Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹5.2 LAccepted-Finance | 1 | Accepted-Finance L-1 | |
| 2 | 2₹5.9 L+₹71,200 (13.7%)Accepted-Finance | 2 | Accepted-Finance L-2 |
Tender Value
₹5.2 L
EMD Value
₹6,000
Closing Date
15 Jun 2022, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE
ETC-II, UPPTCL, PAARESHAN BHAWAN, VIBHUTI KHAND, GOMTI NAGAR, LUCKNOW-226010
WORK
2022_UPTCL_702963_1
ETC-II/L/05/2022-23
Open Tender
Electrical Works
Item Rate
90 days
SAROJININAGAR
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
SE, ETC-II, UPPTCL, LUCKNOW
₹6,000
31 Aug 2022
25 May 2022
16 Jun 2022
25 May 2022
15 Jun 2022
25 May 2022
180 days
Amount
Following works are to be carried out for installation of New 400 KV Bus-Bar Protection Panels including Dismantling (of old panels) Erection (of new panels), Cabling, Glanding, Termination and other associated works at 400 KV S/S Sarojininagar with all cost of men, mis. consumables, T&P etc. to complete the job satisfactorily as per direction of the Supervising Engineer :-
Safe Loading of following Control Cable of from various 400 KV and 220 KV Sub-Stations as mentioned below with due shifting, their safe carriage on Truck and Unloading, Shifting & Placing at designated place at 400 KV S/S Sarojininagar, Lucknow with all other associated works for satisfactory completion of the job:
400 KV S/S Muradnagar-II (approx.distance upto 480Km) 5CX2.5SQMM Armoured Control Cable (05KM)
400 KV S/S Moradabad (approx.distance upto 365Km) 5CX2.5SQMM Armoured Control Cable (02KM)
400 KV S/S Sarnath (approx.distance upto 320Km) 7CX2.5SQMM Armoured Control Cable (06KM)
Dismantling of existing old 02 Nos. Bus Bar Protection Panels (Electromechnical type) and 02 Nos. Tertiary Reactor Protection Panels (not in service) after disconnection of all the control cables including recording of connection, removal of control cables with Glands, Cutting/Removal of Earthing, then Shifting the Panels with due care & safety to site store. (One Job each Panel)
Laying of following sizes Copper Control Cables (Provided by UPPTCL) in the Cable Trenches from new 400 KV Bus Bar Protection Panels to CT Junction Boxes, Bus isolators in Switchyard and Control/Relay Panels in Control Room etc. including Carriage of Cable Drums from Store to Site and Shifting back to Store and all other associated works to complete the job satisfactorily as per technical specification :
5X2.5mm² size Control Cable
7X2.5mm² size Control Cable
10X2.5mm² size Control Cable
Erection of 04 Nos. New Numerical Type 400 KV Bus Bar Protection Panels (GE T&D make) comprising of Main and Trip Unit after shifting from site store with due care & safety to control room area with grouting and earthing. Followed by Inter-connection of above installed 400 KV Bus Bar Protection Panels with existing 400 KV Lines and Transformer Bays (CT Junction Boxes, Bus Isolator MOM Boxes in Switchyard & Control/Relay Panels in Control Room) using Control Cables (Provided by UPPTCL as per Cable Schedule including making holes in Base Plate, Glanding & Termination and Ferruling alongwith Preparation of Inter-connection Drawing and Commissioning of the Panel/Feeders in co-ordination with T&C wing including providing of 2 sets of Hard copies of as executed inter-connection Drawing (01 Job for each 400 KV Bay)
MANAS ELECTRICALS
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .