Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹73.0 LAccepted-AOC 355 85 GALI NO 16 ASHOK VIHAR PHASE II BHIM GARH KHERI ASHOK VIHAR PHASE II GURGAON GURGAON HARYANA 122001 | GURUGRAM | HARYANA | 122001 | 1 | Accepted-AOC L-1 FIRM | |
| 2 | 2₹74.2 L+₹1.2 L (1.64%)Rejected-Finance | 2 | Rejected-Finance L-3 FIRM | |
| 3 | 3₹77.5 L+₹4.5 L (6.23%)Rejected-Finance | 3 | Rejected-Finance L-3 FIRM |
| Sl No | Description | Qty | Unit | BRITE INDUSTRIES L3 | CAPITAL ENGINEERS L2 | Mark Engineering Inc. L1 |
|---|---|---|---|---|---|---|
| 1.00Supply, installation, testing, commissioning of following modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled outdoor units suitable for cooling and heating having 100% hermetically sealed inverter type rotary/ scroll compressor(s),minimum two compressors(with individual separate PCB) for above 14HP module, microprocessor based controller, top discharge/side discharge type condensing unit(s), with R-410A refrigerant or equivalent, Vibration isolators with suitable masonry foundation work etc. complete as required. To have a better efficiency condenser fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD specification and work even at 50-degree Celsius ambient temperature without tripping. The unit shall be able to deliver 100% of rated capacity up to 39 degree Celsius. The unit shall be suitable to work on 400V +/-10%,3 Phase,50 Hz AC power supply and BMS compatible. The unit shall be filled with first charge of refrigerant and ready for use as required. The condenser should be coated with hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion and reduce the risk of degradation, thereby improving overall performance and durability. The ISEER of the unit shall be as per ECSBC-2024 as below and complete as per CPWD specification, connections and interconnections etc. as required. (The ISEER should not less than 5.6) | ||||||
| 1.10 | Outdoor unit- 14HP | 4 | Nos. | 4,35,000 ₹17,40,000 | 4,68,210 ₹18,72,840 | 4,06,274 ₹16,25,096 Lowest |
| 1.20 | Outdoor unit- 20HP | 1 | No. | 5,65,000 ₹5,65,000 | 6,21,294 ₹6,21,294 | 5,10,000 ₹5,10,000 Lowest |
| 1.30 | Outdoor unit- 16HP | 1 | No. | 4,75,000 ₹4,75,000 Lowest | 4,96,248 ₹4,96,248 | 4,90,000 ₹4,90,000 |
| 2.00Supply, installation, testing, commissioning of following minimum capacity 4 way flow compact VRV/VRF Cassette type indoor ceiling mounted unit equipped with synthetic washable media pre filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolations, corded less remote control and necessary accessories etc., suitable for operation on 230V +/- 10%, 50Hz,single phase AC supply, complete as required. The unit must shut down upon receiving signal from BMS system. The unit shall be capable to adjust air flow as per room requirement automatically. The cooling capacity of indoor unit will be at air inlet conditions of 27-degree C DB and 19-degree C WB temperature. (Make will be same as of outdoor unit) | ||||||
| 2.10 | Compact Cassette type indoor unit 1.5 TR | 24 | Nos. | 58,500 ₹14,04,000 | 47,042 ₹11,29,008 Lowest | 52,500 ₹12,60,000 |
| 3.00Supply, installation, testing, commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cord less remote control, drain pan, necessary accessories etc., suitable for operation on 230V +/- 10%, 50Hz, single phase AC supply, complete as required. The unit shall have force shut down provision in case of fire on receiving signal from BMS system. The cooling capacity of indoor unit will be at air inlet conditions of 27 degree C DB and 19 degree C WB temperature. (Make will be same as of outdoor unit) | ||||||
| 3.10 | High Wall type Indoor unit 2.0 TR | 20 | Nos. | 34,242 ₹6,84,840 | 34,805 ₹6,96,100 | 30,800 ₹6,16,000 Lowest |
| 3.20 | High wall type Indoor unit 1.5 TR | 4 | Nos. | 33,939 ₹1,35,756 | 29,422 ₹1,17,688 | 29,000 ₹1,16,000 Lowest |
| 4.00Laying and fixing one number of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on surface wall as required. | ||||||
Tender Value
₹74.6 L
EMD Value
₹1.5 L
Closing Date
7 Aug 2025, 3:00 pmClosed
CoA CSIR CEERI PILANI
CSIR CEERI PILANI
Provision of air conditioning work for embedded system prototyping lab and Gyrotron lab at CSIR CEERI Pilani Rajasthan
2025_CSIR_243325_1
13-8(173)-2025/EME
Open Tender
Electrical Works
Works
60 days
CSIR CEERI PILANI
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
DIRECTOR CSIR CEERI PILANI
₹1.5 L
1 Sept 2025
1 Aug 2025
8 Aug 2025
1 Aug 2025
7 Aug 2025
1 Aug 2025
Amount
Supply, installation, testing, commissioning of following modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled outdoor units suitable for cooling and heating having 100% hermetically sealed inverter type rotary/ scroll compressor(s),minimum two compressors(with individual separate PCB) for above 14HP module, microprocessor based controller, top discharge/side discharge type condensing unit(s), with R-410A refrigerant or equivalent, Vibration isolators with suitable masonry foundation work etc. complete as required. To have a better efficiency condenser fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD specification and work even at 50-degree Celsius ambient temperature without tripping. The unit shall be able to deliver 100% of rated capacity up to 39 degree Celsius. The unit shall be suitable to work on 400V +/-10%,3 Phase,50 Hz AC power supply and BMS compatible. The unit shall be filled with first charge of refrigerant and ready for use as required. The condenser should be coated with hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion and reduce the risk of degradation, thereby improving overall performance and durability. The ISEER of the unit shall be as per ECSBC-2024 as below and complete as per CPWD specification, connections and interconnections etc. as required. (The ISEER should not less than 5.6)
Outdoor unit- 14HP
Outdoor unit- 20HP
Outdoor unit- 16HP
Supply, installation, testing, commissioning of following minimum capacity 4 way flow compact VRV/VRF Cassette type indoor ceiling mounted unit equipped with synthetic washable media pre filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolations, corded less remote control and necessary accessories etc., suitable for operation on 230V +/- 10%, 50Hz,single phase AC supply, complete as required. The unit must shut down upon receiving signal from BMS system. The unit shall be capable to adjust air flow as per room requirement automatically. The cooling capacity of indoor unit will be at air inlet conditions of 27-degree C DB and 19-degree C WB temperature. (Make will be same as of outdoor unit)
Compact Cassette type indoor unit 1.5 TR
Supply, installation, testing, commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cord less remote control, drain pan, necessary accessories etc., suitable for operation on 230V +/- 10%, 50Hz, single phase AC supply, complete as required. The unit shall have force shut down provision in case of fire on receiving signal from BMS system. The cooling capacity of indoor unit will be at air inlet conditions of 27 degree C DB and 19 degree C WB temperature. (Make will be same as of outdoor unit)
High Wall type Indoor unit 2.0 TR
High wall type Indoor unit 1.5 TR
Laying and fixing one number of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on surface wall as required.
Above 35 Sq.mm and up to 95 Sq.mm
Up to 35 Sq.mm
Laying and fixing one number of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
Above 35 Sq.mm and up to 95 Sq.mm
Supply& making one end termination with heavy duty single compression brass gland SIBG type, copper lugs duly crimped with crimping tool, PVC tape etc. for following size of armored PVC insulated & PVC sheathed copper cable of 1.1 KV grade as required.
3.5core x 50 Sq.mm. copper Cable
3.5core x 25 Sq.mm. copper cable
Providing and fixing 4.00 mm dia. copper earth wire on surface or in recess for loop earthing along with existing surface / UG cable as required.
Supply, Installation, Testing, Commissioning including vaccumization and nitrogen testing of nominal sizes of soft/hard drawn copper refrigerant piping(Thickness greater than or equal 0.8 mm) for VRV/VRF system, complete with fittings, refnets/Y-joints/ branch headers/connection piping kits with suitable ring type hanger supports, jointing/brazing including accessories, insulated with XLPE class-O tubler section/with class-O closed cell elastomeric nitrile rubber tubular sleeves sections of 12/19mm thickness for suction and liquid lines, all accessories as per specification etc. as required:
Supplying and fixing following size powder coated M.S. ‘C’ channel type trays with cover including connectors, bend, tee etc. and fitted on wall/floor/ roof with M.S. fasteners, supports, clamps/MS hanger etc. as required.
250 mm width X 75 mm depth X 1.0mm thickness.
Supply and fixing of following sizes piping drain on wall complete with fittings and clamps/supports etc. The joints shall be properly sealed with rubber-based adhesive to ensure proper bonding. The rate shall include UPVC Coupler, reducer, socket, bend, Tee as required as per the site to connect with the Drain Hopper of IDUs.
25 mm dia. rigid uPVC pipe.
12 mm nylone braided PVC pipe
Supplying and Fixing of following sizes de-rusted, cleaned, primed and duly painted M.S. stand for outdoor units, including Fasteners (Fischer) & Fixtures etc. Complete in all respect.
M.S. stand (14 HP outdoor unit)
M.S. stand (20 HP outdoor unit)
M.S. stand (16HP outdoor unit)
Supply and laying of following sizes of FRLS PVC insulated flexible copper conductor cable of 1.1 KV grade for power supply to indoor unit i/c providing and laying of suitable size PVC conduit where ever required etc. as required.
3C x 1.5 Sq.mm cable
Supply and laying of following size overall shielded Control cum Communication cable in suitable PVC conduits between indoor and outdoor units.
2C x 1.0 Sq.mm shielded cable
Supply of following sizes of 1.1KV grade copper conductor XLPE insulated and PVC sheathed armored cable conforming to IS : 7098 (Part-I) 1988 of as required.
3.5 core x 50 Sq.mm. copper Cable
3.5core x 25 Sq.mm. Copper Cable
CAPITAL ENGINEERS (BID ID -882986)
BRITE INDUSTRIES (BID ID -882523)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .