Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.8 LAccepted-AOC NO 15 ELECTRICAL INDUSTRIAL ESTATE KAKKALUR THIRUVALLUR 602003 | THIRUVALLUR | TAMIL NADU | 602003 | L1 | Accepted-AOC L1 | |
| 2 | L2₹15.5 L+₹5.7 L (57.9%)Rejected-Finance SALEM | SALEM | L2 | Rejected-Finance NOT A LOWEST PRICE | |
| 3 | Rejected-Technical | - | Rejected-Technical Engine Power output does not match | |
| 4 | Rejected-Technical | - | Rejected-Technical Engine Power output does not match |
| Sl No | Description | Qty | Unit | Delta Roto Tech Private LimitedV H1 | Pulsetronics Engineering Private Limited H2 |
|---|---|---|---|---|---|
| 1.0058.5 kVA Diesel Generator | |||||
| 1.01 | Engine Specifications:
Parameter Specification
Rated Output (kW) 54.4
Rated Output (HP) 74
No. of Cylinders 4
Cubic Capacity (Ltrs) 3.24
Bore x Stroke (mm) 96 x 112
Rated Speed (RPM) 1500
Aspiration Turbocharged with Aftercooler (TA)
Lube Oil Change Period (hrs) 500
Lube Oil Sump Capacity (Ltrs) 10
Coolant Capacity (Ltrs) 12.7
Alternator Specifications:
Parameter Specification:
Insulation Class Class H
Efficiency (at 100% load, 0.8 pf) 90.8%
Max Voltage Dip at Full Load (0.8 pf lag) <20%
Max Time to Build Rated Voltage <2 sec (at rated speed)
Frequency 50 Hz
Power Factor 0.8 lagging
Voltage 415 V (3 Phase)
Governing Class (ISO 8528 Part-V) G2
Starting System 12V DC Battery Start
Genset Specifications
Parameter Specification
Genset Rating (kVA) (as per ISO8528) 58.5
Prime Power (kW) 46.8
Fuel Tank Capacity (Ltrs) 165
Noise Level @ 1m (with canopy) <75 dBA
Cooling System Water Cooled
Speed Regulation ±1%
Additional Requirement:
Installation Requirementp:
• The offer shall include complete installation of the DG set at the designated location..
• The scope of installation shall cover:
• Electrical wiring, termination, and commissioning.
• Laying of power cable between the DG installation point and the main power distribution panel.
• Civil construction works, including foundation, vibration pads, and any structural support required for proper installation.
• All installation work shall comply with CPCB IV+ norms, CEIG/Electrical Inspectorate requirements, and standard safety guidelines.
Key Features
• Complies with CPCB IV+ emission and noise regulations.
• 500-hour lube oil change interval for reduced maintenance cost.
• Inbuilt silencer and compact canopy for reduced noise and better aesthetics.
• Microprocessor-based control panel with LCD display and diagnostic capability.
• Remote monitoring compatibility for real-time tracking of parameters.
• Optimized fuel efficiency across 50–100% loading range.
• Rugged and compact design suitable for continuous prime power applications.
Note: Bidders must upload the OEM-issued technical specification data sheet while participating in the tender. | 1 | Nos | 13,02,000 ₹15,46,360 | 8,29,876 ₹9,79,253.68 Lowest |
Tender Value
Refer Docs
Closing Date
10 Dec 2025, 6:00 pmClosed
Dr.V.THIRUNAVUKKARASU
GOVERNMENT COLLEGE OF ENGINEERING BARGUR 635 104
Purchase of 58.5 kVA Diesel Generator
2025_DoTE_626340_1
4894/B1/Mech/2025
Open Tender
Electrical Goods/Equipments
Supply
10 days
GOVERNMENT COLLEGE OF ENGINEERING BARGUR
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
Exempted
7 Jan 2026
25 Nov 2025
12 Dec 2025
25 Nov 2025
10 Dec 2025
25 Nov 2025
58.5 kVA Diesel Generator
Engine Specifications: Parameter Specification Rated Output (kW) 54.4 Rated Output (HP) 74 No. of Cylinders 4 Cubic Capacity (Ltrs) 3.24 Bore x Stroke (mm) 96 x 112 Rated Speed (RPM) 1500 Aspiration Turbocharged with Aftercooler (TA) Lube Oil Change Period (hrs) 500 Lube Oil Sump Capacity (Ltrs) 10 Coolant Capacity (Ltrs) 12.7 Alternator Specifications: Parameter Specification: Insulation Class Class H Efficiency (at 100% load, 0.8 pf) 90.8% Max Voltage Dip at Full Load (0.8 pf lag) <20% Max Time to Build Rated Voltage <2 sec (at rated speed) Frequency 50 Hz Power Factor 0.8 lagging Voltage 415 V (3 Phase) Governing Class (ISO 8528 Part-V) G2 Starting System 12V DC Battery Start Genset Specifications Parameter Specification Genset Rating (kVA) (as per ISO8528) 58.5 Prime Power (kW) 46.8 Fuel Tank Capacity (Ltrs) 165 Noise Level @ 1m (with canopy) <75 dBA Cooling System Water Cooled Speed Regulation ±1% Additional Requirement: Installation Requirementp: • The offer shall include complete installation of the DG set at the designated location.. • The scope of installation shall cover: • Electrical wiring, termination, and commissioning. • Laying of power cable between the DG installation point and the main power distribution panel. • Civil construction works, including foundation, vibration pads, and any structural support required for proper installation. • All installation work shall comply with CPCB IV+ norms, CEIG/Electrical Inspectorate requirements, and standard safety guidelines. Key Features • Complies with CPCB IV+ emission and noise regulations. • 500-hour lube oil change interval for reduced maintenance cost. • Inbuilt silencer and compact canopy for reduced noise and better aesthetics. • Microprocessor-based control panel with LCD display and diagnostic capability. • Remote monitoring compatibility for real-time tracking of parameters. • Optimized fuel efficiency across 50–100% loading range. • Rugged and compact design suitable for continuous prime power applications. Note: Bidders must upload the OEM-issued technical specification data sheet while participating in the tender.
Pulsetronics Engineering Private Limited (BID ID -1530805)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.39 MB
BOQ_748956.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .