Electrical work in connection with Provision of holiday home for staff visiting Prayagraj at Loco colony. Electrical work in connection with Prayagraj Provision of holiday homes at Prayagraj area near Coral club, Balaipur colony. Electrical works in connection with "Replacement of severely deteriorated Relay Hut (RH-2) between NYN-PRYJ including indoor S&T installations". Electrical work in connection with Provision of new Conference hall, PME room & waiting hall on 2nd floor of OPD building of Central Hospital.
ELG-36-2627
ELG-36-2627
Open
6 Months
Prayagraj, Uttar Pradesh
₹0
₹2.3 L
3 Jul 2026
3 Jul 2026
13 Jul 2026
Item Breakup - A-1
Wiring for circuit / sub main wiring along with earth wire Metre with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed PVC conduit as required. 2 x 4 sq. mm+ 1 x 4 sq. mm earth wire. Inspection by-Consignee.
Wiring for circuit / sub main wiring along with earth wire Metre with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed PVC conduit as required. 2 x 6 sq. mm+ 1 x 6 sq. mm earth wire. Inspection by-Consignee.
Wiring for circuit / sub main wiring along with earth wire Metre with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed PVC conduit as required. 2 x 10 sq. mm+ 1 x 10 sq. mm earth wire. Inspection by-Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Wiring for light/power plug with 2x4 sq.mm FRLS PVC Point insulated copper conductor single core cable insurface/recessed medium class PVC conduit, along with 1 No. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. Inspection by- Consignee.
Supply, Erection, Testing and Commissioning of following Numbers 1150.00 Modular Type switch 10 A (1-way) complete in all respect. Inspection by-Consignee.
Supply, Erection, Testing and Commissioning of following Numbers 470.00 Modular type Plug socket outlet 2/3 Pin 10 A complete in all respect. Inspection by-Consignee.
Supply, Erection, Testing and Commissioning of following Numbers 210.00 Modular Type switch 20 A (1-way) complete in all respect. Inspection by-Consignee.
Supply, Erection, Testing and Commissioning of following Numbers 210.00 Modular type Plug socket outlet 5/3 Pin 20 A complete in all respect. Inspection by-Consignee.
Supply and Erection of Modular type switch blanking set to Numbers 170.00 fill the blank space White finished mounting cover plate complete in all respect. Inspection by-Consignee.
Supply and Erection of Junction Box cover POP type Numbers 840.00 complete in all respect including hardware material for fixing. Inspection by- Consignee.
Supply and Erection of white finish single mounting cover Numbers 158.00 plate with base frame suitable 3 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee.
Supply and Erection of white finish single mounting cover Numbers 148.00 plate with base frame suitable 8 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee.
Supply and Erection of white finish single mounting cover Numbers plate with base frame suitable 12 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee.
Supply and Erection of Modular Metal boxes concealed Numbers 158.00 Boards suitable for mounting of 3 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by- Consignee.
Supply and Erection of Modular Metal boxes concealed Numbers 148.00 Boards suitable for mounting of 8 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by- Consignee.
Supply and Erection of Modular Metal boxes concealed Numbers Boards suitable for mounting of 12 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by- Consignee.
Supply and recessing/fixing of PVC Conduit pipe 25 mm Metre (Medium) conforming to IS 9537/ Part III/1983 (Latest version) with accessories, junction box, etc including making chase, plastering/ clamping etc as per technical specifications. Inspection by- Consignee.
Supply of PVC insulated multi stranded copper conductor Metre single core FRLSH cable 2.5 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning. Inspection by-Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply of PVC insulated multi stranded copper conductor Metre single core FRLSH cable 4.0 Sq. mm conforming to IS: 694(latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning. Inspection by-Consignee.
Supply of PVC insulated multi stranded copper conductor Metre single core FRLSH cable 6.0 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning. Inspection by-Consignee.
Supply of PVC insulated multi stranded copper conductor Metre single core HRFR cable 1.5 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for Earth wire as required as per technical specification including connections, testing and commissioning. Inspection by-Consignee.
Supply and Installation of Ceiling rose 3 plate as per IS No. Numbers 1300.00 371/1999 (Latest Version) including connections, Testing and commissioning as per Tech. Specification. Inspection by-Consignee.
Supply, Erection, Testing and Commissioning of following Numbers Modular type step type Electronic Fan Regulator complete in all respect.Inspection by- Consignee.
Fabrication, Supply and Fixing of Fan Hook withclamp duly Numbers painted madeof 50x6 mm MS Flatwith nut bolts suitable to fix on PP shelterbracing angle as required. Inspection by- Consignee.
Supply and Erection of Fan Box cover POP typecomplete in Numbers 110.00 all respect including hardwarematerial for fixing. Inspection by-Consignee.
Termination of LT XLPE cables of various sizes (One Job Job means all 4 cores of cables). Inspection by-Consignee.
Supply and recessing/fixing on surface of 6 SWG GI wire Metre conforming to IS: 280/2006 (Latest Version) for loop earthing as required for earthing of installation as per IE Rule.
Supply and laying of B class, 50 mm dia, GI pipe of for Metre cable riser/road crossing as required and as per relevant technical specification. Inspection by- Consignee.
Collecting, Transporting from SSE/PS/ store to site, laying, Metre testing, and commissioning of above LT cable . Laying direct in ground (Including excavation, sand cushioning, protection brick covering and refilling the trench etc.), direct in RCC/Metal pipes in rod/track crossings and on surface/required in wall/in concrete floor by cutting recessed and finished originally as required as per relevant technical specifications.
Excavation of cable duct by horizontal boring method 1.4 Metre to 2.1 mtr depths from the bottom of sleeper for trench less track crossing and laying of 120 mm outer dia. DWC pipe. The work shall be done as per extent practice and instruction of site engineer. It includes supply of DWC/DHPE pipes conforming to IS : 14930 (Part 2, 2001).( Rex Poly Extrusion or similar make
Supply, erection, testing and commissioning of One phase Numbers distribution board comprising of one no. 32/40 amps DP MCB with 40 A ELCB/RCCB as incoming and 4 nos. 10 amps SP MCB , 4 nos. 20 A SP MCB as outgoing complete with copper bus bars, neutral link and other accessories housed in CRCA sheet enclosure with double door type. Inspection by-Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, Installation, Testing and Commissioning of 1200 Numbers 126.00 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. Inspection by- Consignee.
Supply, fixing, testing, connecting and commissioning of Numbers wall mounted Bracket Fan 400 mm sweep including supply of M.S. fixing clamps & its hardware with flexible copper cable twin twisted size 24/0.20 01 mtr long for each fittings as required. Inspection by-Consignee.
Supply, fixing, testing and commissioning of 250 mm Metre sweep fresh air fan complete and conforming to Explanatory Note. Inspection by-Consignee.
Supply, erection, testing and commissioning of single earth Numbers electrode of 50 mm. dia 4000mm long GI pipe class B complete with earth box with CI cover hinged to CI frame including connection from earth electrode to MDB/SDB/poles/with 8 swg GI wire/strip as per attached drawing. Inspection by-Consignee.
Supply, fixing, testing and commissioning of wall mounted Numbers LT distribution board made up of steel sheet, phosphatised powder painted complete with neutral link,earth point, Din rail and prewired confirming to IS:13032 & 8623:1991 with following items to be fixed in distribution board, confirming to IS:8828 :1996 orlatest, IE rules and site requirement. 4P, MCCB 125 Amps. 10 kA 'C' series= 01 No.(Incoming) DP RCCB (25, 40 Amps., three nos. each) 10 kA 'C' series = 06 Nos.(Outgoing). Inspection by-Consignee.
Supply, fixing, testing and commissioning of wall mounted Numbers LT distribution board made up of steel sheet, phosphatised powder painted complete with neutral link,earth point, Din rail and prewired confirming to IS:13032 & 8623:1991 with following items to be fixed in distribution board, confirming to IS:8828 :1996 orlatest, IE rules and site requirement. 4P, MCCB 125 Amps. 10 kA 'C' series= 01 No.(Incoming) DP RCCB (40 & 63 Amps., two nos. each) 10 kA 'C' series = 04 Nos.(Outgoing). Inspection by-Consignee.
Supply, fixing, testing and commissioning of LED down Numbers 419.00 lighter, housing aluminum die cast, white powder coated and PMMA diffuser having system wattage equal to 15-18 Watt complete with all mounting arrangement, accessories complete of make Phillips, Bajaj, Havells or similar conforming to CEE/NR's spec. No. CEE/NR/121- lect/PS/2018 (Rev- '3') or latest at Tech Spec-III attached & PCEE/NR's spec. No. PCEE/NR/121- Elect/PS/2019 (Rev- '4') at Tech Spec-IV attached or latest. Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, fixing, testing, connecting and commissioning of Numbers 24/36 watt 2x2 LED lights fittings as per IS:10322 , recess LED Fitting 24/36 watt, suitable for surface/ recessed mounting. LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and driver together with parts of distribute light, to position and protect the light source, and to connect the light source to a branch circuit.The light source it self may be an LED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106 (2012). Light Source (LED) in the Luminaries should be of make:- (1):- NICHIA/CREE/ OSRAM/ SEOUL /PHILIPS / LUMILEDS /LEDNIUM. (2):-LEDs to IS:16105(2012). IS: 16108(2012), IEC:62471. 1. Input operating voltage :-105-295 V AC.2:- Normal Voltage-220 VAC. 3. Driver type: constant current driver with short circuit protection. 4.Control of distribution:- Full cut off. 5. Lumens-2880/4320 . 6. Efficiency of driver electronic: > 85%. 7. Colour temperature:4000K. 8.Colour rendering index (CRI):>75. 9. Ingress protection : IP-20. 10.Lumen output: >=120 lumens/ watt @ Max. 350 mA drive current. 11. Power factor:->0.97. 12. Total harmonics distortion (THD):-<20%. 13.Lamp cover :Acrylic cover whichdoes not result in loss of lumens. 14. Finishing: Power coated/Anodized. 15. Secondry optics: poly carbonate reflector/ poly carbonate lens. 16. Construction of housing: extruded aluminum/ CRCA/Pressure die cast aluminum. 17. Mounting: Suitable for surface mounting/ recessed mounting. 18. Certificate:Firm to submit LM80 (In respect of LED used) & LM79 (In respect of luminare used) test certificate from National/International accredited Laboratory and OEM certificate for complience of BIS/IEC. 19. Warranty: Firm to submit warranty certificate for five year along with the supply. All fittings shall be fitted as surface mounting/recessed mounting with twisted twin flexible cord of minimum size 16/0.2 mm copper conductor as per relevant technical specification. Material parameters must remain unchanged during entire warranty period. Inspection by-Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, fixing, testing, connecting andcommissioning of 12 Numbers Watt or above LEDStraight Shape Led Mirror Picture WallLight- Dressing Table Lights | VanityLights for Mirror | Bathroom Lights forWash Basin.20 Inch Wall Spotlight forPainting,Scenery,For Display Art worklight fitting with die cast aluminiumhousing with toughened glass.LEDLuminaries:-(1) A complete LEDlighting unit consisting of alight sourceand driver together with parts ofdistribute lights,to position and protectthe light source, and to connect thelightsource to a branch circuit.The lightsource itself may be an LEDarray andLED module, or an LED lamp.(2):-Supplied LEDluminaries shall confirm toIS:16101 (2012) IS:16106(2012). LightSource (LED) in the Luminaries shouldbe ofmake:- (1):- NICHIA/CREE/OSRAM/ SEOUL/PHILIPS/LUMILEDS/LEDNIUM. (2):-LEDstoIS:16105(2012).IS:16108(2012),IEC:62471.Type LED:-Highpower LED,SMD (Surface Mountingdevice)/COB (Clip on board). 1.Inputoperating voltage :-105-295 V AC. 2:-NormalVoltage-220V AC, 3.Driver type:constant current potted driver withshortcircuit protection. 4. LED life:- >=50000burninghours.5.Depreciation:- 30%max. after 50000burninghours.6.Control of distribution:-Full cut off. 7.Surgeprotection: 4KV. 8.Drive component :Industrial gradeonly.9. Efficiency of driver electronic>; 85%.10. Beamangle:>=140 degree alongwith road and &80> degree acrosstheroad. 11.Colour temperature: 5000- 6500K.12. Colourrendering index(CRI):>75. 13. Ingress protection :IP-66. 14. Lumen output: >;=120lumens/watt. 15. Power factor>;=0.95.16. Total harmonics distortion(THD):-<15%. 17. Lampcover :Toughened glassor UV stablised polycarbonate. 18.Finishing:Power coated /Anodized.19.Secondryoptics :poly carbonatereflector/ poly carbonateslens. 20.Construction of housing:extrudedaluminum/CRCA/Pressure diecastaluminum. 21. Mounting: Suitablefor existing pole/Truss/Lanternmounted.22. Certificate:Firm to submit LM 80 (In respect of LEDused) & LM79(In respectof luminaire used) test certificatefromNational/International accreditedLaboratory and OEM certificate forcompliance of BIS/IEC. 23. Warranty:Firm tosubmit warranty certificate forfive year along with the supply.Allfittings should be embossed/sticker withmanufacturing date and warranty detailsat time of supply.24.The weight offixture should be standard for betterheat resistance of LED PCB. All fittingsshall be fitted with new suitablebend/elbow withclamp and proper nutand bolt and connection with twistedtwinflexible cord of minimum size 16/1mm copper conductor as perrelevanttechnical specification. Materialparameters must remain unchangedduring entire warranty period.Aftercompletion of the works all materials tobe deposited to the concern SSEsstores.Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, connectingandcommissioning of 30 Watt or above LED floodlight fittings as perIS:10322 or latest. LED Luminaries:-(1) A complete LED lighting unitconsisting of alight source and driver together with parts ofdistribute lights, to position and protect the lightsource, and toconnect the light source to abranch circuit. The light source itselfmay be anLED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS:16106(2012) or latest.LightSource(LED) in the Luminaries should beofmake:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/PHILIPS/LUMILEDS/LEDNIUM. (2):- LEDs to IS:16105(2012).IS:16108(2012),IEC:62471 or latest .TypeLED:- Highpower LED,SMD(Surface Mountingdevice)/COB(Clip onboard).1.Input operatingvoltage :-105-295 V AC.2:- NormalVoltage- 220VAC,3.Driver type: constant current driver withshortcircuit protection. 4.LED life:- >50000burninghours.5.Depreciation:- 30% max. after50000 burninghours.6.Control of distribution:-Full cut off. 7.Surgeprotection:4KV.8. Drivecomponent: Industrial grade only.9.Efficiency ofdriver electronic: > 85%.10. Beamangle:>=140degree along with road and >=80 degree acrosstheroad.11.Colour temperature:5000- 6500K.12.Colour renderingindex(CRI):>=75.13.Ingress protection: IP-66. 14.Lumenoutput:>120 lumens/watt. 15.Power factor:->0.95.16.Totalharmonics distortion(THD):-<15%.17.Lamp cover :Toughenedglass or UVstablised poly carbonate.18.Finishing:Powercoated/Anodized.19.Secondry optics: polycarbonate reflector/ polycarbonateslens.20.Construction of housing:extrudedaluminum/CRCA/Pressure diecastaluminum.21.Mounting:Suitable forexistingpole/Truss/Lantern mounted.22.Certificate:Firmto submitLM80(In respect of LED used)&LM79(In respect of luminare used)test certificatefrom National/International accreditedLaboratoryand OEM certificate for compliance of BIS/IEC.23 or latest.Warranty:Firm to submit warranty certificate for five yearalong with the supply. All fittings shall be fitted with newsuitablebend/elbow with suitable size & length of MS Chanel andconnection with twisted twin flexible cord of minimum size 16/1mm copper conductor as per relevant technical specification.Materials parameters must remain unchanged duringentirewarranty period. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
"Supply, replacement, fixing, testing, connectingand Numbers commissioning of 72 Watt or above LEDstreet lights fittings as per IS:10322. LEDLuminaries:-(1) A complete LED lighting unitconsisting of a light source and potted drivertogether with parts of distribute lights,toposition and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array andLED module, or an LED lamp.(2):-Supplied LEDluminaries shall confirm to IS:16101 (2012) IS:16106(2012). Light Source(LED) in theLuminaries should be of make:- (1):-NICHIA/CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS/LEDNIUM. (2):-LEDs to IS:16105(2012).IS:16108(2012), IEC:62471. Type LED:- Highpower LED,SMD(Surface Mountingdevice)/COB(Clip on board). 1.Input operatingvoltage :-105-295 V AC.2:- Normal Voltage-220V AC,3.Driver type: constant current driverwith short circuit protection. 4.LED life:->50000 burning hours. 5.Depreciation:- 30%max.after 50000 burning hours.6.Control ofdistribution:-Full cut off. 7.Surgeprotection:4KV. 8.Drive component :Industrialgrade only.9.Efficiency of driver electronic: >85%. 10.Beam angle:>=140 degree along withroad and >=80 degree across theroad.11.Colour temperature: 5000- 6500K.12.Colour rendering index(CRI):>=75.13.Ingress protection :IP-66.14.Lumen output:>120 lumens/watt.15.Power factor:->0.95.16.Total harmonics distortion(THD):- <15%.17.Lamp cover :Toughened glass or UVstabilised poly carbonate. 18.Finishing:Powercoated/Anodized. 19.Secondry optics:polycarbonate reflector/ poly carbonates lens.20.Construction of housing: extrudedaluminum/ CRCA/Pressure die cast aluminum.21.Mounting :Suitable for existing pole/ Truss/Lantern mounted. 22.Certificate:Firm to submitLM 80(In respect of LED used) & LM79 (Inrespect of luminare used) test certificate fromNational/ International accredited Laboratoryand OEM certificate for compliance of" PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
"Supply, replacement, fixing, testing, connecting and Numbers 330.00 commissioning of energy efficient luminaries complete with all accessries of capacity 18/20 watt, 4 feet length, T8 LED lamps with sutable current control driver circuit ,suitable for surface/recessed mounting.LED Luminaries:- (1) A complete LED lighting unit consisting of a light source and driver together with parts of distribute light,to position and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012).Light Source(LED) in the Luminaries should be of make:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS /LEDNIUM. (2):-LEDs to IS:16105(2012).IS:16108(2012),IEC:62471.1.Input operating voltage :-105-295 V AC.2:-Normal Voltage-220V AC.3.Driver type: constant current driver with short circuit protection(For tube light).4.Control of distribution:-Full cut off.5.Drive component :Industrial grade only .6.Efficiency of driver electronic: > 85% (For tube light).7.Colour temperature:5000-6500K(For tube light).8.Colour rendering index(CRI):>75(For tube light).9.Ingress protection :IP-20.10.Lumen output: >100 lumens/[email protected] drive current(For tube light).11.Power factor:->0.90(For tube light). 12.Total hormonics distrotion(THD):-<20%(For tube light).13.Lamp cover :Acrylic cover which does not result in loss of lumens.14.Finishing:Power coated /Anodized.15.Secondry optics:poly corbonate reflector/ poly carbonate lens.16.Construction of housing: extruded aluminum/CRCA/Pressure die cast aluminum.17.Mounting :Suitable for surface mounting/recessed mounting.18.Certificate:Firm to submit LM80(In respect of LED used)& LM79(In respect of luminare used) test certificate from National/International accredited Laboratory and OEM certificate for complience of BIS/IEC.19.Warranty:Firm to submit warranty certificate for five year along with the supply.All fittings shall be fitted as surface mounting/recessed mounting with twisted twin flexible cord of minimum size 16/0.2 mm copper conductor as per relevant technical specification. Materials prameters must remain unchanged during entire warranty period.. 2x18/20watt.Inspection by- Consignee
"Provision of Geyser points having MCB 16 A S/P with 3/5 Numbers pin 5/15 amps plug points with 1.5 sqmm (22/0.3mm) / 2.5 sqmm (36/0.3mm) PVC insulated single core unsheathed stranded Copper conductor ISI marked in recessed PVC pipe of ISI marked and MS switch box having wall thickness 16 SWG with 3 mm thick phenolic laminated sheet cover including providing and fixing 3/5 pin 5/15 Amps socket outlets and 5/15 Amps piano type switch and earthing the 3rd pin with 16 SWG/(1.5sqmm PVC insulated single core unsheathed stranded Copper conductor) Copper earth wire along with pipe duly clamped as required and as per relevant technical specification. ( 15 AMP) ."
Supply & Fixing and commissioning of 25 Ltrs capacity of Numbers Stationary storage type electric water heater closed/vented type suitable for 240 Volts single phase AC 50 Hzsupply ISI marked to IS:2082/1993(reaffirm 2004). Copper inner container shall be of copper purity 90% minimum with impurities of zinc not exceeding 1%. Stainless steelinner container shall conform to material Outer container shall be made of MS sheet duly pretreated and finished in either White Stove enamel paint or powder coated in white color Storage electric water heater shall be complete in all respect with fittings asper general technical requirements. Inspection by- Consignee.
Supply, fixing, connecting and commissioningof Hot and Numbers cold split AC of capacity 1.5 Ton,Nominal Cooling Capacity (KCal/Hr): 6000suitable for 230 volt, AC 1 Phase, Material forbody of indoor unit: ABS, Min. Room DischargeAir flow (Cum/Hr): 700, Guaranteed CooingCapacity (Min) KCal/Hr: 4275 Operation onecofriendly refrigerant R-32 or R-410a, withwall mounting arrangement, confirming toIS:1391 Part- II with latest amendment up todated Star Rating -5. Inspection by-RITES. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, fixing, connecting and commissioningof 5 KVA Numbers single phase, automatic Voltagecorrector as per IS:8448/1973 and latestamendment up to date ,input voltage(Min)-140 Volt, output voltage -230 Volt +10%with time delay relay. Inspection by-consignee.
Supply, fixing, connecting and commissioningof PVC drain Metre pipe of size 3/4' with split unit.Inspection by-Consignee.
Supply erection, testing & commissioning of basic Earthing Numbers Kit 1set as per RDSO spec. No RDSO/PE/SPEC /PS/0109(REV.0)-2008, Amendment '1' or latest specification. Inspection by- Consignee.
Supply, fixing, testing and commissioning of wall Numbers mounted/recessed LT Double door 4Way distribution board made up of steel sheet, phosphatised powder painted complete with neutral link, earth point, Din rail and prewired with following items to be fixed in distribution board and site requirement. Inspection by-Consignee.
Supply, fixing, testing and commissioning of wall Numbers mounted/recessed LT Double door 6Way distribution board made up of steel sheet, phosphatised powder painted complete with neutral link, earth point, Din rail and prewired with following items to be fixed in distribution board and site requirement. Inspection by-Consignee.
Supply, fixing, testing and commissioning of DP RCBO's 10 Numbers (2P, 30 mA) Amp outgoing confirming to IS: 12640-2,IEC- 61009-1 or latest. Inspection by-Consignee.
Supply, fixing, testing and commissioning of DP RCBO's 16 Numbers (2P, 30 mA) Amp outgoing confirming to IS: 12640-2,IEC- 61009-1 or latest. Inspection by-Consignee.
Supply, fixing, testing and commissioning of DP RCBO's 20 Numbers (2P, 30 mA) Amp outgoing confirming to IS: 12640-2, IEC- 61009-1 or latest. Inspection by-Consignee.
Supply, fixing, testing and commissioning of DP RCBO's 25 Numbers (2P, 30 mA) Amp outgoing confirming to IS: 12640-2, IEC- 61009-1 or latest. Inspection by-Consignee.
Supply, fabricating and installing of G.I. perforated type Metre cables trays with perforation not more than 17.5%) including suspending from ceiling with MS angle, rods connection pieces, (L pieces, T pieces,90/45 degree any other fitting required) G.I. nutbolts, G.I. washers, fasteners etc. complete in all respect as required at site and as per specificationat Tech Spec-I. 150 mm wide, 50mm depth 2 mm thick with protective cover. Inspection by-Consignee.
Design, Supply, fixing, testing and commissioning of Numbers outdoor type front operated double door weather proof feeder pillar having IP 65 protection (MCCB - Incoming & MCCB - Outgoing) comprising with the following MCCB's fixed in it of make Havells, Siemens, L&T, Schneider, Legrand or equivalent conforming to IEC 60947-2 / IS 13947: 2008 & IS 8623:2008 or latest with digital measuring instrument & bus-bar arrangement confirming to PCEE'NR's spec No. PCEE/NR/126-Elect/PS/2019 at Tech Spec-VI and as per IS, IE rules and site requirement. 160A Microprocessor MCCB 4P 36 kA = 01 No. (Incoming) 63A Microprocessor MCCB 4P 36 kA = 04 No. (outgoing).Inspection by- Consignee.
Design, supply, fixing, testing and commissioning of front Numbers operated double door type weather proof feeder pillar feeder (MCCB - Incoming & MCCB - Outgoing) comprising with the following MCCB's fixed in it conforming to IEC 60947-2 / IS 13947: 2008 or latest with digital measuring instrument & bus-bar arrangement confirming to PCEE/NR's spec. No. PCEE/NR/126- Elect/PS/2019 at Tech Spec-V attached or latest and as per IS, IE rules and site requirement. 4P MCCB 250 Amps 36 kA with adjustable thermal & fixed magnetic release = 01 No. (Incoming) 4P MCCB 125Amps 36 kA with adjustable thermal & fixed magnetic release = 02 No. (Outgoing) 4P MCCB 63 Amps 36 kA with adjustable thermal & fixed magnetic release = 04 No. (outgoing). Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Design, supply, fixing, testing and commissioning of front Numbers operateddouble door type weather proof feeder pillar feeder (MCCB -Incoming & MCCB - Outgoing) comprising with the following MCCB's fixed in it conforming to IEC 60947-2 / IS 13947: 2008 or latest withdigital measuring instrument & bus- bar arrangement confirming toPCEE/NR's spec. No. PCEE/NR/126- Elect/PS/2019 at Tech Spec-Vattached or latest and as per IS, IE rules and site requirement. 4PMCCB 250 Amps 36 kA with adjustable thermal & fixed magneticrelease = 01 No. (Incoming) 4P MCCB 125Amps 36 kA withadjustable thermal & fixed magnetic release = 02 No. (Outgoing) 4PMCCB 63 Amps 36 kA with adjustable thermal & fixed magneticrelease = 04 No. (outgoing) Inspection by- Consignee.
Supply, fixing, testing and commissioning of wall mounted Numbers distributionboard (TPN MCB - Incoming & SP MCB - Outgoing), made up of steelsheet, phosphatised power painted complete with neutral link, earth point,Din rail conforming to IS:13032 & 8623 with following items of matchingmake to be fixed in distribution board confirming to IS:8828 :1996 orlatest, IE rules and site requirement. TPN MCB 63 Amps 10kA "C" series =01 Nos. (incoming) SP MCB 6-32Amps 10kA "C" series= 18 Nos.(outgoing). Inspection by- Consignee.
Supply, fixing, connecting and commissioning of Indutrial Numbers type Plug & socket SPN distribution board with 02 pole & earth metal Plug & socket complete with 32A S.P. MCB . Inspection by- Consignee.
Supply, installation, testing and commissioning of 63AMP Numbers MCCB 35KA, 240V, 50HZ with suitable distribution box of IP-65 of size 450 x 300x 170mm. Inspection by- Consignee.
Supply, LTdistributionboard double door typemade upof steel sheet,phosphatisedpowder paintedcomplete withneutral link, earthpoint, Din railand prewiredconfirming toIS:13032& 8623:1991of makeHavells, Siemens, L&T,Schneider,Legrand or equivalentwithfollowing items of matchingmaketo be fixed in distributionboard,confirming to IS:8828 :1996orlatest, IE rules andsiterequirement. 160Amicroprocessor MCCB 4P 36 KA=01 No. (Incoming)63Amicroprocessor MCCB 4P 36 KA=04 Nos. (Outgoing) SP MCB 6-32Amp. 10 KA 'C' series = 12 Nos. (Outgoing).Inspection by-consignee.
Supply of Auto change Over panel forCLS 10KVA 60A/63A Numbers capacity as per RDSO Specification no. TI/SPC/PSI/CLS/0023. Inspection by- Consignee
Erection, Testing commissioning of Autochange Over panel Numbers for CLS 10KVA 60A/63A capacity as per RDSOspecification no.TI/SPC/PSI/CLS/0023.
"Variable Refrigerant flow system"Supply, Installation, Numbers testing and commissioning of modular type variable refrigerant flow air conditioning system suitable for both heating and cooling with Inverter Scroll Compressor suitable for 415 ±10% V for outdoor unit including fully charged with refrigerant R410A suitable to operate at -5° to 52 C ambient temperature to outdoor unit . It shall include anti vibration isolator pad for outdoors unit. The unit shall be complete in all respect as per site requirement. The unit shall have auto phase corrector so that unit can work in case of phase reversal and accumulator should be present in outdoor units to prevent liquid back flow in compressor. 12 HP VRF/VRV OUTDOOR UNIT (Cooling & Heating). Inspection by RITES.
Supply, installation, testing and commissioning of MS Numbers fabricated outdoor unit stand for placing outdoor unit of VRV system. The stand shall be manufactured from MS C channel of minimum 3- 4 mm thick. It shall be finished with enamel paint as per client/architect approval.Inspection by- Consignee.
Supply, fixing, testing and commissioning of 63 A 300 mA Numbers 4 pole RCCB complete with box complete as per IS, IE rules and site requirement. Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
"INDOOR commissioning, Loading, Unloading of the indoor unit. Unit shall be complete in all respect and suitable for 230 ±5% volts and suitable for both heating and cooling option,include wired thermostat having a display showing temperature and control of temperature inside the room. Indoor unit shall include hanging arrangement of the unit with necessary supporting rod, nut & bolts, fastners and accessories for complete installation of Indoor unit. User shall be able to adjust the temperature as per their comfort level requirement. The units shall be compatible with BMS system in open protocol with MODBUS/BAC net. Supply, installation, testing & commissioning of Hi Wall units 2.0 Tr. Inspection by- RITES.
Supply, installation, testing & commissioning of T- joints Numbers and headers etc.Inspection by- Consignee.
Supply & testing of Cordless Remote Controls.Inspection Numbers by- Consignee.
Supply & testing of Cordless receiver for indoor units. Numbers Inspection by- Consignee.
Supply, laying, testing & commissioning of Communication Metre cable (1.5 sqmm x 2 Core).Inspection by- Consignee.
Supply of Refrigerant (R410a) charge to the outdoor unit Kg and connected pipes between outdoor unit and AHU as per site requirement.Inspection by- Consignee.
CONDENSATE DRAIN UPVC PIPE Supply, installation,testing Metre and commissioning of uPVC Pipe, complete withfittings, supports, U trap arrangement, Clean Plug andaccessories for AHU/IDU as per site requirement.25 mm dia(with 9mm Nitrile). Inspection by- Consignee.
CONDENSATE DRAIN UPVC PIPE Supply, installation,testing Metre and commissioning of uPVC Pipe, complete withfittings, supports, U trap arrangement, Clean Plug andaccessories for AHU/IDU as per site requirement. 32 mm dia(with 9mm Nitrile). Inspection by- Consignee.
"CONDENSATE DRAIN UPVC PIPE" Supply, installation, Metre testing and commissioning of uPVC Pipe, complete with fittings, supports, U trap arrangement, Clean Plug and accessories for AHU/IDU as per site requirement. 40 mm dia (with 9mm Nitrile).Inspection by- Consignee.
"REFRIGERANT testingand commissioning of following nominal sizes of interconnecting refrigerant piping duly insulated with AL foiledclosed cell polyethylene foam insulation (XLPE) of 30 (+/-3)kg/m3 density and fire rated Class 1 as per BS 476 Part 7.All the refrigerant pipe in outside exposed area shall beprovided with 26 G aluminium cladding as per siterequirement. The insulation shall be provided withprotective coating, confirming to UL 723 or ASTM E-84. Allpiping inside the room shall be properly supported with MShanger/tie rod. 28.6 mm O.D (wall Thickness-1.0 mm) (insulation : 19 mm). Inspection by- Consignee.
REFRIGERANT PIPING Supplying, laying/ fixing, testingand Metre commissioning of following nominal sizes of interconnecting refrigerant piping duly insulated with AL foiledclosed cell polyethylene foam insulation (XLPE) of 30 (+/-3)kg/m3 density and fire rated Class 1 as per BS 476 Part 7.All the refrigerant pipe in outside exposed area shall beprovided with 26 G aluminium cladding as per siterequirement. The insulation shall be provided withprotective coating, confirming to UL 723 or ASTM E-84. Allpiping inside the room shall be properly supported with MShanger/tie rod. 22.2 mm O.D (wall Thickness-1.0 mm) (insulation : 19 mm). Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
REFRIGERANT PIPING Supplying, laying/ fixing, testingand Metre commissioning of following nominal sizes of interconnecting refrigerant piping duly insulated with AL foiledclosed cell polyethylene foam insulation (XLPE) of 30 (+/-3)kg/m3 density and fire rated Class 1 as per BS 476 Part 7.All the refrigerant pipe in outside exposed area shall beprovided with 26 G aluminium cladding as per siterequirement. The insulation shall be provided withprotective coating, confirming to UL 723 or ASTM E-84. Allpiping inside the room shall be properly supported with MShanger/tie rod. 19.5 mm O.D (wall Thickness-1.0 mm) (insulation : 19 mm). Inspection by- Consignee.
REFRIGERANT PIPING Supplying, laying/ fixing, testingand Metre commissioning of following nominal sizes of interconnecting refrigerant piping duly insulated with AL foiledclosed cell polyethylene foam insulation (XLPE) of 30 (+/-3)kg/m3 density and fire rated Class 1 as per BS 476 Part 7.All the refrigerant pipe in outside exposed area shall beprovided with 26 G aluminium cladding as per siterequirement. The insulation shall be provided withprotective coating, confirming to UL 723 or ASTM E-84. Allpiping inside the room shall be properly supported with MShanger/tie rod. 15.9 mm O.D (wall Thickness-1.0 mm) (insulation : 13 mm). Inspection by- Consignee.
REFRIGERANT PIPING Supplying, laying/ fixing, testingand Metre commissioning of following nominal sizes of interconnecting refrigerant piping duly insulated with AL foiledclosed cell polyethylene foam insulation (XLPE) of 30 (+/-3)kg/m3 density and fire rated Class 1 as per BS 476 Part 7.All the refrigerant pipe in outside exposed area shall beprovided with 26 G aluminium cladding as per siterequirement. The insulation shall be provided withprotective coating, confirming to UL 723 or ASTM E-84. Allpiping inside the room shall be properly supported with MShanger/tie rod. 12.7 mm O.D (wall Thickness-1.0 mm) (insulation : 13 mm). Inspection by- Consignee.
REFRIGERANT PIPING Supplying, laying/ fixing, testingand Metre commissioning of following nominal sizes of interconnecting refrigerant piping duly insulated with AL foiledclosed cell polyethylene foam insulation (XLPE) of 30 (+/-3)kg/m3 density and fire rated Class 1 as per BS 476 Part 7.All the refrigerant pipe in outside exposed area shall beprovided with 26 G aluminium cladding as per siterequirement. The insulation shall be provided withprotective coating, confirming to UL 723 or ASTM E-84. Allpiping inside the room shall be properly supported with MShanger/tie rod. 9.5 mm O.D (wall Thickness-1.0 mm) (insulation : 13 mm). Inspection by- Consignee.
REFRIGERANT PIPING Supplying, laying/ fixing, testingand Metre commissioning of following nominal sizes of interconnecting refrigerant piping duly insulated with AL foiledclosed cell polyethylene foam insulation (XLPE) of 30 (+/-3)kg/m3 density and fire rated Class 1 as per BS 476 Part 7.All the refrigerant pipe in outside exposed area shall beprovided with 26 G aluminium cladding as per siterequirement. The insulation shall be provided withprotective coating, confirming to UL 723 or ASTM E-84. Allpiping inside the room shall be properly supported with MShanger/tie rod. 6.35 mm O.D (wall Thickness-1.0 mm) (insulation : 13 mm). Inspection by- Consignee.
CABLE TRAY FOR REFRIGERANT PIPING Supplying Metre andinstalling of following size of perforated hot dip galvanizedG.I cable tray with perforations joined with connectors,suspended from ceiling with G.I suspenders including boltsand nuts, etc. for carrying refrigerant pipe in outdoorapplication as required. 300 mm width x 75 mm depth x 1.6mm thickness.Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, fixing, testing and commissioning of 4Cx16 Metre sq.mm.size copper armoured cable complete conforming to IS:7098(Part-1 & 2), 1988. Laying, testing and commissioning of LTPVC /XLPE 1.1 KV armored power cable in ground/ underthe road/ under the track/ on pole/ in existing GI pipe/Hume pipe etc. including excavation sand cushioning etc.shall be as per tech specification at Tech Spec-I attached orlatest, IS & IE rule. Note: - All cable connection shall bemade with proper size of crimping socket/ glands etc by thecontractor at his own cost and labour. Road/ floor wherecable is to be laid shall be made good as original by the firmat his own cost and labour to the satisfaction of Railwayrepresentative. The cable shall be fixed on wall/ pole withsuitable size of GI clamps. Inspection by- Consignee.
Supply of PVC insulated flexible copper cable 4Cx2.5 Metre sq.mm. complete as per IS, IE rules.Inspection by- Consignee.
Supply of PVC insulated flexible copper cable 3Cx2.5 Metre sq.mm. complete as per IS, IE rules.Inspection by- Consignee.
Dismantling/ De-commissioning work for 37.44 kW Solar KWp plant installed at Platform no 3/4 (a) Dismantling of GI structure, followed by solar panels ( 37.44 kW capacity), along with DC cables Cable, Cable tray, plumbing, earthing, Inverter, LT Panels and other asset of SPV Plan.
Re-installation of complete 37.44 W Solar plant installed at KWp running Room (a). Installation of RCC structure followed by RCC blocks and solar panel installation, string making & marking, cable dressing & associated welding work on roof ,Installation of Inverter Panels, AC and DC Cable followed by Cable Tray laying.
4 sqmm DC cable- 150 mtr, MC4 connectors (15 pair), 2.5 Job sqmm Earthing cable (1 bundle), plumbing accessories, civil material, lugs, self-screw/ rivets, cage nut for mid & end clamps, saddle. puff sealant, paint & miscellaneous items. Total 11681725.10
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
2026_03_13AdvanceCorrectionSlipNo_111.pdf
ATTACHMENT
Bifurcationofquantity36.pdf
ATTACHMENT
TNDoclatest.pdf
ATTACHMENT
GCC_April-2022_27_04_22.pdf
ATTACHMENT
GCCACS2022CORRECTION.pdf
ATTACHMENT
Likelysourceofsupply.pdf
ATTACHMENT
GCC CORRECTION 2
ATTACHMENT
CTIndianRailwaysStandardGeneralConditionsofContractApril-
ATTACHMENT
CTIndianRailwayStandardGeneralConditionsofContractApril-
ATTACHMENT
CTIndianRailwayStandardGeneralConditionsofContractApril-
ATTACHMENT
GCC CORRECTION 6
ATTACHMENT
2024_05_14ClarificationregardingsubmissionofAnnexure-VofGCC.pdf
ATTACHMENT
Annexure-VA.pdf
ATTACHMENT
AnnxVIB.pdf
ATTACHMENT
ACS_7to10.pdf
ATTACHMENT
2022_12_13RBCE_CE-I-CTIndianRailwaysStandardGeneralConditionsofContractApril2022ACSNo_21.pdf
ATTACHMENT
2023_04_26RBCE_CE-I-CTIndianRailwaysStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_3ACS-31.pdf
ATTACHMENT
2023_08_07RBCE_CE-I-CTIndianRailwayStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_4ACS-4_1.pdf
ATTACHMENT
2023_10_20RBCE_CE-I-CTIndianRailwayStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_5ACS-5_1.pdf
ATTACHMENT
2023_12_21IndianRailwaysStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_6ACS-6_1.pdf
ATTACHMENT
Download all tender documents and submit your bid