Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.1 LAccepted-AOC | L1 | Accepted-AOC Being lowest tenderer | |
| 2 | L2₹36.8 L+₹17,362.25 (0.47%)Rejected-Finance | L2 | Rejected-Finance Being other Lowest Tenderer | |
| 3 | L3₹38.8 L+₹2.1 L (5.82%)Rejected-Finance B BLOCK 2 3 RAM BACHAN V B NAGAR PIPE ROAD KURLA W MUMBAI 400070 | MUMBAI SUBURBAN | MAHARASHTRA | 400070 | L3 | Rejected-Finance Being other Lowest Tenderer | |
| 4 | L4₹40.3 L+₹3.7 L (10.00%)Rejected-Finance B 134 GANESH MURTHI NAGAR PART III COLABA MUMBAI 400 005 | MUMBAI | MAHARASHTRA | 400005 | L4 | Rejected-Finance Being other Lowest Tenderer | |
| 5 | L5₹40.3 L+₹3.7 L (10.1%)Rejected-Finance FLAT NO 301 PEARL APARTMENT PLOT NO 121 SECTOR 8A AIROLI NAVI MUMBAI 400708 | NAVI MUMBAI | THANE | MAHARASHTRA | 400708 | L5 | Rejected-Finance Being other Lowest Tenderer |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
11 Oct 2022, 6:00 pmClosed
Lt Col Ng Rajesh Singh GE NW KUNJALI
GARRISON ENGINEER NW KUNJALI DR HOMI BHABHA ROAD NAVY NAGAR COLABA MUMBAI 400005
8485 MAINT REPAIR REPLACEMENT OF LT PANEL LT UG CABLE AND OTHER ALLIED WORKS AT INS KUNJALI INWTC BV YARD CWE COMPLEX UNDER GE NW KUNJALI
2022_MES_551804_1
8485/E8
Open Tender
Civil Works
Item Rate
183 days
GE (NW) KUNJALI
ALL AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
Yes
GE (NW) KUNJALI
₹96,000
Yes
24 Jan 2023
14 Sept 2022
13 Oct 2022
21 Sept 2022
11 Oct 2022
28 Sept 2022
14 Sept 2022 - 21 Sept 2022
Amount
Taking down security/street light fitting for repair & checking internal wiring, cleaning complete & refixing the same on position after rectification of defects/replacement of items
S & F modular power socket 25A,2 module, 25A plug top, 25A mini MCB 'C' series 3KA including 4 module box with cover plate complete all as specified and directed by EIC. Make: Anchor/Roma/Crabtree SAP code : ACNKCXW253, DCTNCSPA025,ACAGXXW253, ACVPPCWV03,ACTXPIWX03
S&F in repair FRP looping box 225x295x122mm with locking arrangement, shockproof and rustproof, rot-proof and termite resistance, cable entry from bottom and side, 100% weather proof for outdoor installation suitable for pole mounting, tamper proof, restricts unauthorised tapping, IS 11731, IP 66/67 suitable for 16-35 sqmm 3.5 core aluminium cable including 1 No MCB 2-32 Amp and connector block two way and fixing with flat aluminium clamps not less than 25 mm x 3 mm with suitable size nuts, bolts and washers inside and outside looping box complets as directed.Make : National/Sintex/Hensel Cat No: KF 3500H
M&L for Scraping old paint from steel tubular poles by wire brush not more than up to 9.0 mtr length above ground level including street light arm applying one coat of steel primer and two coat of aluminium paint and marking pole No. all as directed by Engr-in-charge.
S & F in replacement decorative LED post tops with transparent diffuser 20W, IP 65 protection complete with all accessories and all as specified and directed by Engr-in-charge Make : Bajaj or equivalent in C&S Cart Part No LTGLC20WHPLED/W/ Havells
S & F in replacement LED garden light 9W cylindrical shaped integral decorative LED bollard with opal acrylic diffuser and IP 65 with all accessories includingn PCC foundation tapper plug, bolts, nuts, screws etc complete all as specified and directed by Engr-in-charge. Make : Bajaj /C&S/ Havells
S&F in replacement of LED street light 120 W energy saving and envirment friendly light fitting with housed in pressure dia cast aluminium housing with sealed toughened glass cover, SMD LED with secondery lens luminaires with IP 66 protection including all fixing accessories complete all as specified and directed by Engr-in-Charge. Bajaj/ Havells/C&S
S&F in replacement of LED street light 90 W energy saving and envirment friendly light fitting with housed in pressure dia cast aluminium housing with sealed toughened glass cover, SMD LED with secondery lens luminaires with IP 66 protection including all fixing accessories complete all as specified and directed by Engr-in-Charge. Bajaj/ Havells/C&S
Supply and fix in replacement of LED flood lights 250 W energy saving and enviromental friendly light fitting IP 66 high power LED floodlight with pressure die cast aluminium housing complete with all accessories. C&S / Havells/Bajaj
S&F in replacement of LED highbay light 150 W energy saving and envirment friendly light fitting, pressure dia cast aluminium housing with aim & adjustable bracket, matt finished reflector for gglare elimination, SMD LED with secondary lens with IP 66 protection including all fixing accessories complete all as specified and directed by Engr-in-Charge. bajaj/C&S/Havells/Philips
S&F in repair of LED Aviation Light Luminaries all as specified and directed. Make : Bajaj Cat No BGAV 302 LED/CG/Philips
Supply and Laying 2 core 16 Sqmm testing and commissioning PVC insulated PVC sheathed armoured electric cable with aluminium conductor laid in trenches, passing through pipes, fixed on wall complete including connecting properly by means of thimble and taking out damaged unserviceable cable of the following sizes.
Supply and lay in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded copper conductor of size 10sq mm 4 core. laid in trench/ duct / along pole/wall etc including making connection complete all as directed. MAKE : Gloster/Polycab/Finolex/Havells/Plaza Note : 1. The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and Laying 4 core 16 Sqmm testing and commissioning PVC insulated PVC sheathed armoured electric cable with aluminium conductor laid in trenches, passing through pipes, fixed on wall complete including connecting properly by means of thimble and taking out damaged unserviceable cable of Make : Polycab/ Havells/ Plaza/ Gloster. Note : 1. The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and Laying 3..5 core 25 Sqmm testing and commissioning PVC insulated PVC sheathed armoured electric cable with aluminium conductor laid in trenches, passing through pipes, fixed on wall complete including connecting properly by means of thimble and taking out damaged unserviceable cable. Note : 1. The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and Laying 3.5 core 35 Sqmm testing and commissioning PVC insulated PVC sheathed armoured electric cable with aluminium conductor laid in trenches, passing through pipes, fixed on wall complete including connecting properly by means of thimble and taking out damaged unserviceable cable. Note : 1. The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and Laying 3.5 core 50 Sqmm testing and commissioning PVC insulated PVC sheathed armoured electric cable with aluminium conductor laid in trenches, passing through pipes, fixed on wall complete including connecting properly by means of thimble and taking out damaged unserviceable cable. Note : 1. The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and lay in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded copper conductor of size 95 sq mm 3.5 core. laid in trench/ duct / along pole/wall etc including making connection complete all as directed. MAKE : Gloster/Polycab/Finolex Note : 1. The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and lay in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded copper conductor of size 120 sq mm 3.5 core. laid in trench/ duct / along pole/wall etc including making connection complete all as directed. MAKE : Gloster/Polycab/Finolex Note : 1. The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and lay in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded copper conductor of size 185 sq mm 3.5 core. laid in trench/ duct / along pole/wall etc including making connection complete all as directed. MAKE : Gloster/Polycab/Finolex Note : 1. The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and lay in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded copper conductor of size 240 sq mm 3.5 core. laid in trench/ duct / along pole/wall etc including making connection complete all as directed. MAKE : Gloster/Polycab/Finolex Note : 1. The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supply and lay in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded copper conductor of size 300 Sqmm 3.5 core. laid in trench/ duct / along pole/wall etc including making connection complete all as directed. MAKE : Gloster/Polycab/Finolex/ Note : The cost of thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
S & F in replacement hot dip galvanized anti corroded weather proof octagonal electric poles 8 Mtrs long top mounting on foundation complete with base plate including PCC foundation as per SSR provision and directed with 1500 mm long arms bracket, tapper plug, bolts, nuts and screws etc as specified complete including taking out existing RCC/damaged rusted MS pole with street light and street light bracket complete all as specified and directed by EIC. Make Bajaj
S & F in replacement hot dip galvanized anti corroded weather proof octagonal electric poles 9 Mtrs long top mounting on foundation complete with base plate including PCC foundation as per SSR provision and directed with 1500 mm long arms bracket, tapper plug, bolts, nuts and screws etc as specified complete including taking out existing RCC/damaged rusted MS pole with street light and street light bracket complete all as specified and directed by EIC. Make Bajaj
Excavation in trenches n exc1.5m wide and n exc in depth for laying of cables and getting out in loose/soft soil complete all as directed.
Returing filling in including spreading, levelling watering and well ramming in layers not exc 25cm complete all as directed.
Removing excavated material n exc 50cm and deposting where directed at a level n exc 1.5m above the starting point complete all as directed.
Material and labour for sand filling in trenches fine dry sand as sand cushioning to cable 8 cm before laying of cables and 15 cm after laying cable which shall be punned down to 10 cm complete all as specified and directed. (Note : Only punned down thickness shall be measured and paid)
M&L for un-reinforced,precast concret cable cover of size 250x150x40mm class LV type-I for cable protection all as specified and directed
Supply and fix in replacement MS arms bracket 30 degree bend, 1.5mtr long for mounting one in nos street light fitting including clamps / nut / bolts & washer to brace the same properly with duly painted in synthetic enamel paint of two coat in silver colour complete all as specified and directed by the Engr-in-Charge.
S&F GI tubing light grade 80mm dia with all fittings laid in trenches/fixed on wall/ceiling including dismantling of old pipe etc all as specified and directed. Make : Jindal/Tata/Surya Prakash
S&F GI tubing light grade 100 mm dia with all fittings laid in trenches/fixed on wall/ceiling including dismantling of old pipe etc all as specified and directed. Make : Jindal
Cutting road/hard standing for laying of cable and re mataling/making good the same to match the existing surface complete all as directed by Engr incharge.
Taking down the LT ACB of capacities 630Amps to 2000Amps of any make for repairs, servicing, comprising the following & refixing the same, re-orientation & labour for taking, defective parts & refixing the same spare parts:- (a) Checking /repairs of the mechanism of ACB (b) Checking/repair of the manual closing of the breakers (c) Decarburizing, setting reassembling, cleaning adjustment of fixed contacts, main contact & chamber and applying petroleum jelly all as complete.
Decorbonising /cleaning of LT 415/380V 3 phase bus bar, bus bar chambers of feeder pillar box, electrical connection complete, ACB, switch fuse unit arrangement incoming & outgoing installed in at various location after removing the complete bus bar from the bus chamber, cleaning with CTC & insure proper decorbonising refixing the same applying backtal (red) solution to the bus bar insulator & checking all the connections & tighting the nuts & bolts thimbles of incoming & out going system complete including replacement of defective rusted bolts, nuts & washers all as specified & directed.
Decorbonising/ cleaning of ducts of HT/LT cable from various location as per following description. (a)Removing of accumulated, stanated water/oil from the duct either manually or mechanically.(b) Cleaning of cable bunch in duct of all accumulated slit/mud/debris/foreign material. (c) Removing & repositioning of RCC/MS duct covers including one coat of red oxide and one coat of black paint as required.(d) Patch civil work plastering and concreting work.
S&F in repairs of 0.71mm thick powder coated aluminium sheet cover, alloy 31000 H4 in ridges, Hips vally gutter including suitable size of revits/nut bolts complete bending, shaping, drilling, cutting notching and all as specified and directed by EIC.
S&F in repair of double door type vertical type TPN DB 4 Way ,240V with 100A copper busbar , double door type IK 09 protection suitable for housing MCCB's all as specified and directed by EIC.Make: Legrand cat No 507781/Seimens/C&S. Note : DBs shall be concealed in wall where ever posible including making good the surface to match with surrounding.
S&F in repair of double door type vertical type TPN DB 6 Way ,240V with 100A copper busbar , double door type IK 09 protection suitable for housing MCCB's all as specified and directed by EIC.Make: Legrand cat No 507781/Seimens/C&S. Note : DBs shall be concealed in wall where ever posible including making good the surface to match with surrounding.
S&F in repair of double door type vertical type TPN DB 8 Way ,240V with 200A busbar , with metalic double door type IP 43 IK 09 protection suitable for housing MCCB's all as specified and directed by EIC.Make: Legrand cat No 507783/Seimens/C&S. Note : DBs shall be concealed in wall where ever posible including making good the surface to match with surrounding.
S & F MCCB FP 100 Amps,16KA, complete all as specified and directed. Make : Legrand cat No 420015/Seimens/C&S
S & F in repair of Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20A all as specified and directed by EIC. Make: Siemens/Legrand/C&S.
S & F in repair MCB DB double door SPN 12 Way with 200 Amps rated copper bus bar all as specified and directed. MAKE: C&S/Legrand / seimens/C&S
S & F in repair MCB DB double door SPN 8 Way with 200 Amps rated copper bus bar all as specified and directed. MAKE: C&S/Legrand / seimens/C&S
S & F MCB SP 02 Amps,10KA. 230volts all as specified and directed. MAKE: C&S/Legrand / seimens/C&S
S & F MCB SP 6-32 Amps,10KA. 230volts all as specified and directed. MAKE: C&S/Legrand / seimens/C&S
S & F MCB SPN 63 Amps,10KA, 230Volt all as specified and directed. MAKE: C&S/Legrand / seimens/C&S
M& L for Disconnecting the electric connection and replacement of unserviceable MCCBs of following capacities :-
a) MCCB 63 Amps, 25 KA capacity 3 Pole. Make C& S/ Legrand/GE
b) MCCB 100 Amps 25 KA capacity 3 Pole. Make C& S/ Legrand/GE
c) MCCB 125 Amps 25 KA capacity 4 Pole. Make C& S/ Legrand/GE
d) MCCB 200 Amps 36 KA capacity 4 Pole.Make C& S/ Legrand/GE
e) MCCB 250 Amps 36 KA capacity 4 Pole. Make C& S/ Legrand/GE
f) MCCB 400 Amps 36 KA capacity 4 Pole.Make C& S/ Legrand/GE
g) MCCB 630 Amps 36 KA capacity 4 Pole.Make C& S/ Legrand/GE
Supply and fixing in repair new generation recessed mounted ultra slim panel LED 2X2 Luminaire 36 watt and CRCA powder coated body and high translucent diffuser provides high quality ecomonic energy saving lighting to modern offices. Suitable for 600 x 600 mm modular/POP/Gypsum ceiling. Make : CG/wipro/C&S Cat No: LTCRSLM36WATT2x2/Bajaj/Havells/Philips/Shakti/Goldmodal
Supply and fix in repair of STRAIGHT THROUGH JOINT complete with jointing material (Heat srinkable) for 1100V grade cable for XLPE armoured alluminium conductor cable of size 120 to 185 sqmm 3.5 cre complete all as specified and directed. Make : Rychem/3M
Supply and fix in repair of STRAIGHT THROUGH JOINT complete with jointing material (Heat srinkable) for 1100V grade cable for XLPE armoured alluminium conductor cable of size 240 to 400 sqmm 3.5 cre complete all as specified and directed. Make :Rychem/3M
Supply and fix in repair of STRAIGHT THROUGH JOINT complete with jointing material (Heat srinkable) for 1100V grade cable for XLPE armoured alluminium conductor cable of size 95 to 120 sqmm 3.5 core complete all as specified and directed. Make :Rychem/3M
Supply , fixing, testing in repairs of JEF ECO SAFE Maintenance Free Grounding Solution set comprising of High tensile low carbon steel rod of 3 Mts length & 25 mm dia with 250 micron ( averaSchneider ) molecularly bonded copper on the outer surface to confirm with requirements of UL467 along with Back-fill compound strictly be a Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr as per Clause 14.5D of IEEE : 80 standard. Back-fill compound should be electronically conductive ( Like in metals ) and should not depend on moisture for conduction. JEF Powerfill Loresco compound shall be supplied in 50 Pound Bag. ( 1 Bag of 50 Pounds required per earthing set). Back-fill comound should be environment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground. A suitable earth terminaton clamp should also be supplied along with the set alongwith earth pit weatherproof incl all as specified . Note : Back-fill compund shall not be mixed with any soil while pouring in the bore hole.
S&F in repair of 50 Sqmm single core copper cable or main earthing lead fixed to wall with clamps or recess or croses or buried in ground or drawn in conduits/pipe or fixed to poles or any other indicated situation for loop earthing etc as required all as specified and directed by Engr-in-Charge. Make Polycab/Plaza/Havells
M&L for 25x4mm GI earth continuity conductor or main earthing lead fixed to wall or buried in ground or drawn in conduit/ pipe or fixed to transformer/panel body complete all as specified
SRISHTI CONSTRUCTIONS
Genius Construction Co.
SHRI SAI ENTERPRISES
R J ENTERPRISES
Shree Ayyappa Engineering
AIRDOT ENGINEERING
ORIENT ELECTRIC CO
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .