EE/AED/PWD
Office of the Executive Engineer, PWD, Asansol Electrical Division Bijoy Pal Sarani, Opposite to Polo Ground, Asansol 713304, Paschim Bardhaman.
Electrical Installation work at New Post Netal Ward in Asansol District Hospital, Paschim Barddhaman
2026_WBPWD_1019783_1
WBPWD/EE/AED /eNIQ-53/2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
ASANSOL
Please refer Tender documents.
4 documents required · 4 mandatory
₹19,800
Office of the Executive Engineer, PWD Asansol Elec
24 Mar 2026
9 Mar 2026
23 Mar 2026
9 Mar 2026
20 Mar 2026
14 Mar 2026
13 Mar 2026
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175mmx100mmx65mm inspection box,making earthing attachment, painting the MS box and mending good the damages to original finish Average run 12 mtr.
Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box and mending good the damages to original finish. On Board.
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. 2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC(From TPNDB to SPNDB).
2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC for charging CB.
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. (i) 6 sq mm
(ii) 4 sqmm
(iii) 2.5 sqmm
Supplying and fixing 415V,16-32A per way , double door Horizontal TPN MCB Distribution board (Enclosure (607716)with IP-42/43 protection,with 63A, 4 pole isolator as incomer and SPMCB's ('C' curve,10kA) as outgoing concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Legrand/ABB/Siemens) a) 4 way,,63A FP isolator,12nos. SPMCBs as outgoing
Supplying and fixing double-door SPN MCB Distribution Board(Enclosure (607712)) with IP-42/43 protection, with DP isolators as incomer and SPMCB('C' Curve,10A) as outgoing,fixing at flat iron frame on wall &mending good the damages to original finish; inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.(Make: Legrand/ABB) i) (2+12)Way,with S&F 240V 40Amps DPMCB isolator as incomer and 240V 6-32A SPMCB of Breaking capacity 10KA & C characteristics 12 nos as outgoing 2+12 Way (Legrand/ABB/Siemens)
Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch with indicator & 16A kit-kat flush type fuse (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.
Supply & delivery of XLPE/A Al cable of following size with 2 nos 10 SWG GI wire as ECC.(Make- Havells/Polycab/KEI/Gloster) as per choice of EIC.4Core 35 Sqmm. (From DG panel to Em TPNDB and from Normal Panel To Nornal TPNDB)
Supplying and fixing 415V, 100ATPN SFU with sheet steel enclosure on flat iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (For charging TPNDB)
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :4 core 35 sqmm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials 4 core 35 sqmm.
Laying of 4 core 35 sqmm cable on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting.
Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed.
Laying of 4 core 35 sqmm cable as below, on existing Cable Tray and binding with suitable size GI wire.
Laying of 4 core 35 sqmm cable on wall/surface through existing iron clamp with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting.
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.With out angle iron support. 150x50x1.25mm (18SWG) .
S/Delivery following 250 Volt, 18/20 Watt, 4 Ft. long single LED Tube fittings complete with LED polycarbonate tube lamp having at least 100 lumen/watt and cast iron box type fittings. (Make- Crompton/Philips Master LED)a. Single LED Tube(18/20 Watt)
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
S/F BC LED lamp (B22) as per direction of E.I.C. (Make- Philips/Crompton/Havells)(12watt)
Supplying and delivery of 250 volts, 50Hz, (12”) sweep 1420 R.P.M. heavy duty exhaust fan complete with all accessories (Make-EPC) as per direction of EIC. Exhaust fan(12”)
Supplying and delivery of 250 volts, 50Hz, (9”) sweep 1420 R.P.M. heavy duty exhaust fan complete with all accessories (Make-EPC) as per direction of EIC. Exhaust fan(9”)
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter: (i) 23 cm (9')
Fixing only louver shutter/cowl on wall with necy. bolts & nuts (6 mm dia x 62 mm long) : i)For 23 cm (9") Exhaust fan
ii)For 30 cm (12") Exhaust fan
Supply of 48"ceiling fans complete with all accessories like fan blade,canopy,capacitor etc Model / Cat No. ( Make - USHA /Crompton Greaves ) as per direction of EIC a.1200 mmSweep
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.
Earthing the installation by 2" ( 50 mm) dia ISI (M) GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level & restoring surface duly rammed as per G.S. in morrum soil.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required as per G S.
Connecting the equipments to earth busbar including S & F No.4 SWG GI (Hot Dip) wire of size on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages as per GS.
Excavation of soil for installation of Earth Electrode and filling & ramming. For morrum soil.
S&F of Iron Flat (size 40 mm x 6mm), 2 Ft Long to be fixed on wall by cutting the wall as per requirement and mending good the damages and cable to be fixed by suitable size iron U shape clamp by necessary nut bolt and washer arrengement. as per direction of EIC(For laying of cable through wall)
Dismantling the existing distribution boxes,wiring, Concealed switch board, Concealed type JB,Panel related all acessories light fixtures and fittings etc. and mending good the damages to the original finish by neat cement plaster cover with 1.5mm thick wall putty as existing wall matching as required as per direction of EIC.
Add GST @18% On total from item no 1 to 31.
Add LWC @1% On total from item no 1 to 32.
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.04 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.64 MB
BOQ_2506337.xls
BOQ • 0.42 MB
OID.pdf
Additional Documents • 0.50 MB
2911.pdf
Tender Documents • 0.53 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .