Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.9 LAccepted-Finance | L1 | Accepted-Finance Lowest Bidder | |
| 2 | L2₹4.1 L+₹17,778 (4.52%)Rejected-Finance VILL PO URA BURDWAN | L2 | Rejected-Finance Highest bidder | |
| 3 | L3₹4.1 L+₹20,008 (5.09%)Rejected-Finance 121004 | L3 | Rejected-Finance Highest Bidder |
| Sl No | Description | Qty | Unit | DELTA BROTHERS L1 | GHOSH ENTERPRISE L3 | ANANTA ELECTRICAL ENGG CONSTRUCTION L2 |
|---|---|---|---|---|---|---|
| 1.00 | HT Portion. -
Checking & Servicing of the H.T. 3 Panel Switch Board (12 KV - VCB) along with busbar, risers and sockets contacts 3 Nos. withdrawing this by sectionwise for megger (2.5KV) testing. Throughout checking of VCB’s with their mechanism. All the components of the switch board incl. spouts of the panel , P.T. plugging chamber .etc. thoroughly checking and cleaning. As per direction by EIC. | 3 | nos | 7,150 ₹21,450 Lowest | 10,000 ₹30,000 | 8,000 ₹24,000 |
| 2.00 | Testing the overload and earth fault tripping Relays of all the gears of H.T. 3-Panel Switch Board by Primary injection Relay Testing Set incl. making necessary calibration for proper tripping according to full load current of the transformers incl. carrying the Relay Testing set to and from site. As per direction by EIC. | 1 | Set | 29,795 ₹29,795 Lowest | 30,000 ₹30,000 | 30,000 ₹30,000 |
| 3.00 | Servicing 2 nos. 750KVA Dry type transformer with check cleaning and tightening of all visible components. As per direction by EIC. | 2 | Nos | 9,535 ₹19,070 | 9,000 ₹18,000 Lowest | 9,000 ₹18,000 Lowest |
| 4.00 | Supply & Fixing of 22.5mm Dia, 24 V - 240V LED Indication Light for H.T. Panel with Inter Connection. As per direction by EIC. | 21 | Nos | 715 ₹15,015 Lowest | 950 ₹19,950 | 1,000 ₹21,000 |
| 5.00 | Repairing & Fixing of existing Digital TVM meter with inter connection. As per direction by EIC. | 1 | no | 7,150 ₹7,150 | 4,500 ₹4,500 Lowest | 5,000 ₹5,000 |
| 6.00 | Supply of 1no. Mechanically operated charging handle for VCB (12 KV - Crompton Graves). As per direction by EIC. | 1 | no | 4,172 ₹4,172 | 3,500 ₹3,500 Lowest | 3,500 ₹3,500 Lowest |
| 7.00 | Testing of Mechanically On Off for all the gears of H.T. 3-Panel Switch Board by Primarily Mechanically operated charging handle Set incl. making necessary calibration for proper On Off according to full accuracy of the Panel. As per direction by EIC. | 3 | nos | 1,192 ₹3,576 | 950 ₹2,850 Lowest | 1,000 ₹3,000 |
| 8.00 | Testing the Sub-Station Earthing value by Earth tester and treated the earth pit by charcoal, salt etc. For healthy earth condition and lower the earthing resistance value. As per direction by EIC. | 16 | nos | 596 ₹9,536 Lowest | 600 ₹9,600 | 600 ₹9,600 |
| 9.00 | Earthing with 50 mm dia GI pipe (TATA Medium) 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level by ISI-Medium GI pipe. As per direction by EIC.
[PWD/GS, Item No. 2(a), Page No. G-1] | 5 | nos | 1,872 ₹9,360 | 1,600 ₹8,000 Lowest | 1,600 ₹8,000 Lowest |
| 10.00 | Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. As per direction by EIC.
[PWD/GS, Item No. 5(c), Page No. G-3] | 100 | Mtr | 135 ₹13,500 | 150 ₹15,000 | 100 ₹10,000 Lowest |
Tender Value
Refer Docs
EMD Value
₹8,000
Closing Date
18 Mar 2026, 2:30 pmClosed
AE/BESD/PWD
Office of The Assistant Engineer BURDHAMAN ELECTRICAL SUB- DIVISION, P.W.DTE Kachari Road, Court Compound, Purba Bardhaman
Urgent servicing and repairing of HT panel with Transformer including LT panels and allied EI works for 11 KV 433 V Sub-station at DM office complex building, Purba Bardhaman, Under the maintenance of BES I , PWD.
2026_WBPWD_1021234_1
WBPWD/AE/BESD/NIQ 41/e-T of 25-26
Open Tender
ELECTRICAL WORKS M/R
Item Rate
7 days
Old Collectorate Bldg Sub Station
Please refer Tender documents.
4 documents required · 4 mandatory
₹8,000
7 Jul 2026
12 Mar 2026
20 Mar 2026
12 Mar 2026
18 Mar 2026
15 Mar 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | HT Portion. -
Checking & Servicing of the H.T. 3 Panel Switch Board (12 KV - VCB) along with busbar, risers and sockets contacts 3 Nos. withdrawing this by sectionwise for megger (2.5KV) testing. Throughout checking of VCB’s with their mechanism. All the components of the switch board incl. spouts of the panel , P.T. plugging chamber .etc. thoroughly checking and cleaning. As per direction by EIC. | 3 | nos | - | - |
| 2 | Testing the overload and earth fault tripping Relays of all the gears of H.T. 3-Panel Switch Board by Primary injection Relay Testing Set incl. making necessary calibration for proper tripping according to full load current of the transformers incl. carrying the Relay Testing set to and from site. As per direction by EIC. | 1 | Set | - | - |
| 3 | Servicing 2 nos. 750KVA Dry type transformer with check cleaning and tightening of all visible components. As per direction by EIC. | 2 | Nos | - | - |
| 4 | Supply & Fixing of 22.5mm Dia, 24 V - 240V LED Indication Light for H.T. Panel with Inter Connection. As per direction by EIC. | 21 | Nos | - | - |
| 5 | Repairing & Fixing of existing Digital TVM meter with inter connection. As per direction by EIC. | 1 | no | - | - |
| 6 | Supply of 1no. Mechanically operated charging handle for VCB (12 KV - Crompton Graves). As per direction by EIC. | 1 | no | - | - |
| 7 | Testing of Mechanically On Off for all the gears of H.T. 3-Panel Switch Board by Primarily Mechanically operated charging handle Set incl. making necessary calibration for proper On Off according to full accuracy of the Panel. As per direction by EIC. | 3 | nos | - | - |
| 8 | Testing the Sub-Station Earthing value by Earth tester and treated the earth pit by charcoal, salt etc. For healthy earth condition and lower the earthing resistance value. As per direction by EIC. | 16 | nos | - | - |
| 9 | Earthing with 50 mm dia GI pipe (TATA Medium) 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level by ISI-Medium GI pipe. As per direction by EIC.
[PWD/GS, Item No. 2(a), Page No. G-1] | 5 | nos | - | - |
| 10 | Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. As per direction by EIC.
[PWD/GS, Item No. 5(c), Page No. G-3] | 100 | Mtr | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.33 MB
NewForm2911.pdf
Tender Documents • 1.85 MB
BOQ_2510077.xls
BOQ • 0.67 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .