| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.7 LAccepted-AOC | L1 | Accepted-AOC Being First Lowest | |
| 2 | L2₹30.0 L+₹50,094.04 (1.70%)Rejected-Finance 31 TILAK NAGAR SRI GANGANAGAR 335001 RAJ | GANGANAGAR | RAJASTHAN | 335001 | L2 | Rejected-Finance Other Than First Lowest | |
| 3 | L3₹34.1 L+₹4.6 L (15.8%)Rejected-Finance | L3 | Rejected-Finance Other Than First Lowest | |
| 4 | L4₹36.8 L+₹7.3 L (24.9%)Rejected-Finance | L4 | Rejected-Finance Other Than First Lowest |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
16 Oct 2024, 6:00 pmClosed
GE Lalgarh Jattan
GE Lalgarh Jattan
REPAIR/REPLACEMENT OF OLD U/S INTERNAL WIRING AND CONNECTED ACCESSORIES FOR OR and JCOs MD ACCN AT LGJ MIL STN
2024_MES_661651_2
8935-08/GE/2024-25
Open Tender
Electrical and Maintenance Works
Works
180 days
GE Lalgarh Jattan
As per tender document
8 documents required · 8 mandatory
₹500
GE Lalgarh Jattan
₹80,000
Yes
13 Dec 2024
24 Sept 2024
18 Oct 2024
24 Sept 2024
16 Oct 2024
2 Oct 2024
Amount
Taking down carefully copper/aluminum point wiring (light, fan, socket or power) complete including fittings such as switches, ceiling rose, pendent holder, sketch fitting, sockets, regulator etc and making good distrubed surfaces of walls and floors etc to match with the existing complete all as specified and as directed by Engineer-in-charge
Taking down MCB with sheet metal enclosure, main switch, DB etc and making good disturbed surface to match with existing surface complete all as specified and as directed by Engineer-in-charge.
Taking down sub main wiring of any size/capacity complete all as specified and making good disturbed surface to match with the existing surface complete all as specified and as directed by Engineer-in-charge
Taking down carefully by unscrewing from boards/outlet boxes fittings and fixtures such as switches, sockit, ceiling roses, lamp holders, brackets, ceiling fitting, bulk head fitting tube l;ight etc complete all as specified and directed by Engr-in-Charge.
M&L for concealed Point wiring for One Light point controlled by one, one way switch with single core PVC insulate, unsheathed multistranded copper conductor cable of size 1.5 sq.mm (FRLS) drawn in and including electrical grade PVC conduit 20 mm dia concealed on wall/ceiling/floor including PVC insulated unsheathed earth wire with multi stranded copper conductor of size 1.5 sq.mm(FRLS) including MS shunk sheet metal box with 3 mm thick bakeliteplastic laminated sheet top cover with brass counter shunk screws with washer complete all as specified. Note - quoted rate shall include making good to the disturbed surfaces including plastering and painting to match with the existing colour complete all as specified and as directed by Engineer-in-charge.
All as per ser No 5 but for one 3 pin switch socket outlet, 5 Amp on the same board with other switches.
All as per ser No 5 but for One 3 pin 5 amps switch socket outlet point on independent board.
All as per ser No 5 but for One bell/buzzer point controlled by one bell push
All as per ser No 5 but for Two way point controlled by two way switch
M&L for concealed Point wiring for One ceiling/exhaust fan point controlled by one switch and regulator with single core PVC insulate, unsheathed multistranded copper conductor cable of size 1.5 sq.mm (FRLS) drawn existing electrical grade PVC conduit 20 mm dia concealed on wall/ceiling/floor including PVC insulated unsheathed earth wire with multi stranded copper conductor of size 1.5 sq.mm(FRLS) including MS shunk sheet metal box with 3 mm thick bakeliteplastic laminated sheet top cover with brass counter shunk screws with washer complete all as specified. Note - quoted rate shall include making good to the disturbed surfaces including plastering and painting to match with the existing colour complete all as specified and as directed by Engineer-in-charge.
All as per srl item No 10 above, here in before but wiring with 2.5 sqmm mutlistranded cable and earth wire with copper conductor of size 2.5 sq.mm for 15 amps power gyaser point
S&F in repair Piano type switch single pole 1 way 5/6 amps 230 volt AC supply complete all as specified and directed by Engr-in-Charge.
S&F in repair Piano type switch single pole 2 way 5/6 amps 230 volt AC supply complete all as specified and directed by Engr-in-Charge.
M&L in repair switch piano type flush button single pole one way 15/16 Amps 230 volts complete all as specified and as directed by Engineer-in-charge
S&F Ding Dong bell along with bell push flush type 5 amps complete all as specified and directed by Engr-in-Charge.
S&F in repair socket two in one 6/5 Pin 5 Amps 230 volt AC supply complete all as specified and directed by Engr-in-Charge.
S&F in repair socket two in one 6/5 Pin 15/16 Amps 230 volt AC supply complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair LED lights fitting 1x 20 W, 220V,AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed by Engr-In-Charge
Supply and fix in repair Lamp holder, PVC/Polycarbonate type complete with lamp LED 9 Watt for Batten fitting with back plate and all fittings complete all as specified and directed by Engr-In-Charge
Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed by Engr-In-Charge
Supply and fix ceiling rose surface bakelite two to three terminals/plate, polycarbonate, isolated body complete all as specified and as directed by Engineer-in-charge.
Supply and fix sheet metal enclosure DB single pole and neutral for 240 volts 8 way with 200 Amps rated busbar flush/surface mounting double door complete all as specified and as directed by Engineer-in-charge.
Supply and fix in repair Switch socket combination 2 in 1, 5 A flush type complete all as specified and as directed by Engineer-in-charge.
Supply and fix in repair Switch socket combination 5A/16A, 5 in 1 complete all as specified and as directed.
Supply and fix in repair Switch socket combination 2 in 1, 5 A with box flush type complete all as specified and as directed.
Supply and fix in repair Switch socket combination 5A/16A, 5 in 1 with box complete all as specified and as directed by Engineer-in-charge
Supply and fixing SP 6-32 Amp 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning complete all as specified and directed by Engr-In-Charge
All as per ser No 27 above but for SPN 63 Amp all as specified and directed by Engr-in-Charge
Supply and fix Vertical DB 4 way suitable for Double Pole outgoing MCB-40 Amp-04 Nos with incoming 100 Amps MCCB 4 pole-01 Nos complete with 250 Amps rated Copper busbar flush mounting, double door, proction class IP-30, IK08 complete all as specified and as directed by Engineer-in-charge.
Supply and fix MCCB 100 Amps, 4 pole, 16 KA thermal and magnetic release in V TPN DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing PVC Blanking Plates one way with internal lock complete all as specified and as directed by Engineer-in-charge.
S & F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. as reqd complete all as specified and directed by Engr in charge.
S & F modular fan regulator, 120W-2 Module complete all as specified and directed by Engr in charge.
Material & Labour for Sub Main Wiring in repair with two run single core 4 Sqmm PVC insulated unsheathed (FRLS) cable with stranded copper conductor drawn in PVC conduit & accessories Suitable size with and including 4 Sqmm copper green colour earth wire all as specified and directed by Engr-in-Charge. NOTE-two run of 4 sq.mm & One run of 4 sq.mm & One run of PVC conduit with accessories shall be measured as One length complete all as specified and as directed by Engineer-in-charge.
Material & Labour for Sub Main Wiring in repair with two run single core 6 Sqmm PVC insulated unsheathed (FRLS) cable with stranded copper conductor drawn in PVC conduit & accessories Suitable size with and including 6 Sqmm copper green colour earth wire all as specified and directed by Engr-in-Charge. NOTE-two run of 6 sq.mm & One run of 6 sq.mm & One run of PVC conduit with accessories shall be measured as One length complete all as specified and as directed by Engineer-in-charge.
M & L for Earthing complete with galvanised steel earth plate electrode 60 x 60 cm x 6 mm thick burried directly in ground earth pit not less than 2.25 Mtr deep below normal ground level with top edge of earth plate not less than 1.5 Mtr below normal ground level, connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts, checknuts and washers of galvanised iron all as shown in electrical plate No 5 of SSR Part-I, connected to transformer / feeder pillar all as specified including GI pipe 20 mm bore medium grade for watering and 15 mm GI Pipe light grade for protection of earth lead wire, PCC chamber using PCC 1:3:6 type C-2 CI frame and cover, funnel and wiremesh, all excavation and earth work etc complete all as specified and directed by Engr-in-Charge
Supply and fixing LED light fitting as building security lights of 35 Watt Cap 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, with epoxy powder coated CRCA sheet steel grey tray, clear acrylic cover, incl street light bracket made out of 25 mm dia GI medium grade pipe 0.6 mtr long complete with 2 sets of FI clamps made out of 30x5 MS flat & nuts, bolts & washer including painting to clamp with two coats of aluminium silver paint over a coat of primer, with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed by Engr-In-Charge
Supply and fix single phase electronic meter tamper proof LCD Display with poly carbonate cover 230 V,10-60 Amp accuracyclass -I 50 Hz, conforming to IS 13779, IP-54 with parameters to show data, time, current reading , load, PF, Voltage and KWH complete all as specified and as directed by Engr-In-Charge.
S/F in repair motor for ceiling fan 1200 mm sweep AC 230V, super enamelled, copper winding of 'B' class insulation, single phase, minium 26W (± 10%), 0.90 (Min) PF, 210 CFM 350 RPM (± 10%), temperature rise 40 degree maximum, down rod , white colour, total harmonic less than 10%, 5 speed, with service value 6.00 BEE Five star rated, including hanging in position and connection with fle-xible cord twin core twisted copper conductor of size 23/0.0026 from ceiling rose to fan complete all as specified and as directed by Engineer-in-charge.
Supply and fix Fresh air fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250 MM complete all as specified and directed by Engr-In-Charge
Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300 mm sweep with, blades, and frame and louvers complete all as specified and as directed by Engineer-in-charge
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric poer cable (heavy duty) 1100 conductor of size 25 Sq mm 4.0 core complete all as specified and as directed by Engineer-in-charge
Excavation in trenches not exc 1.5 m wide and n. exc 1.5 m deep in soft/loose soil for foundation/ cable etc n exc 10 Sqm on plan and n exc 1.5 Sqm in depth all as specified and directed by Engr-in-Charge
Returning, filling in including spreading levelling, watering and well ramming in layer n. exc 25 cm thick complete all as specified and as directed by Engineer-in-charge
Removing surplus soil to a distance n. exc 50 m and depositing where directed at level n. exc 1.5 m above the starting point complete all as specified and directed
Supply and spreading, levelling river sand in trenches for cables cushioning on top and bottom of cable complete all as specified and as directed by Engineer-in-charge.
M&L brick protection with sub class'B' brick laid flat across the cable complete all as specified and as directed by Engineer-in-charge
M&L for boring under roads for crossing of UG Cables complete all as specifie and directed by Engr-In-Charge.
Supply and fix GI Pipe light grade of size 40 mm laid in trenches under road/fixed on wall/pole for cable protection complete all as specified and directed by Engr-In-Charge
Note:- The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender, from total amount of Schedule 'A'/BOQ
Singla Electricals (BID ID -3140708)
Soma Enterprises (BID ID -3141458)
Lalgarhia Enterprises (BID ID -3133424)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .