Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
14 Sept 2024, 6:00 pmClosed
CWE JHANSI
HQ CWE JHANSI
REPAIR/MAINT TO VARIOUS DG SETS, EOT CRANES, INCINERATOR, CONTROL PANELS AND CONNECTED WORKS UNDER AGE E/M AT GE JHANSI
2024_MES_665449_1
CWE/JHA/J/TOKEN/24 OF 2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
JHANSI
As per tender documents
9 documents required · 9 mandatory
₹500
GE JHANSI
₹90,000
Yes
27 Sept 2024
11 Jul 2024
16 Sept 2024
11 Jul 2024
14 Sept 2024
26 Jul 2024
Amount
Material and Labour for servicing of DG set by carrying out the following maintenance including testing on completion at connected load for entire satisfaction of Engineer-in-Charge and complete all as specified and directed for the DG set of capacity 320 KVA :- (i) Draining out engine oil from the sump by removing drain plug, cleaning the sump thoroughly and refilling the sump with new engine oil to required level. Note : Engine Oil will be measured and paid separately as 'Supply Only'. (ii) Draining out of diesel from tank and storing in cleaned containers, cleaning the tank thoroughly by removing sediments settled at the bottom and refilling the drained out diesel duly filtered. (iii) Supply and replace complete set of fuel filters, engine oil filters and air filter element. (iv) Draining out complete coolant water mixture from the radiator and re-filling the radiator with new coolant and water mixture with proportionate ratio. Note: Coolant will be measured and paid separately as 'Supply Only'. (v) Check and top up the electrolyte/distilled water in starting batteries to maintain the required specific gravity. Cleaning of battery terminals & applying petroleum jelly to battery poles & brass connectors. (vi) Tightening all the fasteners of complete DG set to the required torque.
All as per Ser item No1.00 above but for DG set of capacity 125 KVA complete all as specified and directed.
All as per Ser item No 1.00 above but for DG set of capacity 100 KVA complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
All as per Ser item No 1.00 above but for DG set of capacity 82.5 KVA complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
All as per Ser item No1.00 above but for DG set of capacity 75 KVA complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
All as per Ser item No1.00 above but for DG set of capacity 62.5 / 63 KVA complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
All as per Ser item No1.00 above but for DG set of capacity 50 KVA complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
All as per Ser item No1.00 above but for DG set of capacity 40 KVA complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
All as per Ser item No1.00 above but for DG set of capacity 30 KVA complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
All as per Ser item No1.00 above but for DG set of capacity 25 KVA complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
All as per Ser item No1.00 above but for DG set of capacity 15 KVA / 20 KVA complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
All as per Ser item No 1.00 above but for DG set of capacity 7/5.5 KVA complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
Supply only engine oil of grade 15W-40 for various DG Sets complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
Supply only of coolant water mixture (50:50) suitable for DG sets complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
Supply and replace complete set of fuel pipes & leak off pipe with clamps suitable for existing make & model of DG set up to 320 KVA capacity complete all as specified and directed.
Supply and replace 'V' belt suitable for existing make & model of DG set up to 320 KVA capacity complete all as specified and directed.
Supply and replace complete set of hoses with clamps suitable for existing make & model of DG set up to 320 KVA capacity complete all as specified and directed.
Attending of urgent complaints in any breakdown of standby DG sets upto 320 KVA and EOT Cranes at any location in Jhansi Cantt and AAU under GE Jhansi, whenever required round the clock, rectify the fault and restore the standby supply within one hour after receipt of the complaint, complete all as specified and directed. Note : (i) The cost of all kind of replaced defective parts / spares / control cards / oil / lubricants etc, as and when required to making the DG Set and EOT Cranes fully functional, will be measured and paid seperately under respective items only. (ii) The cost of all kind of minor parts / spares, other than mentioned in BOQ, as and when required to making the DG Set/EOT Cranes fully functional, is deemed to be included in quoted rates and no extra cost shall be paid to the contractor in this effect. (iii) If complaint is not attended by the contractor within two hour the penality as applicable shall be impossed on him. (iv) Contractor to give the name of machanic, electrician and helpers those will attend the urgent breakdown. (v) All kind of transportation (to and fro) for all kind of necessary equipment/T&P shall be arranged/brought by contractor to complete the job at site or at workshop and no extra cost shall be paid to the contractor in this effect. (vi) Complaints shall be lodged by telephonically, so contractor has to give the telephone number of person who will receive the complaint round the clock.Normal defect rectification such as relay settings , loose wirings , oiling / greasing , sensor based settings include in this work . No separate cost will be charged against minor defect rectification.
De-scaling of radiator assembly by carefully removing from the engine, transporting to civil workshop and removing the sediments, scales and rust etc by means of chemical cleaning, high pressure water washing and air cleaning, arresting the leakages by gas welding / soldering with suitable material, re-assembling the same with new gaskets including replacement of radiator cap (wherever required) and transporting to the site, fixing to the engine for DG Set of capacity 320 KVA and testing for satisfactory performance complete all as specified and directed.
All as per item No.19.00 here-in-before but for DG Set of capacity from 100 KVA / 125 KVA complete all as specified and directed.
All as per item No.19.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA complete all as specified and directed.
All as per item No.19.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA complete all as specified and directed.
All as per item No.19.00 here-in-before but for DG Set of capacity from 15 KVA to 25 KVA complete all as specified and directed.
Dismantling the defective water pump assembly and Supply and fix new water pump assembly suitable for existing DG set of capacity 320 KVA complete all as specified and directed.
All as per item No.24.00 here-in-before but for DG Set of capacity from 100 KVA / 125 KVA complete all as specified and directed.
All as per item No.24.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA complete all as specified and directed.
All as per item No.24.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA complete all as specified and directed.
Dismantling the defective fuel injectors & FIP from the engine and Material & Labour for repair/calibration of fuel injectors & FIP including replacement of barrel plunger, cups & ‘O’ rings etc. for DG Set of capacity 320 KVA complete all as specified and directed.
All as per item No.28.00 here-in-before but for DG Set of capacity from 100 KVA / 125 KVA complete all as specified and directed.
All as per item No.28.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA complete all as specified and directed.
All as per item No.28.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA complete all as specified and directed.
All as per item No.28.00 here-in-before but for DG Set of capacity up to 25 KVA complete all as specified and directed.
Taking down unserviceable lube oil pressure sencer and Supply and fix Lube Oil Pressure Sender (Sensor + Switch) suitable for DG set of capacity 320 KVA complete all as specified and directed.
All as per item No.33.00 here-in-before but for DG Set of capacity from 100 KVA / 125 KVA complete all as specified and directed.
All as per item No.33.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA complete all as specified and directed.
All as per item No.33.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA complete all as specified and directed.
All as per item No.33.00 here-in-before but for DG Set of capacity up to 25 KVA complete all as specified and directed.
Dismantling the fly wheel coupling between engine and alternator and Supply and replace complete set of bullet rubber bushes, coupling nuts & bolts including proper alignment of engine & alternator for smooth running for DG set of capacity 100 KVA / 125 KVA complete all as specified and directed.
All as per item No. 38 here-in-before but for DG set of capacity 62.5 KVA to 83 KVA complete all as specified and directed.
All as per item No 38.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA complete all as specified and directed.
Taking down unserviceable engine wiring and Material & Labour for rewiring of engine safety control system from control panel to engine control gadgets like HWT, LLOP, shut down valve, dynamo & self-starter etc with suitable gauge and grade of wires for DG set of capacity from 100KVA / 125 KVA complete all as specified and directed.
All as per item No.41.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA complete all as specified and directed.
All as per item No.41.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA complete all as specified and directed.
All as per item No.41.00 here-in-before but for DG Set of capacity up to 25 KVA complete all as specified and directed.
Dismantling the defective self starter assembly 12V/24V carefully from the DG set and carryout repair and servicing by cleaning all accessories with suitable cleaning agent and supply and replace commutator, carbon brush set, carbon brush holder, king pin holder, armature choke nut, body screens, clutch plate assembly and solenoid etc, re-assembling and re-fixing the same and testing on completion for DG set of capacity from 320 KVA complete all as specified and directed.
All as per item No.45.00 here-in-before but for DG Set of capacity from 100 KVA / 125 KVA complete all as specified and directed.
All as per item No.45.00 here-in-before but for DG Set of capacity from 62.5 KVA to 83 KVA complete all as specified and directed.
All as per item No.45.00 here-in-before but for DG Set of capacity from 30 KVA to 50 KVA complete all as specified and directed.
All as per item No.45.00 here-in-before but for DG Set of capacity up to 25 KVA complete all as specified and directed.
Taking down the existing defective unserviceable Self starter from Genset 12 V Capacity installed at various installation and replace with new self starter in same position and testing complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
All as per item No. 50 here in before but 24V complete all as specified and directed.
Dismantling the defective 24 V battery charging alternator carefully from any capacity of DG set and carryout repair and servicing by cleaning all accessories with suitable cleaning agent and supply and replace carbon brush, brush holders, bushes/bearings, varnishing etc, re-assembling and re-fixing the same and testing on completion complete all as specified and directed.
All as per item No.52.00 here-in-before but 12 V battery charging alternator for any capacity of DG set complete all as specified and directed.
Supply and fix RPM Meter with cable suitable for DG Set including taking down of existing unserviceable meter complete all as specified and directed.
Supply and fix Oil Pressure Gauge suitable for DG Sets including taking down existing unserviceable gauge complete all as specified and directed.
Supply and fix Water Temperature Gauge suitable for DG Sets including taking down existing unserviceable gauge complete all as specified and directed.
M&L Scraping down the old faded existing paint from the following capacity DG Set of making the surface smooth by filling up the uneven surfaces with putty and scraping with emery sheet, applying two coats of synthetic enamel paint over one coat of red oxide primer, painting the details of panel over the panel all as specified and directed.
62.5 KVA DG set with trolly
75 KVA to 83 KVA DG Set
62.5 KVA DG set at Signal Centre
Supply and connect battery lead (1.50m long each set of 2 Red & Black) made out of PVC Insulated Plain/Striped Automobile Cables with high conductivity bright annealed copper conductor bunched together, insulated with dielectric grade PVC compound (impervious to oils, greases, acids, petrol and water) conforming to IS 2465 of size 25 sqmm soldered one end with brass connector with nuts and bolts for battery pole and the other with copper lug for self starter terminal including taking down of existing u/s battery lead with connector and lug of any description complete all as specified and directed.
Draining out the existing diesel from the tank from the following capacity DG Set , kept as side for repouring, taking down the complete fuel tank of any capacity from its position after disconnecting all the fuel lines, carryout cleaning work with solutions, removing the dust and foreign materials from the tank, drying the tank, blow with air painting and carry out recaliberation of diesel tank to the specified level including replacement of PVC level pipe, refix the tank in its original position, connecting all the removed fuel connections, refilling the kept diesel back to the tank carefully, remove air from the fuel connections, start the engine and test for satisfactory function complete all as specified and directed.
20/30/50 KVA Capacity Genset
62.5 to 100 KVA Capacity Genset
160 to 320 KVA Capacity Genset
Supply and replace brass connector with bolt and nut suitable for positive/negative pole of battery of any size complete all as specified and directed.
Taking down unserviceable AVR of any description from alternator including supply and fixing of new AVR of suitable model for existing alternator of capacity 320 KVA complete all as specified and directed.
All as per item No. 61 here-in-before but for DG set of capacity from 100 KVA / 125 KVA complete all as specified and directed.
All as per item No. 61 here-in-before but for DG set of capacity up to 83 KVA complete all as specified and directed.
Supply and fix battery 12V, 100 AH for DG set including initial filling & Charging complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
All as per item No. 64 here-in-before but of rating 12V, 180 AH complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
Material and labour for reconditioning 12 V 180 AH, 24 plates Batteries including replacement with new parts such as –ve & +ve plates, PVC separators, terminal post, Acid and distilled water etc making in serviceable conditions, all as specified and directed.
All as per Item No. 66.00 here in before but 12 Volts 100/150 AH, 24 Plate battery complete all as specified and directed.
Dismantling the defective alternator from DG set, transporting to civil work shop, separating the stator and rotor from alternator housing, cutting and removing burnt winding of stator completely, cleaning the slots and rewinding the stator with existing gauge of super enameled copper wire with suitable grade of insulation, applying varnish and heating in heating chamber till completely dried and reassembling the alternator, transporting back to site and re-fixing to the DG set including proper alignment for smooth running and testing on completion for DG set of capacity 100 KVA / 125 KVA complete all as specified and directed.
All as per item No. 68 here-in-before but for DG set of capacity 62.5 KVA to 83 KVA complete all as specified and directed.
All as per item No. 68 here-in-before but for DG set of capacity 30 KVA to 50 KVA complete all as specified and directed.
All as per item No. 68 here-in-before but for DG set of capacity 20 KVA to 25 KVA complete all as specified and directed.
All as per item No. 68 here-in-before but for DG set of capacity up to 15 KVA complete all as specified and directed.
Supply and fix in replacement of left hand/ right hand hinge suitable for acoustic enclosure doors for DG set of capacity up to 320 KVA including removing of existing broken hinge complete all as specified and directed.
Supply and fix in replacement of left hand/ right hand lock with catcher suitable for locking doors of acoustic enclosure for DG set of capacity up to 320 KVA including removing of existing unserviceable lock complete all as specified and directed.
Material & Labour for 2.0mm thick Mild steel, plain, black sheet in mobile DG set housing, wall cladding, steel gates and similar work, cut to size, holes punched; including round headed screws, clout nails or rivets and fixed steel framing with plain 40 mm lap joints with riveted or welded seams, including bending or turning up, mitred angles, etc. as required and applying two coats of synthetic enamel paint of approved colour over a coat of red oxide primer including cutting and removing corroded sheet complete all as specified and directed.
M&L for Dismantling complete 62.5 KVA to 83 KVA engine, removing all accessories required for overhauling of DG set, repair/replacement, cleaning, washing of all the parts, and reassembling the engine after repair/replacement and commissioning testing on full load complete all as specified and directed.( 62.5 KVA DG set at Signal Centre, 82.5 KVA DIV HQ) (i) M&L for replacement of cylinder liner -06 Nos (ii) M&L for replacement of Piston Assembly - 06 Nos (iii) M&L for replacement of Piston Ring set - 06 set (iv) M&L for replacement of gas kit set complete - 01 set (v) M&L for replacement of liner 'O' Ring -16 Nos (compressor/oil scrapper Ring) (vi) M&L for replacement of Big Endbearing top - 06 Nos (vii) M&L for replacement of Big Endbearing Bottom - 06 Nos (viii) M&L for replacement of inlet valve seat-06 Nos (ix) M&L for replacement of exhaust valve seat - 06 Nos (x) M&L for replacement of valve inlet/exh-06 Nos (xi) M&L for replacement of valve guide-16 Nos (xii) M&L for replacement of Gaskit Cylinder head -06 Nos (xiii) M&L for replacement of V wrapped belt -01 Nos (xiv) M&L for replacement of Injectors -04 Nos (xv) M&L for replacement of water pump assy-01 Nos (xvi) Cylinder Headrepair including replacement of valve, seal - 01 Job (xvii) FIP calibration and radiator cleaning - 01Job
M&L for Dismantling complete 300 KVA engine, removing all accessories required for overhauling of DG set, repair/replacement, cleaning, washing of all the parts, and reassembling the engine after repair/replacement and commissioning testing on full load complete all as specified and directed. (i) M&L for replacement of cylinder liner -04 Nos (ii) M&L for replacement of Piston Assembly - 04 Nos (iii) M&L for replacement of Piston Ring set - 03 set (iv) M&L for replacement of gas kit set complete - 01 set (v) M&L for replacement of liner 'O' Ring -8 Nos (compressor/oil scrapper Ring) (vi) M&L for replacement of Big Endbearing top - 04 Nos (vii) M&L for replacement of Big Endbearing Bottom - 04 Nos (viii) M&L for replacement of inlet valve seat-04 Nos (ix) M&L for replacement of exhaust valve seat - 04 Nos (x) M&L for replacement of valve inlet/exh-04 Nos (xi) M&L for replacement of valve guide-08 Nos (xii) M&L for replacement of Gaskit Cylinder head -04 Nos (xiii) M&L for replacement of V wrapped belt -01 Nos (xiv) M&L for replacement of Injectors -04 Nos (xv) M&L for replacement of water pump assy-01 Nos (xvi) Cylinder Headrepair including replacement of valve, seal - 01 Job (xvii) FIP calibration and radiator cleaning - 01Job
Design, Fabricate, Supply, Installation, Testing & Commissioning of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 900mm x 900mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed :-
Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors. (ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Material & labour for Earthing complete using galvanised iron earth plate electrode of size 60cm X 60cm X 6mm thick burried directly in ground vertically at a depth not less than 2.25 m below normal ground level with top edge of earth plate at a depth not less than 1.5 m below normal ground level, earth plate surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using galvanised iron strip of size 32X6 mm by means of bolts, nuts, check nuts and washers made of GI and protected by light grade 40 mm dia galvanised iron pipe and GI pipe light grade 20mm bore for watering, including funnel, wire mesh, CI pit cover and PCC chamber pit with PCC 1:2:4 type B-2 (including necessary excavation and earth work disposal of surplus soil to a distance not exceeding 50 m all as specified and shown on electrical plate No 3 of SSR Part-I 2009 and testing on completion all as specified and directed. Note :- On testing after completion from test point the desired earth resistance shall be not less than 2 ohm If the desired result is not obtained the earthing will be re done no extra cost.
Material & Labour for framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete in Fe 410 -W (Gde- E- 250) quality- A and applying two coats of synthetic enamel paint of approved colour over a coat of red oxide primer including cutting and removing corroded frames complete all as specified and directed.
Supply and fix in replacement of MCCB, 630 A, 3 Pole, 50 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed.
Supply and fix in replacement of MCCB, 400 A, 3 Pole, 50 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed.
Supply and fix in replacement of MCCB, 250 A, 3 Pole, 36 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed.
Supply and fix in replacement of MCCB, 200 A, 3 Pole, 25 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed.
Supply and fix in replacement of MCCB, 160 A, 3 Pole, 25 KA (Ics=100%Icu), 415 V, 50 Hz, with fixed thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed.
Supply and fix in replacement of MCCB, 63A to 100 A, 3 Pole, 16 KA (Ics=100%Icu), 415 V, 50 Hz, with fixed thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed.
Supply & fix in repair of Turbo kit for 125/320 KVA DG Set for Kirloskar/Greaves DG Set alongwith its connected items such as nuts & Bolts , Seals ,impeller as per existing etc complete all as specified and directed.
Supply and fix in repair of Turbo kit for 25 /100 KVA DG Set for Ashok Leyland/Kirloskar/Greaves DG Set alongwith its connected items such as nuts & Bolts , Seals ,impeller as per existing etc complete all as specified and directed.
Shifting / refixing of DG set, of capacity 20 KVA/100 KVA desmentaling all electric connection and costruction of suitable size plith (hight upto 2 feet form ground level) for DG set made by brick messonary and well plasterd. Refixing of DG set and panel with proper connection and earthing as per requirement complete all as specified and directed. Note:- Earthing will be measured and paid separately.
Supply, laying, jointing, testing and commissioning LT underground cables, 1100 volts grade, XLPE , heavy duty armoured, with multistranded aluminium conductors, IS-1554 marked, laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe complete all as specified and directed for the following sizes:-
150 Sqmm 3.5 Core
95 Sqmm 3.5 Core
70 Sqmm 3.5 Core
50 Sqmm 3.5 Core
35 Sqmm 3.5 Core
25 Sqmm 4 Core
16 Sqmm 4 Core
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of LT UG cables in soft/ loose soil and getting out it, including trimming sides and bottom of trenches complete all as specified and directed.
Returning, filling-in, including spreading, watering and well ramming in layers not exceeding 25 cm thick each, in soft / loose soil complete all as specified and directed.
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
Supply and filling of sand in and around LT cables 80mm thick below the cable and 150mm thick after laying the cable and gently punning down complete all as specified and directed.
Supplying and laying precast concrete cable cover, class LV, type 1, flat size 250mmx 150mm x 40mm complete all as specified and directed.
Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends etc for protection of LT cable XLPE grade 1100 Volts complete all as specified and directed.
Servicing of AMF panel of upto DG set 320 KVA of capacity installed at Jhansi Cantt Area by cleaning the complete panel with suitable cleaning agent and checking the controller relays, timer, contactors for proper functioning, replacing defective spare parts, replacement of defective small wires of existing size, tightening of all connections and applying jelly on contactors complete all as specified and directed. Note : Spare parts required will be measured and paid separately as 'Supply Only' but cost of small wires shall be included in the quoted rate.
Supply only of following spare parts suitable for existing DG set AMF Panels, 3 Phase, 415 Volts, 50 Hz :-
AMF Logic controller relay complete assembly
Control relay
Timer
Battery Charging Unit 12 / 24 Volts
Auto / Manual switch complete assembly
Start/stop push button
Supply and fix in replacement of engine control panel consisting of ignition switch, water temperature gauge, oil pressure gauge, VAF meter, push button, indication lamp and provision for mounting MCCB etc suitable for DG set of capacity 30 KVA to 100 KVA complete all as specified and directed.
Material and Labour for overhauling of EOT Cranes of 15 Ton / 20 Ton capacity i.e. servicing and checking the serviceability of all mechanical parts such as Gear boxes, gears, rope drums, wire ropes, rope sheaves, track wheels, brakes, bearings etc including greasing and lubricating all moving parts and checking the serviceability of all electrical parts such as Motors, Control panels, switchgears, power & control cables, DSL, Limit switches, Control pendants, indicating lamps, push buttons, MCBs, earth wire etc, identifying the fault for replacement of defective spare parts and testing on completion for smooth functioning complete all as specified and directed. Note : (i) The cost of grease shall deemed to be included in the quoted rate. (ii) Supply and replacement of Gear Oil and all other mechanical and electrical spare parts required for replacement shall be measured and paid separately.
Supply and fill in replacement of gear oil of suitable grade for EOT cranes complete all as specified and directed.
Supply and fix in replacement of limit switch for LT/CT motion suitable for 15 Ton / 20 Ton EOT crane complete all as specified and directed.
Supply and fix in replacement of limit switch for vertical motion suitable for 15 Ton / 20 Ton EOT crane complete all as specified and directed.
Supply and fix in replacement of brake liner of LT and CT motion suitable for 15 Ton / 20 Ton EOT crane complete all as specified and directed.
Supply and fix in replacement of DE / NDE bearings suitable for existing make and model of electric motor of EOT cranes complete all as specified and directed.
Supply and fix in replacement replacement of TPN current collectors suitable for copper bus bar of 15 Ton / 20 Ton EOT crane including necessary fabrication work complete all as specified and directed.
Supply and fix in replacement of push button switch spring type in red or green colour suitable for control panel of 15 Ton / 20 Ton EOT crane complete all as specified and directed.
Supply and fix in replacement of transformer of capacity 250 VA having primary side 0-415 volts and secondary side 0-110 V AC complete all as specified and directed.
Supply and fix in replacement of AC 3 pole, 415V, ML2 power contactor 32A (make: L&T or equivalent ) suitable for electric panel of EOT crane complete all as specified and directed.
Supply and fix in replacement of AC 3 pole ML4 power contactor 70A to 80 A (make: L&T or equivalent) suitable for electric panel of EOT crane complete all as specified and directed.
Supply and fix in replacement of 3 Pole AC Control CE15 A Series 2.2 KW , 6A (make: BCH or equivalent) suitable for electric panel of EOT crane complete all as specified and directed.
Supply and fix in replacement of AC 3 phase ‘NHD’ Series 4 Pole Contactor 16 A (make : BCH Cat No. C00N or equivalent) suitable for electric panel of EOT crane complete all as specified and directed.
Supply and fix in replacement of AC 3 phase ‘NHD’ Series 4 Pole Contactor 40 A (make : BCH Cat No. N1N or equivalent) suitable for electric panel of EOT crane complete all as specified and directed.
Supply and fix in replacement of R/Y/B indication lamp complete all as specified and directed.
Supply and fix in replacement of single phasing preventer complete all as specified and directed.
Supply and fix in replacement of Voltmeter / Ammeter of existing model suitable for 3 phase AC supply complete all as specified and directed.
Supply and fix in replacement of timer suitable for control panel of 15 ton / 20 ton EOT crane complete all as specified and directed.
Supply and fix in replacement of Overload Relay (OLR) suitable for control panel of 15 ton / 20 ton EOT crane complete all as specified and directed.
Supply and fix in replacement of wire rope 16mm dia, 6 x 36 construction of required strength suitable for 15 Ton / 20 Ton EOT crane complete all as specified and directed.
Rewinding of electric motor of capacity up to 3 HP, 3 Phase, 415 Volts, 50 Hz by cutting and removing burnt out winding and rewinding with super enameled copper winding wire of existing gauge and number of turns including varnishing, heating etc including carefully taking down the motor from EOT crane from height up to 12 meters by disconnecting all electrical cables, earth strips and dismounting from base channel, Shifting of motor to civil workshop for repair / rewinding and bringing back and reinstalling in its original position, checking alignment and testing on completion for satisfactory performance complete all as specified and directed.
All as per item No 121.00 here-in-before but for motor of capacity 5 HP / 7.5 HP, 3 Ph, 415 Volts, 50 Hz complete all as specified and directed.
All as per item No 121.00 here-in-before but for motor of capacity 15 HP / 20 HP, 3 Ph, 415 Volts, 50 Hz complete all as specified and directed.
Servicing of elcetric motor of capacity upto 15 HP, 3 Phase , 415 Volts 50 Hz by means of oiling and greasing , replacement of fan blade , nuts and bolts , vibration dampers , mounting assembly etc including minor defect rectification complete all as specified and directed.
Supply and and connect in replacement of PVC insulated and PVC Round Sheathed, multistranded Copper Conductor (flexible) industrial cable of size 2.5 sqmm, 3 core 1100 Volts, conforming to IS: 694 complete all as specified and directed.
All as per item No.125.00 here-in-before but of size 4 sqmm, 3 core complete all as specified and directed.
All as per item No. 125.00 here-in-before but of size 6 sqmm, 3 core complete all as specified and directed.
Supply and fix in replacement of nozzle for primary / secondary chamber as per sample suitable for existing oil fired incinerator complete all as specified and directed.
Supply and fix in replacement of solenoid valve for primary / secondary chamber as per sample suitable for existing oil fired incinerator complete all as specified and directed.
Supply and fix in replacement of fuel pump as per sample suitable for existing oil fired incinerator complete all as specified and directed.
Supply and fix in replacement of pressure gauge as per sample suitable for existing oil fired incinerator complete all as specified and directed.
Supply and fix in replacement of fuel filter as per sample suitable for existing oil fired incinerator complete all as specified and directed.
Supply and fix in replacement of photocell for primary / secondary chamber as per sample suitable for existing oil fired incinerator complete all as specified and directed.
Supply and fix in replacement of power contactor in control panel as per sample suitable for existing oil fired incinerator complete all as specified and directed.
Supply and fix in replacement of relay in control panel as per sample suitable for existing oil fired incinerator complete all as specified and directed.
Supply and fix in replacement of timer in control panel as per sample suitable for existing oil fired incinerator complete all as specified and directed.
Supply and fix in replacement of conveyer belt as per sample suitable for existing oil fired incinerator complete all as specified and directed.
Supply and fix in replacement of AC 3 pole power contactor MCX 45, 415V , 10A , MNX A6 suitable for DG set panel suitable for electric panel of EOT crane complete all as specified and directed. Note : Bidder to check with the already existing/fitted item at site before quoting for compatibility.
Supply and fix in replacement of Controller safety unit suitable for upto 82.5 KVA DG Set make and size as per existing complete all as specified and directed.
Supply and fixing in replacement of Air Circuit Breaker (ACB) E- series, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity In 800 Amps, 4 Pole Ui 1000V, Uimp 12 Kv, Ics = 100% Icu all as specified and directed.
S&F in replacement of fuel pump as per sample suitable for diesel engine of any capacity complete all as specified and directed.
Supply and fix in replacement of On-Load Changeover switch 4 Pole, 125A, 415 V in sheet steel enclosure with front operated handle complete all as specified and directed.
Supply and fix in replacement of On-Load Changeover switch 4 Pole, 250A, 415 V in sheet Metal enclosure with front operated handle complete all as specified and directed.
Supply and fix in replacement of On-Load Changeover switch 4 Pole, 400A, 415 V in sheet Metal enclosure with front operated handle complete all as specified and directed.
Supply and fix electronics based/ sensor based/ On-Load Changeover switch 4 Pole, 125 Amp to 250 Amp, 415 V in sheet metal enclosure as per size of change over switch complete all as specified and directed.
M&L for replacing the old unserviceable battery Terminals ( Positive& Nagative ) including brazing work and applying jelly over the battery pole and terminals complete all as specified and directed.
M&L for replacing the damaged/burn out battery terminal pole (positive/nageative) 12 V DC battery and recosting lead as per the site requirement complete all as specified and directed.
M&L for replacing the old unserviceable battery lead with copper terminals approximately 2.5 mtr length including applying jelly over the battery pole and terminals complete all as specified and directed.
S&F in replacement of radiator suitable for 62.5 KVA DG set and as per site requirement all as specified and directed.
M&L for testing of earthing of DG set properly and desired earth resistance shall be not less than 2 ohm complete all as specified and directed.
M&L for writing of SM to Engine and alternator of DG set properly applying of paint all as specified and directed.
ADARSH ENTERPRISES (BID ID -3094434)
M/S SHARADA ASOCIATE (BID ID -3091190)
NATIONAL AUTO MOBILES (BID ID -3083515)
Soni Traders (BID ID -3091131)
M/S Kharya Associates (BID ID -3091038)
ROHIT ENTERPRISES (BID ID -3096065)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .