Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.6 LAdmitted-Finance | ₹15.6 L | L1 | Admitted-Finance |
| 2 | L2₹15.8 LAdmitted-Finance PLOT NO 15 JAYASURIYA STREET GANGAI NAGAR KALLIKUPPAM AMBATTUR CHENNAI 600053 | CHENNAI | CHENNAI | TAMIL NADU | 600053 | ₹15.8 L | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Banyan Engineers and Contractors L2 | SHRI AKSHAYA TRADERS L1 |
|---|---|---|---|---|---|
| .10EXTERNAL ELECTRIFICATION | |||||
| 1.00 | M&L for attending any breakdown in LT UG cable by Excavating, Returning filling, Removing and fix the heat shrink cable join kit of 6-16 Sqmm 4 core complete all as specified and as directed. | 1 | EACH JOB | 5,000 ₹5,000 | 5,500 ₹5,500 |
| 2.00 | M&L for attending any breakdown in LT UG cable by Excavating, Returning filling, Removing and fix the heat shrink cable join kit of 25-50 Sqmm 3.5 core complete all as specified and as directed. | 1 | EACH JOB | 6,000 ₹6,000 | 6,500 ₹6,500 |
| 3.00 | M&L for attending any breakdown in LT UG cable by Excavating, Returning filling, Removing and fix the heat shrink cable join kit of 70-120sqmm 3.5 core complete all as specified and as directed. | 1 | EACH JOB | 8,000 ₹8,000 | 8,000 ₹8,000 |
| 4.00 | M&L for attending any breakdown in LT UG cable by Excavating, Returning filling, Removing and fix the heat shrink cable join kit of 150-185sqmm 3.5 core complete all as specified and as directed. | 1 | EACH JOB | 12,000 ₹12,000 | 9,000 ₹9,000 |
| 5.00 | M&L for Painting of LT panel/Feeder pillar any size after cleaning the body surface by rubbing with emery paper to remove existing paint and applying one coat of promer two coat of synthetic enamel paint wring panel name, incoming and outgoing feeder details as specifed and as directed. | 5 | EACH JOB | 3,000 ₹15,000 | 2,500 ₹12,500 |
| 6.00 | Supply and fix heat shrinkable sleeves over bare conductor of LT cable of suitable size as per site after disconnecting cable from terminal box complete all as specifed and as directed. | 2 | RM | 500 ₹1,000 | 100 ₹200 |
| 7.00Supply and lay in trenches/drawn through pipes or in road crossings/ paths/drains/ ducts/ floors/ along poles/ equipments etc., of LT cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric power cable with stranded aluminium conductor, 1100 volts grade confirming to IS-7098 (Part-I) 1988 of following size including connecting up using suitable size aluminium lugs testing and commissioning etc., complete all as specified and as directed. Note : Excavation earth work, sand cushioning and brick protection shall be measured and paid separately under relevant items. | |||||
| 7.01 | LT UG Cable 2 core x 6 Sqmm | 10 | RM | 250 ₹2,500 | 180 ₹1,800 |
| 7.02 | LT UG Cable 2 core x 10 Sqmm | 10 | RM | 320 ₹3,200 | 220 ₹2,200 |
Updated dates
Tender Value
₹16.5 L
EMD Value
₹33,000
Closing Date
16 Mar 2026, 6:00 pmClosed
Garrison Engineer (I) (CG) Chennai
Garrison Engineer (I) (CG), P-16, CGRA Meenambakkam 4th Street NGO Colony, Nanganallur, Chennai 600061
MAINT/REPAIR/REPLACEMENT OF EXTERNAL ELECTRIFICATION, INTERNAL ELECTRIFICATION, COOLING APPLIANCES, EXTERNAL WTER SUPPLY INSTALLATIONS, FIRE FIGHTING SYSTEMS, ROUTINE MAINTENANCE OF SWIMMING POOL AND ALLIED WORKS AT AOR OF AGE B/R (CG) TUTICORIN...
2026_MES_752010_1
8263/E8
Open Tender
Civil Works
273 days
TUTICORIN
As per tender documents
7 documents required · 7 mandatory
₹500
Garrison Engineer (I) (CG)
₹33,000
Yes
23 Mar 2026
11 Feb 2026
18 Mar 2026
11 Feb 2026
16 Mar 2026
25 Feb 2026
11 Feb 2026 - 18 Feb 2026
EXTERNAL ELECTRIFICATION
M&L for attending any breakdown in LT UG cable by Excavating, Returning filling, Removing and fix the heat shrink cable join kit of 6-16 Sqmm 4 core complete all as specified and as directed.
M&L for attending any breakdown in LT UG cable by Excavating, Returning filling, Removing and fix the heat shrink cable join kit of 25-50 Sqmm 3.5 core complete all as specified and as directed.
M&L for attending any breakdown in LT UG cable by Excavating, Returning filling, Removing and fix the heat shrink cable join kit of 70-120sqmm 3.5 core complete all as specified and as directed.
M&L for attending any breakdown in LT UG cable by Excavating, Returning filling, Removing and fix the heat shrink cable join kit of 150-185sqmm 3.5 core complete all as specified and as directed.
M&L for Painting of LT panel/Feeder pillar any size after cleaning the body surface by rubbing with emery paper to remove existing paint and applying one coat of promer two coat of synthetic enamel paint wring panel name, incoming and outgoing feeder details as specifed and as directed.
Supply and fix heat shrinkable sleeves over bare conductor of LT cable of suitable size as per site after disconnecting cable from terminal box complete all as specifed and as directed.
Supply and lay in trenches/drawn through pipes or in road crossings/ paths/drains/ ducts/ floors/ along poles/ equipments etc., of LT cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric power cable with stranded aluminium conductor, 1100 volts grade confirming to IS-7098 (Part-I) 1988 of following size including connecting up using suitable size aluminium lugs testing and commissioning etc., complete all as specified and as directed. Note : Excavation earth work, sand cushioning and brick protection shall be measured and paid separately under relevant items.
LT UG Cable 2 core x 6 Sqmm
LT UG Cable 2 core x 10 Sqmm
LT UG Cable 2 core x 16 Sqmm
LT UG Cable 2 core x 25 Sqmm
LT UG Cable 3.5 core x 70 Sqmm
LT UG Cable 3.5 core x 95 Sqmm
LT UG Cable 3.5 core x 120 Sqmm
LT UG Cable 3.5 core x 150 Sqmm
LT UG Cable 4 core x 6 Sqmm
LT UG Cable 4 core x 10 Sqmm
LT UG Cable 4 core x 16 Sqmm
LT UG Cable 4 core x 25 Sqmm
LT UG Cable 4 core x 35 Sqmm
LT UG Cable 4 core x 50 Sqmm
M&L for replacement of blue silica gel crystal in breather complete as specifed and directed.
Excavating in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for laying of under ground cables, pipes/pipe lines, etc. and the like not exc. 10 Sqm on plan and not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in any type soil complete all as specified and as directed.
Removing excavated soil to a distance not exceeding 50 Metre and depositing where directed at a level not exceeding 1.50 Metre above the starting point complete all as specified and as directed.
Supply, lay / spread in trenches clean dry M - sand for cushioning of cable to the full width of excavated trench, 8cm thick before laying cable and 15cm thick above the cable, gently punned down, stretching and testing of cable on transformer yard etc., complete all as specified and as directed. Note : Punned thickness only will be considered or payment.
Supply and lay kiln burnt sub class 'B' bricks of size 230mmx115mmx75mm of 45Kg/Sq Cm laid flat adjacent to each other, perpendicular to cable with width equal to length in trenches for protection of cable etc., complete all as specified and as directed.
M&L for Painting of transformer after cleaning the body surface of 400KVA/500KVA transformer by rubbing with emery Paper to remove oil stains, dust etc and applying one coat of metal primer and two coat of synthetic enamel paint incl writing incoming/outgoing cable details of transformer/LT Panel capacity all as directed.
M&L for Dehydration/filtration of transformer oil by means of centrifugal filtration plant to achieve the specified dielectric strength of 35 to 40 KV at 2.5 mm gap in existing position of transformer (400KVA / 500 KVA) and including topping up of oil required quantity all as directed.
S&F in replacement of pin type, porcelain, vitrious, white, brown or green insulator including galvanized mild steel spindle, two galvanised iron washers,and galvanised iron nut, min 150 mm hight,100 mm dia for 22KV volt grade complete all as specified and directed.
M&L for Painting of Two pole structure after cleaning the body surface of by rubbing with emery Paper to remove oil stains, dust etc and applying one coat of metal primer and two coat of synthetic enamel paint all as directed.
Supply and fix lightening arrestor HT 22KV 10 KA station class on 2 pole structure all as specified and directed.
Material and labour for provision of earth continuity conductor 32 X 6mm GI stnp with saddles and fixing screws etc. for roof conductors and down conductor buried in ground or drawn in pipe all as specified and directed.
Material and labour for light grade GI pipe 40mm dia for protection of GI strip earth strip all as specified and directed.
Repair to LT panel door hinges by replacing with hinges having lubricating hole by welding as directed.
Maintenance of two pole structure by applying of petroleum jelly on the male and female contactors,cleaning of insulators, restringing of lines, replacement of burnt jumpers, replacement of damaged conductor, tightening of all nut and bolts to avoid any sparking and replacement of earth strip insulator complete all as specified and directed.
Supply and fix in repair MCCB four pole 415 volts 50 Hz , 100 amps, with rupturing capacity 10 KA fixed directly on board/panel/wall including taking down old unserviceable MCCB and taken as credit complete all as specified and as directed.
Supply and fix in repair MCCB four pole 415 volts 50 Hz , 125 amps, with rupturing capacity 10 KA fixed directly on board/panel/wall including taking down old unserviceable MCCB and taken as credit complete all as specified and as directed.
Supply and fix in repair MCCB four pole 415 volts 50 Hz , 160 amps, with rupturing capacity 36 KA fixed directly on board/panel/wall including taking down old unserviceable MCCB and taken as credit complete all as specified and as directed.
Supply and fix in repair MCCB four pole 415 volts 50 Hz, 200 amps, with rupturing capacity 36 KA fixed directly on board/panel/wall including taking down old unserviceable MCCB and taken as credit complete all as specified and as directed.
Supply and fix in repair MCCB four pole 415 volts 50 Hz, 250 amps, with rupturing capacity 36 KA fixed directly on board/panel/wall including taking down old unserviceable MCCB and taken as credit complete all as specified and as directed.
Supply and fixing in repair 415V 10KA 'B' curve miniature circuit breaker (MCB) of four pole 40 to 100 A of current carrying capacity in the DB complete with connection testing and commissioning complete all as specified and as directed.
Supply and fixing in repair 415V 10KA 'B' curve miniature circuit breaker (MCB) of SPN 40 to 63A current carrying capacity in the DB complete with connection testing and commissioning complete all as specified and as directed.
Supply and fixing in repair 415V 10KA 'B' curve miniature circuit breaker (MCB) of SPN 32 A current carrying capacity in the DB complete with connection testing and commissioning complete all as specified and as directed.
Supply and fixing of stainless steel rail MCB channel of standard side inside Distribution box as specified and directed
Supply of Aluminium end terminals/lugs suitable for XLPE conductors of size 6, 10, 16, 25, 35, 50, 70, 95, 120, 185, 300 sqmm (each set of 10 Nos) complete all as specified and as directed.
M&L for servicing and calibration of VCB at CGRA/OTM including relay setting, disconnecting electric connections and taking out busbar.insulator,CTs and measure IR value using 2.5 KV megger,Clean the inner compartment with moisture free using external heater load checking , distribution & proper checking & fixing of nuts & bolts of cable connections, changing of thermostat, if necessary, greasing where ever required include earth testing etc., complete all as specified and as directed. Note: Servicing should be carried out through OEM ( i.e. Schneider) authorised service provider only
M&L for taking down LT Panel door shutter area exc. 1sqm & n. exc 2 sqm and refixing the shutters in same opening properly complete all as specified and as directed.
M&L for shutters of any description area exc. 1sqm & n. exc 2 sqm each resecuring or pivot adjusting without taking down as specified and as directed.
Supply, lay Double walled corrugated High Density Polyethylene pipe (DWC-HDPE pipe) of 120mm and 103 mm as outer dia and inner dia respectively with all bends and angles having corrugated on the outer wall and plain surface on inner wall confirming to IS-14930 Part-I and Part-II complete with necessary HDPE fittings for protection of 1.1 KV Grade under ground cable directly buried in ground at a depth of 60 cm below GL including neceaasry earth work and returning filling of excavated soil and removing surplus earth off premises complete all as specified and as directed.
Supply and fix in replacement of sealed lead acid battery 42Ah 12V suitable for VCB spring charging system including taking down unserviceable battery any type capacity complete all as directed. Make Exide Powersafe plus EP 42-12V SMF or equivalent of Amaron / Luminous
INTERNAL ELECTRIFICATION
M&L for dismantling ceiling fan, remove wornt out bearing, burnt winding and cleaning the slot, rewinding with super enamelled copper wire of suitable size, varnishing heating and insulating icluding fixing of ball bearing/bush complete all as specified.
M&L for dismantling exhaust fan 300mm sweep, remove wornt out bearing , burnt winding and cleaning the slot, rewinding with super enamelled copper wire of suitable size, varnishing heating and insulating icluding fixing of ball bearing/bush complete all as specified.
Supply and fix in replacement of capacitor 2.5 mfd suitable for ceiling fan complete all as specifed and directed.
M&L for dismantling wall mounting motor, remove wornt out bearing, burnt winding and cleaning the slot, rewinding with super enamelled copper wire of suitable size, varnishing heating and insulating icluding fixing of ball bearing/bush complete all as specified.
Taking down carefully storage type water heater (Geyser) of any type and any make upto 50 Litre capacity after disconnecting all electric connection from any height, bringing down to floor descaling the inner container, heating element, base assembly etc. by using diluted hydrochloric acid and cleaning thoroughly, filling the inner container with water and checking and arresting leakage if any, reassembling the geyser after servicing and replacing unserviceable spare parts and refixing including making water connections and testing on completion complete all as specified and directed. Notes: (i) Spare parts like heating element, thermostats, etc., shall be measured and pair separately.
Supply only thermostat automatic cut off with ISI mark suitable to geysers of any range from 20° C to 90° C all as specified and directed.
Supply only phase indicating neon lamp round or rectangular type suitable for single phase 230 volts, 50Hz AC for respective make of the geysers. Note: Set of two lamps containing green and red colour shall be counted as one unit.
M&L for checking of ceiling fan clamps/split pin, rubber bushes,canopy condition and replace the above items if unserviceable to ensure safety hanging of ceiling fans at CGRA qtrs/OTM accn area complete all as specified and directed.
Supply and fix louver suitable exhaust fan 300mm with protection mesh and without shutter to avoid birds entering including taking down unserviceable louvers complete all as specified and directed.
Supply and fix LED light fittings 18W, 230V, 1x1ft square size surface mount min 6000K, 90lumens/watt with suitable integeral electronic drivers in CRCA sheet housing all as per Crompton Cat No.LCTLRN-18-CDL or technocommercially equivalent of other specified makes including connecting up with driver with three core flexible copper conductor cable of suitable size from ceiling rose to fitting and taking down old fittings any type complete all as specified and as directed.
Supply and fix of LED light fittings 18W, 230V, 1x1ft square size recess mount type min 6000K, 90lumens/watt with suitable integeral electronic drivers in CRCA sheet housing all as per Crompton Cat No LCTLSN-18-CDL or technocommercially equivalent of other specified makes including connecting up with driver with three core flexible copper conductor cable of suitable size from ceiling rose to fitting and taking down old fittings any type complete all as specified and as directed.
Supply and fix LED light fittings 24W, 230V, 2x2ft square size recess mount type min 6000K, 90lumens/watt with suitable integeral electronic drivers in CRCA sheet housing all as per Crompton Cat No LCTLRP-24-FO-CDL or technocommercially equivalent of other specified makes including connecting up with driver with three core flexible copper conductor cable of suitable size from ceiling rose to fitting and taking down old fittings any type complete all as specified and as directed.
Supply and fix 4 feet 1 x 20 Watts LED light fitting, basic all purpose surface and wall mounted LED batten with polycarbonate housing with integrated electronic drive all as per Cat No. LUMILINEBS20WLED865 SPCWH of Havells or Light Linear of Crompton or technocommercially equivalent of other specified makes fixed on surfaces of wall or ceiling with necessary hanging/fixing arrangements and connecting of flexible wire twin core from ceiling rose to fitting drawn through and including flexible conduit etc., including taking down old fitting complete all as specified and directed.
Supply and fix in replacement of MCB SP 40Amps, 'C' curve, 10KA complete all as specifed and directed.
Supply and fix in replacement of MCB SPN 40Amps, C curve complete all as specifed and directed.
Material and labour for point wiring complete with two runs of 1.5 Sqmm (for Phase and Neutral) PVC insulated unsheathed multistranded, copper conductor FRLSH cable of 1100V grade conforming to IS - 694 drawn through and including new PVC casing and caping of suitable size with accessories fixed on surfaces of wall / floor and fixed on ceiling/roof etc, including cutting chasing for provision of modular metal flush sunken box of adequate size for mounting modular switches, sockets, regulators etc. and provn of 1.5sqmm PVC insulated unsheathed copper conductor cable of green colour for earth continuity and connecting to common earth dolly etc., complete all as specified for one light/fan point controlled by one switch. Note : (i) The wiring shall be done in proper color coding using red, yellow, blue for phases, black for neutral and green for earth. (ii) Modular metel flush box, frame and cover plate shall be measured and paid separately.
All as per item No.53.00 but wiring for one 3pin socket outlet 5 Amps on independent board.
Material and labour for point wiring complete with two runs of 2.5 Sqmm (for Phase and Neutral) PVC insulated unsheathed multistranded, copper conductor FRLSH cable of 1100V grade conforming to IS - 694 drawn through and including new PVC casing and caping of suitable size with accessories fixed on surfaces of wall / floor and fixed on ceiling/roof etc, including cutting chasing for provision of modular metal flush sunken box of adequate size for mounting modular switches, sockets etc. and provn of 2.5sqmm PVC insulated unsheathed copper conductor cable of green colour for earth continuity and connecting to common earth dolly etc., complete all as specified for one15 Amps power point on independent board. Note : (i) The wiring shall be done in proper color coding using red, yellow, blue for phases, black for neutral and green for earth. (ii) Modular metel flush box, frame and cover plate shall be measured and paid separately.
Material and labour for submain wiring complete with two runs of 4.00 Sqmm single core, multistranded, FRLS PVC insulated unsheathed cable 1100 volts grade with copper conductor, drawn through and including new rigid non metallic PVC conduit medium grade ISI marked 25mm external dia fixed on surfaces of wall / floor and fixed on ceiling/roof etc, with one run of 6.00 Sqmm PVC insulated unsheathed copper conductor cable as earth continuity conductor and connecting to AC metal clad/DBs including taking down existing submain wiring with conduit any type complete all as specified and as directed. Note: Three runs of 6.00 Sqmm multistranded cable one run of PVC conduit shall be considered as one unit length.
S&F Modular switch 6 Amps, single pole,oneway,1 module complete all as specified and as directed
S&F Modular socket outlet combination, 6 A,2/3 pin combined, 2 module, complete all as specified and as directed
S&F Modular switch 1 way 16A, 1 module complete all as specified and as directed
S&F Modular socket outlet combination,16A, 6 pin combined 2 module, complete all as specified and as directed
S&F Modular white cover plate with frame, suitable for 2 module complete all as specified and as directed
S&F Modular white cover plate with frme, suitable for 3 module complete all as specified and as directed
S&F Modular white cover plate with frame, suitable for 4 module complete all as specified and as directed
S&F Modular metal flush box suitable for 1/2 module complete all as specified and as directed
S&F Modular metal flush box suitable for 3 module complete all as specified and as directed
S&F Modular metal flush box suitable for 4 module complete all as specified and as directed
Material and labour for submain wiring complete with two runs of 6.00 Sqmm single core, multistranded, FRLS PVC insulated unsheathed cable 1100 volts grade with copper conductor, drawn through and including new rigid non metallic PVC conduit medium grade ISI marked 25mm external dia fixed on surfaces of wall / floor and fixed on ceiling/roof etc, with one run of 6.00 Sqmm PVC insulated unsheathed copper conductor cable as earth continuity conductor and connecting to AC metal clad/DBs including taking down existing submain wiring with conduit any type complete all as specified and as directed. Note: Three runs of 6.00 Sqmm multistranded cable one run of PVC conduit shall be considered as one unit length.
Supply and Fix in replacement of Call bell ding dong, AC, 240 V, single pole, including taking down old unserviceable calling bell complete all specified and directed.
Supply and Fix in replacement of Bell push, flush type, single pole, 5/6 Amps, AC, 240 volts including taking down old damaged Bell push complete all specified and as directed.
Supply and fix in replacement of Ceiling rose, surface mount type, PVC/ Polycarbonate, with face bakelite 65 x 50mm three terminals, 240 Volt, AC Single phase including taking down old damaged ceiling rose complete all as specified and as directed.
S&F in replacement of switch piano flush button, single pole, one way 5 Amps complete all as specifed and directed.
S&F in replacement of switch socket combination 2 in1, 3 pin, 5 Amps, flush type complete all as specifed and directed.
S&F in replacement of switch socket combination multipurpose, 2 in 1, 3 Pin,5/15A flush type complete all as specifed and directed.
S&F in replacement of stepped type electronic fan regulator flush type socket type complete all as specifed and directed.
M&L for Painting of ceiling fans, in situ with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc. and numbering of ceiling fan of any size complete all as directed.
Supply, fix, connecting and testing factory made, MCB distribution board, (MCB DB), TPN, 4 way, 415 Volts, Vertical type, double door having degree of protection IP 43, flush type made out of 1.2mm thick CRCA sheet metal, Phosphatised, duly powder coated and conforming to IS 8623 with 200 Amps rated copper bus bar with neutral link, earth bar and din rail etc., complete concealed and fixed flush to wall and making good the disturbed surfaces including, disconnecting electric connections, dismantling from position unserviceable DBs complete all as specified and as directed. Note: MCBs will be measured and paid separately.
Supply, fix, connecting and testing factory made, MCB distribution board, (MCB DB), double door, SPN, 12 way, 240 Volts, having degree of protection IP 43, flush type made out of 1.2mm thick CRCA sheet metal, Phosphatised, duly powder coated and conforming to IS 8623 with 200 Amps rated copper bus bar with neutral link, earth bar and din rail etc., complete concealed and fixed flush to wall and making good the disturbed surfaces including, disconnecting electric connections, dismantling from position unserviceable DBs complete all as specified and as directed. Note: MCBs will be measured and paid separately.
Supply and fix 9W Anti-Bac LED bulb with suitable integral electronic drives all as per Crompton Cat No.LED 9W ANTIBAC - CDL or technocommercially equivalent of other specified makes including taking down old CFL bulb complete all as specified and as directed.
Supply and fix in replacement of Modular TV antenna socket outlet as per Anchor Cat No.21157S or technocommercially equivalent of other specified makes complete all as specified and as directed.
Supply and fix in replacement of Modular Telephone socket outlet as per Anchor Cat No.20857S or technocommercially equivalent of other specified makes complete all as specified and as directed.
Supply and fix in repair single phase electronic digital energy meter 5 -30 A inbuilt CT & PT with LCD display suitable for direct measuring including Meter Cupboard with Hinge & Celling arrangement moulded in Engineering Plastic complete all as specified and as directed.
Supply and fix in repair exhaust fan wings (set of 4wings) of suitable size as per site requirement all as specified and directed.
Supply and fix 2 feet 1 x 10 Watts LED light fitting, basic all purpose surface and wall mounted LED batten with polycarbonate housing with integrated electronic drive all as per Cat No.LUMILINEBS10WLED865SPCWH of Havells or technocommercially equivalent of other specified makes fixed on surfaces of wall or ceiling with necessary hanging/fixing arrangements and connecting of flexible wire twin core from ceiling rose to fitting drawn through and including flexible conduit etc., including taking down old fitting complete all as specified and directed.
Supply and fix in repair three phase electronic digital energy meter 10 -60 A inbuilt CT & PT with LCD display suitable for direct measuring including Meter Cupboard with Hinge & Celling arrangement moulded in Engineering Plastic complete all as specified and as directed.
Supply of LED light fittings 5W, 230V, 1ft, wall mount type min 6500K with suitable integral electronic drives all as per Crompton Light Linea 5 W 1 feet or technocommercially equivalent of other specified makes fixed on surfaces of wall or ceiling with necessary hanging/fixing arrangements and connecting of flexible wire twin core from ceiling rose to fitting drawn through and including flexible conduit etc., including taking down old fitting complete all as specified and directed.
Supply and fix in repair/ replacement of new rigid non metallic PVC conduit medium grade ISI marked 25mm external diacomplete all as specified and as directed
Supply and fix in repair/ replacement 18W LED light 4 pin type all as per Philips Cat No. LED PLL 4P 18W/865 2G11 or technocommercially equivalent of other specified makes all as specified and as directed
Supply and fix in repair/ replacement 9W round type recess mounted LED light of diameter 185mm and height of 100mm all as per Philips Cat No.DN195B LED20S-6500 PSU WH S2 or technocommercially equivalent of other specified makes all as specified and as directed
S&F Modular white cover plate with frame, suitable for 1 module complete all as specified and as directed
COOLING APPLIANCES
Taking out the existing unserviceable compressor unit from 1.5 Ton capacity Split type AC and Supply & Fix new hermetically sealed Rotary / Piston type compressor unit suitable for split type AC of capacity 1.5 Ton including pumping out oil, cleaning the refrigeration system with CO2 and charging refrigerant gas (R-22/R-407C/R-410A) providing NRV for further topping up of gas and re fixing in position, testing and commisioning etc., complete all as directed. Note : Freon Gas for charging shall be measured and paid separately.
Taking out the existing unserviceable compressor unit from 2 Ton capacity Split type AC and Supply & Fix new hermetically sealed Rotary / Piston type compressor unit suitable for split type AC of capacity 2 Ton including pumping out oil, cleaning the refrigeration system with CO2 and charging refrigerant gas (R-22/R-407C/R-410A) providing NRV for further topping up of gas and re fixing in position, testing and commisioning etc., complete all as directed. Note : Freon Gas for charging shall be measured and paid separately.
Taking out the existing unserviceable compressor unit from Water cooler 60/120 capacity and Supply & Fix new hermetically sealed Rotary / Piston type compressor unit suitable for water cooler of capacity 60/120 litre including pumping out oil, cleaning the refrigeration system with CO2 and charging refrigerant gas (R-22/R-407C/R-410A) providing NRV for further topping up of gas and re fixing in position, testing and commisioning etc., complete all as directed. Note : Freon Gas for charging shall be measured and paid separately.
Taking out the existing unserviceable compressor unit from Water cooler 40/80 capacity and Supply & Fix new hermetically sealed Rotary / Piston type compressor unit suitable for water cooler of capacity 40/80 litre including pumping out oil, cleaning the refrigeration system with CO2 and charging refrigerant gas (R-22/R-407C/R-410A) providing NRV for further topping up of gas and re fixing in position, testing and commisioning etc., complete all as directed. Note : Freon Gas for charging shall be measured and paid separately.
Supply and Fix in repair starting capacitor of 55 MFD suitable for 1.5 /2.0 Ton AC complete all as specified and as directed.
Supply and Fix in repair starting capacitor of 4 MFD suitable for 1.5 /2.0 Ton AC complete all as specified and as directed.
Supply and Fix in repair/replace air filter same as existing in Indoor unit suitable for 1.5 Ton AC complete all as specified and as directed.
M&L for charging refrigerant gas (R-22/ R-407C / R-410A / R-717/ R-600A/ R744 or other suitable gas) upto maximum capacity for split AC 1.5/2.0 Ton capacity complete all as specified and as directed.
M&L for charging refrigerant gas (R-22/ R-407C / R-410A / R-717/ R-600A/ R744 or other suitable gas) upto maximum capacity for water cooler of 40/80 or 60/120 ltrs capacity complete all as specified and as directed.
Supplly and fix copper pipe of size 5/8 inch dia for any capacity of split AC including taking down unserviceable copper pipe of size 5/8 inch dia complete all as specified and as directed.
Supplly and fix copper pipe of size 1/4 inch dia for Split AC 1.5 Ton capacity including taking down unserviceable copper pipe of size 1/4 inch dia complete all as specified and as directed.
Supplly and fix copper pipe of size 1/2 inch dia for discharge line of Split AC 1.5 Ton capacity including taking down unserviceable copper pipe of size 1/2 inch dia complete all as specified and as directed.
Supply and fix white insulation tape over suction & discharge line of any size for any capacity Split AC from indoor to outdoor for each AC set complete all as specified and directed.
Supply and fix thermal insulation material black rubber sleeve over suction & discharge line of any size for any capacity Split AC from indoor to outdoor for each AC set complete all as specified and directed.
Material and Labour for cleaning, washing with detergent soap solution and servicing, greasing all movale parts of cooling and condensing unit such as cooling coil of blower dip tray, blower motor and condensor compressor etc., and testing complete for Split type Air conditioner of 1.5/2.0 Ton capacity complete all as specified and as directed.
Material and Labour for cleaning of tank, washing with detergent soap solution and servicing, greasing all movale parts of cooling and condensing unit such as cooling coil of blower dip tray, blower motor and condensor compressor etc and testing complete for Water cooler of any capacity complete all as specified and as directed.
Supply and fix in repair/replacement of the PVC drain pipe, flexible, 20mm dia bore complete all as specified and as directed.
Supply and fix in repair/replacement of condensor fan motor unit for Split AC 1.5 Ton Capacity complete all as specified and as directed.
Supply and fix in repair/replacement of new AC remote controller suitable for Split AC of any model of make LG/ Blue Star/ Voltas/ Hitachi/ Carrier/ Samsung as per site requirement and as per directed by the Engineer-in-Charge
M&L for repairing servicing/replace of electronic board of voltage stabilizer 5 KVA capacity complete all as specifed and as directed.
M&L for repairing servicing/replace of electronic board of voltage stabilizer 4 KVA capacity complete all as specifed and as directed.
Supply and fix in repairs with new anti rust powder coated outdoor unit brackets set (stand) suitable for split AC 1.5 Ton capacity including taking down outdoor unit after switching of the circulation gas and removing old brackets and replacing them with new and fixed with new nuts and bolts, refixing the outdoor unit on the new bracketsetc., complete all as specified and as directed.
M&L for painting with two coats of synthetic enamel paint of approved shade /tint including prepartion old steel surfaces and writing the details of MES No. on Split AC outdoor unit complete all as specified and as directed.
M&L for disconnecting copper suction / discharge line, tranposting the indoor unit workshop, dismantling the unit complete water servicng the evaporator unit, roller unit and assembling the unit refixing and connecting the copper pipe from outdoor unit testing complete all as specifed and as directed.
M&L for transporting of water cooler of any capacity to work shop and carry out body tinkering work replacing deteriorated Mild steel bottom/side poriton as existing size and painting with two coats of sythetic enamel paint of approved tint over a coat of red oxide primer including writing SM/MES number etc., complete all as specified and as directed.
Material and Labour for dismantling and disconnecting carefully the existing Split AC /Window AC of any capacity after disconnecting the copper pipe and electrical connection, disconnecting the indoor and outdoor units complete, Shifting to and install at new location by fixing the indoor and outdoor units and making electric and copper pipe connection including top up refrigerant gas testing and commisioning etc., complete all as specified and as directed. Note : The unit rat quoted is deemed to include the cost of Refrigerant gas for top up.
Material and labour for submain wiring complete with two runs of 4.00 Sqmm single core, multistranded, FR PVC insulated unsheathed cable 1100 volts grade with copper conductor, drawn through and including new PVC casing and caping of suitable size with accessories fixed on surfaces of wall / floor and fixed on ceiling/roof etc, with one run of 4.00 Sqmm PVC insulated unsheathed copper conductor cable as earth continuity conductor and connecting to common earth dolly including taking down existing submain wiring with conduit any type complete all as specified and as directed. Note: Three runs of 4.00 Sqmm multistranded cable one run of PVC casing and caping shall be considered as one unit length.
Supply and Fix in replacement of PVC insulated sheated 3-core copper cable 2.5 Sqmm size complete all as specified and as directed.
Supply and fix in repair / replacement of electronic PCB board from Indoor unit of Split AC of any capacity complete all as specifed and as directed.
Supply and fix in repair roller motor unit from Indoor unit of Split AC of any capacity complete all as specifed and as directed.
Supply and fix in repair copper coil for split AC 1.50 /2.00 Ton capacity complete all as specifed and as directed.
Supply and fix in replace of fan blade of suitable size for 1.5/2.0 ton capacity of split type AC complete all as specified and directed
Material and labour for taking down unserviceable items and supply and fix new items of the following for refrigerators of capacity 250 Litres including testing and commissioning etc., complete all as specified and as directed:-
Relay unit
Thermostat assembly
Running Capacitor 10 MFD
Material and labour for taking down unserviceable items and supply and fix new items of the following for deep freezer of capacity 200 Litres including testing and commissioning etc., complete all as specified and as directed.:-
Relay unit
Thermostat assembly
EXTERNAL WATER SUPPLY
Material and Labour for 3-layer PP-R Polypropylene random copolymer) pipes of size 32mm (outer dia), SDR 7.4 & PN 16, outer UV stablized and inner antimicrobial, ISI Marked, conforming to IS-1580, fusion welded having thermal stability for hot and cold water supply including all PP-R plain & brass threaded polypropylene random fittings and accessories laid in trenches etc., complete all as specified and as directed .
Material and Labour for 3-layer PP-R Polypropylene random copolymer) pipes of size 50mm (outer dia), SDR 7.4 & PN 16, outer UV stablized and inner antimicrobial, ISI Marked, conforming to IS-1580, fusion welded having thermal stability for hot and cold water supply including all PP-R plain & brass threaded polypropylene random fittings and accessories laid in trenches etc., complete all as specified and as directed .
Supply and fix in repairs PP-R Ball valves (brass insert) suitable for 32mm outer dia of PP-R pipes complete all as specified and as directed.
Supply and fix in repairs PP-R Ball valves (brass insert) suitable for 50mm outer dia of PP-R pipes complete all as specified and as directed.
Supply and fix in repairs PP-R Gate valves (brass insert) of size suitable for 63mm outer dia of PP-R pipes complete all as specified and as directed.
Supply and fix in repairs CPVC Brass Elbow for fixing with 50mm outer dia CPVC pipes complete all as specified and as directed.
Supply and fix in repairs CPVC Brass Tee for fixing with 50mm outer dia CPVC pipes complete all as specified and as directed.
Supply and fix in repairs CPVC Male Brass Threaded Adaptor (MTA/ MBTA) for fixing with 50mm outer dia CPVC pipes complete all as specified and as directed.
Supply and fix in repairs CPVC Female Brass Threaded Adaptor (FTA/ FBTA) for fixing with 50mm outer dia CPVC pipes complete all as specified and as directed.
Supply and fix in repairs CPVC UNION of size for fixing with 50mm outer dia CPVC pipes complete all as specified and as directed.
Supply and fix in repairs CPVC Flange for fixing with 50mm outer dia CPVC pipes complete all as specified and as directed.
Supply and fix in repair/ replacement 25mm dia bore forged brass ball valve (Screwed) with necessary fixing arrangements all as per Art No.1008 B of Zoloto or equivalent of other specified makes including removing old one all as specified and as directed.
Supply and fix in repair/ replacement 40mm dia bore forged brass ball valve (Screwed) with necessary fixing arrangements all as per Art No.1008 B of Zoloto or equivalent of other specified makes including removing old one all as specified and as directed.
Supply and fix in repair/ replacement 50mm dia bore forged brass ball valve (Screwed) with necessary fixing arrangements all as per Art No.1008 B of Zoloto or equivalent of other specified makes including removing old one all as specified and as directed.
Material and labour for Disconnecting and removing the existing monoblock pumpset of capacity 5HP, any make from the installed position by putting dummy plate to suction and delivery shifting to civil work shop for carrying out repair / overhauling including removing the burnt out windings and rewinding the same with suitable super enameled copper conductor, varnishing., removing, replacing the worn out bushes/ bearing and re-assembling the pumpset, reconditioning, painting the pumpset and bringing back after repair, refixing, testing, commissioning etc., complete all as specified and directed.
Material and labour for Disconnecting and removing the existing monoblock pumpset of capacity 3HP, any make from the installed position by putting dummy plate to suction and delivery shifting to civil work shop for carrying out repair / overhauling including removing the burnt out windings and rewinding the same with suitable super enameled copper conductor, varnishing., removing, replacing the worn out bushes/ bearing and re-assembling the pumpset, reconditioning, painting the pumpset and bringing back after repair, refixing, testing, commissioning etc., complete all as specified and directed.
Material and labour for Disconnecting and removing the existing submersible pumpset of capacity upto 7.5HP, any make from the installed position by putting dummy plate to suction and delivery shifting to civil work shop for carrying out repair / overhauling including removing the burnt out windings and rewinding the same with suitable super enameled copper conductor, varnishing., removing, replacing the worn out bushes/ bearing and re-assembling the pumpset, reconditioning, painting the pumpset and bringing back after repair, refixing, testing, commissioning etc., complete all as specified and directed.
Supply and Fix in repair/ replacement Gun metal Foot valve 100 mm inlcuding removing old one complete all as specified and directed.
Supply and Fix in repair/ replacement Gun metal Foot valve 80 mm inlcuding removing old one complete all as specified and directed.
Supply and fix DOL starter 3 phase 440 volts with relay range upto 16 amps suitable for 5/7.5HP pumpset including taking down the existing unserviceable one complete all as specified and directed.
Material and labour for periodical servicing of RO plant of capacity 25 litres by removing the filters and cleaning, refixing to ensure proper flow of treated water complete and replacing spares and filters any type if required complete all as specifed and as directed. Note : (i) Spares will be measured and paid seperately as supply only. (ii) Each plant to be serviced every six month interval period.
Material and labour for periodical servicing of RO plant of capacity 50 litres by removing the filters and cleaning, refixing to ensure proper flow of treated water complete and replacing spares and filters any type if required complete all as specifed and as directed. Note : (i) Spares will be measured and paid seperately as supply only. (ii) Each plant to be serviced every six month interval period.
Supply only in repair/ replacement Sediment filter suitable for RO plant of capacity 25 litres.
Supply only in repair/ replacement Activated carbon filter for RO plant of capacity 25 litres.
Supply only in repair/ replacement RO membrane min 80GPD for RO plant of capacity 25 litres.
Supply only in repair/ replacement Post carbon filter suitable for RO plant of capacity 25 litres.
Supply only in repair/ replacement Sediment filter suitable for RO plant of capacity 50 litres.
Supply only in repair/ replacement Activated carbon filter suitable for RO plant of capacity 50 litres.
Supply only in repair/ replacement RO membrane min 100GPD suitable for RO plant of capacity 50 litres.
Supply only in repair/ replacement Post carbon filter suitable for RO plant of capacity 50 litres.
Supply and fix in repair/ replacement Booster pump min flow rate 1.5LPM,140 PSI out DC 24/48V operation complete incl taking down u/s pump from RO plant complete all as specified and as directed.
Supply and fix in repair/ replacement of 48V adapter for RO plant of any capacity complete all as specified and directed
Supply and fix in repair/ replacement of 48V solenoid valve for RO plant of any capacity complete all as specified and directed
Supply and fix in repair/ replacement of membrane housing for RO plant of any capacity complete all as specified and directed
Supply and fix in repair/ replacement Filter housing (10 inch) for RO plant of any capacity complete all as specified and directed
Supply and fix in repair/ replacement Filter housing (20 inch) for RO plant of any capacity complete all as specified and directed
Material and labour for preparation old painted surface of pump motor coping guard MS common case farein and painting with two coats synthetic enamel paint of approved of quality and shade as specified below for any capacity Motor and pump - Smoke grey colour Coupling gaurd and grill post - Office red colour
Supply and fix in repair/ replacement of pressure gauge cum discharge meter for pump of any capacity all as specified and as directed.
Supply and fixing in repairs/replacement of old water level indicator scale all as specified and as directed.
Supply and fix Galvanised Iron (GI) water tubing heavy class/ grade 50mm bore conforming to IS specifications and ISI marked with screwed socket joint together with all fittings such as bends, tees, unions, elbows, connecting pieces, backnuts, caps plugs, couplings, sockets etc., laid in trenches/ open/ fixed on walls including testing after laying complete all as specified and as directed.
Supply and fix in repairs Cast Iron specials and fittings such as bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc) tee pieces, single branch. "Y junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs conforming to IS 13382:2004 suitable for CI pipes of flanged/socket ends of sizes up to 150 mm bore complete all as specified and directed.
Supply & Fix in repairs CI fittings like Connecting pieces one end flanged and other socket or spigot and bell mouth pieces one end flanged other end tapering as bell mouth upto 150m bore complete all as specified and directed.
Material and labour for Lead wool joint for cast iron pipe (spigot and socket pipes) and fittings of 100mm bore and testing after completion all as specified and directed .
Supply and lay Cast Iron pipes with flanged ends, centrifugally cast, class B, ISI maked in any length laid in trenches or on supports including making alteration in existing /new pipe line for insertion of new pipe if necessary of size 50mm bore complete all as specified and as directed :- Note :- Accessories and lead joints shall be measured and paid seperately.
Supply and lay Cast Iron pipes with flanged ends, centrifugally cast, class B, ISI maked in any length laid in trenches or on supports including making alteration in existing /new pipe line for insertion of new pipe if necessary of size 80mm bore complete all as specified and as directed :- Note :- Accessories and lead joints shall be measured and paid seperately.
Supply and lay Cast Iron pipes with flanged ends, centrifugally cast, class B, ISI maked in any length laid in trenches or on supports including making alteration in existing /new pipe line for insertion of new pipe if necessary of size 100mm bore complete all as specified and as directed :- Note :- Accessories and lead joints shall be measured and paid seperately.
Supply and fix in repairs Cast Iron Bends,( any type , radius and angle) tapers any type (straight , bend, increasing, decreasing or double socket etc) Tee Pieces single branch. "y" Junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs of bore up to 100 mm bore complete all as specified and directed.
Supply and fix in repairs Cast Iron Bends, Tapers, Tee pieces (single & double branch) any type and angle/radius and straight connecting pieces suitable for CI pipes and fitting of flanged ends of sizes up to 100 mm bore complete all as specified and directed.
ROUTINE MAINTENANCE OF SWIMMING POOL
Material and labour for Cleaning the internal surface and drain channels of Swimming pool of 8,00,000 Ltrs capacity by scrapping/brushing and removing all silt, dust, algae etc., from walls and floor including removing blockage of inlet on daily basis and pumping out of entire water from swimming pool at an interval as directed by Engineer-in-Charge. After blocking the all inlets with dry cloth or other suitable arrangement and taking out all accumulated silt/spills etc., from floor and walls of swimming pool completely and depositing at location directed by Engineer-in-Charge, scrubbing and removing the scaling deposit from the inner surface of the pool and washing properly with bleaching powder or with suitable chemicals on inner side and floor surfaces, applying joint filler material in tile joints in vertical and floor surface as per the requirements including writing of date of cleaning with white paint on block painted surface at one place of swimming pool and applying chemicals for treatment of water to keep the swimming pool water free from fungus and bacteria complete all as specified and as directed.
Material and labour for Cleaning the internal surface and drain channels of Diving pool of 1,25,000 Ltrs capacity by scrapping / brushing and removing all silt, dust, algae etc., from walls and floor including removing blockage of inlet on daily basis and pumping out of entire water from diving pool at an interval as directed by Engineer-in-Charge. After blocking the all inlets with dry cloth or other suitable arrangement and taking out all accumulated silt/spills etc., from floor and walls of diving pool completely and depositing at location directed by Engineer-in-Charge, scrubbing and removing the scaling deposit from the inner surface of the pool and washing properly with bleaching powder or with suitable chemicals on inner side and floor surfaces, applying joint filler material in tile joints in vertical and floor surface as per the requirements including writing of date of cleaning with white paint on block painted surface at one place of diving pool and applying chemicals for treatment of water to keep the diving pool water free from fungus and bacteria complete all as specified and as directed.
Supply only Chlorine in the form of TCCA-90 (Trichloroisocyanuric Acid) granular (1st quality) used as a disinfecting agent in swimming pools in achieving sparkling clean and clear water. Purity of 99% to provides long-term effects throughout the month in keeping swimming pools free from bacteria and algae, With no side-effects on skin, hair and eye etc. complete all as specified and as direccted. Make/Manufacturer: Keshav Hichem Pvt Ltd / Gem Chemicals / Triveni Chemicals
Supply only Alum gel (1st quality) for "flocculent" agent which attracts dirt particles, phosphates, pathogens, and other undesirable contaminants, causing them to clump together to easily vacuum them out of pool.
Supply only copper sulphate (1st quality)
Supply only sodium carbonate - Soda Ash (1st quality) to raise the pH of pool water as per the site and water requirement.
Supply only chlorine test solution of 20ml each
Supply only pH test solution of 20ml each
FIRE FIGHTING SYSTEM MAINTENANCE WORKS
Supply, install, testing and commissioning of manual call point including taking down existing one complete all as specified and as directed.
Supply, install, testing and commissioning of 12V 7Ah battery for Manual Fire alarm control panel including taking down existing battery complete all as specified and as directed.
Supply, install, testing and commissioning of Manual Fire alarm control panel including taking down the existing one complete all as specified and as directed.
Supply and fix Fire Alarm sounders / hooters, ABS body, 24V DC, for atleast 50 minutes with sound level 65 db to 120 db measured at 1.5 Mtr with sound output variation of + 5 DB, 500 mts range including taking down the existing one complete all as specified and as directed.
Supply, fix and testing first aid hose reel drum with MS construction and spray painted in post office red conforming to IS 884 with 20 mm dia and 30 metre length water hose thermoplastic confirming to IS-5132 mounted suitably to swing upto 180 degrees etc., including taking down the existing one complete all as specified and as directed.
Supply and fix in repairs red plastic jet/ spray hose reel nozzle suitable for instaneous connection to interconnect house pipe coupling as required etc., including taking down the existing one complete all as specified and as directed
Supply and Fix Gun metal globe or gate valve of size 25mm bore confirming to IS 778-1984 with brass spindle and iron wheel head at the top screwed both ends for GI pipe including all fittings / fixtures like nipple, union etc. complete all as specified and as directed
Taking down existing oscilationg First aid hose reel drum, swinging type from wall and fixing the same with all necessary wall bracket nuts and bolts etc., complete all as specified and as directed.
Material and labour for Cutting of broken fire fighting hose reel and fixing back with new hose, clamps and connectors without any leak complete all as specified and directed.
Material and labour for Refilling of CO2 based Fire extinguisher of 3 to 4.5 kgs capacity by a licensed and certified professional complete all as specified and directed.
Material and labour for Refilling of ABC Dry Powder based Fire extinguisher of 4 to 6 kgs capacity by a licensed and certified professional complete all as specified and directed.
Material and labour for Refilling of ABC Dry Powder based Fire extinguisher of 2 kgs capacity by a licensed and certified professional complete all as specified and directed.
Pressure testing of CO2 based Fire extinguisher of any capacity including discharge and accessory hoses to ensure that no hidden weaknesses etc., complete all as specified and as directed.
Pressure testing of ABC Dry Powder based Fire extinguisher of any capacity complete all as specified and as directed.
Supply and fix in repair hose tube for Fire extinguisher of any type and capacity all as specified and as directed.
Material and labour for Painting and stickering of Fire extinguisher of any type and capacity complete all as specified and as directed.
Supply and fix in repairs pressure gauge (0-14 kg/sqcm) all as specified and as directed.
Supply and fix in repairs pressure switch (0-15 kg/sqcm) all as specified and as directed.
Material and labour for applying two coats of synthetic enamel paint of approved colour and shade including prepartion of old treated surfaces of steel complete as specified and as directed. Note: Painting to Fire extinguisher shall not be measured against this item.
Supply and fix in repair Fire fighting hose box door of area not exceeding 0.5 Sqm each including painting with two coats synthetical enamel paint over a coat of primer complete all as specified and as directed.
Supply and fix in repairs of Fire hydrant male and female coupling to avoid any leak complete all as specified and as directed.
Supply and fix in repairs Ball brass valves of size 25mm dia, high pressure, with polythene float and flynut complete, screwed for iron pipe or brass ferrule and fixed complete all as specified and as directed.
Supply and fix in repairs/ replacement of blank flanges with asbestos gasket, nut, bolts, washers complete etc of size 100 mm dia and welding to the existing pipeline complete all as specified and directed.
Cutting upto a depth of 2.5cm into concrete walls and trimming surface where reinforcement is cut through as required, girth exc. 30cm complete all as specified and as directed.
Material and labour for Cement concrete M-20, (1:1.5:3), type A1 using 20mm graded stone aggregate as in repairs to disturbed concrtete walls complete all as specified and as directed.
Material and labour for painting with synthetic enamel paint one coat of approved colur and shade including preparation of old detoriated surfaces of pipes not exc 10cm width or grith complete as specified and directed.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
technical_842266.pdf
techsummary_842266.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.19 MB
8263TENDER.pdf
Tender Documents • 0.95 MB
BOQ_842266.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid