Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹4.5 LAccepted-AOC | 1 | Accepted-AOC Lowest Bidder | |
| 2 | 2₹4.6 L+₹3,000 (0.66%)Rejected-Finance | 2 | Rejected-Finance Not Lowest Bidder | |
| 3 | 3₹4.9 L+₹28,590 (6.26%)Rejected-Finance NEAR SVN UNIVERSITY NARSINGHPUR ROAD SIRONJA SAUGOR MP 470228 | SAUGOR | SAGAR | MP | 470228 | 3 | Rejected-Finance Not Lowest Bidder | |
| 4 | 4₹5.4 L+₹80,300 (17.6%)Rejected-Finance 1442 1 NANADANPURA BABINA CANTT TEHSIL DISTT JHANSI UP | BABINA | JHANSI | UP | 4 | Rejected-Finance Not Lowest Bidder | |
| 5 | 5₹5.4 L+₹82,278 (18.0%)Rejected-Finance SNEH NAGAR COLONY NEAR ABKARI OFFICE SHIVAJI WARD SAGAR MP 47000 | SAGAR | SAGAR | MP | 47000 | 5 | Rejected-Finance Not Lowest Bidder |
Tender Value
₹6 L
EMD Value
₹12,000
Closing Date
6 Aug 2020, 6:00 pmClosed
SANJAY KUMAR AE CIVIL
AGE I DHANA PIN 470228, DIST SAGAR, MP
REPAIR/REPLACEMENT OF SUBMAIN WIRING/DBS AND FITTINGS AT MD ACCN AT DHANA MIL STATION.
2020_MES_359188_1
8300/DH/18/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGE I DHANA
Please refer Tender documents
7 documents required · 7 mandatory
₹500
AGE I DHANA
₹12,000
Yes
10 Sept 2020
10 Jul 2020
8 Aug 2020
10 Jul 2020
6 Aug 2020
24 Jul 2020
Amount
Taking down carefully UNSV copper/aluminium submain wiring with wooden battens / PVC surface conduit, complete all as specified and directed.
M&L for sub-main wiring with 2 single core, 10 Sqmm PVC insulated, unsheathed, 1100 Volts grade, FRLS, copper multi stranded conductor drawn in and including PVC casing and capping of 32mm size including drawing one run of PVC insulated, unsheathed, 1100 Volts grade, FRLS, copper conductor multi stranded, 10 Sqmm size as continuous earth wire drawn through and connected to main switch/DB and testing on completion, complete all as specified and directed. Note:- 2 runs of main conductor, one run of earth conductor and one run of PVC casing and capping shall be measured as one unit length
M&L for sub-main wiring with 2 single core, 6 Sqmm PVC insulated, unsheathed, 1100 Volts grade, FRLS, copper multi stranded conductor drawn in and including PVC casing and capping of 32mm size including drawing one run of PVC insulated, unsheathed, 1100 Volts grade, FRLS, copper conductor multi stranded, 6 Sqmm size as continuous earth wire drawn through and connected to main switch/DB and testing on completion, complete all as specified and directed. Note:- 2 runs of main conductor, one run of earth conductor and one run of PVC casing and capping shall be measured as one unit length
M&L for sub-main wiring with 2 single core, 4 Sqmm PVC insulated, unsheathed, 1100 Volts grade, FRLS, copper multi stranded conductor drawn in and including PVC casing and capping of 32mm size including drawing one run of PVC insulated, unsheathed, 1100 Volts grade, FRLS, copper conductor multi stranded, 4 Sqmm size as continuous earth wire drawn through and connected to main switch/DB and testing on completion, complete all as specified and directed. Note:- 2 runs of main conductor, one run of earth conductor and one run of PVC casing and capping shall be measured as one unit length
S&F, in repairs, sheet metal distribution board, SPN, 12 way 240 Volt, double door factory made and tested complete, protection class IP-43 suitable for mounting MCBs, isolator with 200 A tinned copper bus bar complete all as specified and directed.
S&F, in repairs, sheet metal distribution board, SPN, 8 way 240 Volt, double door factory made and tested complete, protection class IP-43 suitable for mounting MCBs, isolator with 200 A tinned copper bus bar complete all as specified and directed.
S&F, in repairs, sheet metal distribution board, SPN, 6 way 240 Volt, double door factory made and tested complete, protection class IP-43 suitable for mounting MCBs, isolator with 200 A tinned copper bus bar complete all as specified and directed.
S&F, in repairs, sheet metal distribution board, SPN, 4 way 240 Volt, double door factory made and tested complete, protection class IP-43 suitable for mounting MCBs, isolator with 200 A tinned copper bus bar complete all as specified and directed.
S&F, in repairs, sheet metal distribution board, 3 phase with neutral ( TPN ) of 4 way 415 Volt, double door factory made and tested complete, protection class IP-43 suitable for mounting MCBs, isolator with 200 A tinned copper bus bar complete all as specified and directed.
S&F, in repairs, miniature circuit breakers, type curve ‘B’, 10 KA, Single Pole, 6 to 32 Amps complete all as specified and directed.
S&F, in repair, miniature circuit breakers, Single pole and neutral, type curve ‘C’ 10KA, 40 Amps 230 Volts. complete all as specified and directed.
S&F, in repair, miniature circuit breakers, Single pole and neutral, type curve ‘C’ 10KA, 63 Amps 230 Volts. complete all as specified and directed.
S&F, in repair, miniature circuit breakers, Three pole and neutral, type curve ‘C’ 10KA, 40 Amps, 415Volts. complete all as specified and directed.
S&F, in repair, miniature circuit breakers, Three pole and neutral, type curve ‘C’ 10KA, 63 Amps, 415Volts. complete all as specified and directed.
S&F, in repair, miniature circuit breakers, Three pole and neutral, type curve ‘C’ 10KA, 100 Amps, 415Volts. complete all as specified and directed.
S & F in repair single phase temper proof, digital electric meter with LCD display, AC 230 V, rating 10-60 Amps & with 1 push button. (Measures & displays kWh, kVAh, V,I,PF, frequency, kW, kVA, six months history of Energy & MD in kW & kVA) with Transparent Hinge type Box including making incoming and outgoing connections etc complete. Make:- HPL cat No - SPPB1520110002OC00 or equivalent as approved by AGE(I). Note:- Old meters shall be deposited in MES store Yard
S & F, in repair, Distribution Board Power line VTPN, 4 way, 415 volts, factory made powder coated, double door with neutral and earth link, including 3 pole MCCB 63 Amps rating, 10KA breaking capacity for incoming supply and including 12 Nos single pole MCBs 6 Amp to 32 Amp 'C' series for outgoing supply complete all as specified and directed. Make:- Cat No DSDLVDRBAOFO04 of Standard or equivalent make approved by AGE(I) from the make specified in Appx 'B'.
M&L, in repairs, earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6mm thick buried directly in ground [earth pit not less than 2.25 meter deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized earth wire of 4mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 of MES SSR Part I all as specified and testing on completion including provision of earth lead protected by 15 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work in any type of soil, PCC pit with RCC cover, char coal, salt, funnel etc complete. Note:- Rate quoted by tenderers shall be deemed to include for following provisions;-[i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 M. [ii]. PCC 1:3:6 type C1 using 20mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B1 cover 50x50 cm with 8mm TMT bars @ 10 cm C/C both ways with handles.[iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore [ISI marked] medium grade & copper lugs, charcoal & salt as reqd.[v]. GI protection pipe of size 15 mm bore light grade 7.5m.
NOTE :- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs 9540.00 /- ]
M/S Sai supplier
M/S JAINENDRA KUMAR JAIN
M/S SHIVA TRADERS
shubhanshu traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .