| 1 | L1₹5.6 LAccepted-Finance | ₹5.6 L | L1 | Accepted-Finance ok |
| 2 | L2₹5.9 LAccepted-Finance | ₹5.9 L | L2 | Accepted-Finance ok |
| 3 | L3₹5.9 LAccepted-Finance | ₹5.9 L | L3 | Accepted-Finance ok |
| 4 | L4₹6.2 LAccepted-Finance B 26 DSIDC SHOPPING COMPLEX CENTER KALYANPURI DELHI 110091 | EAST | DELHI | 110091 | ₹6.2 L | L4 | Accepted-Finance ok |
| 5 | L5₹6.5 LAccepted-Finance | ₹6.5 L | L5 | Accepted-Finance ok |
Tender Value
₹9.2 L
EMD Value
₹18,427
Closing Date
17 Mar 2026, 3:00 pmClosed
Executive Engineer (E) M 253 PWD
Executive Engineer (E) M 253 PWD, Delhi Sachivalaya, New Delhi
RMO of Electrical and Mechanical installations at Saheed Rajguru College at Vasundhara Enclave, Delhi E.I work of changing room in basement and other associated works)
2026_PWD_288537_1
125/EE(E)/PWD M-253/2025-26
Open Tender
Electrical Works
90 days
M 253 PWD, Delhi Sachivalaya, New Delhi
Please refer Tender documents.
12 documents required · 12 mandatory
₹0
₹18,427
23 Mar 2026
11 Mar 2026
17 Mar 2026
11 Mar 2026
17 Mar 2026
11 Mar 2026
Select, At Par, Excess (+), Less (-) IOCL
Tender Inviting Authority: Executive Engineer(E) PWD M-253
Name of Work:- RMO of Electrical and Mechanical installations at Saheed Rajguru College at Vasundhara Enclave, Delhi (SH:- E.I work of changing room in basement and other associated works)
NIT No.:125/EE(E)/PWD M-253/2025-26 Estimated Cost:-9,21,329/-
Name of the Bidder/ Bidding Firm / Company :
Sl. No. Sub Head Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category
1 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C 40 Point 2078 374800 Excess(+) Full Conversion INR
2 Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. Group C 100 Point 1064 374800 Excess(+) Full Conversion INR
3 Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 x 1.5 sq. mm 50 Metre 104 374800 Excess(+) Full Conversion INR
4 6 x 1.5 sq. mm 50 Metre 195 374800 Excess(+) Full Conversion INR
5 3 x 4 sq. mm 100 Metre 222 374800 Excess(+) Full Conversion INR
6 6 x 4 sq. mm 100 Metre 424 374800 Excess(+) Full Conversion INR
7 3 x 6 sq. mm 100 Metre 326 374800 Excess(+) Full Conversion INR
8 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm 200 Metre 151 374800 Excess(+) Full Conversion INR
9 25 mm 200 Metre 168 374800 Excess(+) Full Conversion INR
10 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. 20 Each 659 374800 Excess(+) Full Conversion INR
11 Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required. 10 Each 807 374800 Excess(+) Full Conversion INR
12 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without CB/RCCB/Isolator) 16 way , Double door 1 Each 2871 374800 Excess(+) Full Conversion INR
13 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole 14 Each 285 374800 Excess(+) Full Conversion INR
14 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. 100 A, 16 KA,TPMCCB 6 Each 4003 374800 Excess(+) Full Conversion INR
15 Supplying and fixing following rating, 240 / 415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A DP MCB 10 Each 1859 374800 Excess(+) Full Conversion INR
16 63 A TP MCB 20 Each 2580 374800 Excess(+) Full Conversion INR
17 LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt) Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim 12 -15 watt 30 Nos 715 374800 Excess(+) Full Conversion INR
18 LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI>80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 36 watt 60 Nos 2508 374800 Excess(+) Full Conversion INR
19 Supplying & fixing following size PVC trunking along with cover & accessories on surface etc. complete as required. 38 mm x 25 mm 50 Mtrs. 163 374800 Excess(+) Full Conversion INR
20 50 mm x 50 mm 50 Mtrs. 246 374800 Excess(+) Full Conversion INR
21 100 mm x 50 mm 50 Mtrs. 653 374800 Excess(+) Full Conversion INR
22 Supplying, laying & fixing of following size one number XLPE insulated and PVC sheathed armoured aluminium conductor power cable of 1.1 kV grade conforming to IS 7098 (Part 1) 1988 on existing cable tray / wall surface as required. 3 x 10 sq. mm Mtrs. 434 374800 Excess(+) Full Conversion INR
23 Supplying, installation, testing & commissioning of 20W LED Mirror light of polycarbonate housing with diffuser & integrated electronic driver having system lumen efficacy: ≥90 lm/W THD: ≤10%, PF: ≥0.90, CRI: ≥80, Colour Temperature: 5700K/6500K, LED life ≥ 25,000Hrs i/c connection with 1.5 sq mm FRLS PVC insulated connection sq mm FRLS PVC insulated copper conductor, single core cable and earthing complete as required. Nos 374800 Excess(+) Full Conversion INR
24 Supplying, installation, testing & commissioning of 300mm Sweep, 900 rpm, single phase heavy duty exhaust fan complete in the existing opening, including making good the damage etc as required. Nos 5084 374800 Excess(+) Full Conversion INR
25 Supplying, installation, testing & commissioning of 200 mm sweep Air Flow Capacity 520cc/min 1350 RPM plastiic body Exhaust fan complete with louver/shelter i/c cutting the suitable size round hour for above fan making good the damage etc as required. Nos 1934 374800 Excess(+) Full Conversion INR
26 Supplying installation testing and commissioning of swing type three speed wall fan of 400mm sweep suitable for operation on 230 Volt 1-Ph 50 Hz AC Supply including wall mounting arrangement, connection etc. as required. Nos 3310 374800 Excess(+) Full Conversion INR
27 Supplying installation testing and commissioning of swing type three speed wall fan of 300mm sweep suitable for operation on 230 Volt 1-Ph 50 Hz AC Supply including wall mounting arrangement, connection etc. as required. Nos 2964 374800 Excess(+) Full Conversion INR
Total in Figures
Quoted Rate in Figures Select
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.15 MB
BOQ_382708.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid