Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.6 LAccepted-AOC 840 1B MADHUR VIHAR COLONY CIVIL LINES JHANSI UP 284 001 | JHANSI | JHANSI | UTTAR PRADESH | 284001 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹21.9 L+₹34,890 (1.62%)Rejected-Finance A 63 ELDECO COUNTY PHASE II RAJGARH JHANSI U P 284135 | JHANSI | JHANSI | UTTAR PRADESH | 284135 | L2 | Rejected-Finance Not become lowest bidder | |
| 3 | L3₹26.5 L+₹4.9 L (22.8%)Rejected-Finance 1A BASEMENT 30 31 RAJA HOUSE NEHERU PLACE NEW DELHI | NEW DELHI | NEW DELHI | DELHI | L3 | Rejected-Finance Not become lowest bidder | |
| 4 | L4₹28.2 L+₹6.6 L (30.7%)Rejected-Finance WARD NO 4 NEAR MASZID BHATTAGAON DISTT JHANSI 284001 UTTAR PRADESH | JHANSI | UTTAR PRADESH | 284001 | L4 | Rejected-Finance Not become lowest bidder |
Tender Value
₹29 L
EMD Value
₹58,000
Closing Date
13 Dec 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Lt Col Deepak Kumar
Garrison Engineer Jhansi
PROVN OF 200 KVA DIESEL GENRATING SET AS EXTERNAL POWER BACKUP FOR SPECIAL MAINTENANCE TOOLS / SPECIAL TEST EQUIPMENTS AT JHANSI
2022_MES_562959_1
GE/JHA/TOK/61 OF 2022-2023
Open Tender
Civil Works
Item Rate
90 days
GE Jhansi
As per NIT and Tender Documents
9 documents required · 9 mandatory
₹500
Yes
GE Jhansi
₹58,000
Yes
19 Jan 2023
14 Nov 2022
15 Dec 2022
14 Nov 2022
13 Dec 2022
29 Nov 2022
14 Nov 2022 - 21 Nov 2022
Amount
Supply, installation, testing and commissioning of silent type Diesel engine driven Generating set of capacity 200 KVA/160 KW, 3 phase, 415 Volts, 50 Hz, at 0.8 pf(lag) with Diesel Engine alongwith attachment of emission control device reduce upto 70%, Alternator and control panel all mounted in acoustic enclosure complete confirming to the detailed specifications as given below and specified in particular specification :-
Diesel Engine : The diesel engine shall be of capacity suitable for alternator of capacity 200 KVA/160 KW developing required power for rated KVA not less than 144KW at 1500 RPM, 6 cylinders in-line, 4 stroke, radiator cooled, continuous duty with 10% overload capacity for any one hour in 12 hours of continuous running and consisting of following:- a) Radiator cooled b) Electrical Starter Motor 12V DC. c) 1No X 12 V battery, 180 AH rating with connecting leads and terminals d) Battery Charging Alternator e) Fuel System with electronic governor f) Full flow Spin-on lube oil filter g) Duel fuel filter with water separator h) Residential type silencer j) Dry type air cleaner k) Fly wheel and fly wheel housing l) First fill of lube oil & Coolant m) Emission control device (Retrofitted) / Catalytic conveter device suitable for DG set 200 KVA for pollution control upto 70%
Alternator : The Alternator shall be of capacity 200 KVA/ 160 KW, 415 Volts, at 0.8 pf(lag), 50 Hz, 3 phase, 4 wire system, suitable for operation at 1500 RPM. The Alternator shall be brushless type, screen protected, revolving field, self excited, self regulated through an AVR, copper wound, Class 'H' insulation, having ±1.0% voltage regulation (max) in static conditions and continuous duty operation.
Mounting Arrangement: Engine and Alternator shall be mounted on a common MS fabricated base frame with Anti Vibration Mounting Pads
Fuel Tank: Integral fuel tank shall be of capacity not less than 360 Liters and provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning.
Acoustic Enclosure: The entire generator, prime mover, fuel tank and DG set control panel should be housed in a sound proof acoustic enclosure made of CRCA sheets with UV resistant powder coated and a structural/sheet metal base frame. The walls of the enclosure should be insulated with high quality noise absorbent and fire-retardant grade acoustic insulation material complying to IS 8183 for better sound attenuation so as to comply with the 75 dBA at 1 meter sound levels at 75% load under free field conditions as specified by MOEF/CPCB. The enclosure should be provided with the following:- (i) Suitable doors on all sides to enter in to the container for easy maintenance. All doors shall be provided with locks and handles for opening/ closing of doors. (ii) Suitable internal lighting to carry out easy inspection and maintenance. (iii) Air Inlet louvers designed to operate at rated load. (iv) Fluid drains for lube oil and fuel. (v) Fuel filling point with locking arrangement. (vi) Push button for emergency stop
Note for Item No. 1:- (i) PCC foundation for DG set as per manufacturer's recommendations shall be included in the quoted rates. (ii) On successful installation, the DG set shall be subjected to load test as specified below and specified in particular specification :- Phase-I : No-load test for 01 hour in the presence of Engineer-in-Charge. Phase-II : Load test for 12 hours continuously (at 25% of full load for fist one hour, 50% of full load for second one hour, 75% of full load for third one hour, 100% load for next 08 hours and 110% of full load for last one hour). Resistive type load bank or Water Load, Fuel and testing instruments as required for load testing shall be arranged by the contractor and cost of the same shall deemed to be included in the quoted rate. (iii) Phase-II load test shall be carried out in the presence of testing officer nominated by accepting officer or IEM.
Material and labour for earthing complete with galvanized iron earth plate electrode 600mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI strip of size 32 x 6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth strip protected by 50mm dia GI pipe medium grade and connected to DG Set / Panel Board all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, earth lead & protection pipe up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II.
Material & Labour for LT Power Cables, Aluminum Stranded Conductor 300 sqmm, 3.5 core, XLPE Insulated, Cores laid up, PVC Inner sheathed, Armoured with galvanized wire or galvanized steel strip, overall PVC Sheathed, 1100V Grade as per IS 7098(Part 1) 1988 complete laid in trenches / floors / fixed to poles / walls / drawn through pipes etc including provn of lugs, glands, nuts, bolts & washers etc for connecting in LT feeder pillar box / transformer bushings and testing on completion all as specified and directed. Note: Excavation, earth work and provn of cable covers / protection pipe etc shall be measured and paid separately under relevant items of BOQ.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting out in any type of soil for laying of cables complete all as specified and directed.
Supply and spread M-sand in trenches for cushioning of cable complete all as specified and directed.(Note: Punned down thickness only shall be measured for the purpose of payment)
Supplying and laying of un-reinforced precast concrete cable cover, class LV, type 1 flat, size 250mm x 150mm x 40mm, ISI marked duly embossed as "ELECTRIC" for cable protection in trenches complete all as specified and directed.
Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed.
Removing surplus excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Material & Labour for cutting of existing hard standing up to 15 cm depth for laying of pipe lines and making good the disturbed surfaces by providing PCC 1:2:4 type B-1 (using 20mm graded aggregate) after laying of pipes lines and returning filling of soil, complete all as specified and directed. Note:- Excavation and earth work below hard standing will be measured and paid under relevant items.
Supply and laying / fixing of 100mm dia bore tubes, 'light grade' galvanized, with all fitting and fixed complete to walls/ poles or laid in trenches/ floors for cable protection complete all as specified and directed.
Supply and laying / fixing of 100 mm dia bore tubes, 'light grade' galvanized, with all fitting and fixed complete to walls/ poles or laid in trenches/ floors for cable protection complete all as specified and directed.
Supply and fixing of on load changeover switch in sheet steel enclosure, 315 Amps, 4 Pole, 415 Volts, 50 Hz complete all as specified and directed.
ROHIT ENTERPRISES
MONA GENERATOR SEVICES PVT. LTD.
M/s JS Constructions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .