Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹35.2 LAccepted-AOC AT PO REMUAN TALCHER DIST ANGUL ODISHA 759100 | TALCHER | ANGUL | ODISHA | 759100 | L-1 | Accepted-AOC ACCEPTED AND AWARDED BY COMPETENT AUTHORITY | |
| 2 | L-2₹42.2 L+₹7.0 L (20.0%)Rejected-Finance AT ITI CHHAK IN FRONT OF SAI MANDIR TALCHER DIST ANGUL ODISHA P O 759100 | TALCHER | ANGUL | ODISHA | 759100 | L-2 | Rejected-Finance SINCE THE BIDDER IS NOT L-1 | |
| 3 | L-3₹46.2 L+₹11.0 L (31.3%)Rejected-Finance AT BRAHMAN SASAN PO TALCHER DIST ANGUL ODISHA 759102 | TALCHER | ANGUL | ODISHA | 759102 | L-3 | Rejected-Finance SINCE THE BIDDER IS NOT L-1 | |
| 4 | L-4₹48.9 L+₹13.8 L (39.2%)Rejected-Finance | L-4 | Rejected-Finance SINCE THE BIDDER IS NOT L-1 | |
| 5 | L-5₹61.1 L+₹25.9 L (73.7%)Rejected-Finance AT PANCHAMAHAL PO KARADAGADIA ANGUL ODISHA 759132 | ANGUL | ANGUL | ODISHA | 759132 | L-5 | Rejected-Finance SINCE THE BIDDER IS NOT L-1 |
Tender Value
₹56.2 L
EMD Value
₹70,300
Closing Date
20 Sept 2024, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SO EnM LINGARAJ AREA
OFFICE OF THE GENERAL MANAGER LINGARAJ AREA, AT/PO- DEULBERA COLLIERY, DIST- ANGUL, ODISHA, 759102
Re-arrangement of 3.3, 11KV feeders of IWSS, Deulbera Colony along with diversion of OHL including laying of Under Ground cabling by HDD method near IWSS plant premises for up-grading power supply arrangement to Deulbera Colony and IWSS of LA
2024_MCL_316698_1
GM/LA/SO/EnM/e-Ten/24-25/27 DT-04.09.24
Open Tender
Electrical and Maintenance Works
Item Rate
60 days
LINGARAJ AREA
AS PER NIT
6 documents required · 6 mandatory
₹70,300
16 Jan 2025
4 Sept 2024
23 Sept 2024
5 Sept 2024
20 Sept 2024
5 Sept 2024
5 Sept 2024 - 13 Sept 2024
Amount
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. (Above 10.00 metre and upto 12.00 metre)
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse and : 6 graded stone aggregate 40mm nominal size) foundation including excavation and refilling etc. as required. Above 8.0 metre and upto 10.0 metre
Supplying and erection of galvanised stay set for 11 KV over head lines complete with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm thick, thimble, stay clamps, turn buckle ( 20 mm X 600 mm ), 7/ 4.00 mm dia G.I. stay wire and 11 KV strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required.
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) pole top bracket/ cross arm for single 11 KV over head line conductor complete with 50 mm X 6mm flat iron clamp, bolts, nuts and washers including drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required.
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) V shape cross arm for two 11 KV over head line conductors complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as rea u i red.
Erection of pole top/ straight two wire/ V shape two wire, angle iron/ channel iron, cross arm on steel tubular/ rail/ PCC pole for 11/22/33 KV as required.
Supplying of 11KV pin insulator
Supplying of 11KV disc insulator for 11KV over head lines
Erection of disc/ pin insulator for 11 KV over head lines as required.
Supply of 6 SWG G.I wire.
Erection of G.I wire 8/6 SWG including binding etc as required.
Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) double pole cross arm for three wire 11KV over head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/ fittings, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required.
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for two 11 KV over head line conductors complete with 50 mm X 50 mm X 6 mm (angle iron bracket welded to the channel iron and complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required.
Supplying and erection of a set of cross bracing FRLSame work for 11 KV over head line double pole structure having four members fabricated out of 50 mm X 50 mm X 6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500 mm height , complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc (as per drawing) and painting with primer and finish paint as required.
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Erection of cradle guard as required.
Erection of ACSR conductor of 7/2.11 mm to 7/3.00 mm diameter including binding etc. as required.
Erection of ACSR conductor of 7/3.35 mm to 7/4.00 diameter and above including binding etc. as required.
Dismantling of over head lines comprising of copper/ aluminium over head conductor, Gl. wire, cross arms, insulators etc. as required.
Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required.
Providing and making steel pole collar with cement concrete (1 cement: 3 coarse sand : 6 stone aggregate 20mm) of specified size and shape including form work, plastering if required, curing etc as required. (volume of pole/ pipe not to be deducted)
Supply of clamps with M.S. nut,bolts and washers as required.
Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required.
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE Aluminium conductor cable of 11 KV grade as required.(120sq.mm)
Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required.(120 SQ MM.)
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE Aluminium conductor cable of 11 KV grade as required.(240sq.mm)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.(120 SQMM)
Supply of 180 mm dia HDPE Pipe etc as required.
Installation, laying,comminissioning & testing of 3-Core,11KV grade,upto 240 sq mm XLPE cable with Horizontal Directional Drilling(HDD) method through 160mm HDPE pipe ( PN-8, PE-80) casing including jointing of HDPE pipe,pit making for machine placement, all required works for cable laying, etc. (At a depth of 3m below railway track and max of upto 6m) (Excluding the cost of the pipe)
Supplying and erection of 75 mm X 90 mm shackle insulator with G. I. Bolt, nuts and straps etc. as required .
Supplying and erection of 100 mm X 65 mm pin insulator complete with G. I. Spindle and nuts etc. as required .
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for 2 wire over head line complete with clamps, bolts, nuts and washer etc including drilling of holes for insulator pins etc (as per drawing) and painting with primer and finished paint as reauired.
Supply and Erection of 11KV ,800Amp double Break GOAB Horizontal Type With all accessories etc as requird.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required.Upto 120 sq.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required.Above 120 sq. mm and upto 400 sq. mm
Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade: One or more coats on old work (1mtr length for pole demarcation)
Lettering with black Japan paint of approved brand and manufacture (For pole & feeder numbering)
Supply of 150 mm dia. G.I. pipe (medium class) etc as required.
Total impact of GST plus Labour Cess [@ 1 % (BOCW Cess to be deducted from the RA bill as per the value of the work progress)] for the purpose of CTC
M/s Santoshi Maa Industries (BID ID -1086106)
SIVA SHEKHAR SAHOO (BID ID -1086301)
M/s DEEPSIKHA ENTERPRISES (BID ID -1088305)
M/S. PHASE AND CONTROL (BID ID -1087974)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .