| 1 | L1₹1.1 CrAccepted-AOC 303 GHS 88 SECTOR 20 PANCHKULA 134113 HARYANA | PANCHKULA | HARYANA | 134113 | ₹1.1 Cr | L1 | Accepted-AOC Being lowest bidder |
| 2 | L2₹1.1 CrRejected-AOC 231 JAGGI GARDEN BALDEV NAGAR AMBALA CITY HARYANA 134003 | AMBALA CITY | AMBALA | HARYANA | 134003 | ₹1.1 Cr | L2 | Rejected-AOC Being other than lowest bidder |
| 3 | L3₹1.1 CrRejected-AOC | ₹1.1 Cr | L3 | Rejected-AOC Being other than lowest bidder |
| 4 | L4₹1.2 CrRejected-AOC HOUSE NO 40 CHOTTI BARADARI PART I GARHA ROAD NEAR MEDICAL COLLEGE JALANDHAR PB 144022 | JALANDHAR | JALANDHAR | PUNJAB | 144022 | ₹1.2 Cr | L4 | Rejected-AOC Being other than lowest bidder |
| 5 | L5₹1.2 CrRejected-AOC | ₹1.2 Cr | L5 | Rejected-AOC Being other than lowest bidder |
| Sl No | Description | Qty | Unit | M/S BALWINDER SINGH L3 | R D Bansal L1 | shivrefrigeration L6 | Bairagi Builders L2 | CHOUDHARY ENTERPRISES L5 | UNITED ENGINEERING CORPORATION L4 | SHRI RAMSONS PROJECTS CORPORATION L7 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00STANDBY POWER SUPPLY | ||||||||||
| 2.00 | Supply, installations, commissioning and testing of eco friendly Diesel Engine driven generating set silent type conforming to CPCB IV conditions/ norms, 125 KVA (100 KW) rating as per BS 5514, 04 cylinder inline 4 stroke cycle, water cooled turbo charge at 1500 RPM, 415V (AC 3 Phase, 4 wire system of supply) 50 Hz at 0.8 power factor directly coupled alternator and engine, water cooled, mounted on common base plate of rigid fabricated mild steel frame platform with floor mounted fuel of tank suitable capacity (minimum 12 hours capacity of consumption) and including all excavation, PCC foundation, anti vibration pad, dampers including standard control panel other accessories as per manufacturers design. The generator set should be fitted with integrated acoustic enclosure manufactured by the OEM of the generating set . The generating set and acoustic enclosure shall confirm to emission norms and noise level. The acoustic enclosure shall be type tested and certificate obtained for the type approved from approved agencies listed in government notifications. Specification of DG set shall be as specified and comprising of the fwg:-
Make of OEM :- (i) M/s Koel Green (ii) M/s Sudhir Power ltd
(iii) M/s Greaves Power. | 1 | Eah Job | 15,50,000 ₹15.5 L | 14,80,000 ₹14.8 L | 16,75,000 ₹16.8 L | 17,50,000 ₹17.5 L | 12,98,000 ₹13.0 L | 18,25,000 ₹18.3 L | 17,51,751 ₹17.5 L |
| 3.00(a) Engine (Prime mover):- Diesel engine vertical type of adequate capacity for 125 KVA (100 KW), 04 cylinder inline, 04 stroke cycle, water cooled turbo charged, at 1500 RPM under NTP conditions of BS : 5514, turbo charged water cooled, compression ratio 18.3:1, 12 Volts 120 Ah electric battery start, complete with fly wheel and all standard fittings, fixtures as per manufacturer instructions including suitable engine control panel / dash board with electronic tachometer, lubrication oil, temperature and pressure gauges water temp gauge and frequency (digital type) including safety automatic shut down in case of fault such as high water temp low oil pressure, over speed etc including self starter, alternator, cogged, V belt, fuel tank with first fill of lub oil and coolant (as applicable) etc complete all as specified and directed. Make of Engine :- Kirloskar, Cummins & greaves power (b) Alternator :- Alternator AC, 3 phase 415V, 4 wire rated line current form output 125 KVA, pf 0.8 1500 RPM, confirming to BS 5000 directly coupled with above engine. The alternator shall be brushless type, screen protected, revolving field, self exited, self regulated through an AVR. The alternator has the following features:- (i) + 0.5% voltage regulations (max) in static conditions. (ii) IP 23 protection with insulation class H (iii) Permissible overload of 10% for 01 hours in 12 hours of operation. | ||||||||||
| 4.00(iv) Anti-vibration pads for mounting engine and alternator assembly on the base frame / plate or as recommended / provided by the manufacturer. (c) Base frame made out of structural steel as per manufacturer’s recommended design / specifications. (d) Acoustic Enclosure Provision of an integral type approved/ certified acoustic enclosure. It shall be made of 16 SWG or manufacturer’s standard norms out of CRCA sheet with powder coated finished on outside and provided with non-igniting fire retardant foam as acoustic material of suitable thickness and perforated sheet of stainless steel as per manufacturer’s design. The doors and glass window shall be as per manufacturer’s design. The base frame shall of ISMC. It shall also include the following:- (i) Silencer, suitable exhaust , residential grade silencer to reduce the noise level. (ii) Internal wiring with PVC copper cable (ISI 694 marked) FRLSH in conduit for light and fan point lamp fittings including lamp. | ||||||||||
| 5.00 | Supply ,laying and jointing 95 Sqmm, 3.5 Core cross sectional area Low Tension,1100 V grade, underground XLPE insulated, armoured, heavy duty, electric cable with stranded aluminum conductor laid in trench/passing through GI tubing complete including making both side connections with cable lugs fixed in repair complete all as specified and as directed by Engr-in Charge. ( Note: GI protection pipe and earth work shall be meaured and paid separately.) | 150 | RM | 600 ₹90,000 | 490 ₹73,500 | 750 ₹1.1 L | 600 ₹90,000 | 590 ₹88,500 | 660 ₹99,000 | 691 ₹1.0 L |
| 6.00 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for foundation of pole, laying of cable and getting out complete all as specified. | 28 | Cum | 100 ₹2,800 | 100 ₹2,800 | 200 ₹5,600 | 200 ₹5,600 | 200 ₹5,600 | 160 ₹4,480 | 201 ₹5,628 |
| 7.00 | Returning and filling excavated soil including spreading levelling, watering and well ramming in layers not exceeding 25mm thick each layer complete all as specified and directed | 22 | Cum | 100 ₹2,200 | 20 ₹440 | 100 ₹2,200 | 50 ₹1,100 | 77 ₹1,694 | 60 ₹1,320 | 51 ₹1,122 |
| 8.00 | Removing excavated surplus soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtrs above the starting points complete all as spcified and directed. | 6 | Cum | 100 ₹600 | 30 ₹180 | 100 ₹600 | 90 ₹540 | 148 ₹888 | 60 ₹360 | 91 ₹546 |
| 9.00 | M/L for Sand cushioning for underground cable 8 cm below and 15 cm above the cable with clean dry river sand in trenches including spreading, leveling etc. complete all as directed by Engr-in-Charge.
Note: Punned down thickness 18 cm shall be measured and paid. | 2 | Cum | 400 ₹800 | 450 ₹900 | 900 ₹1,800 | 700 ₹1,400 | 888 ₹1,776 | 550 ₹1,100 | 2,121 ₹4,242 |
| 10.00 | M & L of old size sub class bricks B class for protection of cable laid dry and flat adjacent to each other perpendicular to direction of cable complete all specified and directed. | 0.84 | Per 1000 Nos | 5,000 ₹4,200 | 4,500 ₹3,780 | 1,000 ₹840 | 6,000 ₹5,040 | 5,555 ₹4,666.20 | 5,000 ₹4,200 | 7,771 ₹6,527.64 |
Updated dates
Tender Value
Refer Docs
EMD Value
₹1.9 L
Closing Date
24 Oct 2025, 6:00 pmClosed
CWE AF Chandigarh
HQ CWE AF Chandigarh Pin-160003
SPECIAL REPAIR TO BER EM EQUIPMENTS COOLING APPLIANCES AT VARIOUS LOCATIONS AND PROVN OF ACs IN ANTE ROOM BAR ROOM AND DINING HALL OF OFFICERs MESS AT AF STN CHANDIGARH
2025_MES_729470_1
CWE/AF CHD/CHD/T-10/2025-26
Open Tender
Civil Works
365 days
Chandigarh
As per NIT
8 documents required · 8 mandatory
₹1,000
GE (AF) Chandigarh
₹1.9 L
26 Dec 2025
4 Sept 2025
31 Oct 2025
4 Sept 2025
24 Oct 2025
10 Oct 2025
Amount
STANDBY POWER SUPPLY
Supply, installations, commissioning and testing of eco friendly Diesel Engine driven generating set silent type conforming to CPCB IV conditions/ norms, 125 KVA (100 KW) rating as per BS 5514, 04 cylinder inline 4 stroke cycle, water cooled turbo charge at 1500 RPM, 415V (AC 3 Phase, 4 wire system of supply) 50 Hz at 0.8 power factor directly coupled alternator and engine, water cooled, mounted on common base plate of rigid fabricated mild steel frame platform with floor mounted fuel of tank suitable capacity (minimum 12 hours capacity of consumption) and including all excavation, PCC foundation, anti vibration pad, dampers including standard control panel other accessories as per manufacturers design. The generator set should be fitted with integrated acoustic enclosure manufactured by the OEM of the generating set . The generating set and acoustic enclosure shall confirm to emission norms and noise level. The acoustic enclosure shall be type tested and certificate obtained for the type approved from approved agencies listed in government notifications. Specification of DG set shall be as specified and comprising of the fwg:- Make of OEM :- (i) M/s Koel Green (ii) M/s Sudhir Power ltd (iii) M/s Greaves Power.
(a) Engine (Prime mover):- Diesel engine vertical type of adequate capacity for 125 KVA (100 KW), 04 cylinder inline, 04 stroke cycle, water cooled turbo charged, at 1500 RPM under NTP conditions of BS : 5514, turbo charged water cooled, compression ratio 18.3:1, 12 Volts 120 Ah electric battery start, complete with fly wheel and all standard fittings, fixtures as per manufacturer instructions including suitable engine control panel / dash board with electronic tachometer, lubrication oil, temperature and pressure gauges water temp gauge and frequency (digital type) including safety automatic shut down in case of fault such as high water temp low oil pressure, over speed etc including self starter, alternator, cogged, V belt, fuel tank with first fill of lub oil and coolant (as applicable) etc complete all as specified and directed. Make of Engine :- Kirloskar, Cummins & greaves power (b) Alternator :- Alternator AC, 3 phase 415V, 4 wire rated line current form output 125 KVA, pf 0.8 1500 RPM, confirming to BS 5000 directly coupled with above engine. The alternator shall be brushless type, screen protected, revolving field, self exited, self regulated through an AVR. The alternator has the following features:- (i) + 0.5% voltage regulations (max) in static conditions. (ii) IP 23 protection with insulation class H (iii) Permissible overload of 10% for 01 hours in 12 hours of operation.
(iv) Anti-vibration pads for mounting engine and alternator assembly on the base frame / plate or as recommended / provided by the manufacturer. (c) Base frame made out of structural steel as per manufacturer’s recommended design / specifications. (d) Acoustic Enclosure Provision of an integral type approved/ certified acoustic enclosure. It shall be made of 16 SWG or manufacturer’s standard norms out of CRCA sheet with powder coated finished on outside and provided with non-igniting fire retardant foam as acoustic material of suitable thickness and perforated sheet of stainless steel as per manufacturer’s design. The doors and glass window shall be as per manufacturer’s design. The base frame shall of ISMC. It shall also include the following:- (i) Silencer, suitable exhaust , residential grade silencer to reduce the noise level. (ii) Internal wiring with PVC copper cable (ISI 694 marked) FRLSH in conduit for light and fan point lamp fittings including lamp.
Supply ,laying and jointing 95 Sqmm, 3.5 Core cross sectional area Low Tension,1100 V grade, underground XLPE insulated, armoured, heavy duty, electric cable with stranded aluminum conductor laid in trench/passing through GI tubing complete including making both side connections with cable lugs fixed in repair complete all as specified and as directed by Engr-in Charge. ( Note: GI protection pipe and earth work shall be meaured and paid separately.)
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for foundation of pole, laying of cable and getting out complete all as specified.
Returning and filling excavated soil including spreading levelling, watering and well ramming in layers not exceeding 25mm thick each layer complete all as specified and directed
Removing excavated surplus soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtrs above the starting points complete all as spcified and directed.
M/L for Sand cushioning for underground cable 8 cm below and 15 cm above the cable with clean dry river sand in trenches including spreading, leveling etc. complete all as directed by Engr-in-Charge. Note: Punned down thickness 18 cm shall be measured and paid.
M & L of old size sub class bricks B class for protection of cable laid dry and flat adjacent to each other perpendicular to direction of cable complete all specified and directed.
Supply and laying GI tubing 50mm bore GI tubing light grade with all fitting laid in trenches, fixed to well etc complete all as specified and directed .
Material and labour for earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick burried directly in ground vertically (depth of pit not less than 2.25 m below normal ground level), with top edge of earth plate not less than 1.5 m below normal ground level, earth plate surrounded from all sides by 15cm thick packed alternate layers of charcoal dust and common salt, electrode connections using galvanized iron strip of size 32mmx6mm thick (upto body of equipment) by means of nuts, bolts, check nuts & GI washers, connected to main switch board or main control board or test point, protected by galvanized iron pipe light grade 40mm dia bore, and watering pipe 20 mm bore GI light grade pipe with funnel & wire mesh, including all necessary excavation & earth work, PCC chamber in PCC (1:2:4) type B-1 & RCC cover, all as shown in electrical plate No 3 of MES Schedule Part-I (2009), testing on completion complete all as specified and as directed. Note(s) :- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm. (ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit. (iii) Rate shall include GI strip and protection pipe of length 7.5m, GI pipe beyond 7.5m length required at site shall be measured and paid separately. (iv) Earth resistance should be less than 2 Ohm. In case the test results are not found below 2 Ohm, complete earthing will be redone without any extra cost to Govt.
COOLING APPLIANCES
Supply ,installation ,testing and commissioning split type AC (outdoor and indoor) of capacity 1.5 Ton 5 star rating with EER 3.2 electric driven , single phase, indoor and outdoor unit with coordless remote control and with in built air ionizer and plazma filter for better indoor air quality , necessary suction and discharge copper pipe lines from inner unit to outer units duly insulated including welding, brazing to make leak proof, 15mm or higher size bore PVC pipe of superior quality for dranige of condensed water including suitable stand for mounting unit as per manufacturer's instructions including connection using PVC insulated and sheathed copper conductor cable 2.5 sqmm (nominal area) 3/4 core cable from indoor unit to outdoor unit.with cable of required size upto DB enclosure including taking out old unserviceable split AC any capacity , any loacation and depositing the same to MES store complete all as specified and as directed.
Supply ,installation ,testing and commissioning split type AC (outdoor and indoor) of capacity 2.0 Ton 5 star rating with EER 3.2 electric driven , single phase, indoor and outdoor unit with coordless remote control and with in built air ionizer and plazma filter for better indoor air quality , necessary suction and discharge copper pipe lines from inner unit to outer units duly insulated including welding, brazing to make leak proof, 15mm or higher size bore PVC pipe of superior quality for dranige of condensed water including suitable stand for mounting unit as per manufacturer's instructions including connection using PVC insulated and sheathed copper conductor cable 4 sqmm (nominal area) 3/4 core cable from indoor unit to outdoor unit.with cable of required size upto DB enclosure including taking out old unserviceable split AC any capacity , any loacation and depositing the same to MES store complete all as specified and as directed.
S & F single pole and netural enclouser with two pin and earth plug and socket complete including one single pole MCB 20/25 Amps complete all as specified
Disconnnecting / dismantling old unserviceable AC Plant of Capacity 8.75 TR, alongwith cooling tower and other connected items complete from site (PMS-I) and depositing the same to MES yard including necessary transportation and T&P if required at site complete all as specified and as directed by Engr-in-Charge
CENTRAL AIR CONDITIONING
(i) Design, Supply, Installation, Testing & Comissioning of central AC plant 22 TR comprising Microprocessor based water cooled package unit of nominal capacity minimum 11 TR x 03 units (02 working + one standby) suitable for year round air conditioning to maintain inside conditions DB 23 ± 3 degree C and RH 55 ± 5%, 02 air changes / hour, equipment load 5 KW and occupancy load 6 persons under GE (AF) Chandigarh for outside condition of Air Force Station Chandigarh as per IMD data, Multi circuit, Hermetically sealed Scroll type compressor suitable for operation on R-407/410a refrigerants, with all necessary refrigerant controls, Cooling coils having multi row copper tubes and hydraulically bonded aluminium fins including electrical connection Evaporator blower section made of galvanised steel sheet, statistically and dynamically balanced fan designed for quiet operation, suitable capacity motor for 415 + 5% Volts, 50c/s, 3 Phase AC supply, complete with all accessories such as MS watering pipes, butterfly valve, balancing valve, NRV, pot strainer or y strainer, Ball valve, flow switch, pressure gauge, thermometers, drain pipes complete all as per functional requirements and manufacturing design for the plant to be fully functional with and including the following :-
(a) Refrigerant piping, fittings, valves and accessories to interconnect indoor & outdoor unit and expansion valves. (b) Supply & charging of refrigerant gas to full capacity. (c) Microprocessor based control panel complete with all safety controls and LED display as per manufacturer's design. (d) Refrigerant line accessories comprising of safety valves, angle valve, liquid line indications. (e) Adequately designed PCC foundation/angle iron supports as per manufacturers recommendations for the AC plant components (e.g compressors, motors etc) of the package units as per site requirement including vibration, isolation pads for mounting all equipments on foundation. Notes :- (i) The cost of plain cement concrete foundation for installation of each package unit (2 working simultaneously & 1 stand by) as per OEM/manufacturer's recommentation shall deemed to be included in unit rate quoted.
(ii) The Contractor will submit the OEM's heat load calculation sheet for summer, mansoon, winter alongwith duct layout showing various sections/damper alongwith SLD of air ciruit, condenser water circuit and power/ control circuit drawing for approval of Accepting officer. (iii) The contractor have to get the AC plant designed, supplied, installation, testing and commissioned by any one of the original equipment manufacturers (OEM) namely Blue Star/Voltas/Carrier/Daikin with their own make or with their recommended makes for the components which are not manufactured by the OEM.Any other make whcih are other than OEM or other than OEM recommendation shall not be accepted. Contractor shall submit proper doucmentary evidence of all the components recommended by OEM before procurement action . (iv) The Approval of the Accepting Officer is to be obtained through proper Channel before engaging the OEM by entering into MOU with the OEM.
Supply & fixing monoblock centrifugal type pumping set (2W+1S) suitable for 300 LPM at 20 mtr head for Condenser water circulation of size complete with and including PCC foundation complete all as specfied Make :- Kirloskar / Beacon / KSB.
Supply, installation, testing and commissioning of FRP cooling tower of minimum 30 TR heat rejection capacity with FRP water basin PVC fillings with integral louvers and drift eliminators complete with hot water basin either fitted with spray nozzles or having self rotating sprinklers, statically & dynamically balanced axial flow type fan direct driven or driven through reduction gear box with TEFC induction motor, suction screen, make up quick filling arrangement, over flow and drain connections with necessary valves and suitable inspection ladder, access arrangement for cooling lower in suction interior, installed on MS girders (MS-I Section) fixed in masonry foundation in cement mortar 1:4 and plain cement concrete footing 1;2:4 type B-1 including all accessories, basin fittings, fan, fan motor suitable for 415 Volts supporting structure, anti vibration mounting, 50 Hz power supply having isolator panel with MCB at cooling tower with following technical data complete all as specified and as directed :- (a) Water flow/ tower 125 USGPM (b) Ent water temp 97 deg F (c) Basin water temp 90 deg F Make :- Mihir / Paharpur/ Delta Note :- The cost of concrete foundation / Pedestal strictly as per OEM’s specifications for installation of cooling tower shall deemed to be included in unit rate quoted .
Suppy, jointing and testing of the following nominal sizes Mild steel condenser pipes 'C' class as per IS : 1239 with necessary anti vibration clamps, isolators with and including all fittings, flanges, union etc but excluding valves, strainers, gauges etc cut to required lengths and seamless welding to joints complete all as specified and as directed. (a) 65 mm dia
(b) 50 mm dia
(c) 40 mm dia
(d) 32 mm dia
Supply & fixing MS Fabricated 'Y' strainer flanged type & brass backets of size 65 mm dia complete all as specified
Supply & fixing MS Fabricated 'Y' strainer flanged type & brass backets of size 50 mm dia complete all as specified
Supply & fixing CI Butterfly valve with flange of size 65 mm dia complete all as specified
Supply & fixing CI Butterfly valve with flange of size 50 mm dia complete all as specified
Supply & fixing Gun metal gate / Ball valves of size 20 mm dia complete all as specified.
Supply & fixing CI Non Return valve with flange of size 65 mm dia complete all as specified
Supply & fixing CI Butterfly valve with flange of size 40 mm dia complete all as specified
Supply & fixing dial type pressure gauge with syphon & cock on condenser lines complete all as specified
Supply & fixing dial type industrial thermometer with syphon & cock on condenser lines complete all as specified
supply, fabrication and fixing of GI sheet ducting made of GI sheet of Class-VIII as per IS-277 fabricated as per IS – 655, 24 gauge including supports, nuts & bolts duly insulated with 13mm thick aluminium foil faced XPE foam complete all as specified. Make :- Sail/ Nippo / Loyyed / Bhushan
supply, fabrication and fixing of GI sheet ducting made of GI sheet of Class-VIII as per IS-277 fabricated as per IS – 655, 22 gauge including supports, nuts & bolts duly insulated with 13mm thick aluminium foil faced XPE foam complete all as specified. Make :- Sail/ Nippo / Loyyed / Bhushan
Supply & fixing air Grill / diffusers made of aluminium section powder coated with Volume Control damper complete all as specified.
Supply & fixing return air Grill / diffusers made of aluminium section powder coated without Volume Control damper complete all as specified.
Supply & fixing Fire damper made of GI sheet 18 guage with fuse link complete all as specified.
Supply & fixing fresh air grill with damper made of GI sheet 18 guage with bird screen complete all as specified.
Supply & fixing volume control damper made of GI sheet 18 guage for PAC Units complete all as specified.
Supply, fabrication & fixing double canvas flexible connection fabricted form fire resistant material as per the manufacturer's specification & drawings complete all as specified and directed.
Supply, laying, jointing, commissioning and testing Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 16 Sqmm 4 core copper conductor 1100volts grade cable including both side connection laid under floor , along walls or poles or passing through pipes complete all as specified and as directed.
Supply, laying, jointing, commissioning and testing Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 10 Sqmm 4 core copper conductor 1100volts grade cable including both side connection laid under floor , along walls or poles or passing through pipes complete all as specified and as directed.
Supply, laying, jointing, commissioning and testing Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 4 Sqmm 3 core copper conductor 1100volts grade cable including both side connection laid under floor , along walls or poles or passing through pipes complete all as specified and as directed.
Supply, installation, testing and commissioning, CPRI approved factory made, dust and vermin proof, cubical type LT panel suitable for 3 phase, 415Volts, 35 MVA rupturing capacity, made of 3.15 mm thick CRCA sheet external/ exposed compartment and 2 mm thick internal compartments, superior powder coated conforming to IP-55 including interconnection wiring, indicating lamps , indoor type, free floor standing type, complete with locking arrangement & earth bus bar, the panel shall have compartmentalized arrangement to accommodate one feeder in each compartment, a vertical cable alley of suitable width shall be provided to serve one or two vertical feeder sections, the openings between the busbar chamber and the feeder section seprated with Bakelite sheet minimum 3 mm thick, all the hardware used in fabrication of panel shall be galvanized with zinc passiveness comprising the following complete all as specified and directed:-
Material & labour, earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6.00mm thick, burried directly in ground vertically to a depth not less than 2.25 m below normal ground level, with top edge of the plate not less than 1.5m below normal ground level, earth plate surrounded by 15cm thick and packed alternate layers of charcoal dust and common salt, connected with and including earth lead of GI strip 25X4 mm by means of bolts, nuts, check nuts and washers of galvanized iron or thimbles and other end of the earth lead connected to main switch board and protected by galvanized iron pipe light grade 32 mm bore including watering pipe 20mm bore GI light grade (ISI marked) with funnel and wire mesh, including all necessary excavation and earth work, PCC chamber in plain cement concrete (1:3:6) type C-1 and 80 mm thick pit cover of presast RCC (1:2:4), type B-1 reinforced with XPM of weight not less than 4Kg/Sqm and MS frame etc and all as shown in electrical plate No 3 of MES Sch Part-I (2009), complete all as specified and directed. Note(s) :- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm. (ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit. (iii) Rate shall include GI strip and protection pipe of length 7.5m, GI pipe beyond 7.5m length required at site shall be measured and paid separately. (iv) Earth resistance should be less than 3 Ohm. In case the test results are not found below 3 Ohm, complete earthing will be redone without any extra cost to Govt.
Supply, installation, testing and commissioning of heating system with electric hot water generator suitable capacity for 22 TR plant including 2 row copper hot water coil with aluminium fins with automatic controlled, heating thermostat, ducting, mono block pumps-02 Nos (01Working &1stand by) for hot water generator, C class MS piping, aluminium cladding with 0.5 mm aluminium sheet overlapping on joints and fixed with self tapping screws on hot water piping as per specifications, butterfly valves duly insulated, balancing valves strainer, industrical type pressure gauge with gun metal valves for isolation and necessary fittings, mercury in glass filled industrial thermometers, ball valve duly insulated as per specifications flow switch, control wiring and cabling, civil work complete all as specified and directet
Supply and fix ceiling fans 1200mm sweep with three blades, down rod, accessories ,230V, bushless direct current motor (BLDC) , minimum air delivery 210 CFM with service value 6.00 BEE with and including copper cable 23/0.0076 from ceiling rose to ceiling fan and connecting complete all as specified Makes:- Crompton/Bajaj/Khaitan/Usha/Orient
Supply and fix exhaust fan, steel body AC single Phase 230V , 50 HZ ,copper winding , low noise , 300m sweep with frame and louvers fixed to existing opening in wall with and including copper cable 23/0.0076 from ceiling rose to exhaust fan and connecting complete all as specified Makes:- Crompton/Bajaj/Khaitan/Usha/Orient
Supply and fix electric water heater, storage type steel body with glass lined inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated with all accessories such as safety valve, thermostat, NRV, two Hot water steel wired PVC connections omplete all as specified
EXTERNAL WATER SUPPLY
Supply, installation testing and commissioning of electric drvien centrifugal pump set with bronze impeller having discharge 1140-1160 LPM at 42 meter head including TEFC electric motor of suitable capacity heavy duty copper winding, three phase 415 volts ,50 HZ mounted on common base frame and PCC foundation complete all as specified and as directed
Supply, installation testing and commissioning of electric drvien sumbersible pump set with bronze impellers having discharge 300-350 LPM at 150 meter head including submerisible motor of suitable capacity, heavy duty copper winding three phase 415 volts 50 HZ complete all as specified and as directed .
AIR CONDITIONER (DUCTABLE TYPE)
Supply, installation, errection, testing and commissioning of ductable type air conditioning system of 8.5 TR capacity operating on three phase 415 V, 50 Hz AC supply (outdoor unit) & single phase 230 V 50 Hz AC supply indoor unit, LED display control, with scroll compressor, horizontal discharge direct driven DIDW forward curved centrifugal fan for indoor units (02 Nos) and propeller type fan with horizontal discharge for outdoor unit (01 No), permanent split capacitor type fan motor for indoor and outdoor units with indoor / outdoor units individual remote control with wireless remote, initially fully charged with R-410A refrigerant, condensing unit capable to operate at outside ambient temperature upto 50 degree celcius complete all as specified and directed and comprising of the following:- (a) Wall mounting type outdoor unit 12 HP capacity – 01 No complete with MS section mounting arrangement of suitable size duly painted with two coats of synthetic enamelled paint over a coat of red oxide primer complete. (b) Ductable type indoor unit hanging/fixed to roof slab/ceiling duly supported including refrigerant pipes of size 5/8” for liquid line and 1-1/8” for suction line duly insulated with closed cell nitrile rubber insulation of suitable size as per OEM specifications from outdoor unit to indoor unit complete all as specified and directed. (c) Heavy duty PVC pipeof dia not less than 20 mm duly insulated with closed cell nitrile rubber insulation of suitable size as per OEM specifications for draining out condensed water from indoor units. Notes :- (i) The PVC pipe shall be concealed in walls/ floor to the nearest available / directed drain point outside the building complete all as specified and directed
(d) Control and transmission wiring with PVC insulated round flexible copper conductor cable of size as per OEM specifications between indoor and outdoor laid through and including 20 mm dia non-metallic PVC rigid concealed conduit Note :- (i) Apart from the above items if any other item / materials and any civil / electrical work is required at the site for the smooth functioning of air conditioning system, the cost of the same shall be deemed to be including in the unit rate quoted and no extra payment will be made for the same. Make :- Carrier (Model 40LC010GB DUCTED IDU R4) or equivalent in Blue star / Voltas.
B/R WORKS
Supply and fixing designer UPVC Doors (fix sides) , white profile, white georgian bars, reinforcement size 8x27x33mm & 8x27x32mm , casement Inward sash 60x98mm ,casement reinforcement 50x30mm casement Fly Mullion 60x64mm , casement T Mullion 60x74mm using 8 mm Clear toughened glass , 3D hinges including necessary fixing arrengment to wall with fastners and MS clamp complete all as per manufacturer's instructions and as directed by Engineer in charge. Outer component no. 220100001-W, Outer RI no. S-711TRE11 -1.2MM Coupler no. 220100051-W, 220100016-W, Mullion no. 220100005-W, , Mullion RI No. S-711TRE11-1.2MM or fully compatible no of other manufacturers specified here in after.
Providing and fixing factory made false ceiling of grid size 600x1200mm using 10mm thick Poly Vinyl ceiling board of size 3900 x 300mm fixed to 0.3 mm thick GI frame grid system with suspenders fixed to ceiling with fasteners with primary channel 1200mm c/c & 'C 'section 25x24mm , secoundry/furring section of size 80x50x26mm complete all as specified and directed
Demolition of brickwork / brick masonry, built in cement or cement lime mortar , including all quions, arches, pillars etc, but excluding ashlar facings, dressed stonework and precast concrete articles, complete all as specified and directed.
M&L for Brick work with sub class ‘B’ bricks, straight or curved on plan exceeding 6 metre mean radius in cement mortar (1:6), using old size sub class B bricks, complete all as specified.
Rendering 15 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:6 finished even and fair without using extra cement for building complete all as specified and directed by Engineer-in-Charge.
Preparation of new plastered or unplastered surfaces of walls and applying two coats of Acrylic based distemper over a coat of primer of the same manufacturer complete all as specified and directed by Engineer-in-Charge.
Note: The Total amount of contract will be subject to deduction of credit of Rs. 9800.00 for old Materials becoming contractor's property as per Schedule of Credit here in after.
Bairagi Builders (BID ID -3458437)
M/S BALWINDER SINGH (BID ID -3452955)
UNITED ENGINEERING CORPORATION (BID ID -3458511)
CHOUDHARY ENTERPRISES (BID ID -3458448)
shivrefrigeration (BID ID -3453251)
SHRI RAMSONS PROJECTS CORPORATION (BID ID -3458637)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.61 MB
TenderdocuT10.pdf
Tender Documents • 1.31 MB
BOQ_816639.xls
BOQ • 2.55 MB
Download all tender documents and submit your bid