Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 47 MURUGESA NAICKER COMPLEX GREAMS ROAD THOUSAND LIGHTS CHENNAI TAMIL NADU 600006 | CHENNAI | TAMIL NADU | 600006 | Admitted-Finance |
| 2 | Admitted-Finance 302 MILINDA MANOR 2 RNT MARG INDORE INDORE MADHYA PRADESH 452001 | INDORE | MADHYA PRADESH | 452001 | Admitted-Finance |
| 3 | Admitted-Finance PLOT NO 37 BADANPUR OLD SER NO 34658 NEAR SAI BARAT PALACE PAWAN BHUMI SHAKTI NAGAR JABALPUR MADHYA PRADESH 482001 | JABALPUR | MADHYA PRADESH | 482001 | Admitted-Finance |
| 4 | Rejected-Technical | Rejected-Technical As per technical evaluation report |
| 5 | Rejected-Technical | Rejected-Technical As per technical evaluation report |
Tender Value
₹43.3 L
EMD Value
₹86,505
Closing Date
26 Dec 2023, 2:00 pmClosed
Project In Charge
IDO Office, Ground Floor, East Wing, Abhinandan Bhawan, IIT Indore 453552
AHU Room and chilled water pipe Insulation work at IIT Indore
2023_IITI_783175_1
IITI/IDO/E/HVAC/INSU RC/NIT/23/03
Open Tender
Electrical Works
Works
90 days
IIT Indore
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹86,505
IDO office, AB,Ground Floor, IIT Indore
13 Feb 2024
30 Nov 2023
27 Dec 2023
30 Nov 2023
26 Dec 2023
9 Dec 2023
7 Dec 2023
Amount
Supplying & fixing of acoustic lining on walls and ceilings of AHU rooms with 50mm thick, density 32 kg/cum resin bonded glass fiber insulation friction fixed in 610mm x 610 mm framework made of 25x50x50x50x25 mm made out of 0.6mm thick GI sheet U shaped channel and covered with reinforced fiber glass tissue and finished with 0.80 mm perforated aluminum sheet etc. complete as required and as per specifications.
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of fire retardant quality expanded polystyrene moulded pipe section, for the following already laid chilled water piping, of density 20 kg/cum after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessian and finally applying 0.63mm aluminum sheet cladding complete with type3 , grade 1 roofing felt strip(as per IS:1322 as amended up to date ) at joints repairing of damage to building etc. as per specifications and as required complete in all respect.
Chilled water piping of nominal size - 600mm dia. (75mm thick expanded polystyrene)
Chilled water piping of nominal size - 300mm dia. (75mm thick expanded polystyrene)
Chilled water piping of nominal size 250 mm dia. (75mm thick expanded polystyrene)
Chilled water piping of nominal size 125 mm dia. (50mm thick expanded polystyrene)
Chilled water piping of nominal size 100 mm dia. (50mm thick expanded polystyrene)
Chilled water piping of nominal size 80 mm dia. (50mm thick expanded polystyrene)
Chilled water piping of nominal size 65 mm dia. (50mm thick expanded polystyrene)
Chilled water piping of nominal size 50 mm dia. (50mm thick expanded polystyrene)
Chilled water piping of nominal size 40 mm dia. (50mm thick expanded polystyrene)
BEARDSELL.CO.IN
INDIA INSULATION PVT. LTD.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .