Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.7 LAccepted-AOC 37 222 BUNDU KATRA AGRA UP | AGRA | UP | L1 | Accepted-AOC ACCEPTED | |
| 2 | L2₹33.4 L+₹3.0 L (9.94%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
16 Oct 2024, 6:00 pmClosed
GE Bharatpur
GE Kanjoli line Bharatpur-321026
Repair maintenance of DG set pump sets cleaning of OH tanks UG sumps and well and repair to MES installation at RMS Dholpur
2024_MES_675008_1
8423/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Bharatpur
As per NIT
8 documents required · 8 mandatory
₹500
GE Bharatpur
₹80,000
Yes
13 Nov 2024
18 Sept 2024
18 Oct 2024
18 Sept 2024
16 Oct 2024
3 Oct 2024
19 Sept 2024 - 2 Oct 2024
Amount
Cleaning of RCC overhead reservoir of 75,000 GLN capacity of 18 Mtr staging including draining out water. Removing, Mud, Slit/dust from Tank. Washing & rubbing with gunny bags & cleaning with fresh water & Bleaching powder including writing the date of cleaning etc by synthetic enamal paint complete all as specified. (a) All necessary ladder and scaffolding arrangement shall be made by the contractor. (b) All kind of safety equipments shall be arranged at site by the contractor. (c) In case of damage of any outlet pipeline/control valves during operation shall be borne by the contractor (d) Disturbed portion if any shall be made good as per existing by the contractor
Cleaning of Masonry /RCC under ground sump of 25000 GLN capacity, Located at Gundrai pump house No 1, including the following works: (i) draining out water with the help of monoblock pumpset (pumpset shall be managed by the contractor) (ii) Removing, Mud, Slit/dust from sump by manually & rubbing & cleaning with gunny bags etc (iii) washing with fresh water & Bleaching powder twon times (iv) writing the date of cleaning etc by synthetic enamel paint (v) applying two coat of light blue colour synthetic enamel wall paint internally upto 84SQM on inside floor and all walls all as directed by Engr-in-Charge.
Cleaning of Masonry /RCC under ground sump of 25000 LTR capacity loacted at Cadets hostel area including the following works: (i) draining out water with the help of monoblock pumpset (pumpset shall be managed by the contractor) (ii) Removing, Mud, Slit/dust from sump by manually & rubbing & cleaning with gunny bags etc (iii) washing with fresh water & Bleaching powder twon times (iv) writing the date of cleaning etc by synthetic enamel paint (v) applying two coat of white wash.
Cleaning of Masonry /RCC under ground sump of 50000 GLN capacity loacted at Kesarbagh Sump House area including the following works: (i) draining out water with the help of monoblock pumpset (pumpset shall be managed by the contractor) (ii) Removing, Mud, Slit/dust from sump by manually & rubbing & cleaning with gunny bags etc (iii) washing with fresh water & Bleaching powder twon times (iv) writing the date of cleaning etc by synthetic enamel paint (v) applying two coat of white wash.
S&F glow sign board of white polished transparent acrylic cover of minimum 2mm thick, unbreakable, heat resistive etc including M&L of steel fabrication of angles and supports of thickness not less than 2mm thick (thickness shall be variable upto 5mm as per site conditions) rectangular box type of size minimum 180cm x 90cm x 20cm thick, computerised letter of blue colour of size 30cm high and 3 to 5cm width or small as per site requirement having glue on backside to stick permanently, including all kind of securing, welding, assembling with proper allignment and height with fine look, including PCC, cement work, excavation if required, LED tube light fittings 1x 20Watt, including connecting wires and switch independent one way 5Amp with well finish of weather proof suitable for exposing at all weathers including taking down of old UNSV sign board of any type complete all as specified.
S&F glow sign board of white polished transparent acrylic cover of minimum 2mm thick, unbreakable, heat resistive etc including M&L of steel fabrication of angles and supports of thickness not less than 2mm thick (thickness shall be variable upto 5mm as per site conditions) rectangular box type of size minimum 400cm x 60cm x 20cm thick, computerised letter of blue colour of size 30cm high and 3 to 5cm width or small as per site requirement having glue on backside to stick permanently, including all kind of securing, welding, assembling with proper allignment and height with fine look, PCC, cement work, excavation if required, LED tube light fittings 1x 20Watt, including connecting wires and switch independent one way 5Amp with well finish of weather proof suitable for exposing at all weathers including taking down of old UNSV sign board of any type complete all as specified.
M&L for Cutting anxious green growth / vegetation growth from root for cleaning out the area around OH tank / pump house No-1&2&3 at Gundrai and kesharbagh sub station , Kesarbagh sump house and at ground level by cutting up root, un- wanted plants / bushes and removal the same to a distance not less than 50 mtr including levelling of land through JCB directed by engineer -in -charge , Note: (i) Rate including Cutting T&P, transporting/disposal/dumping away from the site as per the laid down procedure of waste management system shall be considered with this item rate. (ii) Entire site shall not be given for one time. Area for cleaning shall be given to the contractor on requirement basis as per the site conditions and growth rate of bushes and grass etc. The area shall be divided into several parts and shall be directed to the contractor when cleaning is required at site. (iii) The above job is carried out in beginning from acceptance of contract and other after 3 month .
Cleaning of Shallow wells at Gundrai by cutting the MS sheet of 10mm thick by gas cutter in rectanglur shape approx 10 to 12 RM, welding the MS sheet of 10 mm thick by gas welding with the help of copper rod in rectangular shape approx 10 to 12 RM after completing cleaning work, Lowering the non clog pump set of 5 HP to 40HP capacity in shallow wells and running until well gets empty during the cleaning work is on including transportation expenditure, pipe arrangement etc., Making angle iron fabrication work at site over both shallow wells to rest/fixing chain pully set to draw bucket filled with mud, sludge, dust, fungus, useless stone pieces continuously till all the waste material removed from bottom of shallow well, Cleaning all pores/ Sources of water yield inside well's wall by brooming, brushing, rubbing, clothing until all rubbish material removed from well's wall and cleaning the wall with the help of water jet of sufficient pressure including cleaning of wall by disinfection chemical like bleaching powder properly or as directed by Engineer in Charge.
M&L for painting aluminium coat over Steel tubular pole and cross arms any size and height including preparration of metallic surface with sand papers and applying one coat of metallic primer before applying aluminium paint all as specified and as directed by Engineer-in-Charge. Note: Location - Gundrai to Kesarbagh area. During school hours Shutdown shall be given after getting approval from the Stn I/C oficer and during holidays shutdown shall be given after consulting with Engineer-in-Charge. Continuous shutdown more than 4Hrs shall not be given in a single day because of water supply constraints. All kind of safety deivces, vehicles and ladders shall be arranged by the contractor at site.
Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete fittings such as switches, ceiling roses, pendents, regulators, sockets etc removing materials for taking credit and making good disturbed surfaces of wall, floor & ceiling etc.
M&L point wiring concealed type complete including cutting chases for conduit pipes on stone masonry wall with 1.5 Sqmm 02 x single core multistranded copper conductor of 1100 volts grade PVC pre insulated FRLS and unsheathed cable enclosed in PVC conduit pipes with all PVC accessories such as Tee, bend, collar, elbow, square junction box etc fixed inside the wall/ceiling by means of PVC conduit pipe including 1.5 Sqmm insulated but unsheathed copper earth continuity conductor to common earth and connedcted to earth dolly complete rate including cutting chases and finishing the wall after concealing the pipe with suitable plastering/ putty/ distembering etc all as specified and directed for the following :-
One light point controlled by one way switch.
One ceiling fan/exhaust fan point controlled by one way switch.
One 3 pin or 5 pin 6 Amp socket point outlet on the same board with other switches
One 3 pin or 5 pin 6 Amp socket point outlet on the independent board
All as per item No 11 above but with multi stranded copper conductor cable 2.5 Sqmm size for 3 pin 16 Amps socket point outlet on independent board including 2.5 Sqmm copper cable PVC insulated FRLS unsheathed copper continuous earth wire including connecting to common earth dolly complete all as specified and directed.
S&F modular switch 1 way , 6 Amp, 1 module, as per existing model and type.
S&F modular switch 1 way , 16Amp, 1 module, as per existing model and type.
S&F modular socket on existing plate, 6Amp, 2/3 pin combined, 2 module as per existing type and model.
S&F modular socket on existing plate, 6Amp/16Amp combination, 2/3 pin combined, 2 module as per existing type and model. Make-Legrand/Crabtree/Anchor or equivalent.
S&F modular white cover plate with frame of 3 module as per existing model and type.
S&F modular white cover plate with frame of 4 module as per existing model and type.
S&F modular white cover plate with frame of 6 module as per existing model and type.
S&F modular white cover plate with frame of 8 module as per existing model and type.
S&F modular white cover plate with frame of 12 module as per existing model and type.
S&F modular fan regulator 2 module SP, 240Volt
S&F modular flush metal box 3 module complete
S&F modular flush metal box 4 module complete
S&F modular flush metal box 6 module complete
S&F modular flush metal box 8 module complete
S&F modular flush metal box 12 module complete
Taking down old U/S sub main wiring of any size & make.
M&L for concealed submain wiring complete with 4 Sqmm single core multi standred PVC insulated and sheathed cable FRLS copper conductor two runs and one run of 4 Sqmm copper cable for earth continuity conductor(measured as one RM) in and including drawn through PVC conduit/sleeves with all PVC accessories fixed on wall, floor/ceiling and making good the distrubed surface by putti/cement and paint complete all as specified.
Taking down old U/S rusted main switch/DB including MCBs of any size capacity and make.
Distribution board factory made and tested made of sheet metal enclosure powder coated suitable for mounting the MCB 240 volt of the following DBs :-
4 way TPN with busbar 415 volts (double door type).
8 way SPN with200 Amp rated busbar 240 volts (double door type).
4 Way SPN with 200Amp rated busbar 240V (Double door type)
S&F MCB 240 volts 10 KA, rupturing capacity fixed in DB's of the undermentioned type and rating.
MCB SP 240 volts 10-40 Amps
MCB SPN 240 volts, 40 Amps
MCB TPN 415 volts, 63 Amps 16 KA 4 Pole
S & F in repair LED batten 20watt suitable for 1200mm long with G-13 lamp holder T5 and T8 , housing finished in alluminium powder coating complete with all accessaries all as specified and as directed by Engineer-in-Charge.
M&L in repair batten/angle holder insulated with back plate including suitable size of PVC round block make Anchor code No 51205 complete all as specified and directed by Engineer-in-Charge.
S&F in repair LED bulb 07W cool day light , in-built voltage surge protection > 3.5kV, single ph, 230V, luminous efficacy 100Lm/Watt, base B22, min 3 star rated all as specified and as directed by Engineer-in-Charge.
S & F in repair LED light fitting mirror type with high output diffurser 2 feet, 7w/10w 220V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable suitable size complete all as specified and directed.
Supply and fix in repair LED batten tube light 18/20w with battery and inverter power 230V 50Hz having colour rendering index equal or more then 80 , THD less then 30%, copper wired having colour temperature 6300K, internal surge protection device upto 3kV , comprising of Li Ion battery 1nos and emrgency/power failure backup of minimum 4hours, aluminium extruded housing and polycarbonate front cover, working life should be as per LM 80 all as specified and directed by Engineer in charge.
Excavation in trenches not exc 1.5 m in depth and not exc 1.5 m wide for taking out/laying LT UG cable, Stay wire and LT pole/post holes etc and getting out in hard/disintegrated layer complete all as specified.
Removing excavated soil at a distance not exc 50 m and deposited where directed complete all as directed
Returning,filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm complete all as directed
Supply & laying sub class B bricks, locally available un-burnt bricks suitable for LT cable protection cover all as specified and as directed by Engineer-in-Charge
M &L local river sand for bedding ang sand cushioning of all LT UG cable all as specified and directed by Engr-in-Charge
Supply, laying and testing cable XLPE insulated,screened, PVC bedded, galvanised steel strip or wire armoured,electric power cable (heavy duty) with stranded aluminium conductor 1100V grade , 3 1/2 core of size 95 Sqmm, rate including taking out of old UNSV cable from trench/floor etc all as specified and as directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE insulated,screened, PVC bedded, galvanised steel strip or wire armoured,electric power cable (heavy duty) with stranded aluminium conductor 1100V grade , 3 1/2 core of size 70 Sqmm, rate including taking out of old UNSV cable from trench/floor etc all as specified and as directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE insulated, screened PVC bedded, galvanised steel stripped or wire armoured electric cable heavy duty with stranded aluminium conductor , 1100Volts grade of size 16 Sqmm 4 core all as specified and directed by Engineer in Charge.
S & F in replacement and laying galvanised steel tubing Light grade (ISI marked) for protection of under ground cable on poles/walls under road crossing of size 40 mm borecomplete all as specified and directed by Engg in charge.
S & F street light GI bracket of 1.5 mtr long made out of 40mm dia light grade GI pipe bend to shape of 120 degree end welded at required including 02 Nos MS clamp of FL 40 x 6mm including nuts bolts & washers complete necessary fixing arrangements on pole and including Dismantling old U/S GI bracket of any size & length. complete all as specified.
S&F of "lithium based Energy Efficient Integrated Solar Street Light of 40 Watt"in Single FRP body with duly Polyurethane coating , encases with Monocrystaline Solar PV Panel of 65-67 Wp, Lithium Battery 11.1/12.8V, 33/36AH with inbuilt BMS, IP 65, high brightness, CRI>70, Color temperature 5700-6500K, Microcontroller based charge controller cum driver, automatic dimming function, Dusk to Dawn Operation, suitable to working temperature:(-) 10 degree celcius to (+) 55 degree celcius adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protection: Short Circuit, overload, Reverse polarity and battery protections complete including taking down old u/s street light of any capacity all as specified and directed by Engg in charge.
S&F in repair LED street light fitings of 60 watts new generation energy saving, environmental friendly, long life, versatile pressure die cast aluminium IP66 with 10KV surge protection road way, luminaire with high power LED as light source and suitable drivers etc to complete all as specified and directed by Engg in charge
M&L for rewinding of 7.5/5 HP monoblock pumpset installed at Gundrai Sump and cdts hostel including taking out from mounting , disconnecting all electrical and water connections , transportation to workshop and installaing back after rewinding, replacing defective capacitor, impeller housing, bearing, GI fittings of 20mm all kind, lathe work if required, testing as per the Govt procedure after installation etc all as specified and as directed by Engineer-in-Charge.
Supply and fix in repair on load change over switch 415 v in sheet metel enclouser 4 pole of capacity 160 amp all as specified and directed by engineer -in-charge
Supply and fix in repair on load change over switch 415 v in sheet metel enclouser 4 pole of capacity 200 amp all as specified and directed by engineer -in-charge
Material and labour for renewal of Chemical Earthing complete with copper earth plate electrode of size 600x600x3mm thick buried directly in ground (earth pit should not less than 4 mtr deep below normal ground level ) with top edge of the plate not less than 2.95 mtr deep below normal ground connected to and included copper earth strip 20mmx 3mm by means of copper bolts nuts check nuts and washer returning and filling the pits with excaviated vsoil mixing with charcoal 250 kg crystal salt 200 kg magnisiun sulphate of 100 kg and vegitable soil all around the plate up to 350 mm above from top edge of plate and balence portion filling with excaviated soil in layers not exc 25 mm thick 25 mm bore galvanised iron medium grade watering pipe up to top of plate 50mm bore galvanised iron light grade pipe for earth strip protection including all excavation earth work in any type of soil pcc 1;3;6 type c1 ....for chamber of internal size 300mmx 300mmx300mm with 120mm thick wall and 700mmx700mmx150mm thick bed concreat RCC 1:2:4 ,type b1 for precast chamber cover 50mm thick reinforced with welded steel wire fabric orxPM jali (weight not less than 4.00 kg/sqmm) ,funnel,with wire mesh complete all as specied and directed. Note (i) Quoted rate shall be deemed to include for earth strip with protection pipe up to 7.5 M length
Material and labour for making the hole under road and hard standing for laying Galvanised steel light grade pipe upto 100 mm dia including all fittings as required at site by mechanical drill system or Auger system and making the surface good as per existing surface completed all as specified and directed by Engineer-in-Charge. Note : The cost of Galvanised steel light grade pipe of size upto 100 mm dia shall be measured and paid separately under appropriate item of BOQ.
Supply and fix in repair energy efficient LED flood light fitting of 120 Watt capacity with toughened clear glass , LED chip efficacy > 130 lumen / watt, system efficacy > 120 lumen / watt, luminarie shall be mandatory brand embossed on luminaries, potted antivibration driver. The driver shall be able to withstand for indoor at 440V for 8 hours . The driver should have fascility and cut off voltage. Input over voltage protection will be > 300 Volt AC and for cut off the luminaires should withstand for 48 hours at 100 Volt AC. The LED efficacy shall be more than 85% at a junction temperature of 85 degree centigrade. All screws of the luminaires should be SS304. Luminaires pressure dicast aluminium housing with mendatory secondary optics, CCT: 5700K ANSIBIN, CRI > 70, LED source : 1-5 Watt high power type , driver of luminaire shall be preferably in separate compartment another optical compartment .The LED driver shall be constant current type fully potted. Driver shall be provided for all luminaires. It should be moiture resistant and fire reterdant. At least industrial grade or higher grade component should be used for manufacturing of driver. The driver shall be able to withstand surge (EFT+ESD interference) of minimum 4 KV. Luminaire shall have surge protection device of minimum 10 KV inside the driver compertment. The driver shall have under voltage, over voltage and short circuit protection and auto recovery mode. Total harmonic distortion shall be < 10% with power factor minimum 0.95. It should give consistent performance in the input voltage range of 120 V - 270 V at 50 Hz. Luminaires shall be mandatory brand embossed of luminaries and including all electric connection and bracket of suitable size up to 1.5 m long and MS Flat clamps of suitable size and other accessories complete all as directed.
Supply and fix 3 mtr Designer MS pole in Polyster/PU superior finish with single arm designer bracket suitable for single side mounting of drop down luminaires. Pole should have provision of mounting on foundation with four numbers anchor bolts. Pole should have length from base of 1mtr having dia of 89mm and for rest 2 mtr it should have dia of 76mm complete including dismantling of old PCC pole all as specified and directed by Engineer in Charge.
Supply and install in repair LED 70W Ornamental Road light / street light pendant mounting type having Spun/sheet Aluminium main housing having clear acrylic front cover LM 80 certified high power LED including isolated electronic cc driver with complete internal wiring , Aluminium heat sink operating voltage 140v-270v, operating temperature -10c to 50cwith minimum IP65 protection, CRI not less the 70, THD not more then 10%, CCT 5700k, open and short circuit protection, reverse polarity protection, High voltage cut off at more then 290V, surge protection all as specified and directed by Engineer-in-charge.
M & L for servicing of industrial RO Plant installed at academic complex including back washing, cleansing the filter medium, resetting all TDS upto the recommended level by PHED, checking all valves, servicing the turbo jet motor for raw water, checking and tighting all mounting brackets, nuts. Bolts etc. removing fungus by cleaning of raw water and filtered water storage tank all as specified and as directed by Engineer-in-Charge. Note: Technician should be hired from reputed company of the RO plant. No extra allowance shall be be given to the technician. Coneyance must be ensured by the contractor only. No vehicle shall be provided for the conveyance of the technician by MES.
S&F for replacement of the following spare parts of RO plant of capacity 40 to 200LPH installed at academic complex:
Primary sediment cartridge Filter
Secondary sediment cartridge Filter
RO membrane as per the existing make and model suitable for 200LPH capacity
Rewinding of raw water motor and servicing of pumpassembly of capacity 2HP
PCB control panel with LED display and mounting accessories and testing etc
supply and fix Rubber mat of 1 meter x 2 meter x 25 mm complete all as specified.
Supply only electric rubber hand gloves 11KV all as specified and as directed
Supply only electric rubber hand gloves 33KV all as specified and as directed
Supply only portable and rechargeable type long range LED torch/Beemer light multifunctional having different lighting modestype having rated power minimum 15W and provide 4 hours of backup all as specified and directed
Supply only safety helmet yellow in colour with LED light comprising latest safety norms all as specified and directed
Supply only electric safety PVC/Rubber shoes 10No boot size
Supply and fixing in replacement of old unsv Direct Online Starter of capacity 7.5HP suitable for monoblock pumpsets installed at cadets hostel area complete all as specified and as directed by Engineer-in-Charge.
Replacement in Repair fully automatic star delta starter comprising of voltmeter 0-500 V and ammeter 0-100 Amps, single phase preventor, over load relay and timer housed in single MS sheet powder coated enclosure suitable for up to 40 HP submersible motor pump complete all as specified .
Material and labour for Rotational moulded polyethylene water storage tanks 500Ltr (cylindrical vertical with closed top) hoisted and fixed in position with float valve complete all as specified in SSR Part I
Supply only Calcium based high strength granular Chlorination chemical water disinfectant, a white free flowing granular material which is free of Foreign materials, concentration of Chlorine content should be between 60 to 70 percentage stability,.
Servicing of DG set of capacity of 63 KVA to 82.5KVA water/air cooled (Kirloskar) by unscrewing nuts, bolts and servicing of DG set with checking, draining and changing of Engine oil and Coolant, checking and changing of V-belts, greasing and oiling of all relevant parts and topping up, Cleaning the inner body of Fuel tank and Radiator etc by removing sludge etc and reassembling the DG set after repair and replacement of unserviceable parts of DG set including repair of control panel, opening of alternator, water pump, starter motor for cleaning, servicing and refixing. Checking and servicing of Battery and testing complete in all respect all as directed by Engr-in-charge. Note: Spares shall be measured & paid separately for dismantling of DG set partly or full shall be paid accordingly.
Supply only following spare parts for item above item of capacity range 63 KVA to 82.5 KVA.
Air cleaner element
Water hoses including clamps complete all as specified.
Fuel filter element.
Lubrication oil filter
Fuel level sensor
oil Temp sensor
Fan belt.
Head Gasket
RC Joint, Set of O Rings, Set of Joints
Valve Pair, Valve seal and Valve guide
Battery 150 AH, 12 Volts (Type Flat Bed, Maintenance Free) with minimum 24 Months replacement gurantee.
Analog type Voltmeter as per existing make complete all as speified
Analog type Ammeter as per existing make complete all as speified
coolant in one/two ltrs packing complete all as speified
Supply only distilled water in one/two ltrs packing.
Supply & filling oil of recommended grade (DF-4, 15 W 40) complete all as speified.
Supply only expansion joint of Engine outlet all as specified
Supply only of data card of auto control panel of existing make or as specified
Supply,connect,fix and testing in repair submersible cables copper conductor PVC insulated over all sheathed flat flexible, ISI marked - Conforming to IS 694,1100 volts grade complete of sizes
10 sqmm 3 core
16 sqmm 3 core
Taking out old Existing U/S MCCB from LT panels/ Feeder piller of following capacity and replace with new MCCBs without damaging the LT panel board or any assets associated with the installation. Make Havells/L&T/ABB/Schneider. (a) MCCB 4 pole TPN, 160Amps capacity, 36KA breaking capacity, 415V,adjustable thermal & fixed magnetic setting, Ics = 50% of Icu,
All as above item No 73 but MCCB 4 pole TPN, 200Amps capacity, 36KA breaking capacity, 415V,adjustable thermal & fixed magnetic setting, Ics = 50% of Icu,
All as above item No 73 but MCCB 4 pole TPN, 400 Amps capacity, 36KA breaking capacity, 415V,adjustable thermal & fixed magnetic setting, Ics = 50% of Icu,
All as above item No 73 but MCCB 3 pole TP, 63 Amps capacity, 16KA breaking capacity, 415V,adjustable thermal & fixed magnetic setting, Ics = 50% of Icu,
All as above item No 73 but MCCB 3 pole TP,100Amps capacity, 16KA breaking capacity, 415V,adjustable thermal & fixed magnetic setting, Ics = 50% of Icu,
Dismantling electric motor of centrifugal pump 3 phase for 440 volt 30 HP and rewinding of motor with super enameled copper wire of same guage & turn including material, varnishing, re-assembling, testing & commissioning /complete all as directed by Engr-in-Charge Note: Spares shall be measured & paid separately for dismantling of pump set partially or complete shall be paid accordingly.
Dismantling electric motor of centrifugal pump 3 phase for 440 volt 15 HP and rewinding of motor with super enameled copper wire of same guage & turn including material, varnishing, re-assembling, testing & commissioning /complete all as directed by Engr-in-Charge Note: Spares shall be measured & paid separately for dismantling of pump set partially or complete shall be paid accordingly.
Supply only spare parts for above Centrifugal Pump of 30 HP and 15 HP as item No 78 and 79.
Ball bearing SKF/NBC (6309)
Pump shaft with Key
Coupling Key
Gland Plate (Set of two)
Suction/Discharge stud/Nuts/ Bolts
Gland Bush (Gun metal)
Coupling rubberised
Foot valve 80mm GI or CI heavy grade as per existing
High performance AP3 Grease in 1Kg or 2kg packing Make; NBC/Bosch/Castorl/HP or equivalent
Supply and fixing in repair of GI water tubing IS-1239 marked, medium grade, in replacement including all necessary pipe fittings laid in trenches, on wall, under floor, under road on same or new route and making good the disturbed portion as existing and including taking down of old unserviciable pipe of the following sizes :- Note :-excavation earth work will be measured and paid saperatly.
15mm bore
20mm bore
25mm bore
40mm bore
Taking out submersible pump set of capacity 40HP, 3 Phase 415 volt AC supply alongwith column pipes from the bore well by disconnecting electric connection, disconnecting the motor from pump dismantling the motor & over hauling the same by repairing/ replacing defective part as ordered & re-assembling including M&L for replacing worn- out nuts bolts washers complete, connecting /coupling the motor with pump & with column pipes & lowering the same after repairing, making the connecion complete all as directed by Engr-in-Charge. Note: Spares shall be measured & paid separately for dismantling of pump set partly or full shall be paid accordingly.
Supply only spare parts for above 40HP submersible pump from item No 82
Hook bolt
Motor Bush
Rubber Bush
SS Bush
Stud with nuts & bolts
Neck Ring
Impeller
Top/Bottom bearing bush
SS Rooter sleeves
Thrust Plate
SS shaft
Bowl Bush
Diffuser CI/Steel
M&L for rewinding the submersible Motor 40HP with super enamaled copper winding wire of suitable gauge & superior class of insulation including insulation paper sleeves thimbles etc & testing complete all as specified.
M&L for rewinding the Submersible pump Motor 5HP/7.5HP with super enamaled copper winding wire of suitable guage & class of insulation including insulation paper sleeves thimbles etc & testing complete all as specified.
Supply and fixing of the following spare parts of FASD starters:
Contactor switch 25Amp capacity, with 380-415V coil, ML model of L&T or equivalent
Contactor switch 40Amp capacity, with 380-415V coil, ML model of L&T or equivalent
Contactor switch 70Amp capacity, with 380-415V coil, ML model of L&T or equivalent
Start/Stop push button toggle switch
Starter relay 415V, 40Amp or above upto existing capcity range
Multi controller/single phase preventer & timer switch relay in single box capacity ranging from 7.5HP to 40HP make L&T, cat part No CS94824D000
Labour only for servicing APFC panel board and cochecking all the contact terminals and capacitors, repairing the terminal wire circuits, tightening all kind of nuta sn bolts, screws atc, cleaning inside the chamber, enclosure etc, checking the connection of CT coil from panel to main incoming source and repairing in case of any fault in connections all as specified and as directed by Engineer-in-Charge. Note: Replacement of Spares shall be measured and paid separately.
Supply and replacement and testing at site of the following accessories of APFC panel:
Cylidrical series capacitors, KVAr rating 2, 440V, 3Ph, heavy duty,
Cylindrical series capacitors, KVAr rating 5, 440V, 3Ph, heavy duty,
Cylidrical series capacitors, KVAr rating 10, 440V, 3Ph, heavy duty,
VAF + PF meter accuracy class 1.0. 0.5, input voltage measurement range 50 - 520 VAC (P-P), Aux supply 80-300 VAC/DC, CT secondary side 1A/5A, Flush mounting 96x96, CT/PT programmable, Para meters VLL, VLN, A, F, PF, On Hrs, RPM, Apeak etc with RS485, Cl-1,
Dismantling and taking burned out LT cable ends and supply and fixed Aluminium Lugs of size 16sqmm to 35sqmm all as specified
Dismantling and taking burned out LT cable ends and Supply and fixed Aluminium Lugs of size 50sqmm to 95sqmm all as specified
Dismantling and taking burned out LT cable ends and Supply and fixed Copper lugs of size 16sqmm to 25sqmm all as specified
Supply and fixing in replacement of sluice valves of cast iron body with forged brass spindle, class PN 1.6 and cast iron wheel head, both ends flanged, IS-1486 marked complete with neoprene rubber gasket joints, nuts, bolts (high tensile), and washers etc all as specified and directed of following size:-
150mm bore flanged end.
100mm bore flanged end.
Supply and fixing in replacement of non return valve, flanged ends PN 1.0 ISI marked of 100mm bore.
Supply and fixing in replacement of non return valve, flanged ends PN 1.0 ISI marked of 80mm bore .
M & L for dismantling existing broken valve pit complete with corroded MS sheet cover including removal of all material and construction of valve pit chamber, brick masonry all as specified in drg No TD/2004/26 sheet 1/3 to 3/3 for sluice valve including plastering, PCC in foundation excavation and earth work, MS sheet cover (3mm thick) with locking arrangement, painted with two coats of anticorrosive paint over one coat of primer of following sizes:-
1000mmx 950mm x 1000mm
1200 mmx 1200mmx 1000mm
supply and fix Nuprine rubber / Leather gasket minimum thickness 8mm suitable for tightening the GI flange or any othe joints of 100mm dia with nuts and bolts,
Demolition of old PCC foundation any type and size including removal of anchor bolt and removing debris from site at safe place as eco friendly manner complete all as specified.
M&L for PCC work for pumpset platform and other misc pedestal supports, type C1, mixing ratio 1:3:6 using 20mm gradded aggregate complete including form work etc complete all as specified.
Painting of motor and pumpset centrifugal type upto 30HP,monoblock pumpset,mounting channels of pumpset of any size and Painting of MS sheet cover fabricated on open well No 1, 2 and 3 at Gundrai after preparation ,painting of sluice valve/NRV/Air Release valveand one x sigle coat primer and applying spray painting of two coat synthetical enamel paint of approved colour etc without disturbing anyother parts of the complete set complete all as specified.
Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters figures and conventional skull and bones in singnal red colour and fixed with MS clamps, bolts and nuts of approved size for LT of 20x15cm complete all as specified.
Demolitiion of brick work/stone boulder masonary, built in cement mortar or cement lime mortar including all quions arches,pillars etc but excluding ashlar facings,dressed stone work and precast concrete but exceeding ashlar facingdressed stone work and precast concrete articles complete all as specified.
Brick work with sub- class 'B' bricks, straight or curved on plan exc 6m mean radius, built in CM 1:4 complete all as specified
M&L Brick work with sub- class 'B' bricks, straight or curved on plan to any radius in half brick thick wall in CM, built in CM 1:4 complete all as specified
M&L for rendering 15 mm thick on fair faces of brick work or concrete surfaces of in cement mortar 1:4, finished even and smooth without using extra cement complete all as specified
Taking down cement plaster of any description including racking out joints, hacking for kay scrubing down with water etc complete all as specified
M&L for rendering 15 mm thick on stone masonary surfaces or surfaces other than fair face of brick work or on one side of lathing in cement mortar 1:6, finished even and smooth without using extra cement complete all as specified
M&L for rendering 15mm thick in cement mortar 1:4 on stone masonry surfaces or surface other than fair face of brick work of walls, finished even and sommoth without using extra cement on edges/ Chajjas/Roof projection and simlar courses etc complete all as specified
M&L Preparation of new plastered surfaces of walls or unplastered surface and applying two coats of cement base paint over a coat of Priming with alkali resistant priming paint with hand roller complete all as specified
M & L preparation of newly plastered surfaces of walls or unplastered surfaceand applying three coats of white wash complete all as specified
M & L Preparation of old decorated plastered or undecorated plastered surface of wall including cornices, pilasters etc by brooming down, steel wire brushing ,scraping down smoke soot, moulds, moss and efflorescent salts and treating oil and greasy spots and applying Two coat of white wash complete all as specified
Ditto all as per Srl item No 10 here in above but applying Two coat of white wash on ceiling complete all as specified.
M&L for Preparation of old decorative concrete, plastered/ un-plastered surface of wall including cornices, pilasters etc by brooming down, steel wire brushing ,scraping down smoke soot, moulds, moss and efflorescent salts and trading oil and greasy spots removing nails and filling small holes by putty and rubbing surface by sand paper to prepare the surface and applying Two coat of cement based paint using hand roller of approved colour complete all as specified
M&L for Complete removal of existing treatment,washing, rubbing down and stopping of distemperd and painted surface of old surface by Electric Rotary grinder including brooming down with steel wire brushing, scrapping down smoke soot, moulds, moss and efflorscent salts and trading oil and greasy spots of Wall Surface removing of nails, making good holes , cracks etc , cleaning of floors , glasses, joinery of drops and splashes incl all arrangement necessary for execution of work, complete all as specified
M&L for Two coats of oil emulsion distempering white or tinted (copolymer based resin glue to be added for longer durability and better finish) over plastered & including 1.5mm thick wall care putty on Wall after sand paper gentle rubbing to obtain smooth surfaces including all necessary arrangement for execution of work complete all as specified
M&L for one coats painting with synthetic enamel paint to old wood or wood based surfaces of any description, not otherwise described over 10 CM width or girth including preparation of surface including all preparatory work complete all as specified
M&L for one coats painting with synthetic enamel paint to old steel or steel based surfaces of any description, not otherwise described over 10 CM width or girth including preparation of surface including all preparatory work complete all as specified
Taking down chowkhats or frames not exc. 1.5 sq. m each with shutters (without taking off shutters from the frames)
Taking down chowkhats or frames exc. 1.5 sq. M but not exc 4 sqm each with shutters (without taking off shutters from the frames) complete all as specified
S&F factory made solid panel PVC door shutters 30 mm thick (style) consisting of fram made out of MS tubes for top & bottom rails. MS fram shall be covered with heat moulded plain colour PVC ‘C’ channel having a PVC sheet strip of 20 mm width stuck inside with solvent cement for stiles and plain colour PVC sheet for top rail, lock rail & bottom rail on either side & as gap insert for top rail & bottom rail; Panelling of plain colour PVC sheet to be fitted in the MS fram welded/sealed to the stiles & rails with suitable PVC sheet beading, and jointed together with solvent cement, suppling & fixing in the fram at site as per specification & drawing complete all as specified
S&F PVC Door frame of size 50 mm x 47 mm made out of 5 mm plain colour PVC sheet reinforced with MS squar tube , fixing in opening as per spesification & drawing
S&F 100 mm butt hinges medium weight cold rolled mild steel, ISI marked, fixed to angle iron chowkats including welding complete.
S&F 125 mm Aluminium handles, cast type, anodised complete all as specified
S&F 150 mm Aluminium anodised,barrel tower bolts of extruded section complete all as specified
Hacking out old broken glass (any thickness, size, quality or description) from wooden frames or stone, concrete or brick surrounds, glazed with putty or fixed with beads complete all as specified
S&F 3.00mm thick sheet glass ordinary quality and glazing with oil putty in square n'exc 0.5 sqm in each pane complete all as specified
S&F in repair 25mm curtain Harrison rails, mild steel, chromium plated with fixing brackets, stops, rollers etc complete all as specified
Material and labour Anodised aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified, including powder Coating (minimum thickness of powder coating 50 micron), complete all as specified
S&F anodised Aluminium door shutters,aluminium section weighing 0.55 kg/m including necessary joining cleats,glazing clips, ruber neoprene packing,handles 2 Nos in each door, hinges,anodised aluminum snap beading screws etc. complete all as specified
S&F Anodised aluminium window and ventilator shutters, side hung type without sash bars, aluminium sections weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber packing, anodised aluminium snap beading, screws, anodised aluminium fittings such as peg stays 150mm long (1 no.). hinges type B-21100mm long (2 no.) suitable handle (1no.) complete all as specified
S&F stainless steel wire cloth .36mm nominal dia of wire and average width of aperture 1.40mm and fixed with stainless steel wire staples, complete all as specified
S&F 140 mm long floor door stopper of aluminium alloy body and tongue, anodised, with hard drawn steel spring, fixed in floor complete all as specified
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises complete all as specified.
Non skid coloured ceramic tiles area of each tiles exceeding 0.11 Sqm but not exceeding 0.18 sqm (400x400) 7 to 8 mm thick in floor/skirting set in neat cement slurry and pointed with coloured/white cement to match the surface complete all as specified
M&L Screed bed or bedding layer of mortar 15 mm thick in CM 1:6 for laying floor finishes complete all as specified
M & L Glazed ceramic tiles in vertical surface 300x200x7mm/ 350x 250x 7 mm/ 450X 300X 7mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match the surface over 10 mm thick CM 1:4 complete all as specified
Dismantling of stone slabs and tiles of any description or thickness in floor,apron,roofs laid bedded and pointed in any mortar
M&L 20 mm thick Granite (of any type/ any colour) work (table rubbed and polished) in steps, jambs, pillars, window- cills, cooking platforms and like in cement mortar (1:4) including pointing in white cement (1:2) using marble dust with admixture of pigment to match with shade of granite complete all as specified
Machine cut kota stone slab flooring 20-25mm thick laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and mirror polishing complete all as spacified and directed. over 15mm thk screed bed in CM 1:4 .
Machine cut kota stone slab 20-25mm thick in riser of steps,skirting, dado and pillar laid ove cement screed and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and mirror polishing complete incl 10mm thick plaster in CM 1:4 complete all as specified
Demolition of cement concrete (reinforced) of any description and in any position not otherwise specifically provided for
M & L reinforced cement concrete 1:2:4 (20 mm graded aggregate) type B1 nominal mix as in slab supported on ;walls,beams and column in or,roof, landings, balconies ,canopies, deck slab or as in shelves and chajjas etc all as specified.
M&L Precast reinforced cement concrete 1:2:4 type B-1 (using 20mm graded crushed stone agg) as in landings , cover slabs for man holes etc) chullah hood, chajjas , water troughs mangers ,shelves and similar articles with plain faces ans setting in mortar 1:4 complete all as specified and directed.( reinforcement shall be measured seperately) complete all as specified
Use and waist for form work to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work; not exceeding 200 mm thick (Horizontal or slopping) rough finished flat surfaces complete all as specified
M & L for mild steel 10mm dia, and over deformed bars cut to length bent to shape as required TMT bar including cranking bending with MS steel wire not less than 0.9 mm dia complete all as specified
S&F Iin repair stainless steel gratings of outer frame dia 100 mm openable type incl all necessary fittings such as hinges including embeding in tiles with white cement complete all as specified
S&F in repair Soap dish holder (SS), any type, fixed to plugs with chromium plated brass screws complete all as specified
S&F in Repair Tubular towel rail, 20mmdia, D type, 60cm long between flanges complete all as specified
S&F in repair PVC connection 15 mm size with PTMT nuts of length 450mm fixed complete all as specified
S&F in repair Bib taps, cast copper alloy Chromium plated with crutch or butterfly handle, screwed for iron pipe of 15 mm bore or for brass ferrule and fixed complete all as specified
S&F in repair 15 mm bore Stop valves/angle valve, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed complete all as specified
S&F in repair pillar taps, cast copper alloy, with capstan heads, chromium plated fancy type (swan neck ),screwed down high pressure, with or without lettered 'Hot' or 'Cold' with long screwed shanks and fly-nuts, screwed for iron pipe and fixed complete all as specified
S&F in repair vitreous china wash basin white, ovel type of size 580x 450mm including CP brass waste coupling 32 mm dia , pair of MS angle brackets or MS fastener/ bolts for fixing arrangements complete all as specified
S&F in repair vitreous china urinal Half stall type white with grating and union for discharge pipe incl providing and fixing plugs bedding urinal against wall in CM 1:2 securing urinal to plugs with and incl Urinal spreader of PTMT any colour complete all as specified
S&F in repair PVC waste pipe flexible type suitable for couplings 32 / 40 mm dia and 750 mm long complete all as specified
S & F in repair Vitreous China squatting pan, of ‘Orissa pattern ‘ white of size 580 X 440 mm, with integral foot rests and 'P' or 'S' trap including provision of cement concrete (1 cement, 2 sand or surkhi and 5 aggregate) bedding minimum 150 mm thick complete all as specified
S&F in Repair 10 Liters PVC valveless, syphonic action type,flushing cistern, low level, white, with inlet, ball valve, float and handle including brackets complete all as specified.
Demolition of cement concrete in ground floor and pavings not exc 15cm thickness below or above ground level, including removal of debries complete all as specified
M & L 75mm thick PCC 1:4:8 type D2 using 40mm graded stone aggregate as in Sub floor, Sub -Base, floors and pavings complete all as specified
Providing and laying 60mm thick factory made chamfered edge cement concrete paver block of M-35 grade with approved colour, design & pattern as in footparth, parks, lawns, drive ways or light traffic parking etc., of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50mm thick compacted bed of fine sand, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand complete all as specified
M&L for PCC type B1 1:2:4 (20 mm graded aggregate) as in benching, copings, bed plates, kerbs and the like including weathering, slightly rounded or chamfered anglesand throating etc incl necessary formwork complete all as specified
Dismantling wrought iron or Mild steel work of any description not otherwise provided for complete all as specified
Framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding,with and including either hooks,and hinges or steel hanging,door fittings (exclusive of steel sheeting or other covering,running rails and guides) and,hanging; also fastening and,fixing complete all as specified
Dismantling of expanded metal any thickness or mesh fixed with steel , wood fillets if any.
S&F welded steel wire fabrics n exc 4Kg fitted to steel members all as specified and directed.
Fixing & greasing existing rolling shutters, without ball bearing,including top cover, anchoring rod , hasp and staple; erected in position as indicated,repairing to level gear box and crank handle or Safety lever locks mild steel with 4 levers for rolling shutters (if required)or any other material required to make Rolling Shutter in woking condition complete all as specified
S&F in repair PVC SWR pipes 75 mm bore single socketed in any length with rubber ring joint fixed to wall or laid in trenches or in floors with steel clamps complete all as specified
M&L for preparing surfaces of any description over 10 cm girth or width, not otherwise described and applying two coats of synthetic enamel paint over a coat of Red oxide on new surfaces of steel or iron complete all as specified
Rajesh Mishra (BID ID -3141072)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .