| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.3 LAccepted-AOC A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹38.6 L+₹66,066.98 (1.74%)Rejected-Finance A 303 VEENA CGHS LTD PLOT NO 5D SECTOR 22 DWARKA NEW DELHI 110077 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110077 | L2 | Rejected-Finance BEING NOT LOWEST | |
| 3 | L3₹42.4 L+₹4.5 L (11.8%)Rejected-Finance | L3 | Rejected-Finance BEING NOT LOWEST | |
| 4 | L4₹44.9 L+₹6.9 L (18.3%)Rejected-Finance | L4 | Rejected-Finance BEING NOT LOWEST | |
| 5 | L5₹46.7 L+₹8.7 L (23.1%)Rejected-Finance WZ 1000 NANGAL RAYA PANKHA ROAD SOUTH WEST DELHI DELHI 110046 | DELHI | SOUTH WEST DELHI | DELHI | 110046 | L5 | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹50.0 L
EMD Value
₹1 L
Closing Date
26 Jun 2021, 6:00 pmClosed
SHRI ARJUN PATRO,IDSE
GE (U) ELECTRIC SUPPLY,DELHI CANTT
MANNING AND OPERATION OF 3311 KV MRS AT AHR R 11 KV SUB STATION NO 1 LOCATED AT PARADE GROUND REPAIR REPLACEMENT OF 46 POLE STRUCTURE AT MALL ROAD MANEKSHAW ENCLAVE AND CONNECTED ITEMS IN ADJOINING AREA AGE U ELECT SUPPLY NO II UNDER GE U ELECTRIC
2021_MES_447296_1
GE ELECT/D-29/2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
334 days
GE (U) ELECTRIC SUPPLY
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹1 L
Yes
19 Jul 2021
3 Jun 2021
28 Jun 2021
4 Jun 2021
26 Jun 2021
20 Jun 2021
Amount
Manning and Operation of 33 KV GIS and 11 KV AIS Main receiving Sub station at Army Hospital R&R round the clock ( three shifts) including sunday and holidays by deployment of 01 electrician in each shift including preventive maintenance of following electrical equipments:- (a) Transformer step down 33/11 KVA capacity 8 MVA /10 MVA incl marshal boxes and accessories control cables complete-02 Nos (b) 33 KV GIS breaker & control panel,36 KV, 1250 Amp as incomer - 02 Nos (c) 33 KV GIS breaker & control panel,36 KV, 1250 Amp as as outgoing - 02 Nos (d) 11 KV VCB HT Breaker & control Panel,12 KV, 1250 Amp, 50 Hz as incomer - 02 Nos (e) 11 KV VCB HT Breaker & control Panel,12 KV, 1250 Amp, 50 Hz as outgoing - 05 Nos (f) 11 KV Bus PTpanel -01 Nos (g) 11 KV VCB HT Breaker & control Panel,12 KV, 1250 Amp, 50 Hz as buscoupler - 01 No (h) 11 KV Bus Rise cum Bus PT panel - 01 Nos (i) RTCC Panel for 8/10 MVA transformer -02 Nos (j) Battery charger 110 volt DC -02 Nos (k) Battery bank 110 volts DC -01 Set (l) Substation SCADA including data concentrator unit (DCU), operating workstation Ethernet sitch unit & inverter with battery back etc.
Note : (i) The contracotor will ensure suitable repalcement of electrician while on leave/weekly holidays and Wages for the same deemed to be included in the quoted rate. (ii ) The contractor shall ensure that electricians/ operator always be present in each shift. In case of absence of any worker the penalty @ Rs 100.00 per hour per electrician/ operator shall be imposed on the contractor. (iii) The contractor shall be responsible for maintaining the complete area (i.e. inside boundary wall ) such as building , hard standing , footpath etc in neat and clean position . All necessary T&P for cutting /cleaning of grass and vegitation will be arranged by contractor without any extra cost. (iv) The contractor shall provide uniform , raincoat, protective clothing such as hand gloves ,helmet, safety belt , first aid box and shoes etc to all persons on duty and the cost of the same is deemed to be included in quoted rate. (v) Person employed should be working experience of working on HT and LT Installation. (vi) The contractor shall provide log sheet and maintain the same on daily basis and the cost of the same is deemed to be included in quoted rate.
Worker's wage per person per day per shift (inclusive of GST as applicable)
Employees Provident Fund as per existing rules (Prescribed Rate of EPF as applicable on (minimum wages without GST ) + GST Rate as applicable on Prescribed Rate of EPF as applicable on (minimum wages without GST )
Employees state insurance as per existing rules. (Prescribed Rate of ESI as applicable on (minimum wages without GST) + GST Rate as applicable on Prescribed Rate of ESI as applicable on (minimum wages without GST )
Contribution of Bonus as per existing rules. (Prescribed Rate of BONUS as applicable on (minimum wages without GST) + GST Rate as applicable on Prescribed Rate of BONUS as applicable on (minimum wages without GST)
Over head & profit on total of srl No 1.02 to 1.05 as applicable.
LWC as per existing rules on total of srl no 1.02 to 1.06. The bidder should note that the minimum wages including all statutory provisions as mentioned in item no 1.02 to 1.06 are exclusive of GST for calculating of labour cess. Refer Sch 'A'Note No 33 (e) on Page No 17 of Tender Document.
NOTE For Item 1 and sub items :- (a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, ie proof of payment. (b)The rate quoted shall not be less than minimum wages as notified by Government of India / State Government / Local body whichever is higher including all statutory provisions such as EPF,ESIC,Bonus,taxes etc as applicable and also not less than applicable rates for contribution of employer towards EPF,ESIC and BONUS under respective heading /subitems. In case the rates quoted are less than the minimum wages as notified by the Government of India / State Government / Local body whichever is higher including all statutory provisions such as EPF,ESIC,Bonus,taxes etc on the last due date of bid submission. his tender will be treated as non bonafide and will not be considered for acceptance.In such case,the lowest bidder shall be determined from amongst the valid/bonafide bids only. (c) 'NIL' or 'Zero' quoting against OH & Profit will be treated as 'Non-bonafide'.
d) Contractor is required to quote upto two digits after decimal place or otherwise it will be considered by rounding off to two digits after decimal place in accordance with Rules for Rounding off of Numerical Values in accordance with IS:02 OF 1960(Revised 2016) of BIS. (e) In case of any variation occurs in minimum wage, liability of EPF/ESIC/Bonus/LWC/GST during contract period /extended contract period that shall be adjusted for reimbursement/recovery as under:- (i) Variation in minimum wage including other related statutory provisions shall be adjusted in terms of Condition 63 of GCC (IAFW-2249). (ii)Variation in percentage/rate of GST and LWC shall be adjusted as per instructions in Annexure XVI of MES Manual on Contracts which deals with ‘Reimbursement/Refund on Variation in Taxes Directly Related to Contract Value’
Manning and Operation of 11 KV Sub Station No 1 located at Parade ground round the clock ( three shifts) including sunday and holidays by deployment of 01 electrician in each shift including preventive maintenance of following electrical equipments:- (a) 11 KV VCB HT Breaker & control Panel,12 KV, 800 Amp, 50 Hz as incomer - 02 Nos (b) 11 KV VCB HT Breaker & control Panel,12 KV, 800 Amp, 50 Hz as outgoing - 02 Nos (c) 11 KV VCB HT Breaker & control Panel,12 KV, 800 Amp, 50 Hz as bus coupler - 01 Nos (d) Battery charger with battery bank-01 Nos
Note : (i) The contracotor will ensure suitable repalcement of electrician while on leave/weekly holidays and Wages for the same deemed to be included in the quoted rate. (ii ) The contractor shall ensure that electrician/ operator always be present in each shift. In case of absence of any worker the penalty @ Rs 100.00 per hour per electrician/ operator shall be imposed on the contractor. (iii) The contractor shall be responsible for maintaining the complete area (i.e. inside boundary wall ) such as building , hard standing , footpath etc in neat and clean position . All necessary T&P for cutting /cleaning of grass and vegitation will be arranged by contractor without any extra cost. (iv) The contractor shall provide uniform , raincoat, protective clothing such as hand gloves ,helmet, safety belt , first aid box and shoes etc to all persons on duty and the cost of the same is deemed to be included in quoted rate. (v) Person employed should be working experience of working on HT and LT Installation. (vi) The contractor shall provide log sheet and maintain the the same on daily basis and the cost of the same is deemed to be included in quoted rate.
Worker's wage per person per day per shift (inclusive of GST as applicable)
Employees Provident Fund as per existing rules (Prescribed Rate of EPF as applicable on (minimum wages without GST ) + GST Rate as applicable on Prescribed Rate of EPF as applicable on (minimum wages without GST )
Employees state insurance as per existing rules. (Prescribed Rate of ESI as applicable on (minimum wages without GST) + GST Rate as applicable on Prescribed Rate of ESI as applicable on (minimum wages without GST )
Contribution of Bonus as per existing rules. (Prescribed Rate of BONUS as applicable on (minimum wages without GST) + GST Rate as applicable on Prescribed Rate of BONUS as applicable on (minimum wages without GST)
Over head & profit on total of srl No 2.02 to 2.05 as applicable.
LWC as per existing rules on total of srl no 2.02 to 2.06. The bidder should note that the minimum wages including all statutory provisions as mentioned in item no 2.02 to 2.06 are exclusive of GST for calculating of labour cess. Refer Sch 'A'Note No 33 (e) on Page No 17 of Tender Document.
NOTE For Item 1 and sub items :- (a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, ie proof of payment. (b)The rate quoted shall not be less than minimum wages as notified by Government of India / State Government / Local body whichever is higher including all statutory provisions such as EPF,ESIC,Bonus,taxes etc as applicable and also not less than applicable rates for contribution of employer towards EPF,ESIC and BONUS under respective heading /subitems. In case the rates quoted are less than the minimum wages as notified by the Government of India / State Government / Local body whichever is higher including all statutory provisions such as EPF,ESIC,Bonus,taxes etc on the last due date of bid submission. his tender will be treated as non bonafide and will not be considered for acceptance.In such case,the lowest bidder shall be determined from amongst the valid/bonafide bids only. (c) 'NIL' or 'Zero' quoting against OH & Profit will be treated as 'Non-bonafide'.
(d) Contractor is required to quote upto two digits after decimal place or otherwise it will be considered by rounding off to two digits after decimal place in accordance with Rules for Rounding off of Numerical Values in accordance with IS:02 OF 1960(Revised 2016) of BIS. (e) Any variation in minimum wage, liability of EPF/ESIC/Bonus/LWC/GST shall be adjusted for reimbursement/recovery as under:- (i) Variation in minimum wage including other related statutory provisions shall be adjusted in terms of Condition 63 of GCC (IAFW-2249). (ii)Variation in percentage/rate of GST and LWC shall be adjusted as per instructions in Annexure XVI of MES Manual on Contracts which deals with ‘Reimbursement/Refund on Variation in Taxes Directly Related to Contract Value’
Supplying , installation, testing and commissioning of 11 KV, 630 Amps having short circuit capacity 20kA/3-sec, Outdoor (IP54), RMU (Ring main unit) 5-way comprising of 02 Nos motorized operated Load Break Switch and 03 Nos 630 Amp Fixed-Type motorized spring-charging VCB electrolytic grade copper busbars all inside single, gas-filled, robotically welded stainless steel 304 (Non Ferrite Non Megnetic Grade) tank with min. thickness 3+0.5 mm, IP 67 Degree of Protection , internal-arc classified 20kA/1sec, on-site-repairable with site replacable bushing/coupling/mechanism, gas refilling etc. The enclosure shall have padlockable double-door access with anti-theft hinges, fully covering the front facia and cable boxes to ensure fail-safe anti-theft protection. The unit alongwith Bus-connected, fixed-type Auxiliary transformer shall include the following along with all necessary accessories and fittings as required at site. LOCATION : MALL ROAD CIRCLE -01 NO , CASSEL ROAD SUB STATION -01 NOS
(A) 02 Nos. Incoming Load Break Switch module each consisting of following accessories :- (i) Each switching-unit is designed as a three position switch. This three function switch combines the functions of switch-disconnector and earthing switch. (ii) 11kV, 630A Load Break Switch with interlocked line-earthing scheme both short circuit current - 20kA/3-sec, Making Capacity - 50kAp -01 No (iii) Auxiliary contacts - 1NO + 1NC-01 No (iv) Spring-assisted snap-action motorized mechanism with un-inhibited operating shaft for emergency manual operation with integrated earthing switch -01 No (v) Cable terminals (site replacable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes) with double-door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access upto 11 KV , 300 Sqmm , 3 Core , XLPE AL cable termination in live-condition. Each Set of 03 (vi) Right angle boots (push on type)-Each Set of 03 (vii) Arc proof cable covers having cable entry from bottom , front with Interlocking mechanism including earth switch -01 No (viii) Capacitive voltage indication fixed type system as per IEC61243 with LED - 01 Set (ix) Fault Passage Indicator - It is to be provided for each incomer load break unit, FPI with LED/digital display to be added for detection of cable fault-01 No (x) ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01 No
(B) 03 Nos. Outgoing VCB module each consisting of following accessories :- (i) Each function-unit consists of a vacuum-circuit breaker in combination with a three position-switch.The three-position-switch fulfills the operation of the disconnector-function and earthing function. (ii) 11kV, 630A Fixed-Type VCB module with series disconnector cum earthing switch of short circuit breaking current/withstand - 20kA/3-sec, Making Capacity - 50kAp-01 No (iii) Aux. contacts - 1NO+1NC-01 No (iv) Stored-energy motorized high-endurance spring charging mechanism (M1+), with inbuilt spring-charging lever and mechanically latched ON/OFF push-buttons to allow handle-less and un-inhibited operation -01 No (v) Cable terminals (site replacable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes) with double-door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access upto 11 KV , 185 Sqmm , 3 Core, XLPE AL cable termination in live-condition. Each Set of 3 (vi) Right angle boots (push on type)-Each set of 3 (vii) 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. Relay should have facility to display the maximum loaded phase current also.Relay shall record minimum 5 fault records with time stamping. Relay shall be communicable with RS 485 Port on MODBUS Protocol-01 No (viii) Associated ring-core cast-resin insulated CTs 50/1 Amp , 2.5 VA, 10P10 for protection - Each Set of 3 (ix) Arc proof cable covers with self Interlocking mechanism with earth switch -01 No (x) Capacitive voltage indication fixed type system as per IEC61243 with LED -01 No (xi) Push button for breaker trip (xii) Shunt trip coil 24V DC - 01 (xiii) ON, OFF, TRIP mechanical indication on the front mimic of the panel - 01. (xiv) Emergency Trip Push Button - 01.
(C) 01 No. Bus-connected, fixed-type Auxiliary transformer with floor-mounted compartment of matching height and depth, positioned along-side RMU or on the top of the RMU to provide required aux. supply and metering consisting of following accessories :- (i) 1-Ph (11kV/rt3):230VAC, 500VA Auxiliary transformer-01 No (ii) 2x12 Volt DC battery-01 Set (iii) Battery charger-01 No (iv) HRC fuse-links for primary side isolation and AC/DC MCBs for secondary isolation-01 Set (v) Voltmeter & RYB LED Indications to confirm AC/DC supply availability-01 Set (vi) Anti-condensation space-heater-01 No (vii) CFL lamp for illumination and 3-pin socket with switch -01 No
(D) Additional equipment deliverd separately or mounted seperately :- (i) Operationg Handle for Manual Isolator/Disconnector/Earthing Operation-02 Nos (ii) Standard Manometer -01 No (iii) Operation and Maintenance Manual -01 No (iv) Installation & Commissioning Manual -01 No (v) Cable clamping provision (standard) -01No
Note:- (i) It is preferable to have all feeder-switches inside single stainless steel compartment with incomer feeders at the extremities to prevent chances of failure due to plug-in coupling arrangement. (ii) Necessay interclocking arrangement shall be provided for safety and operations (iii) Above switchgear shall confirm to relevant IEC (62271-200) for design, manufacturing and internal arc compliance. Any claims towards internal arc compliance, number of mechanical/electrical/short-circuit operations, gas-leakage rates etc. shall not be accepted unless proven via type-test reports of model being offered. (iv) Cost of provn of plinth for RMU as per OEM drawing is deemed to be included in the cost.
Disconnecting electrically (and mechanically, ) outdoor transforemrs upto 315 KVA capacity, lowering down from 4 pole structure carefully and Re-installation of transformer on plinth , connecting electrically and mechanically, testing and commissioning complete all as specified and directed.
Dismantling of HT insulators any type, any size complete all as specified and directed..
Dismantling of air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism complete all as directed at site by Engr-in-charge.
Dismantling of cross-arms or M.S. channel or angle sections etccomplete all as directed at site by Engr-in-charge.
Dismantling of GI pipe 80mm dia complete all as directed at site by Engr-in-charge.
Dismentaling of existing 4/6 pole structure complete all as directed at site by Engr-in-charge.
S&F in replacement 80 mm bore GI Pipe light grade with necessary accessories/ fittings for cable protections complete all as directed at site.
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft/loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge.
Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables and in foundatin of transformer etc, complete all as specified. Note : Measurement shall be taken after punning down.
S&F sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.
All as per srl item No 15 here-in-before but using old bricks obtained under srl item No 11 here in before.
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm.
All as per srl item No 17 here-in-before but using old un-reinforced precast concrete cable cove obtained under srl item No 11 here in before.
M&L Brick work with sub-class 'B' bricks, straight or curved on plan exc 6 m mean radius, built in cement mortar 1:6 complete as specified and directed.
M&L Rendering 15mm thick on fair faces of brick work or concrete surfaces in cement mortar (1:4) finished fair and even without using extra cement complete as specified and directed.
M & L for PCC 1:3:6 type C-2 (using 40 mm gradded aggregate) for foundation, filling and mass concrete etc completefinished the surface fair and even without using extra cement all as specified and directed .
M & L for cement concrete type B-2, 1:2:4, 75 mm thick (using 40 mm gradded aggregate) for floors and paving etc complete all as specified and directed.
S&F of Mild Steel Angle, Channel,etc. In posts and struts in fencing including cutting top to shape as directed ,drilling holes,notching for wire ,etc,flat iron fillets (for security wire mesh etc) including all necessary drilling,bolting or riveting etc and similar work conforming to Fe-290 Gde E-165 complete all as specified and as directed..
Dismantling of fencing wire mesh of any type and S&F 4 mm dia mild steel wire 75x75 mm mesh,made up into mattresses or cages ,lapped wired and liad in position including welding for fencing in grid complete all as specified and as directed.
M & L for 2 coats of synthetic enamel painting over a coat of red oxide primer to steel surfaces including preparation of newly surface complete all as specified.
Dismantling posts or struts (wood,steel or RCC) any section ,including taking out embedded portion and making good disturbed ground posts embedded in natural ground complete all as specified and as directed.
All as per Sr Item No 26 here in before but posts embedded in concrete etc complete all as specified and as directed..
M&L for ON load Centrifuging and dehydration including filteration and cleaning of transformer oil by dehydration machine of 33 KV transformer at site and topping up deficient transformer oil including testing of samples before and after dehydration and filteration complete all as specified and directed. Note :- Deficient quantity of Transformer oil required for top up shall be measured and paid separately under item No 27 here-in -after as supply only.
Supply only transformer oil of approved quality as per IS having dielectric strength of 45-60 KV in 2.5mm gap for filling in OLTC & for topping up in transformer as required and directed
Supply, laying, jointing, testing and commissioning in replacment LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 marked, laid in trenches of size of cable 240 sqmm,3.5 core complete all as specified and directed.
Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminium conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches fixed to pole, including jointing & testing cable of size 120sqmm ,3 core complete all as specified and directed .
Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminium conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches fixed to pole, including jointing & testing cable of size 185 sqmm ,3 core complete all as specified and directed .
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm complete all as specified. .
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm complete all as specified. .
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 Sqmm to 185 Smmm complete all as specified..
Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches fixed to pole, including jointing & testing cable of size 240 sqmm ,3 core complete all as specified and directed LOCATION : 11 KV CIRCUIT PARADE GROUND
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.6 mpa working pressure complete all as specified. LOCATION : FOR 11 KV CIRCUIT PARADE GROUND
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 Sqmm complete all as specified..
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 240 Sqmm complete all as specified..
Note : (i)contractor should provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge.
Ridhi engineers and builders
Rajindera Enterprises
Buddham Builders
mayur enterprises
Vijay Electricals
MV Engineers And Contractors
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .