 1440*900, 1920*1080, 3840*2160/EDID), VGA (1024*768, 1280*720, 1280*1024, 1440*900, 1920*1080). NVR shall offer the following recording resolution streams Video Resolution: 8MP, 5MP, 3MP, 2MP(1080P), 1.3MP(960P), and 1.0MP(720P). NVR shall support Motion Detection. NVR shall support 4 zones of Privacy Mask. NVR shall offer intelligent analysis functions powered including Human and Vehicle Detection, Perimeter Intrusion Detection, Line Crossing Detection, Stationary Object Detection, Crossing Counting, Heat Map, Crowd Density Detection, Rare Sound detection (gunshot/baby crying/dog barking), Face Detection. NVR shall support G.711A/G.711U Audio compression. NVR shall integrate Audio input 1 CH RCA port. Video Recording and Playback. NVR shall have 2HDDs Slots. NVR shall support a 1-30fps Video Frame Rate. NVR shall have Record Mode: schedule, event-based - motion, I/O, PIR. NVR shall offer 16 CH max sync playback. NVR shall be able to playback according to different types, including Playback Mode Instant playback, Local video, and local image. NVR shall support Record Search Time, calendar, channel search, and event search, (ANR, regular video, motion detection video, alarm video, intelligent detection video). NVR shall support the following Video Playback: Start, stop, normal play, back play, frame-by-frame forward, full screen, Fast forward / backward (2x, 4x, 8x,16x), Slow forward (1/2x, 1/4x, 1/8x,1/16x), Add custom/Default Tag, digital zoom, video clip, sub-stream/main-stream, playback video bar, scale of 30 mins to 24 hrs. Storage and Backup. NVR shall offer USB mobile hard disk, U disk, and network backup Methods. NVR Should support FTP for uploading alarm video. NVR shall ANR Support Smart IPC (with SD card) ANR. Function. NVR shall support the following protocols: IPv4, IPv6, TCP/IP, HTTP, HTTPS, DDNS, RTMP, SMTP(SSL), SNMP, DHCP, PPPoE, UPnP, NTP, P2P, FTP, IP filter. NVR shall support ONVIF Profile S Support. NVR shall support ONVIF/RTSP/HTTP/HTTPS/RTMP port customized. NVR shall support Mobile Surveillance Support Apple, Android & Internet Explorer Support IE, Chrome, Firefox, and Safari. NVR shall have Digital Zoom support. NVR shall have IPC timing Manual/auto/timing/reconnect timing. Approved makes bosch, mountxross, axis, pelco shall support the following Event Actions: pre and post-recording, Sending an email, showing a message, sending an email, FTP upload
video or screenshot, Cloud upload video or screenshot, full screen, voice prompts, Alarm output trigger, PTZ linkage. NVR Should support a combination of different events for effective alarm trigger and response. NVR Shall have exception alarms on event type of no space on disk, disk error, and video loss. NVR Shall be able to configure covert on camera by which recording is happening, but the live view is restricted. Network Detection monitoring, Utilization of total and used bandwidth, IP filter with blacklist and whitelist. NVR makes bosch, mountxross, axis, pelco Shall support video cover privacy mask both on live and recording up to 4 areas. NVR shall have User Management User add, delete, modify, permission management, and support. NVR Shall be able to trigger PTZ presets on any camera AI event. NVR shall support Security Mode authorized username and password, HTTPS with a password, and RTSP Validation. NVR should Manage IPC Support IPC centralized management, including IPC parameter configuration, information export and import, real-time information acquisition and upgrade. NVR shall have Statistics of events for face recognition, vehicle & and human, cross count, and heat map. Network Interface. NVR shall integrate 1 X RJ45 10M/100M/1000M adaptive Ethernet port. NVR shall integrate 1* RS485,& USB2.0*1(front) USB3.0*1+USB2.0*1(rear). General. The power consumption shall be 12V/2A and power Consumption ≤12W (Without HDD). Operation Temp./ Humidity -10°C ~ 55°C/10%-90%. Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Supply of 20 Port Gigabit Intelligent Standard PoE Switch, I/O Interface Power AC INPUT (100-240 V) Ethernet 16*Gigabit PoE Ports 2*Uplink ports 2*Gigabit SFP Ports Chipset EN8850DH,RTL8238B Performance Bandwidth 40Gbps Packet Forward Rate 29.76Mpps Package Cache 3Mbit MAC Address 8K Forwarding Mode Store and forward Standard Network Protocol IEEE802.3 (Ethernet) IEEE802.3u (Fast Ethernet) IEEE802.3ab (Gigabit Ethernet) IEEE802.3x (Flow Control) IEEE 802.3z (Gigabit Ethernet Fiber Standard) PoE protocol IEEE802.3af (15.4W) IEEE802.3at (30W)POE port output voltage: DC 44-57V POE power supply core: 1/2+; 3/6- Industry Standard EMS: EN61000-4-2 (ESD), IEN61000-4-5 (Surge) Network medium 10Base-T: Cat 3, 4, 5 Class or above UTP/STP (≤ 100m) 100Base-TX: Cat 5 Class or above UTP/STP (≤ 100m) 1000Base-TX: Cat 5 Class or above UTP/STP (≤ 100m) approved make hp, juniper, mountxross, hrui, cisco, should have Optical Medium Multimode optical fiber: 50/125, 62.5/125, 100/140um Single-mode optical fiber: 8/125, 8.7/125, 9/125, 10/125um Certification Safety Certificate CE/FCC/ROHS, Environment Standard Working Environment Working temperature: -10~50°C Storage temperature: -40~70°C Working humidity: 10%~90%, non-condensing Storage humidity: 5%~95%, non-condensing
Supply, Installation, Testing & Commissioning of HDD Formatted capacity 6TB surveillance ,Data transfer rate (max) Buffer to host Host to/from drive (sustained) 6 Gb/s 171 MB/s,Cache (MB) 64,Rotational speed (RPM) IntelliPower ,Load/unload cycles4 300,000,Non-recoverable read errors per bits read <1 in 1014, Operating (2 ms, read/write) 30, Operating (2 ms, read)65, Non-operating (2 ms)250, Average power requirements (W) Read/Write 5.90,Idle 4.90,Standby and Sleep 0.40 complete in all respects.Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Display : 43 inch, 4K (3,840 x 2,160), Direct LED, Professional Display with 4K Processor, Native Contrast ratio 5,000:1 or higher, Response time 12 ms or lower, Brightness 400 cd/m² or higher, 24/7, Portrait/Tilt functionality, HDMI Auto wake up, HTML5 platform, 16GB On Board Storage, HDMI*4 with HDCP 2.3 / RS232 / USB / RJ45 / Wi-Fi Direct / 20W Speakers / Android OS or similar, Viewing angle 178 degree, Apple AirPlay & Chromecast.complete in all respects.Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing, Commissionning & Laying of Cat 6 Cable in existing conduit Category 6 Unshielded Twisted Pair 23 AWG:305mtr. ,4 pair 100W cable shall be compliant with ANSI/TIA/EIA-568-C.2 Additional Transmission Performance Specifications for 4-pair 100W Category 6Cabling. Tested upto 600 MHZ; Construction: 4 twisted pairs separated by internal X shaped, 4 channel, polymer spine / full separator. Half shall not be accepted.Sheath : FRPVC/LSZH,Outer Diameter 6.1 mm nominal;Temperature Range -20° to +60°C.Manufacturer should have ISO 9001:2008 Certification for Quality Management System.Manufacturer should have ISO 14001:2004 Certification for Environmental Management System.All UTP and Its Components should be from same OEM...Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of 6U Rack ,Front Glass Door (tinted,Toughened) with Lock & Key,2 pairs of 19" Mounting Rails with U-Marking,Welded Side Walls With Metal Logo,1U Cable Manager (1), Hardware Packet (1 Pkt),6 Socket 5 Amp. Power Distribution Unit (1 No),Roof Mounted Fan Unit / 90 CFM /230V AC (1 No) .Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of 6 Mtr HDMI Cable for NVR, UL Listed .Including Warrenty and service for one year complete in all respects as approved and desired by the Engineer in-charge at site.
PVC, HDPE PIPES & PVC FLEXIBLE PIPES:
Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:-
Heavy Gauge PVC Conduit Pipe 25mm dia. (Flushed)
Providing Fire Alarm System (Smoke, MCP, Hooter & Control Module Only)
Supply, installation, testing & Commissioning of Addressable Smoke photo-Thermal Detector and base with sensitivity range of 0.5 to 4.0% obs/ft.The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Designed to meet UL268, 7th Edition. The solution should be from single OEM including warrenty and service for one years complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Addressable Rate of Rise Heat Detector rated at 8.3 deg C/min.NFPA 72. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches.UL & FM Approved The solution should be from single OEM including warrenty and service for one years complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device complete in all respects as approved and desired by the Engineer in-charge at site. UL & FM Approved including warrenty and service for one years complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Sounder cum Strobe rated at 80 dBA @ 3m for Audible annunciation and Min.110 cd flashintg at 1 Hz for visual indication. UL & FM Approved including warrenty and service for one years complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, Installation, Testing & Commissioning of Addressable Control Module for Sounders/ Strobes/ Sounder cum Strobes/ Telephone Jack. The control module shall provide supervised NAC output rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary / Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period)
Supply and erection of fire survival cable for fire alarm & PA system with annealed stranded copper conductor, fire resistant mica tape wrapped (at 950°C for 180 minutes), XLPE insulated, LSHZ (low smoke & zero halogen) bedding, LSZH (low smoke & zero halogen) red outer sheath, galvanized steel wire armour, 600/1000 volts grade, Fire resistant to IEC 331 & BS7846 F2/BS6387 & CWZ, Acid gas emission to BS EN 50267 (IEC60754), smoke emission to BS EN 50268 (IEC61034) and flame propagation to BS EN 50265, BS EN 50266 (IEC 60332-3) left bare in pipe or casing or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:-
Fire Survival cable 2Core x 1.5 sq.mm
Providing Power Supply for PH Services
XLPE INSULATED UN-ARMOURED CABLES (ON SURFACE):
Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid (On Surface) as per PWD General Specifications:-
Overall size 16sq.mm (4Core) Un-armoured (On-Surface)
XLPE INSULATED UN-ARMOURED CABLES (LOOSE):
Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-
Overall size 16sq.mm (4Core) Un-armoured (Loose)
DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:
Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:-
Double Walled Corrugated HDPE Pipe 50/ 38mm (Outer/ Inner dia.)
MCCB's (FOR PANELS & SHEET ENCLOSURE):
Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-
MCCB Four Pole 63/80/100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MCCB's (MOULDED CASE CIRCUIT BREAKER):
Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-
MCCB Four Pole 63/80/100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MS SHEET ENCLOSURE FOR MCCB's:
Supply & Erection of indoor type MCCB enclosure of suitable size having provision for MCCB with extended rotary handle. The Enclosure shall be made from 14/16 SWG CRCA sheet, confirming to IS 8623/1977-82. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The Enclosure door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. The Enclosure will be wall mounting type having provision for cable entry from bottom/top with cable glands etc. The sheet metal is sprayed with corrosion resistant etch primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work:-
MS Sheet Enclosure having provision for MCCB 40-160Amp.with extended rotary handle (Approx. Size 500mm x 300mm x 200mm)
SHEET METAL BUS BAR CHAMBERS (COPPER STRIPS):
Supply and erection of sheet metal bus-bar chamber (factory fabricated) duly powder coated on existing surface with required 4Nos. of tin plated copper bus-bar strips of suitable length and cross-sectional area mounted on DMC/ SMC moulds at sufficient distance, enclosure made of M.S. sheet 1.6mm thick with hinged cover and lock, fitted with dust excluding gaskets and secured with sufficient no. of cadmium plated iron screws and of given overall dimensions and to be fixed with G.I. bolts and nuts/ rag bolts and nuts etc. complete with all accessories including connections with suitable size of thimbles, bonding to the existing earth and painting etc. as desired by the Engineer-in-charge at site:-
Bus Bar Chamber 200amp., 415volts Overall Dimensions (610mm x 510mm x 215mm) nominal
COPPER EARTHING
COPPER EARTHING (Upto 14 metre in Length):
Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 4.50 metre (14.76 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 8metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 3metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-
Earthing with 20mm x 3mm Copper Tape (upto 14Metre in Length)
COPPER EARTHING STRIP (As Additional Length):
Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
Additional Length 20mm x 3mm thick Copper Tape
Networking Work Demand For PET-SPECT and LA Raised on 10.11.2025
Supply & erection of CAT 6A ONE Meter long Patch Cord Having RJ-45 Male Connectors on both ends DCC up-to 10/100/1000/10000 mbpsConductor: 24 AWG, Multi-strands Conductor Metal: Bare Copper Insulation Material: HD-PE Material: FR-PVC s TIA/EIA 568C.2 standard ISO/IEC 11801 Class EA. Gold Plated: 50U° Contact Blade: Copper Alloy Dielectric withstanding voltage: 1000V DC/min, 500M Ù, 1000V DC/min UL Applications: PC UL94-V-0 Complete in all respect as desired by the Engineer in charge of work at site.
Supply & erection of CAT 6A TWO Meter long Patch Cord Having RJ-45 Male Connectors on both ends DCC up-to 10/100/1000/10000 mbps Conductor: 24 AWG, Multi-strands Conductor Metal: Bare Copper Insulation Material: HD-PE Material: FR-PVC s TIA/EIA 568C.2 standard ISO/IEC 11801 Class EA. Gold Plated: 50U° Contact Blade: Copper Alloy Dielectric withstanding voltage: 1000V DC/min, 500M Ù, 1000V DC/min UL Applications: PC UL94-V-0 Complete in all respect as desired by the Engineer in charge of work at site.
Supply & erection of CAT 6A 24 Port Fully loaded Patch Panel, Rack Mountable for cable termination, ID Plate PC transparent color with paper, Panel: SPCC,1.5mm thickness with black color painted, RJ45 Jack- Housing: P B T + g la ssfiber, UL-94V-0 Contact Brackets: PBT + glass fiber, UL-94V-0, RJ45 Jack Contact- Material: Phosphor bronze with nickel plated Finish: 50 micro-inches Gold plated on plug contact area, IDC Housing: PC, UL 94V-0 Terminal: phosphor bronze with tin plated, e ANSI/TIA/EIA 568C.2 & ISO/IEC 11801 standard Complete in all respect as desired by the Engineer in charge of work at site.
Supply & erection of CAT 6A UTP Cable Having speed upto 10Gbps Complete in all respect as desired by the Engineer in charge of work at site.
Supply & erection of CAT6A Information Outlet with 3 x3 sheet Having speed upto 10Gbps. Complete in all respect as desired by the Engineer in charge of work at site.
Supply & erection of 6 Core Optical Fiber Cable Unitube Double Jacket Fiber Optic Cables Steel tape armor and PE jacket provide rodent protection along with improved crush and impact protection, Water blocking tape & Water blocking yarns over FRP, Working Temperature –40°C ~+60°C Speed 10 Gbps, Complete in all respect as desired by the Engineer in charge of work at site.
Supply & erection of Duplex Fiber Patch Cord LC-LC type connector Single Mode-G.657A1, Working Temperature –10°C ~+70°C, MechanicalSpecification3.0mm x 6.2mm / 2.0mm x 4.2mm nominal for Duplex 10GBPS Speed, Insertion Loss-Typical:<0.2dB, Max. 0.3dB(MTRJ: Max. 0.5dB) , Return Loss- PC>_45dB, UPC>_50dB,APC>_60dB (SM Complete in all respect as desired by the Engineer in charge of work at site.
Supply & erection of 12 Ports LIU Features: - • Aluminium base material for light mounting.Slim 1 unit mountingheightFrontmountedcablesaddlesforjumpermanagement.Can manage both splicesand terminations. • Pre assembled shelves in multiple configurations. • Can include adapter panelfor maximum 48 LC, 24 SC, 24 ST or 24 FCterminations.Rubber fiber slotted bracket building,metal surplice self to protect.2 fiber spools built in for 900 um tight buffered fibers peradapter.Snap in locker design, easy tochange adapter panels for variousconnectorpatching. Removable front & rear covers for better access to interior ofLIU.Removal rubber from grommet allows for pre terminated fiber trunk installation, protects cable &minimize dust,build-up.Accessory kit consists of cable ties mounting ear screws & spiralwraptube.Complete in all respect as desired by the Engineer in charge of work at site.
Supply & erection of Fiber Pig tail LC type connector Single Mode-G.652D, Working Temperature –40°C ~+85°C, Mechanical0.9mm 10GBPS Speed, Insertion Loss-Typical:<0.2dB, Max. 0.3dB(MTRJ: Max. 0.5dB) , Return Loss- PC>_45dB, UPC>_50dB,APC>_60dB (SM). Complete in all respect as desired by the Engineer in charge of work at site.
Supply & erection of 15U Wall mount 19’’ Rack with glass door lock & key facility 500mm depth. with CPD, Cable Manager & Fan, Mounting Hardware, screw/ fastener for mounting, 2 No. of keys, removable glass door, inlet for cables, powder coated painted Complete in all respect as desired by the Engineer in charge of work at site.
Supply & Erection of 48 Port 10/100/1000 Mbps layer 2 switching, VLAN support, Spanning Tree Protocol (STP), advanced threat protection, Standard 802.1d Spanning Tree support Fast convergence using 802.1w (Rapid Spanning Tree [RSTP]), enabled by default Multiple Spanning Tree instances using 802.1s (MSTP); 8 instances are supported, Per-VLAN Spanning Tree Plus (PVST+) and Rapid PVST+ (RPVST+); 126 instances are supported IPv6 first-hop security, Support for up to 4,094 VLANs simultaneously Port-based and 802.1Q tag-based VLANs; MAC-based VLAN; protocol-based VLAN; IP subnet-based VLAN, Management VLAN, Wire speed routing of IPv4 packets Up to 990 static routes and up to 128 IP interfaces ,Configuration of Layer 3 interface on physical port, Link Aggregation (LAG), VLAN interface, or loopback interface ,Switch functions as an IPv4 DHCP server serving IP addresses for multiple DHCP pools/scopes, Support for DHCP options ,USB
Type-A slot on the front panel of the switch for easy file and image management, Reset button, UL (UL 62368), CSA (CSA 22.2), CE mark, FCC Part 15 (CFR 47) Class A, Operating temperature 23° to 122°F (-5° to 50°C)quality of service (QoS), dynamic routing Smart Managed Data switch having IEEE 802.3 10BASE-T Ethernet, IEEE 802.3u 100BASE-TX Fast Ethernet, IEEE 802.3ab 1000BASE-T Gigabit Ethernet, IEEE 802.3z Gigabit Ethernet, IEEE 802.3x Flow Control, 802.1p priority, Energy Efficient Ethernet, Switching capacity 176 Gbps, HOL blocking prevention, 802.1p priority based, hardware queues, priority queuing and Weighted Round-Robin (WRR) Jumbo frame. Console port with 4 No. 10/100/1000/10000 Mbps(10G) SFP+ Port. Complete in all respect as desired by the Engineer in charge of work at site.
Supply & erection of 10G SFP+ Module Support upto 10KM compatible with Cisco core switches and Access switches , LC type Connector Metal Casing , Hot-swappable input/output device that plugs into an Ethernet SFP+ port of a Cisco switch (no need to power down if installing or replacing, Wave1310nm, Single Mode Fiber, Transmit and Receive Wavelength (nm) -1260 to 1355 length, Power consumption 1 Watt, Dimensions (H x W x D): 8.5 x 13.4 x 56.5mm. Cisco SFP+ connectors typically weight 75 grams or less, temperature range (COM): 0 to 70°C (32 to 158°F) Complete in all respect as desired by the Engineer in charge of work at site.
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
SBD.pdf
Tender Documents • 15.23 MB
BOQ_318260.xls
BOQ • 1.15 MB
Download all tender documents and submit your bid