| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.7 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹39.0 L+₹2.7 L (7.31%)Rejected-Finance R O WARD NO 08 H NO 108 DHAR ROAD UDHAMPUR TEHSIL DISTT UDHAMPUR 182101 | UDHAMPUR | UDHAMPUR | JAMMU KASHMIR | 182101 | L2 | Rejected-Finance OTHER THAN L1 | |
| 3 | L3₹39.3 L+₹2.9 L (7.91%)Rejected-Finance 53 HOUSING BOARD COLONY PHASE II UDHAMPUR 182101 J K | UDHAMPUR | UDHAMPUR | J K | 182101 | L3 | Rejected-Finance OTHER THAN L1 | |
| 4 | L4₹39.8 L+₹3.4 L (9.47%)Rejected-Finance 6 RAILWAY STATION ROAD ONKAR INDUSTRIES GULAMALI PURA BAHRAICH UTTAR PRADESH 271801 | BAHRAICH | UTTAR PRADESH | 271801 | L4 | Rejected-Finance OTHER THAN L1 | |
| 5 | L5₹40.5 L+₹4.1 L (11.4%)Rejected-Finance NEAR INDUSTRIAL ESTATE THANDA PADDAR UDHAMPUR J K 182101 | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L5 | Rejected-Finance OTHER THAN L1 |
Tender Value
Refer Docs
EMD Value
₹99,600
Closing Date
31 Mar 2023, 6:00 pmClosed
GE (UTILITIES) UDHAMPUR
GE (UTILITIES) UDHAMPUR, PO-GARHI, PIN-182121
Repair/Maint Of LT distribution System and security lights, street lights alongwith connected works in certain different locations Under GE(Utility) Udhampur.
2023_MES_577818_2
GE/ U- /2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (UTILITIES) UDHAMPUR
Please refer Tender documents
8 documents required · 8 mandatory
₹500
GE (UTILITIES) UDHAMPUR
₹99,600
Yes
16 May 2023
10 Mar 2023
3 Apr 2023
10 Mar 2023
31 Mar 2023
17 Mar 2023
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for foundations of poles/stays etc .not exc 10 Sqm area on plan and getting out in soft/loose soil complete all as specified and as directed by Engineer-in-Charge.
Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed by Engr-in-Charge.
Removing of excavated soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge.
M&L for cement concreate 1:2:4 type D-2 (using 40 mm graded stone aggregate) as in coping etc including necessary form work and finishing the surface with cement mortar 1:4, 5mm thick finished to the portion of PCC muffs above ground level complete all as specified and directed by Engr-in-Charge.
M&L for PCC 1:4:8 type D-2 (using 40 mm grade stone aggregrate in foundation, mass concrate) as in foundation of poles & stay etc complete all as specified and directed by Engr-in-Charge.
Supply, fixing and testing 3 finger Divider sleeves including all material and accessories suitable for 4 core/3.5core X 16 to 240Sqmm XLPE cable of 1100 volts (E)grade complete all as specified and directed by Engr-in-Charge.
S&F in replacement Ampere meter digital type of ratio 0-100 Amp, size 95 Sqmm square type including making incoming/outgoing connections complete all as specified and directed by Engr-in-Charge.
S&F in replacement Voltmeter digital type of ratio 0-415 volt , size 95 Sqmm square type including making incoming/outgoing connections complete all as specified and directed by Engr-in-Charge.
M&L in replacement Indicator lamp assembly LED type with red/green/blue including making connections complete all as specified and directed by Engr-in-Charge.
M&L in replacement of Current transformer (CT) ratio 100/5 including making connections complete all as specified and directed by Engr-in-Charge.
S&F On load change over switch FP 100 Amps, 415 Volt, 4 pole complete all as specefied and directed by Engr-in-Charge.
S&F On load change over switch FP 63 Amps, 415 Volt, 4 pole complete all as specefied and directed by Engr-in-Charge.
S&F On load change over switch FP 800 Amps, 415 Volt, 4 poles in Sheet sheel encloser complete all as specefied and directed by Engr-in-Charge.
Supply, installation and commissioning in replacement LT Feeder pillar box of size 75x75x45 cm outdoor type factory made manufactured by a CPRI approved manufacturer, made out of 3.15 mm thick CRCA sheet and self supporting, built upon Rigid frame work suitable fo 440 volt 3 phase 4 wire system having front and rear hinger doors with neorprene rubber gasket epoxy powder coated with danger plate, earthing strip point and bottom detachable gland plate complete with suitable size zinc chromium plated nuts, bolts and washers etc having colour code aluminium bus bar interconnections for easy identification including incoming/outgoing cable holes at bottom, provision of six nos connectors and embedded with mild steel anglr iron frame of size 50x50x6 mm and 450 mm above normal ground level complete with PCC foundation in cement concrete (1:2:4) type B1 graded stone aggregate and testing after installation including taking down unserviceable Feeder Pillar box with connected acessories after disconnecting all incoming and outgoing cable etc complete all as specefied and comprising with the following:- (a) Aluminium Bus-bar 1600 Amp, supported with suitable size of Heavy Duty Porcelain Stand Lock with suitable size of Brass Nut, Bolts and Washer with Heat Shrinkable PVC Sleeving. The Bar shall be Colour Coded (Red, Yellow & Blue) for Three Phases and Black for Neutral. – 04 Nos. (b) ON load change over 1000 Amp four pole.
M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600mm x 6.0mm thick buried directly in ground ( earth pit not less than 2.25 mtr below normal ground level ) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size 32 x 6mm as earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common slat including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle and angle iron 40 x 40 x 5 mm frame, GI medium grade watering pipe 20 mm bore and funnel with wire mesh light grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed by Engr-in-Charge. Note: - On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-Charge.
S&F in replacement earth continuity conductor on main earthing lead fixed to pole or buried in ground or at any other situation for loop earthing extra as required (beyond 7.5 M) of GI Strip 32 x 6 mm complete all as specified and directed by Engr-in-Charge.
M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size 25 x 4 mm as earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common salt including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle and angle iron 40x40x5mm frame, GI medium grade watering pipe 20 mm bore and funnel with wire mesh light grade protection pipe 20 mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed by Engr-in-Charge. Note: - On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engr-in-Charge.
S&F in replacement earth continuity conductor on main earthing lead fixed to pole or buried in ground or at any other situation for loop earthing extra as required (beyond 7.5 M) of GI Strip 25 x 4 mm complete all as specified and directed by Engr-in-Charge.
M&L for switchyard gravelling of 15.0 cm (loose thickness) by broken stone of 40 mm size in and around two pole/ four pole structure/ substation complete all as specified and directed by Engr-in-Charge.
Taking out/dismantling any type of LT Panel by disconnecting the electric connection carefully after taking proper shutdown and removing from the site and stacking complete all as specefied and directed by Engr-in-Charge.
Supply, Installation , testing and commissioing in replacement of outdoor type, weather proof, cubicle panel board made out of 3.15 mm thick CRCA steel sheet mounted on 60 cm long legs made out of 40 x 40 x 6 mm equal angle, embedded in PCC 1:2:4 type B-1 blocks of size 15 x 15 x 15 cm front and back openable, double door openable up to minimum 150 degree & removable type having magnetic catche system, lockable/ openable by keys from both sides having chromium plated locks, louvers and air vent gaskets for natural air flow suitable foamed in PU gasket to make it dust/vermin proof, IP 54 protection, powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliset for short circuit current of 50 KA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produced to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels complete suitable cable glands for cable entry. The panel shall accomodate the following equipments:- (a) Aluminium Bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 1250 Amps for phases and neutral - 01 set .
Supply, installation and commissioning in replacement LT Feeder pillar box of size 75x75x45 cm outdoor type factory made manufactured by a CPRI approved manufacturer, made out of 3.15 mm thick CRCA sheet and self supporting, built upon Rigid frame work suitable fo 440 volt 3 phase 4 wire system having front and rear hinger doors with neorprene rubber gasket epoxy powder coated with danger plate, earthing strip point and bottom detachable gland plate complete with suitable size zinc chromium plated nuts, bolts and washers etc having colour code aluminium bus bar interconnections for easy identification including incoming/outgoing cable holes at bottom, provision of six nos connectors and embedded with mild steel anglr iron frame of size 50x50x6 mm and 450 mm above normal ground level complete with PCC foundation in cement concrete (1:2:4) type B1 graded stone aggregate and testing after installation including taking down unserviceable Feeder Pillar box with connected acessories after disconnecting all incoming and outgoing cable etc complete all as specefied and comprising with the following:-(a) Aluminium Bus-bar 400 Amp, supported with suitable size of Heavy Duty Porcelain Stand Lock with suitable size of Brass Nut, Bolts and Washer with Heat Shrinkable PVC Sleeving. The Bar shall be Colour Coded (Red, Yellow & Blue) for Three Phases and Black for Neutral. – 04 Nos. (b) MCCB 4 Pole, Ics = 100% Icu, 35/36 KA, 415 Volts, 160 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos (AS INCOMING).
Taking down carefully Unserviceable Security light 60 watt /Flood Light/ High Mast light fitting from pole/Structure and repair/replacement of worn out parts such as driver, SPD etc, cleaning of fittings, cover, copper wire,clamps, nuts and bolts, mounting bracket and re assembling the same after repair, testing and refixing in pole/other location including provision of necessery T & P like ladder/Boom Vehicle, tools ets as required for taking down and refixing of street light complete all as specified and directed by Engr-in-Charge. Note: - Replacement of defective spare parts of fitting (to make functional) will be measured and paid separately as supply only. However, cost of replacement screws, nuts, bolts, and cleaning of fittings shall be deemed to be included in quoted rate.
All as per serial item No 25.00 here-in-before but Secutiy light fittings 90 watt street light fitting.
All as per serial item No 25.00 here-in-before but Flood light fittings 120 watt street light fitting.
All as per serial item No 25.00 here-in-before but Flood light fittings 150 watt street light fitting.
Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cable PVC tape PVC sheathed 2.5 Sqmm aluminium solid conductor 2 core nominal cross section laid in trenches/fixed to walls/ passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specefied and directed by Engr-in-Charge.
Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cable PVC tape PVC sheathed 4 Sqmm aluminium solid conductor 2 core nominal cross section laid in trenches/fixed to walls/ passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specefied and directed by Engr-in-Charge.
S&F in replacement modular box of size 333 x 233 x 120 mm made of FRP inpact resistance plastic & heat resistant materials including MCB SP 6 A, Connector terminal block 4 pole 16 A capacity and fixing to the street light or post top light pole with suitable sizes of clamps, nuts and bolts complete all as specefied and directed by Engr-in-Charge.
S&F in replacement MS bracket for street light fittings made out of 40 mm dia GI pipe of medium grade 1.5 mtr long each bent to required shape & size and fixed to pole with and including flat iron clamps 02 Nos made out of 32x6 mm flat iron including GI Nuts, bolts and washers and painting of clamps and street light brackets with two coat of aluminium paint over a coat of red oxide primer and fittings bracket to street light fittings complete all as specefied and directed by Engr-in-Charge.
Taking down carefully existing old unserviceable street lights/garden lights fittings of any capacity & size from poles/buildings and refixing the same on poles/ building after making the fittings serviceable complete all as specified and directed by Engr-in-Charge. Note:- (i) Spare parts required for making the street light functional shall be measured and paid separately under relevent items of BOQ. (ii) The cost of Replacement of minor Parts i.e. nuts/bolts,TC wire,connectors etc are deemed to be included in this item. (iii) Necessary elevator/VMSL shall be arranged by contractor for repairs.
S&F in replacement 250 Watt LED Flood light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 110 lumen/Watt (Minimum lumen output of luminarie should be 13200 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-Charge.
S&F in replacement 120 Watt LED Flood light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 110 lumen/Watt (Minimum lumen output of luminarie should be 13200 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-Charge.
S&F in replacement 90 Watt LED street light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 9000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-Charge.
S&F in replacement 60 Watt LED street light with sun pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 6000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-Charge.
S&F 15 Watt new generation, Post top lantern, energy saving, enviornmentla friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminarie with high power LEDs with IP-65 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 1500 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided complete all as specified and directed by Engr-in-Charge.
S&F Multi Colour (Red, green, orange ) LED flood light, 100 watt, 230 V, AC outdoor type with thermal management in multiple optics, powder coated, pressure die cast aluminium body with toughened glass visor, and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp,CCT 5700K, lumen efficacy not less than 110 lumen/watts (in repair) complete all as specified and directed by Engr-in-Charge.
S&F in replacement 90 Watt, 230 V AC outdoor type LED street light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 6000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-Charge.
Cleaning the existing exposed surfaces of steel tubular pole of 11.0 mtr long including cross arms, brackets, clamps etc and painting with two coats of synthetic enamel paint (Aluminium shade) marking five black & white bands at lower portion of pole, each 300 mm wide alternately and marking pole No. with yellow paint on black base at suitable height complete all as specified and directed by Engr-in-Charge.
Supply, laying, jointing & testing in replacement XLPE insulated, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade cross sectional area 10 Sqmm 2 core laind in trenches or passing through pipe or fixed on poles complete all as specified and directed by Engr-in-Charge.
All as per serial item No 42.00 here-in-before but of size 16 Sqmm 4 core.
Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed by Engr-in-Charge.
S&F double walled corrugated (DWC) pipe of size 77 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT cable in under ground complete all as specified and directed by Engr-in-Charge.
Supply and Laying in replacement Galvanised iron steel tubes, ISI marked light grade of size 40 mm bore for cable protection along the poles under road under drains, laid in trenches/fixed on walls/poles with suitable clamps bolts nuts etc including taking down of old unserviceble pipe complete all as specified and directed by Engineer-in-Charge.
S&F in replacement Power contactor 3 phase 415 Volts, 40 Amps, coil voltage of rating 240 Volts including taking down old unserviceable power contactor complete all as specefied and directed by Engr-in-Charge.
S&F in replacement Power contactor 4 pole 240 Volts, 30 Amps , coil voltage of rating 240 Volts including taking down old unserviceable power contactor all as specified and as directed by Engr-In-Charge.
Supply only Driver for LED energy saving & enviornment area light fitting > 75 watts security light with active power factor correction (APFC) electronic driver. LED driver 75 Watt with operating voltage between 100-270 V of existing specifications & make complete all as specefied and as directed by Engr-in-Charge.
Supply only Driver for LED energy saving & enviornment area light fitting > 45 watts security light with active power factor correction (APFC) electronic driver. LED driver 45 Watt with operating voltage between 100-270 V of existing specifications & make complete all as specefied and as directed by Engr-in-Charge.
S&F in replacement MS Channel/angle iron/flat iron of required size and bend to shape as cross arms, bracing and support including, MS clamps back plates with bolts, nuts, and washers drilled for insulators including painting two coats of synthetic enemel paint (Aluminium shade) over a coat of red oxide primer complete all as specefied and directed by Engr-in-Charge.
S&F in replacement MCCB four pole 63 Amps, 50 Hz with breaking capacity 16KA, Ics = 100% Icu , 415 Volts, Adjustable thermal & Fixed magnetic setting including making all incoming/ outgoing connections complete all as specified and directed by Engineer in Charge.
M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth wire 4 mm as earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common salt including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle and angle iron 40x40x5mm frame, GI medium grade watering pipe 20 mm bore and funnel with wire mesh light grade protection pipe 20 mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed by Engr-in-Charge.Note: - On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge.
S&F in replacement 70 Watt, 230 V AC outdoor type LED street light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 6000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-Charge.
Post top lantern, LED, type 40 watt , 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant (in repair) complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP-66 protection complete all as specified and directed by Engr-in-Charge.
S&F in replacement ofLED bollard lights of 11 watt capacity including taking down existing unserviceable garden lights of any type/capacity complete all as specified and directed by Engr-in-Charge.
LED lamp warm white/white 5 Watt (in replacement) complete all asspecified & directed by Engr-in-Charge.
LED lamp warm white/white 9 Watt (in replacement) complete all as specified & directed by Engr-in-Charge.
M&L in replacement of PVC insulated multi stranded aluminum conductor PVC cable sheathed 10 Sqmm twin core and making connections of street light fittings with overhead lines/UG Cable complete all as specified and directed by Engr-in-Charge.
slathia construction works
vijay kumar gupta and co
MOHAN LAL AND SONS
K S BUILDERS
FANGALIA TRADERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .