84198/E8 REPAIR/ MAINTENANCE OF 11KV HT TRANSFORMER, VCB, HT DISTRIBUTION, PROTECTION SYSTEM AND ALLIED WORKS AT 10WING AND 5AFH AREA UNDER GE (AF) JORHAT
2026_MES_781377_1
84198/E8
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
GE (AF) JORHAT
AS PER NIT
8 documents required · 8 mandatory
₹1,000
GE (AF) JORHAT
₹1.3 L
Yes
28 Jul 2026
28 Jul 2026
3 Sept 2026
28 Jul 2026
27 Aug 2026
20 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Servicing, Repairing and Maintenance of existing HT 11 KV,400/630/800 Amps rating VCBs (Make : Crompton Greaves/ Areva ‘Alstom’/ Schneider/ Seimens/ ITE/Andrew Yule/L&Y/ABB) by removing from housing, overhauling the mechanical parts and periodic maintenance servicing of 11KV indoor/ outdoor VCBs, checking of quality of vacuum interrupter, insulation resistances, static contact resistance, testing ( IR value, Ratio Test, Polarity) and connection checking of 11 KV Current Transformer ( Set of Three) by primary injection kit ,testing and calibration of relay ( Set of, Two Over Current and One Earth Fault Relays) by secondary injection kit including,all other functional tests of the VCB panels including for CTs, PTs, complete all as specified and directed.
NOTES:- (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Calibration and Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iii) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after. | 16 | EACH JOB | - | - |
| 2 | Servicing, Repairing and Maintenance of existing HT 33 KV,1250 Amps rating VCBs (Make : ABB/AREVA) by removing from housing, overhauling the mechanical parts and periodic maintenance servicing of 33 KV indoor outdoor VCBs,checking of quality of vacuum interrupter, insulation resistances, static contact resistance, testing ( IR value, Ratio Test, Polarity) and connection checking of 11 KV Current Transformer ( Set of Three) by primary injection kit ,testing and calibration of relay ( Set of, Two Over Current and One Earth Fault Relays) by secondary injection kit including,all other functional tests of the VCB panels including for CTs, PTs,complete all as specified and as directed.
NOTES:- (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Calibration and Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iii) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after. | 6 | EACH JOB | - | - |
| 3 | Servicing, Repairing and Maintenance of existing HT 11 KV, 630 Amps rating Ring Main Unit (RMU), SF 6 insulated isolator (Make : ABB) by removing from housing, overhauling the mechanical parts and periodic maintenance servicing of 11 KV indoor / outdoor RMUs, including cutting, fabrication and welding of gas chamber and checking of quality of interrupter, insulation resistances, static contact resistance, testing ( IR value, Ratio Test, Polarity) and connection checking of 11 KV Current Transformer ( Set of Three) by primary injection kit ,testing and calibration of relay ( Set of, Two Over Current and One Earth Fault Relays) by secondary injection kit including,all other functional tests of the VCB panels including for CTs, PTs,complete all as specified and directed.
NOTES:- (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Calibration and Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iii) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after. | 3 | EACH JOB | - | - |
| 4 | Servicing, Repairing and Maintenance of existing HT 33 KV, 630 Amps rating Ring Main Unit (RMU), SF 6 insulated isolator (Make : ABB) by removing from housing, overhauling the mechanical parts and periodic maintenance servicing of 33 KV indoor / outdoor RMUs, including cutting, fabrication and welding of gas chamber and checking of quality of interrupter, insulation resistances, static contact resistance, testing ( IR value, Ratio Test, Polarity) and connection checking of 33 KV Current Transformer ( Set of Three) by primary injection kit ,testing and calibration of relay ( Set of, Two Over Current and One Earth Fault Relays) by secondary injection kit including,all other functional tests of the VCB panels including for CTs, PTs,complete all as specified and directed.
Notes:- (i) The work shall be carried out through Authorised & Qualified agencies as approved by the Engineer in Charge. (ii) Calibration and Testing(s) shall be done through State Electrical Licencing Board's valid electrical licence holder for the appropriate class/category of the work as approved by the Engineer in Charge. (iii) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after. | 2 | EACH JOB | - | - |
| 5 | Supply Only, panel indicating lamp fitting, LED type suitable for110 volt/ 230 volt AC with base complete all as specified and as directed.
(Make: L&T / Siemens / STS/AE) | 15 | EACH | - | - |
| 6 | Supply Only, Digital AC Ammeter with 3 ½ digit display and with built in selector switch, Type 3 PH, Range 5 Amp Direct and with CT 50/5 A, size 96 mm X 96 mm, Accuracy Class 1.0, all as per Model No AE 60342 of Make “AE” or equivalent Model of Make MECO/L&T / Secure / Conzerv, complete all as specified and as directed. | 5 | EACH | - | - |
| 7 | Supply Only, Breaker Control Switches,TNC (Trip,Neutral and Close), rating 25 Amps with contact arrangement 1Trip + 1Close, barrel lock mounting type, suitable for 11 KV VCB panels, complete all as specified and as directed. (Cat No 73257SEB90PGBB of Make L&T or equivalent Model of Make: Switron / Recom /Kaycee / Areva) | 4 | EACH | - | - |
| 8 | Supply Only, heater with heater switch & thermostat suitable for 11KV VCB panels, 80 watts, as per OEM's specifications complete all as specified and as directed. (OEMs:-Crompton Greaves/ Areva ‘Alstom’/Schneider/ Seimens/ITE/ Andrew Yule) | 8 | EACH | - | - |
| 9 | Supply Only, HT Current Transformers, single phase indoor solid state (Resin cast) 11 KV, ratio 150/5A, accuracy class 5P10, rated burden 15VA, STC 13.1 KA for 1second,suitable for VCB Panels as per OEM's specifications,complete all as specified and as directed. (OEMs:-Crompton Greaves/ Areva ‘Alstom’/Schneider/Seimens/ITE/ Andrew Yule) | 1 | SET OF THREE | - | - |
| 10 | Supply Only,microprossesor based feeder protection neumerical relay with overcurrent, earth-fault, phase-discontinuity, negative-phase sequence and thermal-overload protections, inrush current detection, reclosing and measurement,preconfigured functionality facilitates, configurable binary inputs/outputs using local HMI or communication interface,modbus and IEC 60870-5-103 protocols supports,universal power supply 24-265 V AC/DC,suitable for 11 KV VCB panels,complete all as specified and as directed. (Cat No REJ601 of Make ABB or equivalent Model of Make: Schneider/ Seimens) | 2 | EACH | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.45 MB
Tender84198.pdf
Tender Documents • 6.37 MB
BOQ_875339.xls
BOQ • 0.61 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].