Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.1 LAccepted-AOC | ₹19.1 L Quoted ₹21.0 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹21.4 L+₹35,257 (1.68%)Rejected-Finance 307 SADAR BAZAR LUCKNOW UP 226002 | LUCKNOW | UTTAR PRADESH | 226002 | ₹21.4 L+₹35,257 (1.68%) | L2 | Rejected-Finance Not Being Lowest Bidder |
| 3 | L3₹23.5 L+₹2.5 L (11.7%)Rejected-Finance | ₹23.5 L+₹2.5 L (11.7%) | L3 | Rejected-Finance Not Being Lowest Bidder |
| 4 | L4₹23.7 L+₹2.7 L (12.8%)Rejected-Finance | ₹23.7 L+₹2.7 L (12.8%) | L4 | Rejected-Finance Not Being Lowest Bidder |
| 5 | L5₹24.4 L+₹3.3 L (15.9%)Rejected-Finance | ₹24.4 L+₹3.3 L (15.9%) | L5 | Rejected-Finance Not Being Lowest Bidder |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
12 Oct 2020, 6:00 pmClosed
GE E/M Lucknow
Garrison Engineer E/M, 36 LBS Marg, Lucknow Cantt, Lucknow (U.P.) PIN 226002
REPAIR/MAINT LT OVER LINE UG CABLE WITH OTHER CONNECTED WORKS AT CHCC UNDER GE E/M LUCKNOW
2020_MES_375495_1
GE/EM/LKO/HOSP/T-45 OF 2020-2021
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Lucknow
Class D or above category b(i)
8 documents required · 8 mandatory
₹500
Yes
GE E/M Lucknow
₹90,000
Yes
10 Dec 2020
7 Sept 2020
14 Oct 2020
7 Sept 2020
12 Oct 2020
28 Sept 2020
Amount
Supplying and laying or fixing in replacement, jointing and testing LT under ground electric power cable crossed linked polyethylene ( XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 10 sqmm cross sectional area, 2 core ,complete all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers complete all as specified and directed. Note :- Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items.
All as per item No 1 above but of size 10 Sqmm 4 core
All as per item No 1 above but of size 16 Sqmm 4 core
All as per item No 1 above but of size 25 Sqmm 3.5 core
All as per item No 1 above but of size 50 Sqmm 3.5 core
All as per item No 1 above but of size 95 Sqmm 3.5 core
All as per item No 1 above but of size150 Sqmm 3.5 core
All as per item No 1 above but of size185 Sqmm 3.5 core
All as per item No 1 above but of size 240 Sqmm 3.5 core
S & F GI Pipes galvanized, “light grade ”, laid in trench complete including fittings 80 mm dia.protection for LT Cable.
S & F GI Pipes galvanized, “light grade ”, laid in trench complete including fittings 50 mm dia.protection for LT Cable.
S & F GI Pipes galvanized, “light grade ”, laid in trench/or fixed on pole complete including fittings 40 mm dia.protection for LT Cable.
M&L for PCC 1:2:4 type B0 12.5 mm graded agregrate as in foundation in copin gin foundation of pole including necessary form work complete all as specifies and directed.
M& L for dismantling of vintage over head LT ACSR conductor distribution line of any capacity complete all as specified and Directed .
M& L for dismantling of GI brackets cross arms, etc of any size anti climbing divices etc complete all as specified and directed.
M& L for dismantling of insulator with pin of any size etc complete all as specified and directed.
M& L for fabrication and fixing canopy headed junction box suitable for LT Pole made out 3.15 mm MS sheet of size 30x25x15 cm with cover ,04 nos aluminium bus bar of size 25x3 mm for phase and neutral 01 nos 06 Amps MCB SP mounting channel for control street light cable gland aluminium lug MS FIixing clamp -02 nos with nut bolt washer painting with two coat of synthectic enamel paint over a coat of red oxide primer on external and internal surface complete all as specified and directed
Labour work required for taking out old LT T XLPE cable 1100 Volts of any size and any description from trenches including proper handling for further uses all as per specified and directed
Labour work required for Laying down LT T XLPE cable 1100 Volts of any size and any description in trenches all as specified and directed (Note - Brick and Sand will mwasure and paid separately )
Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, pipes etc. and getting out including trimming the sides and forming bottom surfaces to required levels in soft/loose soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, and well ramming in layer not exceeding 25 cm thick in soft/loose soil complete all as specified and directed.
Removing excavated material ( soils) not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified.
Material and labour for river sand, washed and screened dry for cushioning to under ground cable in trenches below and around under ground cable including spreading and levelling complete as specified and directed . Note :- Punned thickness shall only be considered for payment
M&L laying well burnt old size bricks, sub class "B" bricks, straight or curved on plan , laid flat with width equal to length of brick , laid dry over electric cable for protection all as specified.
Supply, fixing, connecting and testing energy efficient LED blolard light of 18 Watt including foundation work with pCC a srequired all as specified and directed.
Supply, fixing, connecting and testing energy efficient LED Garden landscape view LANTERN WITH SYMMETRIC LIGHT DISTRIBITION AND LIMITED UPWARD LIGHT COMPONENT light of 18 Watt all as specified and directed.
Supply, installation, testing and commissioning of Polycrystaline Photovoltaic Module of 315Wp each.The PV modules used must qualify to the latest edition of IEC PV module qualification test or equivalent BIS standards. Crystalline Silicon Solar Cell Modules IEC 61215. In addition, the modules must conform to IEC 61730 Part-1 - requirements for construction & Part-2 requirements for testing, for safety qualification or equivalent IS. I-V curve of module at STC should be provided by bidder.The total solar PV array capacity should not be less than allocated capacity (kWp).The module frame shall be made of corrosion resistant materials silver anodized aluminium alloy.The bidder shall carefully design & accommodate requisite numbers of the modules to achieve the rated power. The module junction box should not be less than IP67 protection.The manufacturer should warrant the Solar Module(s) to be free from the defects and/or failures specified below for a period not less than ten(10) years from the date of sale to the original customer. The make of Solar PV modules should be : TATA/Havells/Panasonic or equivalent as approved by GE.
M&L for taking proper shut down, disconnecting incoming / out going cable, control cable from 11 KV OCB/VCB of any type and capacity upto 630 amps and carrying out complete servicing / overhauling, resetting of all electrical and mechanical parts for easy and proper operation, greasing of moving / revolving / sliding parts in VCB Panel, calibration of relays, meters incl thorough cleanining with air blower / vacuum cleaner, decarbonising & providing mineral jelly to all arcing contacts of the VCB panel, and serviceability check from local / remote control panel including replacement of unserviceable minor spare parts viz. nut / bolt / washer / connecting wire / insulation tape / sleeves etc complete including reassembling complete parts reconnecting incoming / outgoing cable, testing on load and all as specified and directed by Engr-in-Charge. Note- 1. Unserviceable items other than minor parts to be replaced will be meaured and paid seperately as supply only under revelent items in the schedule. However, cost of certain minor spares viz nut / bolt / washer / connecting wire / insulation tape / sleeves etc. if required shall deem to be included in the cost of repair of the item. 2. The spare parts to be replaced shall be of reputed brand / make and shall be of same type, design, specifications etc to match with the existing and as per the recommendation of OEM. 3. Complete servicing and calibration work shall be carried out by qualified and reputed service engineer only.
M&L for Space Heater 230 V AC
M&L for Motor and gear assembly 110 V AC/DC VMG -14 type
S&F Digital type Volt meter 0-15KV, PT operated 110 Volt input complete all as specified and directed.
S&F Digital type Ampmeter CT operated, 5 Amp input complete all as specified and directed.
M&L for painting of two pole/four pole structur including cross arms,chanel etc complete structure after scraping old paint with two coats synthetic aluminium paint after applying one coat of zinc oxide primer complete all as directed by Engr-in-Charge
M&L for painting of LT pannel off size structur including cross arms,chanel etc complete structure after scraping old paint with two coats synthetic aluminium paint after applying one coat of zinc oxide primer complete all as directed by Engr-in-Charge
Supply & fixing in replacement MCCB Four Pole 400 Amp,36 kA, 415 volts 'B' curve complete all as specified
Supply & fixing in replacement MCCB Four Pole 600 Amp,36 kA, 415 volts 'B' curve complete all as specified
S&F Straight through joints (Heat Shrink Kits) for LT underground cable indoor/outdoor type complete for Armoured ,PVC sheathed Aluminium conductor cables Including excavating earth, identifying the fault, making proper joint of cable after rectification & returning soil back to earth, complete all as specified and directed for the 3.5 core cable 25 to 50 Sq mm. sizes.
All as per item No 39 above but 3.5 core cable 70 to 150 Sq mm
All as per item No 39 above but 185 sqmm to 300 sqmm 3 ½ core
Supplying, transporting, erecting and fixing Steel tubular swaged poles type 410 SP-31 ( 9.0 metres long) complete with cast iron base plate, finial, taper plug, bolts, nuts and screws as specified, including necessary excavation and earth work , PCC 1:4:8 type D2 in foundations below pole, PCC 1:3:6 type C2 around poles and PCC 1:3:6 type C1 as in plinth block , disposal of surplus soil to a distance not exceeding 50 m and depositing where directed, painting steel tubular poles exposed surafces with Aluminium paint two coats over one coat of red oxide primer and providing 300 mm wide bands (3 bands/ straps with synthetic enamel paint and 2 bands with Black bituminous paint ) from plinth block and numbering of poles , painting embedded portion of poles with one coat of bituminous paint complete all as specified and directed. Note -Old pole will be deposited in MES store yard
M&L Earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased in and including 40 mm dia GI 'light grade' pipe from upper end of earth plate upto equipments,20 dia bore GI pipe 'light grade' as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe and PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as described in electric plate of SSR Part I complete all as specified and directed and testing on completion. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
M/s Vatsh Raj and co
Shree Tirupati Associates
m/s pal associates
Ajanta Associates
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .