Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.0 LAccepted-AOC | L1 | Accepted-AOC Accepted being L1 | |
| 2 | L2₹32.5 L+₹30,527 (0.95%)Rejected-Finance | L2 | Rejected-Finance Rejected. Quoted rates are higher than L1 | |
| 3 | L3₹32.6 L+₹40,517.50 (1.26%)Rejected-Finance | L3 | Rejected-Finance Rejected. Quoted rates are higher than L1 |
Tender Value
Refer Docs
EMD Value
₹83,100
Closing Date
2 Jan 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Garrison Engineer M AF Jalahalli
Garrison Engineer M AF Jalahalli Bangalore 560013
REPAIR MAINT OF SUMMER APPLIANCES AND OTHER MISC WORKS UNDER GE M AF JALAHALLI
2023_MES_630104_1
8855/E8
Open Tender
Electrical and Maintenance Works
Item Rate
181 days
Garrison Engineer M AF Jalahalli
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE AF MAINT JALAHALLI PUBLIC FUND ACCOUNT
₹83,100
18 Jan 2024
30 Nov 2023
4 Jan 2024
30 Nov 2023
2 Jan 2024
14 Dec 2023
30 Nov 2023 - 7 Dec 2023
Amount
Disconnecting electric connection from defective blower/ fan motor and taking out from unit capacity 8.3 TR of existing make and transporting to workshop after getting the gate pass from Engineer-in-Charge. Dismantling the burnt winding & rewinding of 1/6 to 1/8 HP double shaft blower motor with the existing size of super enamelled copper winding wire as per manufacturer instructions including insulation, varnishing, greasing, testing complete and transporting back to the location from where it was disconnected and refixing the same and testing complete all as specified and as directed.
Carrying out pressure leak test of 8.3 ton ductile split type AC whenever required by nitrogen gas pressure for detecting leakage in cooling/condensing unit refrigerant pipe and repairing the leakage by welding or brazing of condensing/ cooling unit, refrigerant pipe and putting under pressure for leakage checking after repair of leaking pipe flushing out by N2 and CTC/ vaccumination complete all as specified and as directed. Note :- Supply & charging of refrigerant gas R-22/R-407C will be measured and paid for separately
Supply and fix Air filter set suitable for 8.3 ton ductable split type AC complete including taking down existing one all as specified and as directed.
Supply and fix PCB (circuit plate) of in-door unit of 8.3 TR ductable split AC complete including taking down existing one all as specified and as directed.
Taking out of defective wiring of indoor/ outdoor unit of PCB, visual eye damp plates, fixing the new wiring in place of damaged items of capacity of AC 8.3 TR including matching the existing system all as specified and as directed.
Supply and fix Thermal relay 20A, 415 Volt, single phase suitable for ductable split type AC of 8.3 TR capacity complete including taking down existing one all as specified and as directed. Make : LG / Tecumseh / Hitech/ Indo Asian/L&T.
Supply and fix Single phase preventer, 230 volt, 50 HZ, AC supply complete including taking down existing one all as specified and as directed. Make : L&T / Seimens / BCH
Supply and fix PCB (circuit plate) of in-door unit of 4.0 TR ductable split AC complete including taking down existing one all as specified and as directed.
Removing the window/ split type AC up to 1.5/ 2 ton capacity of any make from any location for carrying out servicing complete as and when directed and installing back at original location, testing and commissioning all as specified and as directed by Engineer-in-Charge. Note :- The rate of following deemed to be included in quoted rate :- a) Cleaning the body, evaporator and condenser with detergent, combing the pins and flushing with air blower b) Checking electrical connection, cleaning, Greasing, oiling, fan/blower motor, cleaning of air filter with blower c) Wrapping suction and discharge pipe with foam insulation and white roll ,changing drainage pipe when necessary d) The unit rate quoted by the tenderer inclusive for Removing, servicing, installation, commissioning and testing of all equipment’s, tools and plants, and back in on final position complete (e) The work shall be done by a specialized team of Engineer/Technicians of OEM. (f) Spares will be measured and paid separately. (g) Refrigerant gas will be measured & paid separately.
Supply and fix polyurethane foam insulation indoor to outdoor unit suitable for 1.5 Ton to 2 Ton split type A/C any type and at any location including taking down existing one
Supply and fix Over load relay (in replacement) suitable for split type Air Conditioner of any make up to 2.0 TR capacity, including taking down existing one all as specified and directed.
Supply and fixing Blower motor (in replacement) suitable for split type Air Conditioner of any make up to 2 TR capacity including taking down existing unserviceable one, all as specified and directed. Make of fan motor: AUE/ GEC/Himsun.
Supply and fix Suction valve suitable for 1.5 Ton/2 Ton of split type AC of existing make
Supply and fixing Hermetic sealed/Rotory new compressor for 1.5 TR split type AC capacity including disconnecting the electrical and refrigerant connection of defective sealed unit of split type AC of capacity 2 Ton and connection of all pipe line & charging of refrigerant and testing complete including taking down existing one all as specified and directed Make :- Voltas, LG, Blue star, Hitachi, Kirloskar, Tecumseh Note:- (a) Compressor shall be purchased from manufacturer/ authorised dealer of the manufacturer. Compressor shall be in sealed condition and shall bear warranty for 12 months from the date of purchase.
Supply and fix discharge valve suitable for 1.5 Ton/2 Ton of split type AC including taking down existing one.
Supply and fixing Remote sensing unit (in replacement) for upto 2.0 TR split type AC including taking down existing unserviceable one all as specified and directed. Make : As per existing AC at the site.
Supply and fixing Condenser coil (in replacement) after disconnecting the refrigerant connection of defective condenser coil unit of split type AC upto 2.0 TR and replacing the condenser coil unit connecting the same unit with refrigerant connections complete including taking down existing one all as specified and directed.
Supply and fixing Remote assembly corded/cordless (in replacement) for any type and size of split type ACs, upto 2.0 TR including taking down existing one all as specified and directed.
Supply and fixing Blower of indoor unit suitable for 1.5 Ton / 2 Ton split AC including taking down existing unserviceable one at any location all as specified and directed.
Supply and fix MS wall bracket suitable for fixing of out door unit of split type Air Conditioner with necessary nuts, bolts & washers and removing old unserviceable items and making good disturbed surfaces to match with the existing complete all as specified and directed.
Supply and fixing Condenser Fan motor (in replacement) suitable for window type Air Conditioner of any make up to and including 1.5/2.0 TR capacity, including taking down existing one all as specified directed. Make of fan motor: AUE/GEC/Himsun.
Supply and fixing Filter (in replacement) suitable for split type Air Conditioner of any make upto 2 TR capacity, including taking down existing one all as specified and directed.
Supply and fixing Copper tube, 9 mm bore (in replacement) superior quality suitable for refrigeration and discharge lines of split ACs, drawn trough pipes/ fixed to walls/ laid on floor or roof including taking down existing one all as specified and directed.
Supply and fixing Hermetic sealed/Rotory new compressor for 2 TR split type AC capacity including disconnecting the electrical and refrigerant connection of defective sealed unit of split type AC of capacity 2 Ton and connection of all pipe line & charging of refrigerant and testing complete including taking down existing one all as specified and directed Make :- Voltas, LG, Blue star, Hitachi, Kirloskar, Tecumseh Note:- (a) Compressor shall be purchased from manufacturer/ authorised dealer of the manufacturer. Compressor shall be in sealed condition and shall bear warranty for 12 months from the date of purchase.
Supply and fixing Front grill (in replacement) suitable for split type Air Conditioner of any make up to 2 TR capacity, including taking down existing one all as specified and directed.
Supply and fix Condenser coil (in replacement) after disconnecting the refrigerant connection of defective condenser coil unit of split type AC upto 1.5 TR and replacing the condenser coil unit connecting the same unit with refrigerant connections complete including taking down existing one all as specified and directed.
Supply and fixing flexible PVC pipe of suitable size for indoor unit drain water of split AC suitable for any type and any capacity.
Supply and fix PCB board of any make for indoor unit of split AC 1.5 Ton/ 2 Ton including taking down existing one all as specified and directed.
Material and labour for Refrigerant gas, (R 407C) suitable for cooling equipment's supplied and filled all as specified and directed.
Supply and fix dummy nut of dia 3/8" suitable for 1.5 Ton/2 Ton of split type AC
Supply and fix dummy nut of dia 1/4" suitable for 1.5 Ton/2 Ton of split type AC
Supply and fix dummy nut of dia 5/8" suitable for 1.5 Ton/2 Ton of split type AC
Supply and fix dummy nut of dia 1/2" suitable for 1.5 Ton/2 Ton of split type AC
Supply and fix PVC insulated multi stranded copper conductor 3 core 2.5 sq.mm, including connecting up and taking down existing unserviceable cable of any description and size (in replacement) all as specified and directed.
Supply and fix old UNSV indoor unit including blower fan , PCB board and all accessories capacity 1.5/2.0 Ton split type A/C including taking down existing unserviceable one any type all as specified and directed by Engineer-in-charge
Material and labour for shifting of Air Conditioner, window/Split type capacity up to 2 TR from existing location to new location as per user requirement and installing, toping up of gas, replacement of copper tubing connecting up, commissioning and testing complete all as specified and as directed by Engineer-in-Charge. Note :- The rate for following works deemed to be included in quoted rate :- (a) Transportation of air conditioner any type any capacity from one to other location. (b) Fixing only base plate with necessary fixing material on stone / brick walls and as directed (c) Fixing only outdoor and indoor units as required and directed (d) Connecting indoor / outdoors units of split ACs with copper tubes, flairs nuts, warping suction and discharge lines with inclucating materials with necessary fixing arrangements such as bolts, nuts washers and clamps etc. on walls (e) fixing PVC pipes 50mm dia for outlet of outdoor units to drain out dew water with necessary clamps. (f) Fixing of wall mounting voltage stabilizer of 3 KVA to 5 KVA capacity on the wall with necessary fixing arrangements such as bolts, nuts washers and clamps etc on wall. (g) Fixing PVC hose/ PVC pipes of 15mm sizes as reqd at site with necessary junction boxes, PVC bends etc. including two length of PVC copper cables of 4 sqmm size for electrical connection of ACs. (h) No additional payment shall be made for leakage of gas occurring during shifting of Air Conditioner and topping up of required gas. (j) Fixing of copper tubing of qty of required size.
Supply and fix 3 pin metal clad plug top 20 Amps, AC 230 volts for any type of AC including taking down existing unserviceable one all as specified and as directed.
Supply & fix metal clad switch socket single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20A concealed in walls. Make : Havells/ Indo asian/ Legrand
Supply and fix flair nut of dia 5/8" suitable for 1.5 Ton/2 Ton of split type AC
Supply and fix flair nut of dia 1/2" suitable for 1.5 Ton/2 Ton of split type AC
Supply and fix flair nut of dia 3/8" suitable for 1.5 Ton/2 Ton of split type AC
Supply and fix flair nut of dia 1/4" suitable for 1.5 Ton/2 Ton of split type AC
Supply and fix flair nut of dia 1/16" suitable for 1.5 Ton/2 Ton of split type AC
Supply and fixing Copper tube (in replacement) 15 mm / 18 mm dia, superior quality suitable for refrigeration and suction lines of split ACs, drawn trough pipes/ fixed to walls/ laid on floor or roof all as specified and directed
Supply and fix single phase single pole contactor suitable for 1.5/ 2.0 split type AC all as specified and as directed.
Removing old unserviceable split type air conditioner outdoor unit and deposited in store yard for safe custody and Supply and fix outdoor unit of the split type air conditioner 1.5/2 TR capacity, complete with all accessories such as hermetically sealed compressor and condenser unit, capacitors, relays, fan motor, duly prewired and including connecting of existing refrigerant gas piping, electrical connections and testing etc complete all as specified and directed. Make: Carrier/LG/Blue star/Voltas/ Hitachi
Repair and maintenance of inverter type split AC of any capacity / any Make from any location including attending breakdown calls, routine maintenance and servicing ,testing and commissioning all as specified and directed here under :- a) Cleaning the body, evaporator and condenser with detergent, combing the pins and flushing with air blower. b) Checking electrical connection, cleaning, Greasing, oiling, fan motor, cleaning of air filter with blower. (c) Testing all copper tube ,joints, leads for any leaking and Top up with the refrigerant gas if necessary. (d) The work shall be done by a specialized team of Engineer/Technicians of OEM. (e) Nearly 50 number of inverter type split AC are installed at the distant height. To carryout servicing of these AC's special T&P (Boomer vehicles) of height 24 meter will be required. The cost of arrangement of special T&P will be inclusive in quoted rate.
Supply and fix DC blower fan motor for inverter split AC of 1.5 Ton to 2 Ton and including taking down existing unserviceable one of any capacity and at any location all as specified and directed.
Inspection, checking adjustment and minor repair of unserviceable window type AC any type any capacity placed at any location includes repair/ replacement of defective parts such as checking of electrical connection, condenser, gas leakage, PCB, condenser fan blade, indoor unit, outdoor unit, compressor, PVC pipe etc., complete all as specified and as directed by Engineer-in-Charge. Note :- Repair/ replacement of unserviceable parts shall be measured and paid separately complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing PCB board of inverter type split type AC for 1.5 Ton/2 Ton including taking down existing unserviceable one at any location all as specified and as directed.
Supply and fix Filter (in replacement) suitable for window type Air Conditioner of any make up to 1.5/ 2 TR capacity including taking down existing one all as specified and directed.
Material and labour for pressure testing and rectifying the leakages found in the system of window/ split type ACs capacity up to 2 Ton capacity including vacumizing, charging and checking the gas pressure to desire level complete for satisfactory functioning all as specified and as directed. Note: Toping up of gas will be measured and paid separately
Supply and fix condenser fan blade suitable for 1.5 Ton split/ window AC including taking down existing unserviceable one and all as specified and directed.
Supply and fixing Thermostat (in replacement) suitable for window type Air Conditioner of any make up to 1.5 TR capacity, including taking down existing one all as specified and directed.
Supply and fixing Front grill (in replacement) suitable for window type Air Conditioner of any make up to 1.5 TR capacity, including taking down existing one all as specified and directed.
Supply and fixing Blower motor (in replacement) suitable for window type Air Conditioner of any make up to 1.5/ 2 TR capacity including taking down existing unserviceable one all as specified and directed. Make of fan motor: AUE/ GEC/Himsun.
Supply and fixing Over load relay (in replacement) suitable for window type Air Conditioner of any make up to and including 1.5/ 2 TR capacity, including taking down existing one all as specified and directed.
Supply and fixing Hermetic sealed/Rotory new compressor for window type AC of capacity 1.5 Ton (in replacement) including disconnecting the electrical and refrigerant connection of defective sealed unit of window type AC of capacity 1.5 Ton and connection of all pipe line & charging of refrigerant and testing complete including taking down existing one all as specified and directed Make :- Voltas, LG, Samsung, Blue star, Hitachi Note:- (a) Compressor shall be purchased from manufacturer/ authorised dealer of the manufacturer. Compressor shall be in sealed condition and shall bear warranty for 12 months from the date of purchase.
Supply and fixing Condenser coil (in replacement) after disconnecting the refrigerant connection of defective condenser coil unit of window type AC up to and including 1.5/ 2 Ton and replacing the condenser coil unit connecting the same unit with refrigerant connections complete including taking down existing one all as specified and directed.
Supply and fix overload protector for window/ split AC 1.5/2 Ton TR capacity including taking down existing unserviceable one all as specified and directed.
Taking out 3 phase tower AC complete for repair / servicing and overhauling of capacity 4TR of make - LIYOD after disconnecting refrigerant pipes, drain pipe and electric connection, removing dust by using blower and cleaning the condenser coils and components by using water and caustic soda/cleaning chemical agents, checking and replacing the spares like relay, capacitors, thermostat, fan motor, blades & blower etc. and also connecting of refrigerant pipe, drain pipe and charging of refrigerant gas and testing including fixing back in its original location complete all as specified and directed. Note :-(i) Refrigerant gas will be measured and paid separately.
Taking out, inspection, checking adjustment and minor repair of unserviceable refrigerator 165/175/180/185/190/260/277/286/290/308/310/315/350/360/375 ltr capacity of any type any make for repair/ replacement of defective parts such as condenser, PVC pipe, loose electrical connection etc., cleaning, condenser unit of foreign particle and descaling with carbon di oxide gas to ensure smooth flow of refrigerating gas, reassembling the appliance, testing and placing in original position complete all as specified and as directed by Engineer-in-Charge. Note :- Repair/ replacement of unserviceable parts shall be measured and paid separately complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement condensing coil for refrigerator of capacity 308 to 350 Ltr complete all as specified and directed.
Material and labour for Freezer compartment including door and accessories suitable for refrigerator 260, 286,308, 315 and 350 ltrs capacity refrigerator and including taking existing unserviceable one complete all as specified and as directed.
Material and labour for pressure testing and rectifying the leakage found in the system of refrigerator of capacity 308 to 350 litres including vacuuming and charging the refrigerant (R 134a gas to the desired pressure and filling new compressor oil etc. complete for satisfactory functioning all as specified and as directed. Note: Topping up of gas will be measured and paid separately
Supply and fixing Chiller tray (in replacement) suitable for Refrigerator of any make, 260 to 308 litres capacity, all as specified and directed.
Supply and fixing Evaporator coil, suitable for refrigerator of 260 to 308 ltrs any make size and type (in replacement) all as specified and as directed.
Supply and fixing Vegetable tray (in replacement) suitable for Refrigerator of any make, 260 to 308 litres capacity, all as specified and directed.
Supply and fixing in replacement condensing coil for refrigerator of capacity 260 to 308 Ltr complete all as specified and directed.
Supply and fixing hermetically sealed new compressor (in replacement) for 308 to 350 Ltr capacity of refrigerator including filling of refrigerant suitable and testing complete by disconnecting the electrical and refrigerant connection of defective sealed unit of Refrigerator compressor of capacity 308 to 350 litres. Make :- As per existing make of Refrigerator Note:- (a) Compressor shall be purchased from manufacturer/ authorised dealer of the manufacturer. Compressor shall be in sealed condition and shall bear warranty for 12 months from the date of purchase.
Supply and fixing Evaporator coil, suitable for refrigerator of 308 to 350 ltrs any make size and type (in replacement) all as specified and as directed.
Material and labour for pressure testing and rectifying the leakage found in the system of refrigerator of capacity 260 to 308 litres including vacuuming and charging the refrigerant (R 134a gas to the desired pressure and filling new compressor oil etc. complete for satisfactory functioning all as specified and as directed.Note:Topping up of gas will be measured and paid separately
Supply and fixing ice superior quality plastic/PVC Ice cube tray for refrigerator of capacity 260 Ltrs to 308 ltrs complete all as specified and directed.
Supply and fix in repair electric bulb 20 watt 230v threaded / Bayonet type for refrigerator of any Capacity ltrs complete all as specified and directed.
Supply and fixing PVC shelf transparent type of tough plastic suitable for refrigerator of capacity 260 to 308 ltrs complete including taking down existing unserviceable one all as specified and as directed.
Supply and fixing hermetically sealed new compressor (in replacement) for 260 to 308 Ltr capacity of refrigerator including filling of refrigerant suitable and testing complete by disconnecting the electrical and refrigerant connection of defective sealed unit of Refrigerator compressor of capacity 165 to 255 litres. Make :- As per existing make of Refrigerator Note:- (a) Compressor shall be purchased from manufacturer/ authorised dealer of the manufacturer. Compressor shall be in sealed condition and shall bear warranty for 12 months from the date of purchase.
Material and labour for pressure testing and rectifying the leakage found in the system of refrigerator of capacity 165 to 260 litres including vacuuming and charging the refrigerant (R 134a gas to the desired pressure and filling new compressor oil etc. complete for satisfactory functioning all as specified and as directed.Note:Topping up of gas will be measured and paid separately
Supply and fixing in replacement condensing coil for refrigerator of capacity 165 to 260 Ltr complete all as specified and directed.
Supply and fixing Chiller tray (in replacement) suitable for Refrigerator of any make, 165 to 260 litres capacity, all as specified and directed.
Supply and fix in repair magnetic beading for refrigerator of cap 165 ltrs to 335 ltrs complete all as specified and directed.
Supply and fixing hermetically sealed new compressor (in replacement) for 165 to 260 Ltr capacity of refrigerator including filling of refrigerant suitable and testing complete by disconnecting the electrical and refrigerant connection of defective sealed unit of Refrigerator compressor of capacity 165 to 255 litres. Make :- As per existing make of Refrigerator Note:- (a) Compressor shall be purchased from manufacturer/ authorised dealer of the manufacturer. Compressor shall be in sealed condition and shall bear warranty for 12 months from the date of purchase.
Supply and fixing Relay, box type, suitable for refrigerator of any make 165 to 335 litres capacity (in replacement) fixed in repairs, all as specified and directed.
Supply and fixing Evaporator coil, suitable for refrigerator of 165 to 260 ltrs any make size and type (in replacement) all as specified and as directed.
Material and labour for preparing the old painted surface of refrigerator of capacity 165 litres to 350 litres and spray painting with synthetic enamel paint of approved colour all as specified and directed.
Supply and fixing Vegetable tray (in replacement) suitable for Refrigerator of any make, 165 to 260 litres capacity, all as specified and directed.
Supply and fixing Freezer compartment including door and accessories suitable for refrigerator 165/175 ltrs capacity refrigerator and including taking down existing one complete all as specified and as directed.
Supply and fixing Thermostat, suitable for refrigerator of any make 165 to 350 litres capacity (in replacement) all as specified and directed.
Supply and fixing in replacement Gasket, suitable for door of Refrigerator of any make, 165 to 260 litres capacity, fixed in repairs all as specified and directed.
Supply and fixing Multi capacitors 2 µfd for cooling appliances including taking down existing unserviceable one complete all as specified and as directed. Make :KELTRON/SRIRAM/EPCOS/BHEL/Asian
Servicing the Voltage Stabilizer 0.5 KVA/2KVA single phase after replacing transformer, PCB,u/s electronic parts, setting/testing of buck/boost relay, assemble back & fixing in its original position including testing for proper functioning complete all as specified and as directed.
Supply and fixing Filter of refrigerator including taking down existing unserviceable one complete all as specified and as directed.
Servicing the Voltage Stabilizer 4 KVA to 5 KVA single phase after replacing transformer, PCB,u/s electronic parts, setting/testing of buck/boost relay, assemble back & fixing in its original position including testing for proper functioning complete all as specified and as directed.
Supply and fixing Timer and sensor of Refrigerator including taking down existing unserviceable one complete all as specified and as directed as per Make of Refrigerator
Supply and fixing Over load protector for refrigerator including taking down existing unserviceable one any description complete all as specified and as directed..
Supply and fixing Copper capillary tube suitable for refrigerator including taking down existing unserviceable one, any description complete all as specified and directed.
Supply and fixing Starting relay suitable for refrigerator including taking down existing unserviceable one complete all as specified and as directed Make : SRIRAM/GODREJ/RANUTROL
Supply and fixing Multi capacitors 4 µfd for cooling appliances including taking down existing unserviceable one all as specified and as directed. Make :KELTRON/SRIRAM/EPCOS/BHEL/Asian
Supply and fixing Multi capacitors 2.5 µfd for cooling appliances including taking down existing unserviceable one complete all as specified and as directed. Make :KELTRON/SRIRAM/EPCOS/BHEL/Asian
Material and labour for pressure testing and rectifying the leakage found in the system of Deep freezer of capacity 405 litres including vacuuming and charging the refrigerant Refrigerant gas R-134 a gas to the desired pressure and filling new compressor oil etc. complete for satisfactory functioning all as specified and as directed.Note:Topping up of gas will be measured and paid separately
Supply and fixing Copper capillary tube of Deep freezer including taking down existing unserviceable one, any description complete all as specified and as directed.
Supply and fixing Condenser fan motor of Deep freezer including taking down existing unserviceable one complete all as specified and as directed.
Supply and fixing Thermostat for Deep freezer including taking down existing unserviceable one complete all as specified and as directed.
Supply and fixing hermetic sealed new compressor (in replacement) 1/6 HP suitable for deep freezer of capacity 405 ltr including disconnecting the electrical and refrigerant connection of defective sealed unit of deep freezer 405 litres and connection of all pipe line & charging of refrigerant and testing complete all as specified and directed Note:- (a) Compressor shall be purchased from manufacturer/ authorised dealer of the manufacturer. Compressor shall be in sealed condition and shall bear warranty for 12 months from the date of purchase.
Supply and fixing Starting relay of Deep freezer including taking down existing unserviceable one complete all as specified and as directed.
Supply and fixing Over load protector for Deep freezer including taking down existing unserviceable one, any description complete all as specified and as directed.
Supply and fixing Filter for Deep freezer including taking down existing unserviceable one complete all as specified and as directed
Material and labour for Refrigerant gas, (R 22) Freon suitable for cooling equipment's supplied and filled all as specified and directed.
Taking out, inspection, checking adjustment and minor repair of unserviceable water cooler 40/80/60/120/150/180 ltr capacity of any type any make for repair/ replacement of defective parts such as condenser, PVC pipe, loose water tap, float valve, loose electrical connection etc., cleaning condenser unit of foreign particle and descaling with carbon di oxide gas to ensure smooth flow of water cooler gas, reassembling the appliance, testing and placing in original position complete all as specified and as directed by Engineer-in-Charge. Note :- Repair/ replacement of unserviceable parts shall be measured and paid separately complete all as specified and as directed by Engineer-in-Charge.
Material and labour for pressure testing and rectifying the leakages found in the system of water cooler of capacity 150 litres and vacuuming and charging refrigerant gas (R-134a) and filling new compressor oil etc. complete for satisfactory functioning all as specified and directed. Note:Topping up of gas will be measured and paid separately
Supply and fixing Electric condenser Fan motor, AC 230 volt, single phase with recommended RPM etc. (in replacement) suitable for water cooler of any make of 150/180 litres capacity, all as specified and directed. Make of Fan motor: AUE/ GEC/HIMSUN
Supply and fixing Door gasket (in replacement) suitable for lid of water cooler up to 150 litres capacity, all as specified and directed.
Supply and fix Stainless steel tray (in replacement) suitable for water cooler of 150 Litres capacity all as specified and directed.
Supply and fixing hermetic sealed new compressor (in replacement) for water cooler 150 litre/Hr cooling capacity including disconnecting the electrical and refrigerant connection of defective sealed unit of storage type water cooler of capacity 150 litres and connection of all pipe line & charging of refrigerant and testing complete including taking down existing one all as specified and directed. Make :- As per existing make of Water Cooler Note:- Compressor shall be purchased from manufacturer/ authorised dealer of the manufacturer. Compressor shall be in sealed condition and shall bear warranty for 12 months from the date of purchase.
Taking down corroded bottom portion of water cooler of 150 litres capacity and provision of 14 gauge MS sheet with suitable size angle iron frame work duly welded to the body of the water cooler including two coats of synthetic enamel painting over a coat of red oxide primer to match the existing colour all as specified and directed.
Material and labour for preparing the old painted surface of the water coolers of capacity cap 150 Litres and spray painting with synthetic enamel paint over one coat of red oxide primer including replacement of worn out nut, bolt, washer, screw and writing MES No and capacity all as specified and directed.
Material and labour for pressure testing and rectifying the leakages found in the system of water cooler of capacity 60/120 litres and vacuuming and charging refrigerant gas (R-134a) and filling new compressor oil etc. complete for satisfactory functioning all as specified and directed. Note: Topping up of gas will be measured and paid separately
Supply and fixing Electric condenser Fan motor, AC 230 volt, single phase with recommended RPM etc. (in replacement) suitable for water cooler of any make of 60/120 litres capacity, including taking down existing one all as specified and directed. Make of Fan motor: AUE/ GEC/HIMSUN
Supply and fixing Self closing push type Bib tap 15mm dia made out of cast copper alloy chromium plated (in replacement) suitable for water cooler conforming to ISI mark, including testing and leak proof etc. complete all as specified and directed.
Supply and fixing ball brass valve high pressure 15mm dia complete fitting such as PVC polythene ball, layer check nut washer etc for water cooler of any capacity including taking down existing one all directed.
Supply and fix in replacement of gun metal gate valve 15mm dia including GI nipple including taking down existing one all as specified and as directed
Supply and fixing hermetic sealed new compressor (in replacement) for water cooler 60/120 ltr/Hr cooling capacity including disconnecting the electrical and refrigerant connection of defective sealed unit of storage type water cooler of capacity 60/120 litres and connection of all pipe line & charging of refrigerant and testing complete all as specified and directed. Make :- As per existing make of Water Cooler Note:- Compressor shall be purchased from manufacturer/ authorised dealer of the manufacturer. Compressor shall be in sealed condition and shall bear warranty for 12 months from the date of purchase.
Supply and fixing PVC drain out pipe 30mm dia bore (in replacement) as per existing including providing necessary GI clamps, nut bolt etc.all as specified and directed
Supply and charging of refrigerant gas R-134a to water cooler, refrigerator and deep freezer air conditioner of any type, make and capacity all as specified and directed
Material and labour for pressure testing and rectifying the leakages found in the system of water cooler of capacity 40/ 80 litres and vacuuming and charging refrigerant gas (R-134a) and filling new compressor oil etc. complete for satisfactory functioning all as specified and directed. Note: Topping up of gas will be measured and paid separately
Material and labour for repairing the leakage in the steel water tank of water cooler of any capacity by welding brazing/ soldering complete all as specified and directed.
Taking down corroded bottom portion of water cooler of 40/80 litres capacity and provision of 14 gauge MS sheet with suitable size angle iron frame work duly welded to the body of the water cooler including two coats of synthetic enamel painting over a coat of red oxide primer to match the existing colour all as specified and directed.
Supply and fix Stainless steel tray (in replacement) suitable for water cooler of 40/ 80 litres capacity all as specified and directed.
Supply and fixing Evaporator coil suitable for water cooler of capacity 40/80 ltr/hr cooling capacity (in replacement) complete all as specified directed.
Supply and fixing hermetic sealed new compressor (in replacement) for water cooler 40/80 ltr/Hr cooling capacity including disconnecting the electrical and refrigerant connection of defective sealed unit of storage type water cooler of capacity 40/80 litres and connection of all pipe line & charging of refrigerant and testing complete all as specified and directed. Make :- As per existing make of Water Cooler Note:- Compressor shall be purchased from manufacturer/ authorised dealer of the manufacturer. Compressor shall be in sealed condition and shall bear warranty for 12 months from the date of purchase.
Supply and fixing Electric condenser Fan motor, AC 230 volt, single phase with recommended RPM etc (in replacement) suitable for water cooler of any make of 40/80 litres capacity, all as specified and directed. Make of Fan motor: AUE/ GEC/HIMSUN
Supply and fixing Condensing coil suitable for water cooler of capacity 40/80 ltr/hr cooling capacity (in replacement) complete all as specified directed.
Supply and fixing Carbon (filter) 12” size incl taking down old unsv all as specified and directed
Supply and fixing Multi capacitors 45 µfd for cooling appliances including taking down existing unserviceable one complete all as specified and as directed. Make :KELTRON/SRIRAM/EPCOS/BHEL/Asian
Supply and fixing Multi capacitors 6 µfd for cooling appliances including taking down existing unserviceable one complete all as specified and as directed. Make :KELTRON/SRIRAM/EPCOS/BHEL/Asian
Material and labour for preparing the old painted surface of the water coolers of capacity up to 40/80 Litres and spray painting with synthetic enamel paint over one coat of red oxide primer including replacement of worn out nut, bolt, washer, screw and writing MES No and capacity all as specified and directed.
Supply and fix in replacement of filter for water cooler of any size any make all as specified and as directed
Material and labour for Servicing of Air curtains unit, of any type capacity and length, single phase AC, 230 Volts as in preventive maintenance along with blower assembly filter and other components including checking electrical connections all as specified and as directed.
Material and labour for blower motor assembly of Air curtain unit of any type capacity and length, single phase AC, 230 Volts as including electrical connections all as specified and as directed.
Inspection, checking adjustments and minor repairs of storage water heater 25/50 ltr capacity of any type any make vertical/ horizontal type which includes the following :- (a) Inspection, taking out of drain plug & dewatering and refix the same complete all as directed . (b) Checking water tightness of storage tank . (c) Checking stop cocks with outlet/inlet pipe of geysers, pressure reducing valves etc to ensure free movement of water and easy functioning of parts. (d) Inspecting over flow vent pipe connections to ensure water-tightness and proper flow. (e) Checking and correct earth continuity of electrical items. (f) Checking functioning of heating element and correct setting adjustment of thermostat upto 55º C. (g) Adjustment of reducing valves, checking of dead weight type high pressure release valve and visual check of fusible plug for its intactness. (h) Replacement of defective spares shall be measured and paid under relevant items mentioned below separately as supply and fix.
Note : The following deemed to be inclusive in quoted rate :-
The above job shall be carried out by a trained electrician having ITI in electrical, documentary proof of the education of tradesman shall be produced, before commencement of work.
In case of major defects, entire job shall be completed within 15 days from the date of registration of complaint, failing which penalty charges @100/- per day shall be recovered.
In case of minor defects, entire job shall be completed with in 12 hrs from the time of registration of complaint, failing which penalty charges @ 50/- per job shall be recovered.
The entire job will be carried out in entire area of Air Force stn Jalahalli
All types of T&P, PVC insulation tape, minor nuts, bolts, washers etc required for maintaining the services shall be provided by contractor without any cost to the department.
Supply and fixing Outer body of MS sheet not less than 20 gauge suitable for 25 ltr geyser with white synthetic enamelled paints taking down existing one complete all as specified and as directed.
Supply and fixing Heating element, tikona type, 1.5 KW 230 volts, ISI marked suitable for 25/50 ltrs geysers of any capacity and any make including taking down old one including washer/ packing suitable complete all as specified and as directed.
Supply and fixing PVC connection for hot/ cold water made of double layer nylon braided and fabric at a pressure of 6kg/sq cm at both ends, 450 mm long, heavy duty with CP brass adopters, washers, suitable for 15 mm bore pipe taking down existing one complete all as specified and as directed.
Supply and fixing Outer body of MS sheet not less than 20 gauge suitable for 50 ltr geyser with white synthetic enamelled paint complete all as specified and as directed.
Material and labour for Grouting 4 Nos of M12 X100mm bolt in stone /brick masonry wall with 1:4 CM suitable for hanging geysers
Supply and fixing for provision brazing of inner copper tank Geysers using quality of copper electrode blow lamp welding process brazing length n.exc 10 cm all as specified and directed at site the Engr-in-Charge.
Supply and fixing in replacement pressure relieving valve CP brass confirming to relevant IS with washer suitable for 15mm bore GI pipe suitable for 25/50 ltrs geysers complete all as specified and as directed.
Material and labour in replacement PVC connection for hot/ cold water made of double layer nylon braided and fabric at a pressure of 6kg/sq cm at both ends, 600 mm long, heavy duty with CP brass adopters, washers, suitable for 15 mm bore pipe complete all as specified and as directed.
Supply and fixing Heating element, thread type, 1.5 KW 230 volts, ISI marked suitable for 25/50 ltrs geysers of any capacity and any make including taking down old one including washer/packing suitable taking down existing one complete all as specified and as directed.
Supply and fixing Indicator lamp for geyser 25/50 ltr capacity of colour green & red complete all as specified and as directed.
Supply and fixing Glass wool for insulator of Geysers any capacity and any make taking down existing one complete all as directed by the Engr-in-Charge.
Supply and fixing in replacement thermostat switch range of 30-80 degree suitable for geysers of 25/50 ltrs capacity (ISI marked) complete all as specified and as directed.
Supply and fixing in replacement heating element, cup (square) type, 1.5 KW 230 volts, ISI marked suitable for 25/50 ltrs geysers of any capacity and any make including taking down old one including washer/packing suitable complete all as specified and as directed.
Supply and fixing Copper inner tank of minimum 20 gauge sheet rated pressure not less than 7kg/sqcm suitable for 25 ltrs capacity geysers (wt not less than 3.75 kg) as per sample taking down existing one complete all as specified and as directed.
Material and labour for Cutting and screwing existing steel water tubing 15/20/25 mm bore for addition /alteration required for connections to geysers etc taking down existing one complete all as specified and directed.
Supply and fixing Heating element, tikona type, 2.00 KW 230 volts, ISI marked suitable for 25/50 ltrs geysers of any capacity and any make including taking down old one including washer/packing suitable complete all as specified and as directed.
Supply and fixing in replacement brass non return valves, screwed down, high pressure, screwed both ends for 15mm bore iron pipe or for union, ISI marked, complete all as specified and as directed.
Heating element, thread type, 2.00 KW 230 volts, ISI marked suitable for 25/50 ltrs geysers of any capacity and any make including taking down old one including washer/packing suitable taking down existing one complete all as specified and as directed.
Supply and fixing in replacement bottom cover of MS sheet 20 gauge suitable for 25 ltrs capacity geysers and providing a coat of red oxide to inner surface and applying one coat of synthetic enamel paint by spray painting to outer surface complete all as specified and as directed.
Taking down carefully storage water heater (geyser) 25 ltr capacity of any type, any make from the location by removing the electric & water supply connection and shifted to work shop/MES store yard for repair and re-installation at any location including Supply and fixing in repair of heavy duty pin type fastener 4" long and making necessary inlet/outlet electric & water supply connection from existing source to geyser complete all as specified and as directed. Note :- Adjustment of reducing valves, checking of dead weight type high pressure release valve and visual check of fusible plug for its intactness.
All as per item No. 166 here-in-above but 50 Ltr capacity.
Material and labour for painting of outer surface of 50 ltrs storage type water geysers after cleaning of dust & other organic/inorganic materials if any and applying one coat of synthetic enamel white paint by spray painting and writing MES No on the geyser complete all as specified and as directed.
Supply and install water heater storage type (Geyser) vertical of capacity 25 Ltr, suitable for high pressure up to 8 bar powder coated metal body, temperature indicating dial , glass line coated tank, magnesium anode, efficient long life copper heating element, wattage 2 KW electrically operated, AC 230 Volt, BEE 5 Star Rated with complete fittings/parts and accessories for fixing on wall/surface all as per site required and specified and directed by Engineer-in-Charge. Make:- Bajaj / Recold / Havells
Supply and fixing Copper inner tank of minimum 20 gauge sheet rated pressure not less than 7 Kg/sqcm suitable for 50 ltrs capacity geysers (wt not less than 5.25 kg) as per sample taking down existing one complete all as specified and as directed.
Material and labour for painting of outer surface of 25 ltrs storage type water geysers after cleaning of dust & other organic/inorganic materials if any and applying one coat of synthetic enamel white paint by spray painting and writing MES No on the geyser complete all as specified and as directed.
Supply and fixing in replacement 50 Ltr capacity in any make indoor assembly, compatible to existing geyser, with inlet and thermostat pipe with drain plug inclusive of clamps for holding the element with nuts, bolts and gasket complete all as specified and as directed.
Supply and fixing in replacement 25 Ltr capacity in any make indoor assembly, compatible to existing geyser, with inlet and thermostat pipe with drain plug inclusive of clamps for holding the element with nuts, bolts and gasket complete all as specified and as directed.
Dismantling carefully solar storage water heating system of 100/200/300 Ltr capacity anny type for following works with testing and refixing the same in original position making all water/ electric connection to entire satisfaction of Engineer-in-charge after repair as under :-(a) Inspection, opening, of all parts, descaling, washing of inner tank with chemical solution and cleaning of outer cover storage tank. (b) Checking water tightness of storage tank after cleaning. (c) Checking and correcting earth continuity of electrical items. (d) Adjustment of reducing valves, checking of dead weight type high pressure release valve and visual check of fusible plug for its intactness. (e) Replacement of damaged solar cells (f) Necessary T&P such as ladder, helper shall be contractor responsibility.
Note : The following deemed to be inclusive in quoted rate :-
The above job shall be carried out by a trained electrician having ITI in electrical, documentary proof of the education of tradesman shall be produced, before commencement of work.
In case of major defects, entire job shall be completed within 15 days from the date of registration of complaint, failing which penalty charges @ Rs. 500/- per day shall be recovered.
In case of minor defects, entire job shall be completed with 12 hrs from the time of registration of complaint, failing which penalty charges @ Rs. 100/- per job shall be recovered.
The entire job will be carried out in entire area of Air Force stn Jalahalli
Necessary T&P such as ladder, helper shall be contractor responsibility.
All types of T&P, PVC insulation tape, minor nuts, bolts, washers etc required for maintaining the services shall be provided by contractor without any cost to the department.
Gasket set for solar water heater panel suitable for 100Ltr capacity
Supply and fixing in replacement bib taps, cast copper alloy, with crutch or butterfly handle, chromium plated, fancy type, screwed down, screwed for 15mm bore iron pipe, ISI marked, complete all as specified and as directed.
Supply and Fix in replacement of solar water heater tank 100 ltr capacity tank should be 1.60 mm thickness low carbon steel with porcelain coating, outer tank should be 0.4 mm thickness stainless steel 202 grade Non Magnetic grade, insulation is PUF 50mm including provn for suitable solar tubes complete all as specified and directed. Note :- Solar tubes will be measured and paid separately
Supply only solar cells to replace the damaged cells in the solar panel for solar water heater 100 Ltr capacity
Supply only solar cells to replace the damaged cells in the solar panel for solar water heater 200 Ltr capacity
Supply and fixing in replacement thermostat switch suitable for solar water heater of any make and size complete all as specified and as directed.
Supply and replace solar panel glass suitable for 100 ltrs capacity solar water heater with gasket complete.
Supply and replacement of solar tube as per existing type.
Supply and fix in replacement rotational moulded 300 litres capacity double layered HDPE water storage tanks cylindrical vertical with closed top as per IS 12701-1996 hoisted and fixed in position, including provn of inlet pipe, over flow pipe, washout pipe etc complete all as specified in SSR Part I
Supply and fixing Stop valves, 15 mm Bore of pipe in mm fancy type, chromium plated , high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed.
Material and labour for Staging / steel frame work for Solar water tanks using standard mild steel sections like angle iron / MS pipe / flat iron / sheets etc using steel of Fe 410-W (Gde E-250) quality - A including necessary welding suitable to keep 300 ltrs PVC water tank in repairs complete all as specified and directed by Engr in charge.
Material and labour for taking down of ceiling fan of size 1200/1400mm for safety checking by replacing defective parts/painting/rewinding and re-fixing the ceiling fan after repairs, all as specified and as directed by Engr-in-charge. (Note:- The replacement of unserviceable items like capacitor, Bearings, Bush, Canopy, down rod etc. shall be made as directed by the Engineer-in-Charge which will be measured and paid separately under respective items as Supply only. However, parts of minor nature such as screws, lugs, insulation tape, nuts, bolts, washers etc after cleaning the metal surface, greasing/lubricant etc to make it functional and making connection by replacing PVC insulated unsheathed cable of copper conduct of size 1.5 Sqmm from ceiling rose/ connector fan (minimum 0.50 Mtr length) including cost of labour for above replacement are deemed to be inclusive in quoted rate all as directed.
Note:- The following items shall be deemed to be inclusive in the unit rate quoted against Sl Item No 193 (a) In each job, checking the functioning of fan including its connections, cleaning of fan, greasing of fan and mechanical check i.e. tightening of loose screw, nuts, bolts, etc are inclusive in unit quoted rate.
(b) The above job shall be carried out by a trained electrician having qualified in ITI ( electrician Trade), documentary proof of the education of tradesman shall be produced, before commencement of work.
(c) Replacement of unserviceable parts like rubber bush, clamps, bolts, nuts, washers, safety pin, bearing etc will be paid under respective item here-in-after as supply only through proper documentation.
(d) The entire job will be carried out in Air Force stn Jalahalli
(e) Necessary T&P such as ladder, required manpower for taking down and refixing after repair shall be of contractor's responsibility.
(f) All types of T&P, PVC insulation tape, minor nuts, bolts, washers etc required for maintaining the services shall be provided by contractor without any cost to the department.
(g) Any fan found defective/not working shall be brought to AGE E/M store yard & re-fixed after repairing.
(j) In case of major defects, entire job shall be completed within 10 days from the date of registration of complaint, failing which penalty charges @100/- per day shall be recovered.
(k) In case of minor defects, entire job shall be completed within12 hrs from the time of registration of complaint, failing which penalty charges @ 50/- per job shall be recovered.
Supply only rotor of ceiling fan of any size
Supply only fan canopies for ceiling fan size of 1200mm/1400mm
Supply only gun metal bush of suitable size for ceiling fan 1200mm /1400 mm sweep
Supply only fan bearing suitable for ceiling fan 1200mm /1400 mm sweep (bearing with 8 balls shall be used ) Make:- NBC/TATA/SKF
Supply only down rod for ceiling fan with 15mm dia (of length not less than 45cm and not more than 60cm) with hanging clamps for ceiling fan complete all as specified and directed.
Supply only Rubber reel bushes for ceiling fan of size 1200/1400mm
Supply only 'U' clamp for hanging ceiling fan with all nuts, bolts and washers.
Supply only outer body of ceiling fan of any size
Supply only safety pins 40mm to 50mm long with nuts and bolt with washers for ceiling fan of size 1200/1400mm
Supply only steel screw (for fixing of fan blade) as per site requirement for any make of ceiling fan complete all as specified and directed.
Supply only blades (made of aluminum) suitable for 1400mm sweep ceiling fan of any make with set of screws complete all as specified and directed. Note- Old us blade will be deposited to MES store yard.
Supply only blades (made of aluminum) suitable for 1200mm sweep ceiling fan of any make with set of screws complete all as specified and directed . Note- Old us blade will be deposited to MES store yard.
Supply only down rod for ceiling fan with 15mm dia (of length not less than 90cm and not more than 120cm) with hanging clamps for ceiling fan complete all as specified and directed.
Supply only down rod for ceiling fan with 15mm dia (of length not less than 180cm and not more than 210cm) with hanging clamps for ceiling fan complete all as specified and directed.
Supply and fixing in replacement of unserviceable Ceiling fan 1200mm sweep, energy efficient ISI mark with star rating 230 Volts AC 50 Hz, single phase including provision of fixing arrangement, nut and bolt and flexible 3 core of size 1.5 sqmm not less than 0.5 m long complete including taking down existing one, writing MES No with synthetic enamel paint all as specified and as directed. Make : Havells/ Bajaj/ Orient. Note:- (a) Old Unserviceable ceiling fan shall be deposited to MES store yard.
Supply and fixing in replacement of unserviceable Ceiling fan 1400mm sweep, energy efficient ISI mark with star rating 230 Volts AC 50 Hz, single phase including provision of fixing arrangement, nut and bolt and flexible 3 core of size 1.5 sqmm not less than 0.5 m long complete including taking down existing one, writing MES No with synthetic enamel paint all as specified and as directed. Make : Havells/ Bajaj/ Orient. Note:- (a) Old Unserviceable ceiling fan shall be deposited to MES store yard.
Material and labour for winding of ceiling fan motor 1200 mm sweep of any make with super enamelled copper winding wire of existing gauge (wt of copper winding wire per fan 350 to 500 gms) including cutting and getting out old burnt winding, sleeve work, varnishing with E class insulation varnish, threading, connections with twin core copper flexible wire of size 0.0076mm of length not more than one meter with each fan complete all as specified and directed. (i) Old burnt wire shall be contractor’s property and necessary credit shall be recovered as per credit schedule. (ii) taking down of fan, and re hanging measured under item No. separately.
Description all as per Sl item No 219 here in above but ceiling fan of 1400 mm sweep
(a) Taking down of exhaust fan any size/capacity after disconnecting cable connection, and refixing same in original position after necessary repair/over hauling including replacement of parts of minor nature such as screws, lugs, insulation tape, nuts, bolts, washers etc after cleaning the metal surface, greasing/lubricant etc to make it functional and making connection by replacing PVC insulated unsheathed cable of copper conduct of size 1.5 Sqmm from ceiling rose/ connector fan (minimum 0.50 Mtr length) are deemed to be inclusive in quoted rate all as specified and as directed. (Note:- Rewinding, and materials to be replaced are measured separately.)
(b) The above job shall be carried out by a trained electrician having qualified in ITI ( electrician Trade), documentary proof of the education of tradesman shall be produced, before commencement of work.
(c) Defecting unserviceable part like fan bush, bearing etc. will be paid under respective item here-in-after as supply only through proper documentation.
(d) The entire job will be carried out in Air Force stn Jalahalli
(e) Necessary T&P such as ladder, helper shall be contractor responsibility.
(f) All types of T&P, PVC insulation tape, minor nuts, bolts, washers etc required for maintaining the services shall be provided by contractor without any cost to the department.
(g) Any fan found defective/not working shall be brought to AGE E/M store yard & re-fixed after repairing.
(j) In case of major defects, entire job shall be completed within 10 days from the date of registration of complaint, failing which penalty charges @100/- per day shall be recovered.
(k) In case of minor defects, entire job shall be completed with 12 hrs from the time of registration of complaint, failing which penalty charges @ 50/- per job shall be recovered.
Supply only fan bush of suitable size for exhaust fan of the any sweep
Supply only 4 mfd capacity ceiling /exhaust fan condensers. Make:- Asian/ Tyton/ CG/ Usha
Supply only metal louvers of suitable size for exhaust fan of the 450mm sweep
Supply only fan bearing of suitable size for exhaust fan of 450mm sweep including greasing.
Supply only 3.15 mfd capacity exhaust fan condensers. Make:- Asian/ Tyton/ CG/ Usha
Supply only metal louvers of suitable size for exhaust fan of the 300mm sweep
Supply only fan bearing of suitable size for exhaust fan of 300mm sweep including greasing.
Supply only 2.5 mfd capacity ceiling /exhaust fan condensers. Make:- Asian/ Tyton/ CG/ Usha
Supply only metal louvers of suitable size for exhaust fan of the 250mm sweep
Supply only fan bearing of suitable size for exhaust fan of 250mm sweep including greasing.
Supply and fixing Exhaust Fan 300 mm sweep, 230/240 volt AC single phase, heavy duty, 1400 RPM, corrosion less mild steel body of motor, including necessary cutting, making holes on stone/brick walls where required, fixing arrangement with MS pipe 350 mm dia of required length for protect reshape of stone masonry, suitable hold fast with necessary nut, bolts / screws including taking down existing one writing MES No with synthetic enamel paint all specified and directed. Make- havells /bajaj/ Almonard. Note:- Old Unserviceable domestic exhaust fan shall be deposited to MES store yard.
Supply and fixing Exhaust fan 250 mm sweep 230/ 240 volt AC single phase 410 W, 1400 RPM including necessary nut, bolts / screws including taking down existing one writing MES No with synthetic enamel paint all specified and directed. Make-Havells /bajaj/ Crompton Greaves. Note:- Old Unserviceable Exhaust fan shall be deposited to MES store yard.
Material and labour for winding of Exhaust fan 450 mm sweep of any make with super enamelled copper winding wire of existing gauge (wt of copper winding wire per fan 250 to 500 gms) including cutting and getting out old burnt winding, sleeve work, varnishing with E class insulation varnish, threading, connections with twin core copper flexible wire of size 0.0076mm of length not more than one meter with each fan complete all as specified and directed. Note :- (i) Old burnt wire shall be contractor’s property and necessary credit shall be recovered as per credit schedule.
Description all as per Sl item No 242 here in above but 300 mm sweep
Description all as per Sl item No 242 here in above but 250 mm sweep
Taking down of wall mounted fan any size/capacity after disconnecting cable connection, and refixing same in original position after necessary repair/over hauling . (Note:- Repair, rewinding, over hauling and materials to be replaced are measured separately.)
Supply only fan bearing of suitable size for wall mounted fan of 300 mm sweep make-: SKF/TATA/NBC
Description all as per Sl item No 246 here in above but 400 mm sweep.
Supply only fan bush of suitable size for wall mounted fan of the any sweep
Material and labour for winding of wall mounted fan 300 mm sweep of any make with super enamelled copper winding wire of existing gauge (wt of copper winding wire per fan 350 to 500 gms) including cutting and getting out old burnt winding, sleeve work, varnishing with E class insulation varnish, threading, connections with twin core copper flexible wire of size 0.0076mm of length not more than one meter with each fan complete all as specified and directed. Note :- (i) Old burnt wire shall be contractor’s property and necessary credit shall be recovered as per credit schedule.
Description all as per Sl item No 249 here in above but 400 mm sweep
Taking down aluminum/copper point wiring on & including hard wood battens, surface conduit and board/ blocks etc or through conduits for light, socket or power point, fan point complete (Taking down of fittings such as switches, sockets, bells, ceiling rose, holders , regulators, light fittings, MCB, lamps etc shall be measured and paid separately) and making good the disturbed plaster surfaces of wall, floor, ceiling and painting 2 coat of white wash/distemper to meet the existing surface and removing materials and debris to reinstate the premise neat and clean complete all as specified and directed.
Material and labour in repairs for point wiring using approved colour coding as per IS for one light/bell/buzzer point controlled by one switch or one fan point controlled by one switch & fan regulator with PVC insulated, unsheathed FRLS multi stranded copper conductor 1.5 sqmm (nominal area) 1100 volt grade ISI 694 marked cable for phase & neutral drawn through surface PVC conduit/ existing concealed PVC Conduit, ISI marked with and including new MS/ cast iron sunken boxes duly painted with two coats of anticorrosive paint over a coat of red oxide primer on surface in touch with wall and synthetic enamel paint over a coat of red oxide on other side, covered with 3mm thick plastic laminated sheet for mounting switches, regulators, sockets etc including 1.5 sqmm (nominal area) copper conductor PVC insulated, unsheathed, multi stranded FRLS cable as earth wire and connected to earth dolly complete all as specified and as directed. Make of Conduit : Avon Plast/ Supreme/ Diplast Make of Wire : Plaza/ Polycab/ Havells Note: (a) Switches, sockets outlets, blanking plate, Light fittngs, fans, bells & regulators will be measured and paid for separately).
One light point/fan/bell point controlled by one switch
All as per item No. 253 here in before but for one 3 pin socket out 5 amp on the same board
All as per item No. 253 here in before but for one switch socket outlet 3 pin 5 Amps on independent board
All as per Sl No 253 above but Wiring with 4 Sqmm copper multistranded unsheathed cable and 4 Sqmm copper cable for earth continuity conductor controlled by one 15A switch socket independently
Material and labour in repairs for point wiring complete with 1.5 sqmm single core PVC insulated, unsheathed fire retacable 1100 volts grade, multi stranded with copper conductor drawn through and incl surface PVC Conduit/ existing concealed conduit with accessories in wall/roof/ceiling etc incl MS modular terminal boxes, concealed surface to walls covered with modular plates with cover etc and 1.5 sqmm PVC insulated, unsheathed copper conductor multistranded cable 1100V grade as earth continuity conductor & connecting to common earth dolly all as specified for Make of Cable : Plaza/ Polycab/ Havells Make of Conduit : Supreme/ Diplast/ Avon Plast Note: (a) Switches, sockets outlets, blanking plate, Light fittngs, fans, bells & regulators will be measured and paid for separetely).
One light point/fan/bell point controlled by one switch
All as per item No. 258 here in before but for One 3 pin socket out 5 amp on the same board
All as per item No. 258 here in before but for one switch socket outlet 3 pin 5 Amps on independent board
All as per Sl No 258 above but Wiring with 4 Sqmm copper multistranded unsheathed cable and 4 Sqmm copper cable for earth continuity conductor controlled by one 15A switch socket independently
Supply and Fix switch piano flush type 5 Amps 240 volts single pole one way. Make : Anchor, Havells, L&T
Supply and Fix switch piano flush type 15 Amps 240 volts single pole one way. Make : Anchor, Havells, L&T
Supply and Fix shuttered socket outlet 3 pin 5 amps, flush type Make : Anchor, Havells, L&T
Supply and Fix shuttered socket outlet 2 in 1, 3 pin, 5 and15 amps Make : Anchor, Havells, L&T
Supply and Fix modular switch 1 way 6 amp.1 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply and Fix modular Socket, 6A - 2/3 pin combined 2 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply and Fix modular switch 1 way 16 amp.1 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply and Fix modular Socket, 16A - 2/3 pin combined 2 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply and fixing in replacement on distribution board MCCB four pole, 100 Amp ultimate breaking capacity 16 KA complete conforming to IEC -61439-1 complete all as specified. Make : Indoasian/ L&T/ Havells
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables for foundation and laying of cable/erecting poles up to proper level complete all as specified and directed by Engr-in-charge.
Returning and filling in soil including spreading leveling watering and well ramming in layers not exceeding 25cm all as specified.
Removing surplus excavated material from excavation not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point complete all as specified and directed by Engr-in-charge.
Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983 and as directed. Note :- Excavated approved soil shall be ribbed by using sieve to separate composite particles etc as per IS and refiiling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is than gently punned down to a depth of 10 cm above the top of upper most cable (ii) For the purpose of measurement only punned thickness only will be considered for payment.
Material and labour for well burnt as class ‘B’ bricks as mechanical protection to under ground cables laying with length of the bricks equal to the width of the trench complete all as specified and directed by Engr-in-charge.
Material and labour for cutting of bituminious road/ hard standing/PCC path/wall up to a size not exceeding 20cm width and not exceeding 60cm in depth for laying of protection pipe for cable including making good the disturbed road/hard standing by providing PCC (1:2:4) type B1, 40 mm grade crushed stone aggregate up to existing surface level or removing the any type of tiles carefully and refixing properly as per existing surface complete all as specified and as directed.
Supply and fixing in replacement of GI tubing light grade of size 40 mm dia fixed on walls / laid in trenches as protection pipe for under ground cable including provisioning of specials and clamps etc complete all as speified and directed.
Supply, Laying and testing XLPE UG cable 25 sqmm cross sectional area and 3.5 core PVC insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade in trenches including taking up defective unserviceable cable all as specified and directed.
Supply, Laying and testing XLPE UG cable 35 sqmm cross sectional area and 3.5 core PVC insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade in trenches including taking up defective unserviceable cable all as specified and directed.
Material and labour Earthing with Galvanised Earth Plate Electrode 600x600x 6mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, connected with Galvanised Earth Strip of size 25x6mm (upto 7.5m length) by means of Bolts, Nuts, Check Nuts and Washers of GI or Steel and connected Earthing Testing Point/Bus-bar including GI 40mm bore (dia) light grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt, Magneisum Sulphate (1 : 1 : 0.5) in alternate layers of not exc 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50 mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, Funnel with GI Watering Pipe 20mm bore (dia) medium grade including necessary Excavation in any type of soil, Returning, Filling in and Removal of surplus Spoil disposal to out side MD land and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including taking down old unserviceable one, complete all as per specified and as directed.
(a) All Joints should be joined by Exothermic Welding or Brazing. (b) After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge, User and proper record shall be maintained duly signed by all concerned. (c) Earth resistance tester shall be provided by the contractor. It should be calibrated from authorised company/ lab. (d) After testing if desired earth resistance of less than 5 Ohm is not obtained, the earthing will be redone at no extra cost to Govt till desired result is obtained.
Material and labour in repairs Galvanised Earth strip of size 25 x 6 mm fixed on proper post insulator at the instrument end complete all as per specified and as directed.
PLATINUM CONSTRUCTIONS
eurekaenterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .