Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹48.0 LAccepted-AOC | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹49.0 L+₹1.0 L (2.12%)Rejected-Finance 121004 | L2 | Rejected-Finance BEING NOT LOWEST TENDER | |
| 3 | L3₹49.5 L+₹1.5 L (3.15%)Rejected-Finance | L3 | Rejected-Finance BEING NOT LOWEST TENDER | |
| 4 | L4₹49.5 L+₹1.5 L (3.16%)Rejected-Finance 31 CHAIRMAN KARUPPANA THEVAR STEET SULUR COIMBATORE 641 402 | COIMBATORE | TAMIL NADU | 641402 | L4 | Rejected-Finance BEING NOT LOWEST TENDER | |
| 5 | L5₹49.6 L+₹1.6 L (3.28%)Rejected-Finance | L5 | Rejected-Finance BEING NOT LOWEST TENDER |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
16 Mar 2020, 6:00 pmClosed
GE AF SULUR
Garrison Engineer AF Sulur Military Engineer Services Kangayampalayam Post Sulur Coimbatore 641 401
CERTAIN MISC E M WORKS AT AFS SULUR
2020_MES_328325_1
GE(AF)/SUL/Token/71 of 2019-2020
Open Tender
Miscellaneous Works
Item Rate
180 days
GE AF SULUR
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
Yes
GE AF SULUR
₹96,000
Yes
23 Mar 2020
25 Feb 2020
17 Mar 2020
25 Feb 2020
16 Mar 2020
10 Mar 2020
25 Feb 2020 - 9 Mar 2020
Amount
SCHEDULE A BOQ
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5m deep in hard/dense soil and getting out for taking down/laying of pipes
Returning, refilling including spreading levelling watering and well ramming in layers not exceeding 25cms thick in hard/dense soil
Removing excavated materials not exceeding 50m distance and depositing where directed at level not exceeding 1.5 m above the starting point
Supply and spread Riddling Sand for cable protection 8cm under the cable and 15cm above the cable in trench and get the thick layer of 18cm after ramming. Note :- In case sufficient sand not obtained from excavation, the required additional qty obtain from out side land as directed by the Engineer-in-Charge. The rate is deemed to be included.
Fly ash cable protection cover of size 23x11.5 x7.5cm including taking down existing bricks of any size.
Disconnecting the electric supply to the panel boards, cleaning and removing the carbon deposits in the panel board, bus bar with CTC/ CRC, tightening of nuts, bolts and replacement of unserviceable lugs, bolts, nuts, washers etc complete all as directed.
Machine pressed precast concrete interlocking paver block with grey cement and pigment any shape and size, polished confirming to IS-15658 of 60mm thickness M-35 grade, laid over and including M sand cushion of 50mm thick complete inculding packing the sides with PCC 1:3:6 and disposal ofrubish material to out side MD land all as specified and directed. Note : The Unit rate quoted is included for Demolition of Stone Slabs and tiles of any description or thickness in floors,aprons etc laid bedded and pointed in any mortar
Dismantling unserviceable/ burnt electric wiring from any type of panel boards, feeder pillar box, rewiring the panel boards with suitable size of PVC insulated, sheathed, stranded copper cable washers etc., including electric connections and testing complete all as specified and directed
XLPE insulated, screened, PVC Bedded, galvanised steel strip of wire armoured, electric power cable heavy duty with aluminium condutor 1100Volts grade cross sectional area 16 Sqmm 4 core laid in trenches /ducts/fixed to wall/pole/ inside panel/ drawn through pipe including cable glands and terminal sockets etc including taking down existing cable all as specified and directed. Note : Excavation and earth work shall be measured and paid seperately. Make : Havells/ KEI/ CCI
XLPE insulated,screened ,PVC Bedded,galvanised steel strip of wire armoured, electric power cable heavy duty with aluminium condutor 1100Volts grade cross sectional area 25 sq mm 4 core laid in trenches /ducts/fixed to wall/pole/ inside panel/ drawn through pipe including cable glands and terminal sockets etc including taking down existing cable all as specified and directed. Note : Excavation and earth work shall be measured and paid seperately. Make : Havells/ KEI/ CCI
40 mm bore of pipe high density polyethylene pipes (HDPE) of pressure rating 6 kgf/ cm2 laid in trenches for cable protection passing under road/ floor or for fixing to poles complete including taking down existing one all as specified and directed
Cable jointing kit for 1.1 KV grade cable for outdoor stright through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armored aluminium conductor cable of size 16 sqmm to 25 sqmm including taking down existing one all as specified and directed Make : Reychems, Densons, M-Seal
XLPE insulated,screened ,PVC Bedded,galvanised steel strip of wire armoured, electric power cable heavy duty with aluminium condutor 1100Volts grade cross sectional area 50 sq mm 3.5 core laid in trenches /ducts/fixed to wall/pole/ inside panel/ drawn through pipe including cable glands and terminal sockets etc including taking down existing cable all as specified and directed. Note : Excavation and earth work shall be measured and paid seperately. Make : Havells/ KEI/ CCI
IP 66 Pole Mounted street lighting Junction Box 160x240x120 mm made of Polycarbonate, supplied with 1 No. 6A 10KA SP MCB, 1 No. 63A 4P FR Polyamide color coded RYBN Terminals Block, 1 No. each of Earth & Neutral Terminal mounted on 35mm DIN channel and fitted inside Enclosure alongwith Pole Mounting bracket, pole clamp & hardware made of Stainless Steel 304. The Junction Box enclosure Cover should have inbuilt 2 nos Polycarbonate Hinges with SS 304 Hinge pin, for Cover not to detach from Base on opening and should be properly tightened to base with Polycarbonate screws having sealing gaskets of extruded silicon rubber. The Polycarbonate enclosure should have properties Flame Retardant UL94V0, UV, Glow Wire test 960 Deg C, Impact IK08, Halogen free & RoHS compliant, Glow Wire Test for 960⁰ C. Type test reports from NABL lab in India along with Polycarbonate manufacturer batch test certificate should be submitted including taking down existing one and all as specified and directed. Make of junction box shall be as per make mentioned in list of makes in PS.
One integrated solar street light of less than 18W with 3000 lumen and system lumen efficiency of more than 170 lumen per watt. The luminaire shall use highly efficient microcontroller based integrated MPPT charge controller, both charger and driver to be on same board with more than 90% efficiency of both charger and driver. High grade aluminium die-cast housing to ensure good heat dissipation. The luminaire shall have flexi mount of 0 to 15 degree to adapt to certain geography diversity. The luminaire shall be with smart self-diagnosis feature with LED indicators alongwith battery charging and deep discharging out off indications. The system shall use long time maintenance free lithium Ferro Phosphate (Li Fe PO 4) battery with BIS certification. Battery capacity of minimum 170 wh for autonomy of 24 hrs with fully charged battery. The luminaire shall be with hybrid feature (integrated/ seperated) ON-OFF switch, Outer mounting diameter of 48-60 mm. Operating temp range for light engine is 0 to +35 Dep C. operating humidity shall be upto 95%. System lumen output should be atleast 12V DC, 2000 lm. Solar panel module capacity of 12V, 35W Peak Mono-crystalline. Solar cell efficiency with min 12%. LED burning hrs to be 50,000 hrs at L70. Rating of IP 65 and IK 08 to comply with UV stabilized poly carbonate front cover. Colour temp of 5700K and CRI > 70 including taking down existing one and all as specified and directed.. Make : Philips Cat No BRP 710 LED 30 series with Hy brid option or equivalent in Wipro/ Bajaj.
Notes:- (a) The contractor shall submit to Engr-in-Charge LM-80 and LM-79 report including BIS certification. (b) The contractor shall submit warranty certificate from manufacturer for minimum 5 years. (c) The contractor shall also submit test report from the manufacture to comply with all requirements and specifications given in the contract. (d) The contractor shall also submit safety and performance standard compliance of IEC 60598-2-3 for road and street lights, IEC 62109-1 for power converters used in Solar Panel, EN 50530 for MPPT performance evaluation, IEC 61607 for EMC immunity, CISPR 15 for Radio disturbance characteristics, IEC 62133, IEC 61960 and UL 1642 for safety of lithium Ferro Phosphate battery and IEC 61730-1, 2 & IEC 61215 for safety of solar panel module. (e) The rates quoted deemed to be included 6 mtr long MS/ GI pipe of 50mm dia medium grade including necessary excavation, PCC foundation, coping, base plate and bend to shape and size suitable for fixing of above fitting all as specified and directed by Engineer-in-Charge.
XLPE insulated,screened ,PVC Bedded,galvanised steel strip of wire armoured, electric power cable heavy duty with aluminium condutor 1100Volts grade cross sectional area 35 sq mm 3.5 core laid in trenches /ducts/fixed to wall/pole/ inside panel/ drawn through pipe including cable glands and terminal sockets etc including taking down existing cable all as specified and directed. Note : Excavation and earth work shall be measured and paid seperately. Make : Havells/ KEI/ CCI
GI pipe 80 mm bore medium grade for cable protection road crossing / under floor / on pole etc including taking down existing pipe and cutting road in any description and make good of cutting of road surface with existing complete including taking down existing one all as specified and as dierced by Engr-in-Charge. Make : Tata, Jindal, Surya Prakash
Cable jointing kit for 1.1 KV grade cable for outdoor stright through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armored aluminium conductor cable of size 35 sqmm to 50 sqmm including taking down existing one all as specified and directed. Make : Reychems, Densons, M-Seal
Repairing, overhauling, Servicing & testing of RMUs, 11 KV, 20 KA, 3 Phase, 50 Hz, AC Supply system, outdoor type for trouble free operation, consisting of one/two incomming and one/two outgoing with SF6 gas filled VCB/ LBS/Fuse units, metal clad totally enclosed free standing floor mounted, non draw out type including the following works complete all as specified and directed. Make of RMU : ABB (Note : The Work shall be carried out through the authorised service engineers of the OEM only) (a) Servicing of Manual operated, 11kV, three position load break switch with snap-action knife blade mechanism along with associated earthing switch (ii) Servicing of true position mechanical indication of switch position ON, OFF and EARTH on the front facia of the panel for proper indication (b) (e) Checking and tightening control wiring and rectifying the defects if any.
Supply, installation, testing & commissioning of maintenance free chemical earthing system comprising 17mm dia copper bonded rod 3 mtr long horizontally pre welded T-terminal rod with provision for connection size of 50 x 150mm long, 6mm thickness with equal space either side, with 12mm dia hole of 02 numbers each on either side of the terminal clamp with 250 microns (average) coating thickness, tested and certified by CPRI India alongwith 50 kg earth energizer compound and 10 litres earth resistance reducing liquid. The earthing energizer compound and resistance reducing earthing liquid shall be tested as per IEC-62561-7 read with ASTM G57-06, CI 3.4 A by any NABL accredited lab. The above mentioned rod shall be installed in 8-10 inch bore, 12 feet depth with a distance of minimum 3 meters between each installation. Make : Model HTSP 3I7 of safeTrode or equivalent in OBO Betterman/ ENNOV/ERICO.
The quoted rate shall also deemed to be included the following :- (i) Prior to installation of maintenance free chemical earthing, soil resistivity test to be carried out at the location where earthing work to be done in presence of Engr-in- Charge/JE (E/M),user and the report has to submit to Garrison Engineer with recommendation of manufacturer, if required additional interconnection of earthing (not more than 04 number of earthing) to achive earth result less then 1 Ohms. The arrangement done for soil resistivity testing and submission of report with recommendation deemed to be included in the quoted rate.
(ii) Rate of earth energizer compound of 25 Kg of 02 bags and earth resistance reducing liquid 10 litre in 02 canes (5 ltrs per cane) for each pit deemed to be included in the quoted rate.
(iii) Copper strip of size 20 x 3 mm should be fixed on proper post insulator at the instrument end ( The rate of earthing strip up to 7.5 Mtrs is included in the quoted rate).
(iv) The electrode shall carry manufacturer's name .
(v) The connection clamp shall be permanentlly welded to the copper bounded rod to avoid any kind of connectivity loss,.The pre-welded copper bounded rod shall not need any additional clamp for termination.
(vi) Testing of earth shall be carried out along with the departmental and user representative and report shall be submitted to Garrison Engineer for his entire satisfaction.
(vii) The contractor shall submit CPRI India certified document for copper bonded rod to ensure genuity of material.
(viii) Earth resistance tester will be provided by the contractor. Tester should be calibrated from authorised company/ lab.
(ix) Sign board of mild steel 2 mm thick duly painted with two coats of synthetic enamel paint over a coat of red oxide Zinc chrome primer showing result of earthing should be fixed near the earth pit after completion as directed by engr -in- charge.
(x) Earth work such as auguring and making good the surrounding area shall carried out in any type of soil.
(xi) The contractor shall given a written guarantee of minimum three years for maintaining the earth resistance less than 1 Ohm after certified date of completion.
(xii) A security deposit of value equal to 2.5 % of the rate quoted for chemical earthing per each earthing shall be retained from payment due to the contractor for the guarantee period.
(xiii) Earthing shall be tested after completion of work by the contractor in presence of Engr-in-charge, user and proper record shall be maintened duly signed by all concerned. After testing if the desired earth resistance of less than 1 Ohm is not obtained, the earthing will be redone at no extra cost to Govt. till desired result is obtained.
(xiv) Resistivity of earth energizer compound and resistance reducing earthing liquid shall be certified by any NABL accredited lab carried out as per IEC-62561-7 read with ASTMG57-06, CI-3.4A and the certificate of same shall be submitted by the contractor before commencement of work.
Supply, installation, commissioning and testing of Factory assembled, Floor mounted, free standing, type tested LT Feeder Pillar Panels, with canopy, as per electrical specifications for outdoor installation, to be made of IP65 Polycarbonate modular enclosures. The Enclosures made of Polycarbonate, should be weather/ vermin proof, anti-acid, anti-corrosive, UV resistance in accordance with IEC 61439-1, Fire retardant and Self-extinguishing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960° in accordance with 60695-2-11. Degree of protection against mechanical load should be IK 08 (5 Joule) in accordance with IEC 62262, IP 65 in accordance with IEC 60529 & IEC60439-1, should have Dielectric Properties, RoHS compliant & Halogen free. The manufacturer of boards/panel shall submit a copy of type test reports as per above-mentioned norms from UL/ERDA/CPRI/NABL labs in India. The panels should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosures should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with 01 No polycarbonate IP 65, 9W LED translucent bulk head luminaire, 6500K, PF > 0.95 under canopy for easy maintenance. Panel should be fitted outside with 01 No of 16A 3P IP 65 industrial socket and 01 No of 32A 5P IP 65 industrial socket. 3 phase and neutral 600 amps current carrying capacity copper bus bar insulated with colour coded heat shinkable sleeves with SMC/DMC insulators, complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) bedding upto a height of 45 cm above gorund level, including dismantling and taking out old u/s LT Panel Board and remove from site reconnecting existing LT Cables with new panel board complete all as directed :-
Complete removal of existing paint from chain link fencing located scattered places of E/M installation including all connected MS channel and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed
Electronic energy meter single Phase 5 to 30Amps range capacity including taking down existing one complete all as specified and directed. Make : BENTEC / L&T/ABB
Replacement of all in one integrated solar street light of less than 28W with 4500 lumen and system lumen efficiency of more than 170 lumen per watt. The luminaire shall use highly efficient microcontroller based integrated MPPT charge controller, both charger and driver to be on same board with more than 90% efficiency of both charger and driver. High grade aluminium die-cast housing to ensure good heat dissipation. The luminaire shall have flexi mount of 0 to 15 degree to adapt to certain geography diversity. The luminaire shall be with smart self-diagnosis feature with LED indicators alongwith battery charging and deep discharging out off indications. The system shall use long time maintenance free lithium Ferro Phosphate (Li Fe PO 4) battery with BIS certification. Battery capacity of minimum 170 wh for autonomy of 24 hrs with fully charged battery. The luminaire shall be with hybrid feature (integrated/ seperated) ON-OFF switch, Outer mounting diameter of 48-60 mm. Operating temp range for light engine is 0 to +35 Dep C. operating humidity shall be upto 95%. System lumen output should be atleast 12V DC, 2000 lm. Solar panel module capacity of 12V, 35W Peak Mono-crystalline. Solar cell efficiency with min 12%. LED burning hrs to be 50,000 hrs at L70. Rating of IP 65 and IK 08 to comply with UV stabilized poly carbonate front cover. Colour temp of 5700K and CRI > 70 including taking down existing one complete all as specified and directed. Make : Philips Cat No BRP 710 LED 45 series with Hy brid option or equivalent in Wipro/ Bajaj.
Notes:- (a) The contractor shall submit to Engr-in-Charge LM-80 and LM-79 report including BIS certification. (b) The contractor shall submit warranty certificate from manufacturer for minimum 5 years. (c) The contractor shall also submit test report from the manufacture to comply with all requirements and specifications given in the contract. (d) The contractor shall also submit safety and performance standard compliance of IEC 60598-2-3 for road and street lights, IEC 62109-1 for power converters used in Solar Panel, EN 50530 for MPPT performance evaluation, IEC 61607 for EMC immunity, CISPR 15 for Radio disturbance characteristics, IEC 62133, IEC 61960 and UL 1642 for safety of lithium Ferro Phosphate battery and IEC 61730-1, 2 & IEC 61215 for safety of solar panel module. (e) The rates quoted deemed to be included 6 mtr long GI pipe of 50mm dia medium grade including necessary excavation, PCC foundation, coping, base plate and bend to shape and size suitable for fixing of above fitting all as specified and directed by Engineer-in-Charge.
XLPE insulated,screened ,PVC Bedded,galvanised steel strip of wire armoured, electric power cable heavy duty with aluminium condutor 1100Volts grade cross sectional area 70 sq mm 3.5 core laid in trenches /ducts/fixed to wall/pole/ inside panel/ drawn through pipe including cable glands and terminal sockets etc including taking down existing cable complete all as specified and directed. Note : Excavation and earth work shall be measured and paid seperately. Make : Havells/ KEI/ CCI
GI pipe 40 mm bore medium grade for cable protection road crossing / under floor / on pole etc including taking down existing pipe and cutting road in any description and make good of cutting of road surface with existing complete including taking down existing one all as specified and as dierced by Engr-in-Charge. Make : Tata, Jindal, Surya Prakash
Supply, installation, commissioning and testing of Factory assembled, Floor mounted, free standing, type tested LT Feeder Pillar Panels, with canopy, as per electrical specifications for outdoor installation, to be made of IP65 Polycarbonate modular enclosures. The Enclosures made of Polycarbonate, should be weather/ vermin proof, anti-acid, anti-corrosive, UV resistance in accordance with IEC 61439-1, Fire retardant and Self-extinguishing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960° in accordance with 60695-2-11. Degree of protection against mechanical load should be IK 08 (5 Joule) in accordance with IEC 62262, IP 65 in accordance with IEC 60529 & IEC60439-1, should have Dielectric Properties, RoHS compliant & Halogen free. The manufacturer of boards/panel shall submit a copy of type test reports as per above-mentioned norms from UL/ERDA/CPRI/NABL labs in India. The panels should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosures should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with 01 No polycarbonate IP 65, 9W LED translucent bulk head luminaire, color temp not less than 6500K, PF > 0.95 under canopy for easy maintenance. Panel should be fitted with 01 No of 16A 3P IP 65 industrial socket and 01 No of 32A 5P IP 65 industrial socket outside. 3 phase and neutral 400 amps current carrying capacity copper bus bar insulated with colour coded heat shinkable sleeves with SMC/ DMC insulators, complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) bedding upto a height of 45 cm above ground level, including dismantling and taking out old u/s LT Panel Board and remove from site reconnecting existing LT Cables with new panel board complete all as directed :-
Rubber mat 19mm thick all as per IS specifications and of size 2m x 1m including taking down existing one complete all as specified and directed.
Cable jointing kit for 1.1 KV grade cable for outdoor stright through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armored aluminium conductor cable of size 70 sqmm to 95 sqmm including taking down existing one complete all as specified and directed. Make : Reychems, Densons, M-Seal
XLPE insulated,screened ,PVC Bedded,galvanised steel strip of wire armoured, electric power cable heavy duty with aluminium condutor 1100Volts grade cross sectional area 95 sq mm 3.5 core laid in trenches /ducts/fixed to wall/pole/ inside panel/ drawn through pipe including cable glands and terminal sockets etc including taking down existing cable complete all as specified and directed.. Note : Excavation and earth work shall be measured and paid seperately. Make : Havells/ KEI/ CCI
Earth pit cover made of heavy duty poly plastic of high grade polypropylene tested and certified by any NABL accredited lab for load bearing capacity not less than 9.2 tonnes with top dia not less than 250mm, bottom dia not less than 330 mm and height not less than 260 mm dia for each electrode pit including taking down existing one complete all as specified and directed. Make : Model SEPC 250 of SAFE TRODE or equivalent in OBO Betterman/ ENNOV/ERICO. Note :- The contractor shall submit load bearing capacity certificate from the manufacturer.
Copper strip of size 20 x 3 mm should be fixed on proper post insulator at the instrument end including taking down existing one complete all as specified and directed.
Electronic energy meter 3 Phase 30 to 60Amps range capacity including taking down existing one complete all as specified and directed. Make : BENTEC / L&T/ABB
Supply, installation, commissioning and testing of Factory assembled, Floor mounted, free standing, type tested LT Feeder Pillar Panels, with canopy, as per electrical specifications for outdoor installation, to be made of IP65 Polycarbonate modular enclosures. The Enclosures made of Polycarbonate, should be weather/ vermin proof, anti-acid, anti-corrosive, UV resistance in accordance with IEC 61439-1, Fire retardant and Self-extinguishing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960° in accordance with 60695-2-11. Degree of protection against mechanical load should be IK 08 (5 Joule) in accordance with IEC 62262, IP 65 in accordance with IEC 60529 & IEC60439-1, should have Dielectric Properties, RoHS compliant & Halogen free. The manufacturer of boards/panel shall submit a copy of type test reports as per above-mentioned norms from UL/ERDA/CPRI/NABL labs in India. The panels should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosures should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with 01 No polycarbonate IP 65, 9W LED translucent bulk head luminaire, color temp not less than 6500K, PF > 0.95 under canopy for easy maintenance. Panel should be fitted with 01 No of 16A 3P IP 65 industrial socket and 01 No of 32A 5P IP 65 industrial socket outside. 3 phase and neutral 600 amps current carrying capacity copper bus bar insulated with colour coded heat shinkable sleeves with SMC/ DMC insulators, complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) bedding upto a height of 45 cm above ground level, including dismantling and taking out old u/s LT Panel Board and remove from site reconnecting existing LT Cables with new panel board complete all as directed :-
Earthing with Galvanised Earth Plate Electrode 600x600x 6mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, connected with Galvanised Earth Strip of size 25x6mm by means of Bolts, Nuts, Check Nuts and Washers of GI or Steel and connected Earthing Testing Point/Bus-bar including GI 40mm bore (dia) light grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt Magnesium Sulphate (1 : 1: 0.5) in alternate layers of not exc 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50 mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, Funnel with GI Watering Pipe 20mm bore (dia) medium grade including necessary Excavation in Soft/Loose Soil, Returning, Filling in and Removal of surplus Spoil upto a distance of 50.00 Metre and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including taking down old unserviceable one, complete all as per specified and as directed. Note :- (a) All Joints should be joined by Exothermic Welding or Brazing. (b) After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge, User and proper record shall be maintained duly signed by all concerned. (c) Earth resistance tester will be provided by the contractor. It should be caliberated from authorised company/ lab. (d) After testing if desired earth resistance of less than 5 Ohm is not obtained, the earthing will be redone at no extra cost to Govt till desired result is obtained.
Neptune Engineers and Builders
A.GOVINDARAJ
kaarthic builders
eurekaenterprises
pk janardhanan
Sreekrupa Enterprises
KUMAR AGENCIES
M/s Shana Constructions
T C KARUNANITHI
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .