Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.8 LAccepted-AOC | L1 | Accepted-AOC Accepting being lowest | |
| 2 | L2₹35.8 L+₹6.1 L (20.6%)Rejected-Finance | L2 | Rejected-Finance Rejected being other than lowest | |
| 3 | L3₹41.2 L+₹11.5 L (38.8%)Rejected-Finance | L3 | Rejected-Finance Rejected being other than lowest |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
22 Jan 2022, 6:00 pmClosed
Maj Pramod Kumar Tripathi
Military Engineer Services, Garrison Engineer (South) Ahmednagar - 414002
Repair/Maint of CI/GI/DI Water Supply distribution system of Md Accn, chloronome Plant, Pump Set, Valves, Cleaning OF OHT/UG Sump and connected works at Mil Stn Aurangabad under GE (S) Ahmednagar
2022_MES_498710_1
8843/E8
Open Tender
Miscellaneous Works
Item Rate
270 days
Aurangabad
Class D Cat a (ii)
8 documents required · 8 mandatory
₹500
Garrison Engineer (South) Ahmednagar - 414002
₹70,000
Yes
2 Feb 2022
1 Jan 2022
24 Jan 2022
1 Jan 2022
22 Jan 2022
8 Jan 2022
1 Jan 2022 - 5 Jan 2022
Amount
Excavation in trenches not exc 1.50 m wide and not exc 1.50 m deep for foundation, laying of pipe or for shafts, wells cesspits,man holes, sluice valves etc not exc 10 Sqm on plan and n exc 1.5m in depth and getting out in soft / loose soil complete all as specified and as directed.
Returning, filling, in soil including spreading, levelling, watering and well ramming in layers n.exc. 25cm thick complete all as specified and as directed.
Removing excavated soil to distance not exc. 50 m and depositing where directed at a level not exc. 1.5 m above the starting point etc complete all as specified and as directed.
Taking up or down defective/unserviceable CI/DI water mains, 100 mm bore, including all necessary fittings from trenches complete all as specified and directed.
Taking up or down defective/unserviceable CI/DI water mains, 150 mm bore, including all necessary fittings from trenches complete all as specified and directed.
Taking up or down defective/unserviceable CI/DI water mains, 200 mm bore, including all necessary fittings from trenches complete all as specified and directed.
M&L for DN 100 mm ductile Iron pipe with spigot and socket ends, centrifugally cast, class DI-K9, cement mortar lining with portland slag cement as per IS 455: 1989, metallic zinc coating as per annex A of IS 8329 with finishing layer of bituminous coating as per annex C of IS 8329, suitable for rubber gasket joint, conforming to IS: 8329 : 2000, ISI marked, in any length, laid in trenches, pressure testing, washing out complete all as specified and as directed. Note : Rubber gasket joint will be measured and paid seperately.
All as per serial item No 7 here-in-before but for DN 150 mm.
All as per serial item No 7 here-in-before but for DN 200 mm.
M&L for CI / DI fittings and specials such as Bends (any type, radius and angle), Tapers any type (straight, bend, increasing, decreasing or double socket etc.), Tee pieces single branch, "Y" junction, double branch, cross (all sockets or socket and spigot), Collars, Caps, Plugs, Connecting pieces one end flanged and other end socketed or spigot ends or all socketed / spigot ends etc, suitable upto 150 mm bore pipe complete all as specified and as directed.
All as per serial item No 10 here-in-before but for 200 mm bore pipe.
M&L for Ring tyton joint including rubber ring,complete for DI/CI pipe 100 mm bore complete all as specified and as directed.
M&L for Ring tyton joint including rubber ring,complete for DI/CI pipe 150 mm bore complete all as specified and as directed.
M&L for Ring tyton joint including rubber ring,complete for DI/CI pipe 200 mm bore complete all as specified and as directed.
Taking up or down old rusted and unserviceable GI water tubing 20 mm bore, including all necceassy fittings complete from walls /floor or trenches all as specified and as directed.
All as per serial item No. 15 here-in-before but of 25 mm bore.
All as per serial item No. 15 here-in-before but of 40 mm bore.
All as per serial item No. 15 here-in-before but of 50 mm bore.
All as per serial item No. 15 here-in-before but of 80 mm bore.
All as per serial item No. 15 here-in-before but of 100 mm bore.
M&L for 25mm bore GI tubing, medium grade, ISI marked complete with all fittings laid in trenches complete all as specified and directed.
All as per serial item No. 21 here-in-before but of 40 mm bore.
All as per serial item No. 21 here-in-before but of 50 mm bore.
All as per serial item No. 21 here-in-before but of 80 mm bore.
All as per serial item No. 21 here-in-before but of 100 mm bore.
M&L for 20mm bore GI tubing, medium grade, ISI marked, complete with all fittings and fixed to walls/ ceiling or laid in floors complete all as specified and directed.
All as per serial item No. 26 here-in-before but of 25 mm bore.
All as per serial item No. 26 here-in-before but of 40 mm bore.
M&L for gun metal gate/ globe valve, 20 mm bore, with iron wheel head, screwed both ends for pipe and fixed including dismantling and taking out existing unserviceable gate valve complete all as specified and directed.
All as per serial item No. 29 here-in-before but of 25 mm bore.
All as per serial item No. 29 here-in-before but of 50 mm bore.
M&L for sluice valve, cast iron, long body, 80 mm bore, both ends flanged as per IS-14846 and drilled with stainless steel spindle, iron wheel head and as per pressure rating PN 1.6, Class I, ISI Marked alongwith nuts, bolts, washers , gaskets etc. including dismantling and taking out existing unserviceable sluice valve from valve chamber / trenches complete all as specified and directed.
All as per serial item No. 32 here-in-before but of 100 mm bore.
All as per serial item No. 32 here-in-before but of 150 mm bore.
All as per serial item No. 32 here-in-before but of 200 mm bore.
All as per serial item No. 32 here-in-before but of 300 mm bore.
Taking LT shutdown, dismantling and removing the 40 HP, 3 phase electric motor of the coupled Pump set from existing foundation / position, shifting to authorized workshop for repair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor with super enamelled copper wire of the size equivalent to the original winding including insulated packing materials, Varnishing, Heating, Drying etc, replacing the bearings, reassembling the motor, transporting to site of work and reinstalling back at it's original position, aligning, testing and commissioning on full load for 8 hrs continuous running complete all as specified & directed.
All as per serial item No. 37 here-in-before but 25 HP, 3 phase electric motor of the coupled pump.
All as per serial item No. 37 here-in-before but 15 HP, 3 phase electric motor of the coupled pump.
All as per serial item No. 37 here-in-before but 5 HP, 3 phase electric motor of the coupled pump.
M&L for PVC insulated, multi stranded, copper conductor submersible cable, 1100 volts grade, ISI marked of size 10 sqmm, 3 Core, including taking down old cable complete all as specified and diercted.
Cleaning the open well having 5m dia and depth upto 10 mtr by flushing out the complete water with water pump and taking out all debries/mud from open well with the help of machine or manually and removal of debris/silt off the premises complete all as specified and as directed.
S&F in repairs, digital submersible motor starter DOL type suitable for 3 phase, 5 HP motor alongwith all connected accessories PLC relay, single phase preventor, dry run protection enclosed in and including box and making electric connection all as specified and as directed.
S&F in repairs, DOL starter, 3 phase, 415 V, suitable for 1.5/2 HP pumpset with overload and short circuit protection and making electric connection, all as specified and as directed.
S&F in repairs, DOL starter, 3 phase, 415 V, suitable for 3/5 HP pumpset with overload and short circuit protection and making electric connection, all as specified and as directed.
S&F in repairs, DOL starter, 3 phase, 415 V, suitable for 7.5 HP pumpset with overload and short circuit protection and making electric connection, all as specified and as directed.
S&F in repairs, single phase preventer, suitable for fully automatic Star Delta starter or Direct - on - Line starter including making connections, all as specified and as directed.
S&F in repairs, 3 phase Fully automatic Star Delta starter including ML-2 contactors in sheet metal enclosure with Phase Protection feature (Motor Rating AC - 3 Duty, 415V, 50Hz, 3Ph) suitable for 25HP pumpset including making connections, all as specified and as directed.
S&F in repairs, 3 phase Fully automatic Star Delta starter including ML-3 contactors in sheet metal enclosure with Phase Protection feature (Motor Rating AC - 3 Duty, 415V, 50Hz, 3Ph) suitable for 40 HP pumpset with suitable relay including making connections, all as specified and as directed.
S&F in repairs, Phase sequence (3 phases as existing or as per site requirement), including making connections, all as specified and as directed.
S&F in repairs, steel coupling suitable for motor and pump as per existing make and model or as directed at site all as specified and as directed.
S&F in repairs, rubber belt suitable for motor & pump including nuts and bolts fixed in replacement complete all as specified and as directed.
S&F in repairs, 3 Pole Power Contactor having AC3 Rating 60 Amps with 2 NO + 2 NC Auxilliary Contacts, all as specified and as directed.
S&F in repairs, Star coupling, Heavy Duty, Styrene Butadiene Rubber suitable for 40 HP pump or motor, all as specified and as directed.
S&F in repairs, Star coupling, Heavy Duty, Styrene Butadiene Rubber suitable for 25 HP pump or motor, all as specified and as directed.
S&F in repairs, Star coupling, Heavy Duty, Styrene Butadiene Rubber suitable for 15 HP pump or motor, all as specified and as directed.
Cleaning of existing RCC overhead water storage reservoir of any type and shape of capacity 200000 gallon having any no. of compartments, at a staging upto 25 mtr height including dewatering of remaining dirty water and removal of sand,silt, sludge and other dust particles, completely washing the reservoir with clean water and applying one coat of epoxy paint of colour as decided by Engineer-in-charge on all internal surfaces before refilling including preparation of external surfaces of OH Reservior (Exposed surfaces) including columns, beam , bracing supports etc. and applying one coat of cement base paint including painting a square plate of 2 m X 0.5 m with black synthetic enamel paint and writing letters on it with white paint regarding. Capacity, date of cleaning, Location and Due Date of next Cleaning etc. complete all as specified and directed.(Size of letter shall be as directed by Engineer-in-Charge). Location of OHT : E/M Yard. Appx Area 1450 Sqm.
All as per serial item No.57 here-in-before but OHT of 100000 gallon capacity located at 3rd Med OTM. Appx Area 900 Sqm
All as per serial item No.57 here-in-before but OHT of 60000 gallon capacity located at Malhotra Enclave/ 5 Med/ MAP. Appx Area 800 Sqm
S&F rubber packing cotton braided, not less than 3.0 mm thick, any size, fixed in position complete all as specified and as directed.
S&F gland packing 6 to 12 mm dia of best quality make Champion to stop leaking in Pump Houses/sluice valve in field area,fixed in position complete all as specified and as directed.
Cleaning of underground sump of 1.5 lakh gallon capacity by pumping out water from U/G sump by booster pump set as directed at site and taking out the remaining water at bottom with buckets manually as required complete and cleaning the walls & bottom surface inside the sump with wire brush and taking out silt, sand and mud etc. settled at the bottom and finally completely cleaning the sump with bleaching powder and applying one coat of epoxy paint to all the internal surfaces and one coat of cement base paint on all external surfaces including making a plate of size of 2 m x 0.5 m with black synthetic enamel paint and writing letters with white synthetic enamel paint viz. the capacity, location , date of cleaning and the due date for further cleaning” complete all as specified and directed.
All as per serial item No. 62 here-in-before but under ground sump of 2.5 lakh gallon capacity.
All as per serial item No. 62 here-in-before but under ground sump of 1 lakh gallon capacity.
M&L for mechanical joint with 2 Nos CI/DI sockets, 1 No CI/DI collar and 2 Nos styrene butadiene rubber gasket (IS : 5382) joint alogwith nuts, bolts and washers including cutting CI/DI pipe for insertion of mechanical joint in position for 80 mm bore pipe, as in repairs complete all as specified and directed.
All as per serial item No.65 here-in-before but for 100 mm bore pipe.
All as per serial item No.65 here-in-before but for 150 mm bore pipe.
All as per serial item No.65 here-in-before but for 200 mm bore pipe.
All as per serial item No.65 here-in-before but for 300 mm bore pipe.
All as per serial item No.65 here-in-before but for 400 mm bore pipe.
S&F Netlon jallies with 1st class teak wood batten duly tightened with wooden patti and nails, and fitted on top of over head reservoir / UG sump or specified windows for air vent / entry / opening to prevent entry of birds / dirt particles etc complete all as specified and as directed.
S&F in repairs, MCCB, 4 pole, 315 A, 50KA, 415V with thermal magnetic release, spreader links, adjustable over load and short circuit setting, all as specified and as directed.
Supply only calcium hypochlorite water disinfectant containing 60 to 70% chlorine contents (Calcuim based granular disinfectant for water treatment) packed in and including 45 Kg plastic drum complete all as specified from any of the following makes:- Make:-As on approved list of EinC's Branch. Note :- The contractor shall submit purchase vouchers, test certificates, Batch No, Lot No and its expiry date etc and other relevant documents alongwith supply of Calcium Hypochlorite granular disinfectant. Engineer-in-Charge shall verify the authenticity and genuiness of PVC and TCs before forwarding contractor's claim of payment. Supply of chemical shall not be accepted without production of these documents and no payments shall be made.
Supply only of bleaching powder grade-I, ISI marked packed in 25 Kg bag, complete all as directed.
Excavation and earthwork along the CI pipe line of dia 300/ 400mm dia (main line) between leaking area, burning out the leaking joints and taking out joint with spun yarn and lead complete and rejointing the same with proper lead joint and lead wool to remove leakage completely including necessary returning filling the earth and well ramming in layers n exc 25cm each complete all as specified and as directed.
Excavation and earthwork along the CI/DI/GI pipe line of dia 80/100/150mm ( main line ) between leaking area,taking out old U/S MS clamp and supply & jointing properly with new clamp of same size, type including nuts, bolts and rubber packing complete including necessary returning filling earth and well ramming in layers n exc 25cm each complete all as specified and as directed.
S&F in repairs, PVC float valve including socket, reducer etc. of size 20 mm bore, all as specified and as directed.
Supply only TCCA 90 (Trichloroisocyanuric Acid) to maintain PH of water and also cleaning the water all as specified and as directed.
Supply only NaCl (Sodium Chloride) for chlorome plant all as specified and as directed.
S&F in repairs, PVC flexible hose pipe 50 mm bore all as specified and as directed.
Supply only Sodium Hypochlorite (NaOCl) solution consisting more than 12% active chlorine, pale yellowish liquid all as specified and as directed.
Cutting the existing road/hard standing surfaces to a depth of 60 cm and 50 cm wide and getting out for laying under ground pipe including returning filling in, watering well ramming in layers not exceeding 25 cm in soil and filling the trench top with 15 cm thick PCC 1:2:4, type B1 using 20mm graded stone aggregate amd making good the disturbed surface complete all as specified and as directed.
Disconnect the electric supply, dismantling coupling and removing 15 HP compressor, shifting to local workshop for repair / servicing, Opening up the compressor unit, dismantle and remove damaged piston, piston connecting rod, rings etc and replace with new one, Reconditioning / welding / filling / grinding / lathework to shaft of the compressor unit, supply & replace suitable size bearing of make : SKF - 2Nos, drain out the out dated compressor oil, cleaning the oil chamber thoroughly by removing the sludges from the oil sump, filling up new compressor oil of specified gravity - 4 Litres, replacement of air filters of suitable size - 2Nos, replacement of gasket set, coupling, aligning, replacement of worn out V - belts ( B-72) of make : Fenner - 3 Nos, reassembling after replacement of defective parts, transporting back to the original location, reinstalling at sie, connecting, testing & commissioning complete all as specified & as directed.
Taking LT shutdown, dismantling and removing the 35 HP, 3 phase submersible pump set from existing foundation / position, shifting to authorized workshop for the repair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor with super enamelled copper wire of the size equivalent to the original winding including insulated packing materials complete including varnishing, heating, drying etc, replacing the bearings, reassembling the motor, transporting to site of work and reinstalling back at it's original position, aligning, testing and commissioning on full load for 8 hrs continuous running complete including grinding the rust from impeller and any other works complete all as specified & as directed.
Taking down sewage pump set of 30 HP from existing foundation/position, shifting to authorised workshop for the repair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor with super enamelled copper wire of the size equivalent to the original winding including insulated packing materials, complete including varnishing, heating, drying etc, replacing the bearings, reassembling the motor, transporting to site of work and reinstalling back at it's original position, aligning, testing and commissioning on full load for 8 hrs continuous running complete including grinding the rust from impeller, change of oil seal and any other works, emptying the sewage sump and cleaning the sludge from sump complete all as specified & as directed.
Taking down centrifuge machine (capacity 120 Kg / day ) from existing location, shifting to authourised workshop for the repair work and servicing, replacement of defective parts as required, testing and reinstalling back at it's original position, connected to sludge line after checking of servicibility of valves and any type leakage etc. complete all as specified and as directed.
Opening the bearing cover from existing pump and replacing by new bearing both side of the pump of suitable size by greasing, before testing close the bearing cover, test pump with smooth sound and without heating the bearing cover complete all as specified and directed.
Taking up or down defective/unserviceable CI/DI water pipe up to 300 mm bore from 32 mtr hight Over head tank due to leakage and blockage of washout pipe line and refixing the pipe line in its orginal position including all necessary fittings and fixing open on wall or floor or OHT complete all as specified and directed.
Excavation along the PVC/HDPE pipe line of any size between leaking area and supply and replacement of PE-AL-PE composite pressure pipes including fittings such as elbows, tee, reducers , coupler/adaptor etc as required at site and returning filling in and well dressing the surface complete all as specified and as directed.
SONU ENTERPRISES
M/S Tirupati Goroba Shendge
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .