| 1 | Supply of 1.5Ton 5 Star rated Inverter Split AC units | Supplying of BEE approved 1.5 TR 5 Star rated Inverter or dual inverter type split Air Conditioning unit having nominal rated cooling capacity not less than 5200 watts with copper Evaporator and Condenser coil and Rotary Compressor suitable for operation on single phase 230 V plus or minus 10 percentage 50 Hz AC supply minimum room air flow 500 CFM and minimum Indian Seasonal Energy Efficient Ratio ISEER 5.20 filled with R32 or R410A refrigerant gas with installation kit comprising of standard lengths of copper refrigerant pipes PU or foam insulation drain pipe and interconnection copper cable etc complete as reqd. The manufacturer and Supplier shall give a warranty of air conditioners for 12months from date of supply. 10years warranty on the compressors and 5years warranty on the PCB for both indoor and outdoor printed circuit board cards. | 8 | Each | bsnl00101860 | 45 |
| 2 | Installation Testing and Commissioning of 1.5Ton 5 Star rated Invereter Split AC units | Installation Testing and commissioning of 1.5 TR Split AC Unit and mounting or Fixing of indoor and outdoor unit and fixing of refrigerant piping with expanded polythene foam insulation and laying of cable for interconnections and laying drain pipe of standard length which is supply along with AC unit with minor civil work including making holes on wall for laying refrigerant pipe lines and control cable and drain pipes and closing the extra openings with cement sand and making good the damages etc as reqd. Extra length of Refrigerant piping and cable shall be paid extra | 8 | Each | bsnl00101860 | 45 |
| 3 | Providing and Fixing of L shaped powder coated MS bracket | Providing and fixing of suitable size L shaped powder coated MS bracket 2nos per set for fixing of the outdoor unit of the split AC units and fixing on wall with anchor bolts and drilling holes etc complete as reqd. | 8 | Set | bsnl00101860 | 45 |
| 4 | Providing and laying of additional copper refrigerant pipes | Providing and laying of additional refrigerant copper pipe for suction and discharge line of size not less than one by fourth inches and half inches dia or as recommended by the manufacturer along with expanded polythene foam insulation including cutting brazing and making joint etc as reqd. The measurement shall be taken on linear basis for one circuit which includes suction and discharge line and foam insulation. | 50 | Mtr | bsnl00101860 | 45 |
| 5 | Supply and laying of extra copper cable for Split Ac units 3 core 2.5sqmm | Supplying and laying of Extra Electrical cable of 3 core 2.5 sqmm PVC insulated and sheathed copper for electrical connection of AC units etc as reqd. Make- Finolex or Polycab or Havells or L and T. | 30 | Mtr | bsnl00101860 | 45 |
| 6 | Supply and laying of extra copper cable for Split Ac units 4 core 2.5sqmm | Supplying and laying of Extra Electrical cable of 4 core 2.5 sqmm PVC insulated and sheathed copper for electrical connection of indoor and outdoor units of ACs etc as reqd. Make- Finolex or Polycab or Havells or L and T. | 50 | Mtr | bsnl00101860 | 45 |
| 7 | Providing and laying additional drain pipes | Providing and laying of additional drain pipe of size 25mm dia polythene or U PVC of M class-ISI marked pipe along with all accessories and fixing on surface of wall with saddles or C-clamps if required suitable for drainage of condensate water etc. as reqd. | 50 | Mtr | bsnl00101860 | 45 |
| 8 | Providing and charging of additional refrigerant gas | Providing of additional R32 or R410A refrigerant gas if required and charging or top up into the Split AC units etc. as reqd. | 5 | Kg | bsnl00101860 | 45 |
| 9 | Supply and fixing of MCB protected Socket outlet box | Supply and Fixing of MCB protected 3 pin socket outlet boxes with metal board consisting of 1 no 20 Amps 3 pin socket outlet with 20 Amps plug top and 1 no 20 or25 amps SP MCB of C series suitable for 220-230 volts single phase 50 Hz AC supply as required. | 8 | Each | bsnl00101860 | 45 |
| 10 | Dismantling of old Window AC unit | Dismantling the existing 1no old and faulty Window AC units along with Accessories and other unwanted electrical boxes conduits angle iron frames as required. | 1 | Job | bsnl00101860 | 45 |