CE AF Udhampur Zone
HQ CE AF Udhampur Zone
CA NO CEAFU-01-2023-24 PROVISION OF INFRASTRUCTURE FOR INDUCTION OF MAFI AT AF STN AWANTIPUR
2023_MES_588205_1
CEAFU-01/2023-24
Open Tender
Civil Works
Lump-sum
548 days
Awantipur
As per tender documents and as per policy in vogue
9 documents required · 9 mandatory
₹3,000
GE AF Awantipur
₹7.1 L
Yes
HQ CE AF Udhampur Zone
13 Sept 2023
5 Apr 2023
24 Jul 2023
20 Apr 2023
15 Jul 2023
1 Jul 2023
5 Apr 2023 - 17 Apr 2023
18 Apr 2023
Amount
SCHEDULE `A' PART-I (BUILDING WORK) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Block of Power Sub Station bldg (PS 1) with plant operator room, attached toilet, Store room, single storey, framed structure, galvalume sheet roof including shutter etc with permenant specification complete all as specified and as shown in drawings.
Block of Power Sub Station bldg (PS 2) with plant operator room, attached toilet, Store room, single storey, framed structure, galvalume sheet roof including shutter etc with permenant specification complete all as specified and as shown in drawings.
Block of MES Sub Station bldg, single storey, framed structure, galvalume sheet roof including shutter etc with permenant specification complete all as specified and as shown in drawings.
Block of open shed 10m x 6m near MES sub station Bldg with permenant specification complete all as specified and as shown in drawings
Block of open shed 16m x 14m for sub station Bldg with permenant specification complete all as specified and as shown in drawings
Total amount of Schedule 'A' PART-I (BUILDING WORK)
Total amount of Sch 'A' PART-II (Sec-I) (INTERNAL ELECTRIC SUPPLY WORKS)
SCHEDULE `A' PART-II (Sec-II) (INTERNAL ELECTRIC SUPPLY WORKS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
S&F integral LED aviation light LDR based Photo control for dusk to down operation with light intensity 3200 candeals minimum working temperature wide rande of -30 deg c + 60 degree ccomprising of aluminium housing with polycarbonate enclosure 240 Volt, 50 Hz ,IP 65 provided for Sub Station Bldg complete all as specified
Supply and fixing MCB SP 2 Amps, 10 KA, 240 Volts, 'C' curve complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing MCB SPN 6 to 32 Amps, 10 KA, 240 Volts, C Curve complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing MCB SP 6 to 32 Amps, 10KA, 240 Volts, C Curve complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing distribution board iron clad TPN DB, double door with IP-43 1K-09 protection suitable for MCCB as incommer and MCB as outgoing 415 Volts 3 phase 50 C/s 4 way, complete with appropriate size copper bus bar. complete with one MCCB 4 pole 415 Volts 40 Amps rating with rupturing cap 16 KA of the same make as of distribution board & including cutting chases to wall for fixing DB and making good the disturbed wall surface all as required at site or directed by Engr-in-Charge. (Note: MCB's and MCCB will be measured and paid seperately under relevent items)
Supply and fixing LED light fitting mirror type with high output diffuser 2 feet ,10 watt 220 Volts AC decorative type energy efficient LED integrated batten type luminaires suitable for wall or ceiling mounting with built in LED Chip & integral LED driver 10 watt, Aluminum channel housing & Polycarbonate diffuser, Color temperature 6500 K or as directed, Luminaire efficacy not less than 100 lm/W with all accessories, fixing arrangement internally pre-wired, making all connection using 1.5 Sqmm copper conductor multistranded PVC insulated 3 core flexible cable from ceiling rose to fitting drawn through PVC flexible conduit complete fixed in position & connecting complete all as specified and directed by Engineer–in-charge
S & F LED batten surface / wall mounted with specially designed powder coated aluminium housing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired up to terminal block, power consumption <20W, luminaire lumen >2000 lm, system efficiency of > 120 lumens/W, LED Make : Nichia/ Cree/ Everlite / Eclison/ Osram/ Lumiled, with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class 1, Ingress protection IP 20, colour rendering index CRI>80, temp range 0 to 450C, driver efficiency>85%, power factor > 0.9, THD <20% as per IEC 61000-3-2, colour temp -6500K, surge protection 2.5 KV, 50,000 burning hrs (min) as per L7O criteria, two stages isolated constant current operated driver with range 150-270V AC and safety extra low voltage safe level < 60 V DC as per IEC standard with LM70 & LM 80 certification all as specified and directed.
Supply and fixing LED batten surface / wall mounted with specially designed powder coated aluminium housing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired up to terminal block, power consumption <10W, luminaire lumen >1000 lm, system efficiency of > 120 lumens/W, with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class 1, Ingress protection IP 20, colour rendering index CRI>80, temp range 0 to 450C, driver efficiency>85%, power factor > 0.9, THD <20% as per IEC 61000-3-2, colour temp -6500K, surge protection 2.5 KV, 50,000 burning hrs (min) as per L7O criteria, two stages isolated constant current operated driver with range 150-270V AC and safety extra low voltage safe level < 60 V DC as per IEC standard with LM79 & LM 80 certification making all connection using 1.0 sqmm copper conductor multistarnd PVC insulated 3 core flexible cable from ceiling rose to fitting drawn through PVC flexible conduit complete all as specified and directed by Engineer–in-Charge.
Supply and fixing 2ft x 2ft recess mounted full panel LED luminaire with white powder coated housing acting as heat sink and frame in CRCA sheet, high efficiency LED grade diffuser , in built electronic driver duly wired up to terminal block, power consumption< 36W, luminaire lumen > 3500lm and system efficiency >120lm/W, CRI>80, LED Make:- Nichia/ Cree/ Everlite / Eclison/ Osram/ Lumiled with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class 1, colour temp -5700K, Ingress protection IP 20, , driver efficiency >85%, 50,000 burning hours (min) as per L70 criteria, ambient temp 0 to 500C, power factor >0.95, THD < 10% , surge protection in CM -3 KV, two stages isolated constant current operated driver with range 150-270V AC and safety extra low voltage safe level <60V DC as per IEC standard, with LM79 & LM80 certification complete all as specified and directed by Engineer–in-Charge.
Supply and fixing street light IP-66 LED light fitting of capacity 35 Watts, 240 Volts single phase 50 Hz consisting of aluminium pressure die cast housing with high purity PC fresnel diffuser with glass silicon gaskets complete assembly with LED and accessories toughened prewired upto terminal block confirming to IS 10322 part 5/sec1: 1967 with inbuilt integrated electronic LED driver voltage surge protection not less than 3 KV, 2/3 stage isolated driver, the LED lumen output colour temperature consistency compliant to LM 6600K standard system lumens of LED luminaire high lumen output minimum 130 lm/Watts complete with 4.00 Sq.mm multi stranded aluminium conductor PVC insulated twin core weather proof cable from fitting to junction box and fixing to pole with and including bracket made out of 40 mm GI Pipe not less than 1.2 meter long bend to shape and to fixed with the pole in any position with fixed iron clamps of size 50 X 6 mm complete all as specified and directed. Note :- Cost of GI pipe bracket, clamps, nuts & bolts etc is deemed to be included in quoted rate.
S & F LED flood light with aluminium pressure die cast housing , high purity PC Fresnel diffuser with thermal management in multiple optics and equipped with IP-66 protection with impact and corrison resistant, power consumption < 70W & luminaire lumen > 7000 lm and system efficiency > 100 lm/W, in built electronic driver prewired upto terminal block with driver efficiency > 85% power factor > 0.95, ambient temperature range 0-450C, THD<10%, colour temperature 5700K, surge protection in CM-3.5KV, 50000 burning hours as per L70 criteria, multistage constant current-constant voltage operated driver with range 150-270V AC and safety extra low voltage safe level < 60V DC as per IEC Standard complete all as specified and directed
Supply and fixing LED Bulk Head type with high output, 10 watt, 220 Volts AC, Color temperature 6500K or as directed, luminous flux of light 1000 lumens (lm) with all accessories, IP 65 protection dust and water resistant, surge protection up to 2.5kV, PC opal high efficiency diffuser ,LM 80 tested made die cast aluminum housing with complete assembly, suitable for surface/wall mounted with driver holder including connecting up using 1.5 Sqmm copper conductor multistranded PVC insulated with three core flexible copper conductor cable of suitable size complete all as specified and directed by Engineer-in-Charge.
Total amount of Sch 'A' PART-II (Section-II) (INTERNAL ELECTRIC SUPPLY WORK)
Total amount of Sch 'A' PART-III (Section-I) (INTERNAL WATER SUPPLY WORK)
SCHEDULE `A' PART-III (SEC-II) (INTERNAL WATER SUPPLY WORK) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
S&F C P health Faucets with flexible tube 15mm dia for EWC including all connection complete and all as specified by Engineer-in-Charge.
Total amount of Sch 'A' PART-IV (PLUMBING WORK)
Total amount of Sch 'A' PART-V (RCC PLINTH FOR INSTALLATION OF LIGHTS WORK)
Total amount of Sch 'A' PART-VI (SEC-I) (LIGHTNING PROTECTION WORK)
Total amount of Sch 'A' PART-VII (ROAD/PATH/CULVERT WORK)
Total amount of Sch 'A' PART-VIII (SEC-I) (SEWAGE DISPOSAL WORK)
Sch 'A' PART-VIII (SEC-II) (SEWAGE DISPOSAL WORK) Note: This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Supply and fixing of LLDPE tank for 10 users including vent shaft and other necessary fixing arrangment including necessory excavation, earth work and other civil works ar per manufacturer's recommendation complete all as specified and as directed Make- Sintex, Code No. PWTS-AM-300-01 or equal approved Make of Comfert polymers or Polycon
Soakage wells of size 2.40m dia x 4.50m effective depth including excavation in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M30 (Design mix) concrete including intercepting chamber and screen chamber made of Brick masonary in CM 1:4, RCC cover slab in M30 (Design Mix)/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats with over flow fillter complete all as shown on drawing No CE/AF/STD-15/2000 Sh 1/2 and 2/2 and as specified.
Total amount of Sch 'A' PART-VIII (SEC-II) (SEWAGE DISPOSAL WORK)
Total amount of Sch 'A' Part-IX (AREA DRAINAGE WORK)
Total amount of Sch 'A' PART-X (FENCING AND GATE WORK)
Total amount of Sch 'A' PART-XI (Section-I) (EXTERNAL WATER SUPPLY WORK)
Sch 'A' Part-XI (Section-II) (EXTERNAL WATER SUPPLY WORK) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Construction of valve chamber of size 900 x 900 x 900mm internal size suitable for valves with PCC 1:4:8 type D2 for foundation and brick wall in cement mortar 1:4 PCC 1:2:4 type B1 for coping rendering in CM (1:4) 15mm thick including provn of mild steel sheet cover 6mm thick on 50 x 50 x 6mm angle iron frame work with two coats of synthetic enamel black paint over a coat of red oxide primer and locking arrangement including necessary excavation earth work all as specified and as directed by Engineer-in-Charge.
Cutting the existing GI steel tubing of size 80 mm dia for addition/ alteration, screwed/ making threads in position including insertion of new Tee for making branch connection of 40 mm dia including supply and fixing of new GI Tee of appropriate size complete all as specified and as directed.
Total amount of Sch 'A' PART-XI (Section-II) (EXTERNAL WATER SUPPLY WORK)
Total amount of Sch 'A' -XII (Section-I) (EXTERNAL ELECTRIFICATION WORK)
Sch 'A' Part-XII (Section-II) (EXTERNAL ELECTRIFICATION WORK) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Supply, install, test & commissioning of HT 11 KV, 630A, VCB panels ICOG comprising of 01 incomer & 2 Nos outgoing, indoor type, totally enclosed, free standing floor mounting type, compartment based with truck mounted vacuum circuit breaker spring operated electrically and manually charged operating mechanism suitable for horizontal isolation, horizontal draw out type VCBs with copper bus bars, Self supported Insulated Bus bar with full voltage rated should be used.back entry type complete VCB panel confirming to IEC 62271-200 standards and IP 4X class of protection comprising necessary bus-bars extension and connections and following protective and control devices as specified below. The switchgear and control gear panels shall be of the fully arc proof LSC 2B, PM, IAC AFLR for 26.3 kA for 3 Sec complete all as specified and as directed. The VCB and VCB Panel should be similar make only
INCOMER VCB: - 01 No. Supply of HT 11KV, 3Phase 50Hz, totally metal clad withdraw able type Vacuum Circuit Breaker panel with copper bus bar of suitable rating, horizontal isolation type VCB of capacity minimum 630 Amps rated current as per IEC 62271-100-200. The switchgear & control gear panels shall be of the fully arc proof LSC 2B, PM, IAC AFLR for 26.3 kA for 3 Sec complete all as specified & as directed & to ensure the following. (i) Mechanical life -30,000 Hrs (ii) No of trippings on overload-10,000 Nos (iii) No of Rated Short Circuit Operations-100.
VCB parameters are as below : (i) Rated Voltage level/ PF withstand voltage/ Impulse level:12KV/ 38 kV/ 95 kVp for the altitude of upto 2000 mtr (ii) Continuous current rating: minimum 630A (iii) Short circuit withstand current: minimum 26.3KA for 3sec. (iv) One no. minimum 630 Amps horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following:- (a) Manually & Motor operated (230V, AC, 50Hz) spring charged type, manually and electrically open (electrical – 24 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 12NO+12NC breaker auxiliary contacts in service position.
(b) Epoxy cast wound current transformer (CT), 12KV of ratio 200-100 /1+1A, 5P10/0.5, 15 VA burden with metering and protection core including necessary control wiring – set of three for each VCB. (c) Potential transformer with three nos. 1 phase, 3 limbs connected in star, dual class, 11 KV/V3/110V/V3,Cl. 0.5, 50 VA with draw able type with automatic safety shutters 100VA burden with primary & secondary fuses. (Conforming related IS specifications). (A) Protection arrangements for the breaker shall comprise of the following: i) SCADA Compatible Feeder Protection Relay confirming to IEC- 61850-7-4: 2010 ,50/51(3-phase over current), 50/51N (Earth over current), 67P (3-phase directional over current), 67N (Earth Fault Directional over current), 37 (3-phase uner current), 46 (Negative phase sequence over current), 27 (Under voltage),59 (Over voltage), 32P (directional power protection (under active / over active / reactive power), 81 U/O (under / over frequency), (Auto Reclose), 50 BF (Circuit
Breaker Failure Detection), cold pickup, with IEC 103 protocol for communication & drawout type having 8 DI and 8 DO - Numerical Type Siemens A1(7SJ62)/ ABB (REF615)/ Schneider (P3U20) (ii )Master Trip (86)/ Anti pumping relay as per IS 3230: 1992 (iii) Trip Circuit Supervision Relay (95) as per IS: 3231:2010
OUTGOING VCB – 02 Nos Supply of HT 11KV, 3Phase 50Hz, totally metal clad withdraw able type Vacuum Circuit Breaker panel with copper bus bar of suitable rating, horizontal isolation type VCB of capacity minimum 630 Amps rated current, as per IEC 62271-100-200.The offered panels shall be tested for IAC level of 26.3 kA / 3 Sec, for better performance and to ensure the following : (i) Mechanical life - 30,000 Nos. (ii) No of trippings on overload – 10,000 Nos (iii) Number of Rated Short Circuit operations – 100 Nos -
VCB parameters are as below: (i) Rated Voltage level/ PF withstand voltage/ Impulse level:12KV/ 38 kV/ 95 kVp for the altitude of upto 2000 mtr (ii) Continuous current rating: minimum 630A (iii) Short circuit withstand current: minimum 26.3KA for 3sec. (iv) One no. minimum 630 Amps horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following :-
(a) Manually & Motor operated (230V, AC, 50Hz) spring charged type, manually and electrically open (electrical – 24 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 12NO+12NC breaker auxiliary contacts in service position. (b) Epoxy cast wound current transformer (CT),12KV of ratio 100-50/1+1A, 5P10/0.5, 15 VA burden with metering and protection core including necessary control wiring – set of Three for each VCB
A) Protection arrangements for the breaker shall comprise of the following: (i) SCADA Compatible Feeder Protection Relay 50/51(3-phase over current), 50/51N (Earth over current), 67P (3-phase directional over current), 67N (Earth Fault Directional over current), 37 (3-phase uner current), 46 (Negative phase sequence over current), 32P (directional power protection (under active / over active / reactive power), 81 U/O (under / over frequency), (Auto Reclose), 50 BF (Circuit Breaker Failure Detection), cold pickup, with IEC 103 protocol for communication & drawout type having 8 DI and 8 DO - Numerical Type Siemens A1(7SJ62)/ ABB (REF615)/ Schneider (P3U20) (ii) Mater Trip Relay (iii) Aux . Transformer protection relay All the Relays shall belong to a common platform and shall be of single make with Electromechanical Relays in Draw-out casing
(ii) The interlocking among the different VCBs Panels shall be done electronically as well as mechinaclly as per the approved scheme to avoid any unintentional/inadvertent switching ON/OFF of any breaker. (iii) Tools & plants, safety devices like helmet, belt, HT/LT insulation gloves, discharge rod, Meggar etc shall be provided by the contractor. (vi) After taking shutdown contractor should complete the commisioning of the Job within 24 hrs. (v) Testing, calibration of relays/primary/secondary injection, testing the relays/submission of test report and control wiring/power wiring complete. (vi) Drawing for panels shall be got approved from GE before placement of order by contractor. (vii) Pre-commissioning test of panels shall be carried by SEI /EI deputed by the Accepting officer. (viii) Rep of Accepting officer will carry out factory inspection of HT VCB before dispatch.
Supply, install, test & commissioning of HT 11 KV, 630A, VCB panels ICOG comprising of 2 Nos incomer VCBs, 2 Nos bus couplers & 4 Nos outgoing VCBs, indoor type’ totally enclosed, free standing floor mounting type, compartment based with truck mounted vacuum circuit breaker spring operated electrically and manually charged operating mechanism suitable for horizontal isolation, horizontal draw out type VCBs with copper bus bars, Self supported Insulated Bus bar with full voltage rated should be used.back entry type complete VCB panel confirming to IEC 62271-200 standards and IP 4X class of protection comprising necessary bus-bars extension and connections and following protective and control devices as specified below. The switchgear and control gear panels shall be of the fully arc proof LSC 2B, PM, IAC AFLR for 26.3 kA for 3 Sec complete all as specified and as directed. The VCB and VCB Panel should be similar make only INCOMER VCB. : 02 Nos Supply of HT 11 KV, 3Phase 50Hz, totally metal clad withdraw able type Vacuum Circuit Breaker panel with copper bus bar of suitable rating, horizontal isolation type VCB of capacity minimum 630 Amps rated current as per IEC 62271-100-200. The switchgear and control gear panels shall be of the fully arc proof LSC 2B, PM, IAC AFLR for 26.3 kA for 3 Sec complete all as specified and as directed and to ensure the following: - (i) Mechanical life - 30,000 Nos. (ii) No of trippings on overload – 10,000 Nos (iii) Number of Rated Short Circuit operations – 100 Nos -
VCB parameters are as below : (i) Rated Voltage level/ PF withstand voltage/ Impulse level:12KV/ 38 kV/ 95 kVp for the altitude of upto 2000 mtr (ii) Continuous current rating: minimum 630A (iii) Short circuit withstand current: minimum 26.3KA for 3sec. (iv) One no. minimum 630 Amps horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following:-
(a) Manually & Motor operated (230V, AC, 50Hz) spring charged type, manually and electrically open (electrical – 24 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 12NO+12NC breaker auxiliary contacts in service position. (b) Epoxy cast wound current transformer (CT),12KV of ratio 200-100 /1+1A, 5P10/0.5, 15 VA burden with metering and protection core including necessary control wiring- set of Three for each VCB (c) Potential transformer with three nos. 1 phase, 3 limbs connected in star, dual class, 11 KV/V3/110V/V3,Cl. 0.5, 50 VA with draw able type with automatic safety shutters 100VA burden with primary & secondary fuses.(Conforming related IS specifications).
A) Protection arrangements for the breaker shall comprise of the following: i) SCADA Compatible Feeder Protection Relay conforming to IEC 61850-7-4 : 2010 , 50/51 (3-phase over current), 50/51N (Earth over current), 67P (3-phase directional over current), 67N (Earth Fault Directional over current), 37 (3-phase uner current), 46 (Negative phase sequence over current), 27 (Under voltage),59 (Over voltage), 32P (directional power protection (under active / over active / reactive power), 81 U/O (under / over frequency), (Auto Reclose), 50 BF (Circuit Breaker Failure Detection), cold pickup, with IEC 103 protocol for communication & drawout type having 8 DI and 8 DO - Numerical Type Siemens A1(7SJ62)/ ABB (REF615) / Schneider (P3U20) (ii) Master Trip (86)/ Anti pumping relay as per IS 3230:1992. (iii) Trip Circuit Supervision Relay (95) as per IS 3231: 2010
Bus Coupler – 02 Nos Supply of HT 12KV, 3Phase 50Hz, totally metal clad Indoor type withdraw able type Vacuum Circuit Breaker panel with copper bus bar of suitable rating, horizontal isolation type VCB of capacity minimum 630 Amps rated current, as per IEC 62271-100-200.The offered panels shall be tested for IAC level of 26.3 kA / 3 Sec, complete all as specified and as directed and to ensure the following: - (i) Mechanical life - 30,000 Nos. (ii) No of trippings on overload – 10,000 Nos (iii) Number of Rated Short Circuit operations – 100 Nos
OUTGOING – 04 Nos Supply of HT 11KV, 3Phase 50Hz, totally metal clad Indoor type withdraw able type Vacuum Circuit Breaker panel with copper bus bar of suitable rating, horizontal isolation type VCB of capacity minimum 630 Amps rated current, as per IEC 62271-100-200.The offered panels shall be tested for IAC level of 26.3 kA / 3 Sec, complete all as specified and as directed and to ensure the following. (i) Mechanical life - 30,000 Nos. (ii) No of trippings on overload – 10,000 Nos (iii) Number of Rated Short Circuit operations – 100 Nos .
VCB parameters are as below: (i) Rated Voltage level/ PF withstand voltage/ Impulse level:12KV/ 38 kV/ 95 kVp for the altitude of upto 2000 mtr (ii) Continuous current rating: minimum 630A (iii) Short circuit withstand current: minimum 26.3KA for 3sec. (iv) One no. minimum 630 Amps horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following :- (a) Manually & Motor operated(230V,AC,50Hz) spring charged type, manually and electrically open (electrical – 24 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 12NO+12NC breaker auxiliary contacts in service position.
(b) Epoxy cast wound current transformer (CT),12KV of ratio 100-50/1+1A, 5P10/0.5, 15 VA burden with metering and protection core including necessary control wiring – set of three. A) Protection arrangements for the breaker shall comprise of the following: i) SCADA Compatible Feeder Protection Relay conforming to IEC 61850-7-4:2010, 50/51 (3-phase over current), 50/51N (Earth over current), 67P (3-phase directional over current), 67N (Earth Fault Directional over current), 37 (3-phase uner current), 46 (Negative phase sequence over current), 32P (directional power protection (under active / over active / reactive power), 81 U/O (under / over frequency), (Auto Reclose), 50 BF (Circuit Breaker Failure Detection), cold pickup, with IEC 103 protocol for communication & drawout type having 8 DI and 8 DO - Numerical Type Siemens A1(7SJ62)/ ABB (REF615)/ Schneider (P3U20)(ii) Mater Trip Relay (iii) Aux . Transformer protection relay All the Relays shall belong to a common platform and shall be of single make with Electromechanical Relays in Draw-out casing.
Note : - The following works before Commissioning of New VCB deemed to be included in the quoted rates:- (i) The complete VCB panel has to be sourced from from OEM only and no channel partner fabrication is permissible. (ii) The interlocking among the different VCBs Panels including Bus Couplers shall be done electronically as well as mechinaclly as per the approved scheme to avoid any unintentional /inadvertent switching ON/OFF of any breaker. (iii) Tools & plants, safety devices like helmet, belt, HT/LT insulation gloves, discharge rod Meggar etc shall be provided by the contractor. (vi) After taking shutdown contractor should complete the commisioning of the Job within 24 hrs. (v) Testing, calibration of relays/primary/secondary injection, testing the relays/submission of test report and control wiring/power wiring complete. (vi) Drawing for panels shall be got approved from GE before placement of order by contractor. (vii) Pre-commissioning test of panels shall be carried by SEI /EI deputed by the Accepting officer. (viii) Rep of Accepting officer will carry out factory inspection of HT VCB before dispatch.
Supply, install, test & commissioning of HT 11 KV, 630A, VCB panels ICOG comprising of 2 Nos incoming VCBs, 2 Nos bus coupler and 2 Nos outgoing VCBs, indoor type, totally enclosed, free standing floor mounting type, compartment based with truck mounted vacuum circuit breaker spring operated electrically and manually charged operating mechanism suitable for horizontal isolation, horizontal draw out type VCBs with copper bus bars, Self supported Insulated Bus bar with full voltage rated should be used.back entry type complete VCB panel conforming to IEC 62271-200 standards and IP 4X class of protection comprising necessary bus-bars extension and connections and following protective and control devices as specified below. The switchgear and control gear panels shall be of the fully arc proof LSC 2B, PM, IAC AFLR for 26.3 kA for 3 Sec complete all as specified and as directed. The VCB and VCB Panel should be similar make only
INCOMER VCB: 02 Nos. Supply of HT 11 KV, 3Phase 50Hz, totally metal clad withdraw able type Vacuum Circuit Breaker panel with copper bus bar of suitable rating, horizontal isolation type VCB of capacity minimum 630 Amps rated current as per IEC 62271-100-200. The switchgear and control gear panels shall be of the fully arc proof LSC 2B, PM, IAC AFLR for 26.3 kA for 3Sec complete all as specified and as directed and to ensure the following. (i) Mechanical life - 30,000 Nos. (ii) No of trippings on overload – 10,000 Nos (iii) Number of Rated Short Circuit operations – 100 Nos VCB parameters are as below : (i) Rated Voltage level/ PF withstand voltage/ Impulse level:12KV/ 38 kV/ 95 kVp for the altitude of upto 2000 mtr (ii) Continuous current rating: minimum 630A (iii) Short circuit withstand current: minimum 26.3KA for 3sec.
(iv) One no. minimum 630 Amps horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following:- (a) Manually & Motor operated(230V,AC,50Hz) spring charged type, manually and electrically open (electrical – 24 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 12NO+12NC breaker auxiliary contacts in service position. (b) Epoxy cast wound current transformer (CT), 12KV of ratio 200-100 /1+1A, 5P10/0.5, 15 VA burden with metering and protection core including necessary control wiring-set of three for each VCB (c) Potential transformer with three nos. 1 phase, 3 limbs connected in star, dual class, 11 KV/V3/110V/V3,Cl. 0.5, 50 VA with draw able type with automatic safety shutters 100VA burden with primary & secondary fuses.(Confirming related IS specifications).
A) Protection arrangements for the breaker shall comprise of the following: i) SCADA Compatible Feeder Protection Relay conforming to IEC 61850-7-4: 2010 ,50/51(3-phase over current), 50/51N (Earth over current), 67P (3-phase directional over current), 67N (Earth Fault Directional over current), 37 (3-phase uner current), 46 (Negative phase sequence over current), 27 (Under voltage),59 (Over voltage), 32P (directional power protection (under active / over active / reactive power), 81 U/O (under / over frequency), (Auto Reclose), 50 BF (Circuit Breaker Failure Detection), cold pickup, with IEC 103 protocol for communication & drawout type having 8 DI and 8 DO - Numerical Type Siemens A1(7SJ62)/ ABB (REF615)/ Schneider (P3U20) (ii) Master Trip (86)/ Anti pumping relay as per IS 3230:1992. (iii) Trip Circuit Supervision Relay (95) as per IS 3231:2010.
Bus Coupler VCB-02 Nos Supply of HT 11KV, 3Phase 50Hz, totally metal clad Indoor type withdraw able type Vacuum Circuit Breaker panel with copper bus bar of suitable rating, horizontal isolation type VCB of capacity minimum 630 Amps rated current, as per IEC 62271-100-200.The offered panels shall be tested for IAC level of 26.3kA / 3 Sec, complete all as specified and as directed and to ensure the following. (i) Mechanical life - 30,000 Nos. (ii) No of trippings on overload – 10,000 Nos (iii) Number of Rated Short Circuit operations – 100 Nos
OUTGOING VCB – 02 Nos Supply of HT 11 KV, 3 Phase 50Hz, totally metal clad Indoor type withdraw able type Vacuum Circuit Breaker panel with copper bus bar of suitable rating, horizontal isolation type VCB of capacity min 630 Amps rated current, as per IEC 62271-100-200. The offered panels shall be tested for IAC level of 26.3kA/3 Sec, complete all as specified & as directed & to ensure the following. (i) Mechanical life-30,000 Nos (ii) No of trippings on overload-10,000 Nos (iii) Number of Rated Short Circuit operations – 100 Nos VCB parameters are as below: (i) Rated Voltage level/ PF withstand voltage/ Impulse level:12KV/ 38 kV/ 95 kVp for the altitude of upto 2000 mtr (ii) Continuous current rating: minimum 630A (iii) Short circuit withstand current: minimum 26.3KA for 3sec. (iv) One no. minimum 630 Amps horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following :-
(a) Manually & Motor operated(230V, AC, 50Hz) spring charged type, manually and electrically open (electrical – 24 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 12NO+12NC breaker auxiliary contacts in service position. (b) Epoxy cast wound current transformer (CT),12KV of ratio 100-50/1+1A, 5P10/0.5, 15 VA burden with metering and protection core including necessary control wiring- set of three for each VCB.
A) Protection arrangements for the breaker shall comprise of the following: i) SCADA Compatible Feeder Protection Relay confirming to IEC 61850-7-4: 2010 ,50/51(3-phase over current), 50/51N (Earth over current), 67P (3-phase directional over current), 67N (Earth Fault Directional over current), 37 (3-phase uner current), 46 (Negative phase sequence over current), 32P (directional power protection (under active / over active / reactive power), 81 U/O (under / over frequency), (Auto Reclose), 50 BF (Circuit Breaker Failure Detection), cold pickup, with IEC 103 protocol for communication & drawout type having 8 DI and 8 DO - Numerical Type Siemens A1(7SJ62)/ ABB (REF615)/ Schneider (P3U20)(ii) Mater Trip Relay (iii) Aux . Transformer protection relay All the Relays shall belong to a common platform and shall be of single make with Electromechanical Relays in Draw-out casing
Note : The following works before Commissioning of New VCB deemed to be included in the quoted rates:- (i) The complete VCB panel has to be sourced from from OEM only and no channel partner fabrication is permissible. (ii) The interlocking among the different VCBs Panels including Bus Couplers shall be done electronically as well as mechinaclly as per the approved scheme to avoid any unintentional/inadvertent switching ON/OFF of any breaker. (iii) Tools & plants, safety devices like helmet, belt, HT/LT insulation gloves, discharge rod, Meggar etc shall be provided by the contractor. (iv) After taking shutdown contractor should complete the commisioning of the Job within 24 hrs. (v) Testing, calibration of relays/primary/secondary injection, testing the relays/submission of test report and control wiring/power wiring complete. (vii) Pre-commissioning test of panels shall be carried by SEI /EI deputed by the Accepting officer. (viii) Rep of Accepting officer will carry out factory inspection of HT VCB before dispatch.
Supply, installing, testing and commissioning of indoor type distribution transformer AC, 3 Phase, 50 HZ, 630 KVA rating, ONAN type copper wound step-down 11000/433 volts (at no load) double wound oil immersed with Easter Oil naturally cooled with external cooling tubes, core type delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector symbol DyN-11 (Vector Group) with neutral brought on secondary side (LV Side) and having 6 tapping changer at +/- 2.5%, +/- 5.0% and +/-7.5% to be changed by means of hand operated off load tap changing gear. The transformer shall be confirming to IS-1180 2014 as per latest ammendments EEL- III standards of BEE and comprising with the following standard fittings/accessories: - with the provision of extendable copper busbar to terminate multiple run of Cable. Transformer must be designed and tested to the standards of IS: 1180 (2014) EEL- III, standards of BEE and equipped with and including following items:-
(i) No load voltage ratio: 11/0.433 KV, (ii) No. of Phases / Freq.: 3 Phase/50 Hz, (iii) Type: Core type, double copper wound (iv) Cooling: ONAN type, (v) Vector group: DyN 11, (vi) Permissible Temperature rise (oil winding): 45 Deg centigrade. (vii) Taps on HV for HV variation: -7.5% to + 7.5% in steps of 2.5% each (on circuit type). (viii) Termination (HV): cable end box suitable for termination of 11.00 KV XLPE insulated 3 core cable. (ix) Termination (LV): cable end box suitable for 1.1 KV, XLPE insulated 3.5 core cable, (x) Conservator with drain valve and level gauge, (xi) Oil level indicator, (xii) Silica gel breather with oil seal. (xiii) First filling of transformer oil having suitable dilectric strength as per IS –335 including makeup fill during installation of transformer plus 10% extra oil.
(xiv) ON circuit switch. Lifting lugs. (xv) Earthing terminals - 2 Nos, (xvi) Thermometer pocket including suitable thermometer of digital type, (xvii) Air release plug, (xviii) Inspection cover. (xix) Top filter valve – 1 No. (xx) Drain valve. (xxi) Oil temperature and winding temperature gauge with max pointer. (xxii) Rating and diagram plate. (xxiii) Bi-directional plain/flanged rollers. (xxiv) Disconnecting facility for HV cable box. (xxv) Bucholz relay with WTI and OTI alarm with necessary with copper conductor Control cable, copper armoured from transformer to VCB for bucholz alarm & trip (xxvi) Marshalling Box and HV fuse unit to be provided by OEM to protect primary windings (xxvii) Temperature range of -15 deg C to 50 deg C (xxviii) Altitude of 1600 Meter above msl without derating the specified KVA rating of the transformer.
Note:- Following points are to be considered by the OEM while manufacturing the transformer: - (i) Oil-Ester Oil: NABL accrediated lab type test for quality, CPRI/ERDA sample oil test certificate for K class in Oil ( IEC 62770:2013/ IS 16659:2017 with latest amendment), (ii) Core: Transformer shall be double wound core type with low loss, non-ageing, high permeability PRIME GRADE, CRGO with M4 Grade or Better, with boltless design, perfectly insulated and clamped to minimize noise and vibrations. (iii) MILL certification to verify core material used are of prime grade and their sourcing documents,
(iv) Inhouse core cutting (NABL Accredited) – Supplier/manufacturer must have Numerically controlled automatic core cutting plant and shall ensure the following:- (a) Dimensional accuracy with respect to Cross sectional area of Built core, (b) Proper monitoring & control on quality, (c) Avoid any possibility of mixing of primary material with defective/ second grade material, which would ultimately affect the quality and life of transformer (v) No other method other than Vapour Phase Drying (VPD) is allowed for the offered transformers ( or ) Winding shall be individually vacuum dried in hermetically sealed drying ovens and pre-shrunk fully under hot conditions. After assembly of windings on core the complete assembly shall again be vacuum dried until desired insulation resistance of each winding is obtained. (vi) Dust free core & coil assembly area. (vii) Provision of DGA to monitor any gas release/traces in transformer main tank (Ester oil)
(viii) Digital Logbook: The supplier shall submit electronic copy of drawings, calculations, technical information, data sheets etc. for purchaser’s review, approval and allowing to proceed with manufacturing. Final set of drawings (as-built), factory acceptance test reports, bought-it major item test reports, operation cum maintenance manuals, technical documents, setting files etc. shall be shared with purchaser in 3 printed copies and 1 digital copy which shall be online and can be accessed with secure user credentials anytime through a bar-code or QR code available upon transformer (inside marshalling box and/or RTCC panel). OEM recommended scheduled maintenance alert shall be provided in the form of digital push notification at the recommended intervals to purchaser operation/maintenance team so that any critical maintenance is not missed, (ix) Manufacturer shall test transformer from NABL accredited lab to ascertain the authenticity of test results and Purchaser may test the transformer from CPRI/ERDA officials with their testing equipments
Supply, installing, testing and commissioning of indoor type distribution transformer AC, 3 Phase, 50 HZ, 200 KVA rating, ONAN type copper wound step-down 11000/433 volts (at no load) double wound oil immersed with Easter Oil naturally cooled with external cooling tubes, core type delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector symbol DyN-11 (Vector Group) with neutral brought on secondary side (LV Side) and having 6 tapping changer at +/- 2.5%, +/- 5.0% and +/-7.5% to be changed by means of hand operated off load tap changing gear. The transformer shall be conforming to IS-1180 2014 as per latest ammendments EEL- III standards of BEE and comprising with the following standard fittings/accessories:- with the provision of extendable copper busbar to terminate multiple run of Cable.
Transformer must be designed and tested to the standards of IS: 1180 (2014) EEL III, standards of BEE and equipped with and including following items:- (i) No load voltage ratio: 11/0.433 KV, (ii) No. of Phases / Freq.: 3 Phase/50 Hz. (iii) Type: Core type, double copper wound, (iv) Cooling: ONAN type (v) Vector group: DyN 11 (v) Permissible Temperature rise (oil winding): 45 Deg centigrade. (vi) Taps on HV for HV variation: -7.5% to + 7.5% in steps of 2.5% each (on circuit type). (vii) Termination (HV): cable end box suitable for termination of 11.00 KV XLPE insulated 3 core cable, (viii) Termination (LV): cable end box suitable for 1.1 KV, XLPE insulated 3.5 core cable (ix) Conservator with drain valve and level gauge, (x) Oil level indicator, (xi) Silica gel breather with oil seal, (xii) First filling of transformer oil of suitable dilectric strength as per IS –335 including makeup fill during installation of transformer plus 10% extra oil, (xiii) ON circuit switch, (xiv) Lifting lugs, (xv) Earthing terminals - 2 Nos, (xvi) Thermometer pocket including suitable thermometer of digital type, (xvii) Air release plug, (xviii) Inspection cover
(xix) Top filter valve – 1 No, (xx) Drain valve, (xxi) Oil temperature and winding temperature gauge with max pointer, (xxii) Rating and diagram plate, (xxiii) Bi-directional plain/flanged rollers, (xxiv) Disconnecting facility for HV cable box, (xxv) WTI and OTI alarm with necessary with copper conductor Control cable, copper armoured from transformer to VCB for bucholz alarm & trip, (xxvi) Marshalling Box and HV fuse unit to be provided by OEM to protect primary windings, (xxvii) Temperature range of -15 deg C to 50 deg C (xxviii) Altitude of 1600 Meter above msl without derating the specified KVA rating of the transformer. Note: - Following points are to be considered by the OEM while manufacturing the transformer
(i) Oil – Ester Oil: NABL accrediated lab type test for quality, CPRI/ERDA sample oil test certificate for K class in Oil (IEC 62770: 2013/ IS 16659: 2017 with latest amendment) (ii) Core: Transformer shall be double wound core type with low loss, non-ageing, high permeability PRIME GRADE, CRGO with M4 Grade or Better, with boltless design, perfectly insulated and clamped to minimize noise and vibrations. (iii). MILL certification to verify core material used are of prime grade and their sourcing documents (iv) Inhouse core cutting (NABL Accredited) – Supplier/manufacturer must have Numerically controlled automatic core cutting plant and shall ensure the following:- (a) Dimensional accuracy with respect to Cross sectional area of Built core, (b) Proper monitoring & control on quality, (c) Avoid any possibility of mixing of primary material with defective/ second grade material, which would ultimately affect the quality and life of transformer (v) No other method other than Vapour Phase Drying (VPD) is allowed for the offered transformers ( or ) Winding shall be individually vacuum dried in hermetically sealed drying ovens and pre-shrunk fully under hot conditions. After assembly of windings on core the complete assembly shall again be vacuum dried until desired insulation resistance of each winding is obtained
(vi) Dust free core & coil assembly area (vii) Provision of DGA to monitor any gas release/traces in transformer main tank (Ester oil), (viii) Digital Logbook: The supplier shall submit electronic copy of drawings, calculations, technical information, data sheets etc. for purchaser’s review, approval and allowing to proceed with manufacturing. Final set of drawings (as-built), factory acceptance test reports, bought-it major item test reports, operation cum maintenance manuals, technical documents, setting files etc. shall be shared with purchaser in 3 printed copies and 1 digital copy which shall be online and can be accessed with secure user credentials anytime through a bar-code or QR code available upon transformer (inside marshalling box and/or RTCC panel). OEM recommended scheduled maintenance alert shall be provided in the form of digital push notification at the recommended intervals to purchaser operation/maintenance team so that any critical maintenance is not missed, (ix) Manufacturer shall test transformer from NABL accredited lab to ascertain the authenticity of test results and Purchaser may test the transformer from CPRI/ERDA officials with their testing equipments
Supply, installation, testing and commissioning of indoor type oil cooled isolation transformer630 KVA, step-III IS 1180, three phase, metalic body, suitable for unbalanced type load, copper wound, withstandard fittings and accessories, as per IS suitable for input voltage of 415 volt +/- 5% output voltage 415 volt+/- 5%, IP-42 ,vector group Dyn-11, of frequency 50Hz and with following description including first fill of transformer oil of IS 335 ISI marked: -(a) Method of cooling - Oil cooled, (b) Ratio - 1:1, (c) Insulation class -Class -E, (d) Winding Temperature - Less than 55* C, (e) Full load lossess- Less than 5%, (f) No load lossess - Less than 0.5%, (g) Mounting - On wheel detachable type, (h) Potential difference between Earth to Neutral voltage – Less than 01 volt.
Supply, installation, testing and commissioning of indoor type oil cooled isolation transformer 200 KVA,step-III ,IS 1180, three phase, metalic body, suitable for unbalanced type load, copper wound ,with standard fittings and accessories as per IS, suitable for input voltage of 415 volt +/- 5% output voltage 415 volt+/- 5%, IP-42 , vector group Dyn-11, of frequency 50Hz and with following description including first fill of transformer oil of oil IS 335 ISI marked:- (a) Method of cooling - Oil cooled, (b) Ratio - 1:1, (c) Insulation class -Class -E, (d) Winding Temperature - Less than 55* C, (e) Full load lossess- Less than 5%, (f) No load lossess - Less than 0.5%, (g) Mounting - On wheel detachable type
Supply, installation, testing and commissioning of indoor automatic/servo voltage stablizer three phase, 50Hz (confirming to IS 9815 : Part 1: 1994 reaffirmed 2009) Naturally oil cooled of 200 KVA, suitable for unbalanced type load, copper wound,with digital display, Relay free smooth and silent operation with first filling of Transformer oil having following specification :- (i) Input voltage 300-480V or as per ground requirement, (ii) Output voltage stabilized at any designed/desired voltage 415 +/- 1% adjustable, (iii) No distortion in wave form, (iv) Response time not to exceed 10 milli seconds (v) Sensitivity (+1%), (vi) Rate of correction 8 volt/second for single phase and 20 volt/second for phase to phase, (vii) No load losses less than 0.5% (viii) Full load losses less than 2.5%, (ix) Duty cycle continuous 24 x 7, Efficiency more than 95%, (x) Type of load 3 Phase, unbalanced type, (xi) Digital display voltmeter and amp meter of suitable rating Protections, (xii) Over load/short circuit protection, (xiii) High/low voltage cut off, (ix) By pass arrangement in case of emergency, (xv) Single phase sequence change protection
Supply, installation, testing and commissioning of indoor automatic/servo voltage stablizer three phase, 50Hz (confirming to IS 9815 : Part 1: 1994 reaffirmed 2009) Naturally oil cooled of 630 KVA, suitable for unbalanced type load, copper wound, digital display with Relay free smooth and silent operation with first filling of Transformer oil having following specification: - (i) Input voltage 300-480V or as per ground requirement, (ii) Output voltage stabilized at any designed/desired voltage, 415 + 1% adjustable, (iii) No distortion in wave form, (iv) Response time not to exceed 10 milli seconds, (v) Sensitivity (+ 1%), (vi) Rate of correction 8 volt/second for single phase and 20 volt/second for phase to phase, (vii) No load losses less than 0.5%, (viii) Full load losses less than 2.5%, (ix) Duty cycle continuous 24 x 7, Efficiency more than 95%, (x) Type of load 3 Phase, unbalanced type, (xi) Digital display voltmeter and amp meter of suitable rating Protections, (xii) Over load/short circuit protection, (xiii) High/low voltage cut off, (ix) By pass arrangement in case of emergency (xv) Single phase sequence change protection.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressue.
M&L for brick masonry chamber of size 100 x 100 x 150cms (internal dimensions) with necessary earth work in any type of soil, plain cement concrete 1:3:6 type C-2 as in foundation 15 cm thick , brick work in cement mortar (1:4) , 23 cms thick wall, 15mm thick plaster in cement mortar (1:4) internally having water proofing compound , top cover shall be of GI having thickness 10 mm and having handles of 10mm dia bars including two caots of synthetic enammell paint over a coat of red oxide primer, necessary excavation and earth work in any type of soil, returning filling and removal of surplus soil not exceeding 50 mtrs, complete all as specified and directed.
Supply and laying insulating Rubber mat of 1 meter X 2 meter x 10 mm all as specified and directed.
Supply, testing and commissioning indoor LT Panel board as per IS/IEC 61439 (Part I & II) factory fabricated indoor cubical type totally enclosed made out of 2.00 mm thick sheet metal enclosure with angle iron frame of size 50 x 50 x 06 mm , IP-42 Icw (1 Sec) = 50KA. IAC should be 50KA for .3Sec, Rated Impulse, Voltage- 12 kV. IK10 Class, Form of seperation- 3b, Seismic Zone IV as per IEC ( tested at 0.4g acceleration), for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel opening doors (covers) on two sides with handles, .bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber/wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands of suitable size for cable entry and exit complete with necessary internal wiring with stranded copper conductor FRLS PVC insulated cables of adequate size, duly with painted one coat of red oxide primer and two coats of synthetic enamel paint of gray or any other approved colour and copper bus bar rating 2000 Amp - 04 Nos mounted on epoxy insulator-01 Set complete with multifunction meter for measuring voltage, current, PF and phase Indicating lamp, ammmeter with suitable size of CTs voltmeter, frequecy meter including connecting the following: - (PS1-ACB Panel No 1 & 2)
(i) Incoming 1250 A 4P EDO (electrically operated Draw-Out type) 50 KA ACB with Ics=Icu=Icw (1 sec) = 50KA having Microprocessor based Releases for O/L, S/C, Instantaneous & E/F protection with applicable time delays and inbuilt LCD Display for Current, Voltage, Energy, Power & PF metering and last 10 trip history. Release should have separate fault Indication LEDs for easy identification of fault and ready to close indication, Shunt & UVT, 12NO+12NC Contact. - 2 Nos.of ACB - (For Sub Station No 1) Panel No. 1 & 2
(ii) Outgoing: - (a) 1250 A 4P EDO type (electrically operated Draw-Out type) 02 Nos ACB with Ics=Icu=Icw (1 sec) = 50KA having Microprocessor based releases for O/L, S/C, Instantaneous &E/F protection with applicable time delays and inbuilt LCD Display for Current, Voltage, Energy, Power & PF metering and last 10 trip history. Release should have separate fault Indication LEDs for easy identification of fault and ready to close indication, Shunt & UVT , with breaker ON, OFF, Trip indication , 12NO+12NC Contact. - 02 No of ACB (01 No for Outgoing Feeder and 01 No for bus couplers)
ACB should be with RS 485 port / Module to Connect breaker ON/OFF status, Breaker trip status, ready to close status, and Control remote open/close of air circuit breakers from Remote/Modbus. ACB should be rated Pollution degree 4 as per IEC 60664 standard. ACB should be fitted with Door interlock, automatic safety shutters, 12NO + 12 NC potential free contact. Mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to IEC 60947-2/IS 1397- 2: 1993 as amended up-to-date complete with following accessories for each ACB. (i) Independent manual spring closing mechanism- 1No. (ii) Microprocessor release (EMI & EMC certified) for over current, earth fault, Instantaneous & short circuit protection- 1 set. (b) Digital Multifunction meter with LED display for Time, Date, system ,meter ID with Phase Sequnce , PF (RYB) measuring voltage L-N ,L-L current (RYB) ,Average Current PF,Frequency, KW,KVA, KVAr,kW/KVA, rising Demand ,Maximum demand and phase indicating lamp, PT Primary,PT secondary with suitable size of CTs Secondary and Primary etc (c) LED indicating lamps (RYB) -03 Nos (d) Earthings- Two terminals should be provided. (e) All control wiring should be copper of suitable sizes with proper tagging with proper terminals/terminal blocks clamps control terminal blocks etc.control and power shall be separted with insulating barrier
Supply,testing and commissioning indoor L.T.Panel board as per IS/IEC:61439 (Part I & II) factory fabricated indoor cubical type totally enclosed made out of 2.00 mm thick sheet metal enclosure with angle iron frame of size 50 x 50 x 06 mm , IP-42 Icw (1 Sec) = 50KA. IAC should be 50KA for .3Sec, Rated Impulse Voltage- 12 kV. IK10 Class, Form of seperation- 3b, Seismic Zone IV as per IEC ( tested at 0.4g acceleration), for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel opening doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber/wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands of suitable size for cable entry and exit complete with necessary internal wiring with stranded copper conductor FRLS PVC insulated cables of adequate size, duly with painted one coat of red oxide primer and two coats of synthetic enamel paint of gray or any other approved colour and copper bus bar rating of 2000 Amp - 04 Nos mounted on epoxy insulator-01 Set complete with multifunction meter for measuring voltage, current, PF and phase indicating lamp, ammmeter with suitable size of CTs voltmeter, frequecy meter including connecting the following: - (Sub station No 1 - ACB Panel No 3)
Incoming:- (a) 1250 A 4P EDO type (electrically operated Draw-Out type) 03 Nos ACB with Ics=Icu=Icw (1 Sec) = 50KA having Microprocessor based releases for O/L, S/C, Instantaneous &E/F protection with applicable time delays and inbuilt LCD Display for Current, Voltage, Energy, Power & PF metering and last 10 trip history. Release should have separate fault Indication LEDs for easy identification of fault and ready to close indication,, Shunt & UVT , 12NO+12NC Contact. - 3 Nos of ACB
Outgoing:- (a) 1250 A 4P EDO type (electrically operated Draw-Out type) 3 Nos ACB with Ics=Icu=Icw (1 Sec) = 50KA having Microprocessor based releases for O/L, S/C, Instantaneous &E/F protection with applicable time delays and inbuilt LCD Display for Current, Voltage, Energy, Power & PF metering and last 10 trip history. Release should have separate fault Indication LEDs for easy identification of fault and ready to close indication, Shunt & UVT , with breaker ON, OFF, Trip indication , 12NO+12NC Contact. - 03 No of ACB (01 No for outgoing to Isolation transformer,01 Nos as bus couplers, 01 No spare)
ACB should be rated Pollution degree 4 as per IEC 60664 standard. ACB should be fitted with Door interlock, automatic safety shutters, 12NO + 12 NC potential free contact. Mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to IEC 60947-2/IS 1397- 2: 1993 as amended up-to-date complete with following accessories for each ACB: - (i) Independent manual spring closing mechanism- 1No. (ii) Microprocessor release (EMI & EMC certified) for over current, earth fault, Instantaneous & short circuit protection- 1set.
(b) Digital Multifunction meter with LED display for Time, Date, system, meter ID with Phase Sequnce , PF (RYB) measuring voltage L-N, L-L current (RYB), Average Current PF, Frequency, KW, KVA, KVAr, kW/KVA, rising Demand ,Maximum demand and phase indicating lamp, PT Primary, PT secondary with suitable size of CTs Secondary and Primary etc (c) LED indicating lamps (RYB) -03 Nos (d) Earthings- Two terminals should be provided. (e) All control wiring should be copper of suitable sizes with proper tagging with proper terminals/terminal blocks clamps control terminal blocks etc.control and power shall be separted with insulating barrier
Supply,testing and commissioning indoor L.T.Panel board as per IS/IEC-6143 (part I & II )factory fabricated indoor cubicle type totally enclosed made out of 2.00 mm thick sheet metal enclosure with angle iron frame of size 50 x 50 x 06 mm , IP-42 Icw (1 Sec) = 50KA. IAC should be 50KA for .3Sec, Rated Impulse Voltage- 12 kV. IK10 Class, Form of seperation- 3b, Seismic Zone IV as per IEC ( tested at 0.4g acceleration), for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel opening doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber/wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands of suitable size for cable entry and exit complete with necessary internal wiring with stranded copper conductor FRLS PVC insulated cables of adequate size, duly with painted one coat of red oxide primer and two coats of synthetic enamel paint of gray or any other approved colour and copper bus bar rating of 2000 Amp - 04 Nos mounted on epoxy insulator-01 Set complete with multifunction meter for measuring voltage, current, PF and phase indicating lamp, ammmeter with suitable size of CTs voltmeter, frequecy meter including connecting the following: -(For sub station No 1 ) Distribution panel Panel No. 4.
Incoming:- (a) 1250 A 4P EOD (electrically operated Draw-Out )type ACB with Ics=Icu=Icw (1 Sec) = 50KA having Microprocessor based releases for O/L, S/C, Instantaneous &E/F protection with applicable time delays and inbuilt LCD Display for Current, Voltage, Energy, Power & PF metering and last 10 trip history. Release should have separate fault Indication LEDs for easy identification of fault and ready to close indication, Shunt & UVT, with breaker ON, OFF, Trip indication - 3 Nos (One No spare) All the ACB should be electrically and Mechanically Interlocked with Digital Load manager with RS 485 Port EM6400NG, RYB Indications
ACB should be rated Pollution degree 4 as per IEC 60664 standard. ACB should be fitted with Door interlock, automatic safety shutters, 12NO + 12 NC potential free contact. Mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to IEC 60947-2/IS 1397- 2: 1993 as amended up-to-date complete with following accessories for each ACB: - (i) Independent manual spring closing mechanism- 1No. (ii) Microprocessor release (EMI & EMC certified) for over current, earth fault, Instantaneous & short circuit protection- 1set. Outgoing:- (a) MCCB, 4 pole, 630 Amp, Icu, = 50 KA, & Ics = 100% of Icu, Double break contact design with adjustable type microprocessor based release & adjustable overload setting (minimum 80% to 100% ) and adjustable SC current 5 to 10 In setting, with extended terminals & Extended Rotary Handle with breaker ON, OFF, Trip indication, along with the phase sepraters - 03 Nos. (2 Nos for CCR & 1 Nos Spare)
(b) MCCB, 100 amp, 4 pole, Icu = 16 KA ,Ics=100% Icu ,with thermal magnetic release and adjustable overload (80-100%) and adjustable short ckt 5 to 10ln setting complete with phase seperators - 02 nos (c) MCCB, 63 amp, 4 pole, Icu = 16 KA ,Ics=100% Icu ,with thermal magnetic releases and adjustable overload (80-100%) and adjustable short ckt 5 to 10ln setting complete with phase seperator - 02 nos (d) MCCB, 32 amp, 4 pole, Icu = 16 KA, Ics=100% Icu ,with thermal magnetic releases and adjustable overload (80-100%) and adjustable short ckt 5 to 10ln setting complete with phase seperator - 04 nos (e) MCCB, 25 amp, 4 pole, Icu =16 KA ,Ics=100% Icu ,with thermal magnetic releases and adjustable overload (80-100%) and adjustable short ckt 5 to 10ln setting complete with phase seperator - 08 nos (f) MCCB, 16 amp, 4 pole, Icu =16 KA, Ics=100% Icu ,with thermal magnetic releases and adjustable overload (80-100%) and adjustable short ckt 5 to 10ln setting complete with phase seperator - 04 nos (g) MCB, 16 Amp, DP, "C" series, 10 KA - 04 Nos. (h) Digital Multifunction meter with LED display for Time, Date, system, meter ID with Phase Sequnce , PF (RYB) measuring voltage L-N ,L-L current (RYB), Average Current PF, Frequency, KW, KVA, KVAr, kW/KVA, rising Demand, Maximum demand and phase indicating lamp, PT Primary, PT secondary with suitable size of CTs Secondary and Primary etc
(j) LED indicating lamps (RYB) -03 Nos (k) Earthings- Two terminals should be provided. (l) All control wiring should be copper of suitable sizes with proper tagging with proper terminals/terminal blocks clamps control terminal blocks etc.control and power shall be separted with insulating barrier.
Supply, testing and commissioning indoor L.T.Panel board as per IEC:61439 (Part I & II) ,65 KA 1 sec factory fabricated indoor cubical type totally enclosed made out of minimum 2.00 mm thick sheet metal enclosure with suitable angle iron frame as per IEC 61439 -1 and 2 and IEC 61641 with internal arc containment for fault level of 65 KA / 0.3 s , Rated Impulse Voltage- 12 kV. IK10 Class, Form of seperation- 3b, Seismic Zone IV as per IEC ( tested at 0.4g acceleration), for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel opening doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber/wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands of suitable size for cable entry and exit complete with necessary internal wiring with stranded copper conductor FRLS PVC insulated cables of adequate size, duly with painted one coat of red oxide primer and two coats of synthetic enamel paint of gray or any other approved colour and copper bus bar rating 800 Amp - 04 Nos mounted on epoxy insulator-01 Set complete with multifunction meter for measuring voltage, current, PF and phase indicating lamp, ammmeter with suitable size of CTs voltmeter, frequecy meter including connecting the following :- (For sub station No 2) Distribution panel (Panel No. 5).
Incoming:- (a) MCCB, 4 pole 400 Amp, Icu = 36 KA , Ics = 100 % of Icu with microprossor release, with shunt & UVT with breaker and adjustable overload (80 to 100%) and adjustable shortcircuit current 5 to 10 In setting complete with ON, OFF Trip indication, along with the phase sepraters - 01 Nos Outgoing:- (a) MCCB, 4 pole 25 Amp, Icu=16 KA with thermal magnetic release, with adjustable overload setting (min 80 to 100%) & adjustable short circuit 5 to 10 In setting complete extended terminals & Extended Rotary Handle with breaker ON, OFF, Trip indication - 07 Nos. (b) MCCB, 4 pole, 16 Amp, Icu= 16 KA with thermal magnetic release, with adjustable overload setting (min 80 to 100%) & adjustable short circuit 5 to 10 In setting complete, with extended terminals & Extended Rotary Handle with breaker ON, OFF, Trip indication - 01 Nos.
(c) MCB, DP, ‘C’ series 16 Amp, 10 KA- 02 Nos (d) Digital Multifunction meter with LED display for Time, Date, system, meter ID with Phase Sequnce , PF (RYB) measuring voltage L-N ,L-L current (RYB), Average Current PF, Frequency, KW, KVA, KVAr, kW/KVA, rising Demand, Maximum demand and phase indicating lamp, PT Primary,PT secondary with suitable size of CTs Secondary and Primary etc (e) LED indicating lamps (RYB) -03 Nos (f) Earthings- Two terminals should be provided. (g) All control wiring should be copper of suitable sizes with proper tagging with proper terminals/terminal blocks clamps control terminal blocks etc.control and power shall be separted with insulating barrier
Supply, fixing, connecting and commissioning with testing of factory made (automatic and manual operation) power factor improvement panel as required as per IEC: 61439 Part I&II and IEC 61921 or IS-16636-2017. The degree of protection of enclosure system of the APFC panel shall be IP42 indoor type front access in accordance with IEC 60529. The capacitor bank shall be internet of things (IOT) enabled and communicable/ integrable with EMS. and of capacity 250 KVAR including interconnection with LT panel with appropriate size of electric cable for transformer (outdoor/indoor) type panel factory made, weather prrof, dust and vermin proof (IP54/IP 42) suitable for 1100V/440 V grade 3 phase 50 Hz AC supply floor mounted, fabricated out of 14 SWG MS sheet and having four Nos angle iron legs made out of40x40x6mm long below frame with front door and back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 Sqmm extension strips and connected with suitable size thimbles, lugs duly painted with Siemens grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles complete all as specified and directed. Note: LT cable required for connection from transformer to panel will be measured and paid seperately
A. Incoming - MCCB 315, 3 pole Amp Icu = 36 KA, Ics = 100 % of Icu with microprossor release with By pass facility, shunt & UVT with breaker and adjustable overload (80 to 100%) and adjustable shortcircuit current 5 to 10 In in setting complete with ON, OFF Trip indication - 01 Nos B. Metering Section - Digital Ammeter (0-400) Amps, digital volt meter (0-500) Volts, RYB indicateing Lamps, 1 Set Control fuses, CTs 3 Nos. C. Insulated Busbar -Insulated Busbar of Copper of 400 A capacity for 3 phases, fixed on insulators, Busbars should be PVC sleeved with red. Yellow, Blue Colour, Busbar support should be of SMC/DMC - 1 set. D. Power factor Controller - Multi 8 step 440V, 5A (144 x 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display.
E. Outgoing feeders :- (i) 25 KVAR capacitor Bank - 2 Nos along with Capacitor duty contractor suitable for 25 KVAR capacitor bank with damping resistores which limits inrush current 440 volt, 3 Phase, 50Hz, Coil-220 V with MCCB, TP, 100A, Icu = 16 KA, Ics = 100% of Icu with thermal magnate release and adjustable overload (min 80 to 100%) and adjustable shortcircuit current 5 to 10 In setting with heavy duty capacitor, on/off indicators, with Start /Stop push button. (ii) 50 KVAR capacitor Bank - 4 Nos along with Capacitor duty contactor suitable for 50 KVAR capacitor bank with damping Resistors which limits inrush current 440 volts, 3 Phase, 50 HZ, Coil-220 VAC with MCCB, TP, 250 A, breaking capacity Icu =36KA Ics= 100% of Icu, micro processor release with adjustable O/L (min 80 to 100%) and adjustable S/C 5 to 10 In setting, with heavy duty capacitor on/off indicators, with start/stop push button. (iii) Ventilating fans of required size to dissipate the heat liberated by capacitor units complete with automatic switching on /off of fans depending upon the panel, 230 Vac 1500 rpm, 160 CU.M /H flying leads. (iv) Automatic power factor controller steps relay microprocessor based for switching ON and OFF of capacitors to display of voltage, current, active power. Apparent power display of PF, THD, and current alarm indication for defective step, low power factor and access temperature. The relay having volt free C/o contact. Automatic detection and uses of optimum capacitor capable of 4 Quadrant operations and any phase offset requirement.
Switching programme : LIFO combi filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 550 Volt , 45 to 65 Hz. Current measuring 10 MA -5A suitable for CTx/1A and X/5A commissiong without additional setting and programming. Three decimal power reading. Phasing out of fault capacitor bank Automatically.
(v) All accessories prewired with suitable size copper wire with stand high temperature, housed in cubical panel made out of 14 swg thick MS sheet factory made duly powder coated front and rar door open able with locking arrangement complete with foundation as required or recommended by manufacturer.
Supply, fixing, connecting and commissioning with testing of factory made (automatic and manual operation) power factor improvement panel as required as per IEC: 61439 Part I&II and IEC 61921 or IS-16636-2017. The degree of protection of enclosure system of the APFC panel shall be IP42 indoor type front access in accordance with IEC 60529. The capacitor bank shall be internet of things (IOT) enabled and communicable/ integrable with EMS. of capacity 100 KVAR including interconnection with LT panel with appropriate size of electric cable for transformer (outdoor/indoor) type panel factory made, weather prrof, dust and vermin proof (IP54/IP 42) suitable for 1100V/440 V grade 3 phase 50 Hz AC supply floor mounted, fabricated out of 14 SWG MS sheet and having four Nos angle iron legs made out of 40x40x6mm long below frame with front door and back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 Sqmm extension strips and connected with suitable size thimbles, lugs duly painted with Siemens grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles complete all as specified and directed. Note: LT cable required for connection from transformer to panel will be measured and paid seperately. Incoming Feeder:- A. Incomer MCCB 160 Amp, three pole , thermal magnetic release with adjustable O/L, (minimum 80 % to 100%) adjustable S/C 5 to 10 In setting ,Class II, front face, Icu = 36 KA, Ics=100% Icu, Isolation with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier -01 Nos
B. Metering Section - Digital Ammeter (0-200) Amps, digital volt meter (0-500) Volts, RYB indicateing Lamps, 1 Set Control fuses, CTs 3. C. Insulated Busbar - Insulated Busbar of Aluminium of 200A capacity for 3 phases, fixed on insulators, Busbars should be PVC sleeved with red. Yellow, Blue Colour, Busbar support should be of SMC/DMC - 1 set D. Power factor Controller - Multi 8 step 440V, 5A (144 x 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display. E. Outgoing feeder :- (i) 03 KVAR capacitor Bank - 1 Nos along with Capacitor duty contractor suitable for 03 KVAR capacitor bank with damping resistors which limits inrush current 440 volt, 3 Phase, 50Hz, Coil-220 Vac with MCB, TP, 10A,C series having breaking capacity 10 KA with heavy duty capacitor, on/off indicators, Start /Stop push button.
(ii) 07 KVAR capacitor Bank - 1 Nos along with Capacitor duty contactor suitable for 07 KVAR capacitor bank with damping resistors which limits inrush current 440 volts, 3 Phase, 50 HZ , Coil-220 V and with MCCB, TP, 20 A having breaking capacity Icu =16 KA, thermal magnetic release with adjustable O/L (min 80 to 100%), S/C setting (5 to 10 x In), Ics = 100% Icu with heavy duty capacitor on/off indicators, start/stop push button. (iii) 10 KVAR capacitor Bank - 02 Nos along with Capacitor duty contactor suitable for 10 KVAR capacitor bank with damping resistors which limits inrush current 440 volts, 3 Phase, 50 HZ , Coil-220 VAC with MCCB, TP, 40 A, having breaking capacity Icu =16KA, thermal magnetic release with adjustable O/L, (min 80 to 100%) S/C setting (5 to 10 x In) Ics = 100% Icu with heavy duty capacitor on/off indicators, start/stop push button. (iv) 15 KVAR capacitor Bank - 02 Nos along with Capacitor duty contactor suitable for 15 KVAR capacitor bank with damping resistors which limits inrush current 440 volts, 3 Phase, 50 HZ , Coil-220 VAC with MCCB, TP, 40 A having breaking capacity Icu =16KA thermal magnetic release with adjustable O/L, (min 80 to 100%) S/C setting (5 to 10 x In) Ics = 100% Icu with heavy duty capacitor on/off indicators, start/stop push button.
(v) 20 KVAR capacitor Bank - 02 Nos along with Capacitor duty contactor suitable for 20 KVAR capacitor bank with damping resistors which limits inrush current 440 volts, 3 Phase, 50 HZ , Coil-220 VAC with MCCB ,TP, 63 A having breaking capacity Icu =16KA thermal magnetic release with adjustable O/L, (mn 80 to 100%) S/C (5 to 10 x In) setting, Ics = 100% Icu with heavy duty capacitor on/off indicators, start/stop push button. (vi) Ventilating fans of required size to dissipate the heat liberated by capacitor units complete with automatic switching on /off of fans depending upon the panel, 230 Vac 1500 rpm, 160 CU.M /H flying leads.
(vii) Automatic power factor controller steps relay microprocessor based for switching ON and OFF of capacitors to display of voltage, current, active power. Apparent power display of PF, THD current alarm indication for defective step, low power factor and access temperature. The relay having volt free C/o contact. Automatic detection and uses of optimum capacitor capable of 4 Quadrant operations and any phase offset requirement. Switching programme : LIFO combi filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 550 Volt , 45 to 65 Hz. Current measuring 10 MA -5A suitable for CTx/1A and X/5A commissiong without additional setting and programming. Three decimal power reading. Phasing out of fault capacitor bank Automatically. (viii) All accessories prewired with suitable size copper wire with stand high temperature, housed in cubical panel made out of 14 swg thick MS sheet factory made duly powder coated front and rar door open able with locking arrangement complete with foundation as required or recommended by manufacturer.
Supply and fixing MCB Single Pole and neutral 16 to 32 Amps rating 240 Volts, 10KA 'C' curve miniature circuit breaker complete with connection testing and commissioning complete all as specified and as directed by Engineer-in-Charge.
M&L for shifting of existing RMU panel by disconnecting the same from existing electric circuit by taking proper shutdown from power house in written to new place within distance not exceeding 1 Km and reinstalling the same to another sub stn and making the connections complete all as sepecified and directed ( Note: Rate include the transportation cost to move the RMU but Termination kit required will be measured and paid separetely)
M&L for shifting of existing Transformer of cap not 250 KVA by disconnecting the same from existing electric circuit by taking proper shutdown from power house in written to new place within distance not exceeding 1 Km and reinstalling the same to another sub stn and making the connections complete all as sepecified and directed ( Note: Rate include the transportation cost to move the Transformer but Termination kit required for alignment will be measured and paid separetely)
M&L for shifting of existing LT pannel by disconnecting the same from existing electric circuit by taking proper shutdown from power house in written to new place within distance not exceeding 1 Km and reinstalling the same to another sub stn and making the connections complete all as sepecified and directed ( Note: Rate include the transportation cost to move the LT panel and necessary PCC work of as in used for foundation of the panel)
Fixing and installation of Light assembly complete with spikes,glass fitting on existing concrete with nut bolts as required at site (Note: Light assembly and its spike will be issued by AF Authorities)
M&L for LED lamp 20 watt all as specified and directed.
M & L for disconnecting Omni lights and fixing the same at new location as directed on PCC base including making necessary elctrical connection all as specified and directed (Note: Necessary PCC work will measured and paid seperatly)
Under ground cable route indicator made out of 100mm dia MS plate with 20mm dia 60cm long MS bar as legs, fixed with and including PCC block 1:2:4, type B-1, including painting with two coats of synthetic enamelled paint over a coat of red oxide primer and writting letters HT/LT all as directed by Engr-in-Charge.
Supply & fix of hot diped galvanised perforated cable tray and cover thickness 12 SWG width 300mm and depth 50mm including all necesaary coupler plates nuts bolts required to fix cable tray with wall all as specified and directed.
Supply and Fixing switch air break gang operated triple pole structure mechanically operated from ground level mounted on and including 12 No insulators and steel frame, outdoor type, suitable for vertical installation, single break, fixed contact made of electrolytic copper strip duly electro silver plated with 8 micron thickness and moving contact made of hard-drawn electrolytic copper rod, flexible jumper flexible breaded tape woven with line tinned copper wire, fixed and moving arcing horn, terminal connector, Operating Mechanism With Padlocking Arrangement at 'OFF' & 'ON' position, HT post type insulator, copper alloy high pressure assembly with Expulsion drop out fuse assembly 11000 volts grade for each phase 100 amps capacity and operating rod of 25mm dia medium grade GI pipe 6.0 mtrs in length complete conforming to IS-9921 (Part-I) of 1981 and 9921 (Part-5) of 1981 with continuous current rating up to 200 amps and voltage 11KV including testing and commissioning all as specified and as directed.
S & F cable route indicator at the distance of 50 mtrs each made out of 45 x 45 x 5 mm angle iron, 80 mm long embedded in PCC block of suitable size with moulded lettter HT CABLE or LT CABLE suitably incribed on CI circular plate 8 mm thick 100 dia including painting with two coats of synthetic enamelled paint over a coat of red oxide primer incl neccessary PCC 1:3:6, type C-2 (using 40 mm graded aggrregate) block of suitable size and neccessary earth work and excavation all as specified and directed.
Supply and fixing cable jointing kit for 1100 volts grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 400 sqmm complete all as specified and as directed.
Supply and fixing cable jointing kit for 1100 volts grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 400 sqmm complete all as specified and as directed.
Supply and fixing cable jointing kit for 1100 volts grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 300 sqmm complete all as specified and as directed.
Supply and fixing cable jointing kit for 1100 volts grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 300 sqmm complete all as specified and as directed.
Supply and fixing cable jointing kit for 1100 volts grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 150 sqmm complete all as specified and as directed.
Supply and fixing cable jointing kit for 1100 volts grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 150 sqmm complete all as specified and as directed.
Total amount of Sch 'A' PART-XII (SEC-II) (EXTERNAL ELECTRICAL SUPPLY WORK)
Total amount of Sch 'A' Part-XIII (FIRE POINT WORK)
Total amount of Sch 'A' Part-XIV {PROVISION OF FALSE FLOORING AND ALUMINIUM PARTITION (BLDG No. P -114) WORK}
Total amount of Sch 'A' Part-XV (PLINTH FOR MAFI NAV AID WORK)
Total amount of Sch 'A' Part-XVI {BULK PETROLEUM INSTALLATION (BPI) WORK}
Total amount of Sch 'A' Part-XVII (DEMOLITION WORK)
Total amount of Sch 'A' Part-XVIII (SITE CLEARANCE, EXCAVATION AND EARTH WORK)
Sch 'A' PART-XIX (DIFFERENT TYPE OF EARTHING/CHEMICAL EARTHING WORKS) Note: This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 4 mm dia galvanized earth lead wire by means of bolts, nuts, check nuts and washers of galvanized standard iron or steel all as specified or indicated in electrical plate No 3 of MES Part-I, including testing on completion including the material and labour of the following: - (a) Excavation and earth work or drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1. (c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm. (d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified. (e) 15 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering. (f) Requisite quantity of common salt and charcoal. (g) Testing of earthing. Note: (1) The earth resistance shall be less than 5 ohms after completion of earthing. If the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.
Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 32 x 6mm GI strip as earth lead burried into ground and connected by means of bolts, nuts, check nuts and washers of galvanized standard iron or steel all as specified or indicated in electrical plate No 3 of MES Part-I, including testing on completion including the material and labour of the following: - (a) Excavation and earth work or drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1. (c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm. (d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified. (e) 40 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering. (f) Requisite quantity of common salt and charcoal. (g) Testing of earthing. Note: (1) The earth resistance shall be less than 5 ohms after completion of earthing. If the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.
Supply and installation of maintenance free earthing with electrode having 1 no copper plate interconnected of size 900 x 600 x 5mm with 32 x 6mm copper strip of length 1.5 mtrs and having solid rod electrode of 17.2 mm dia with 250 microns copper coating of length 3 mtr centrally placed with suitable connectors for lower resistance. Thick layer of suitable conductive concrete with resistivity .001 ohms (compound 25 kgs bag x4) mix with a cement in a ratio of 3:1, make as per IEEE 80 2000, Clause 14.5 D, maintenance free earthing system to give Earthing resistance value of < 1 Ohm. The soil shall be mixed with backfill. Copper bonded Electrode's should be solid and surrounded with highly conductive and non-corrosive nature & covered with Poly plastic Earth pit cover, including excavation in any type of soil, removal of surplus soil, complete including testing all as specified and directed by Engineer-in-Charge. The unit rate includes GI pipe up to 7.5m for protection of earth lead (ii) The unit rate includes main earthing lead/strip from earth electrode to test point up to 7.5 meter (iii) In case measured value of earth resistance is recorded more than 1.0 ohms then the Earthing shall be re- done by the contractor without any extra cost to the department (iv) If there is a requirement of Grid Earthings to achieve desired earth resistance, as directed by Eng-in-charge, then inter connecting of different earthings shall be done at no Extra cost
Sub Total amount of Sch 'A' PART-XIX (Section-II) (DIFFERENT TYPE OF EARTHING/CHEMICAL EARTHING WORKS)
NOTE: Amount against schedule of credit for retrieved materials mentioned under relevant part of Sch of Credit of tender document in PDF form will be deducted offline/manually from overall amount quoted by the lowest bonafide bidder during award of contract.
SAGGI ELECTRIC COMPANY
Sant Construction Co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .