Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.0 LAccepted-AOC 90 E BECHARAM CHATTERJEE ROAD KOLKATA 700034 | KOLKATA | KOLKATA | WEST BENGAL | 700034 | L1 | Accepted-AOC lowest bid quoted | |
| 2 | L2₹9.6 L+₹56,946 (6.33%)Rejected-Finance MOSAT HARIPUR RD VILL P O HARIPUR DIST HOOGHLY PIN 712701 | HARIPUR | HOOGHLY | WEST BENGAL | 712701 | L2 | Rejected-Finance Due to higher rate offered | |
| 3 | L3₹9.9 L+₹87,875 (9.76%)Rejected-Finance 2 SURI LANE KOLKATA 700 014 | KOLKATA | KOLKATA | WEST BENGAL | 700014 | L3 | Rejected-Finance Due to higher rate offered |
Tender Value
Refer Docs
EMD Value
₹18,000
Closing Date
20 Jan 2020, 3:00 pmClosed
EE II CKHED
P12 CIT Road 1st floor Kolkata 700014
Electrical Installation Air Conditioning arrangement supply and installation of UPS and miscellaneous works at CCL Building 3rd floor and annex building of SDCRL
2020_WBPWD_264155_1
WBPWD/EE-I/CKHED/NIT-50/ 2019-20
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
CCL
as per NIT
4 documents required · 4 mandatory
₹18,000
EE CKHED P12 CIT Road 1st floor Kolkata 700014
9 Sept 2020
7 Jan 2020
22 Jan 2020
7 Jan 2020
20 Jan 2020
12 Jan 2020
10 Jan 2020
Amount
Supply and fixing of 240V. Single LED tube light complete with all accessories including nesessary wires for modifiation of the connection of existing tubes (Make: Philips Master LED Tube Model : MAS LEDtube 1200mm 18W865 T8 I – 2100lm)
Supply and fixing of false ceiling fittings (Make :Philips,Model : RC365B LED33-6500 PSU OD WH) with all necessary connection as per direction of EIC
S & F 48″ sweep, 230V 1-Ph. AC ceiling fans incl. all accss. The capacitor of fan must be P-2 type brust proof & must have safety wire directly linked from fan hook to stator of fan. 1200 mm Sweep (Make - CG HS plus/,Orient : Energy star) incl necessary wiring by means of 3x1.5 sqmm FR copper wire
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Gloster /KEI /FINOLEX) of the following sizes in 20/25 mm size PVC rigid conduit 'FR' (Precision make) incl. necy fitting as required.
a) 2 x 2.5 sqmm + 1 x 1.5sqmm
b) 2 x 4 sqmm + 1 x 2.5sqmm
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed] Average run 6 mtr
Wiring in 1.1 KV grade single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) of following sizes in 25mm PVC casing-capping (Precision make) incl. necy. PVC clips, fittings etc. : 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm)
Supply & Fixing 240 V, 2 nos. 20 A plug socket with separate 2 nos. 20A Piano key type switch, indicator (Anchor)) on sheet metal switch board embedded in wall incl. S & F 300x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
a) 2.5/1.5 sqmm
b) 4 sqmm
Supply of 18" Pedestal Fan (Make-EPC) and provide necy. length of PVC insulated cable with plug top.
S & F of 120/240V Electronics Fan Regulator - Step type, socket size as per direction of the E.I.C. incl. making necy conncetion. (Make- Anchor).
S&F starter for AC machine, type OLP3+ having AC load display incl.complete connection as per direction of E.I.C.
S&F 2 module G.I box(Crabtree cat no.- ACTXMIIX01) withcombined cover plate (Crabtree-Athena cat no.- ACAPNCWV- 02), 1 no.-10-25 Amp. modular 3 pin socket (Crabtree cat no.- ACAKCXW253), 1 no. 25Amp plug top(Crabtree cat no.- ACTGNIW253) all to be flushed in the wall incl. necessary interconnection by suitable size of copper wire as per direction of E.I.C.
Supplying and fixing 250 V, 6-16A per way, 2+4 way SPN MCBDB with SS enclosure double-door(Metallic door with acrylic) with IP-43 protection with 32 Amp DP MCB isolator as incomer and 4 nos SPMCBs ('C' Curve, 10kA) as outgoing, concealed in wall after cutting the wall/using angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make-Legrand/Siemens/L&T)
Supplying and fixing 2 way MCB SS enclosure with IP-20/30 protection, powder coated provision for two pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment. Supplying and fixing 240 V 32A DP MCB on din rail of existing DB/SS enclosure and necessary connection. (Make-Legrand).
Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch with indicator & 16A kit-kat flush type fuse (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required
Supply of 2 ton capacity [BEE- 3 Star rated ; ISEER(W/W):- 3.10-3.29] split Air-conditioner machine, Refrigerant R410A, Rated Cooling capacity 24000 BTU/Hr fitted with Rotary compressors (Make- Hitachi/Mitsubishi-Electric).
Installation, testing & commissioning the Split type Room Air conditioner With adjustable Power coated paint iron bracket.
Supply & laying Refrigerant Copper Pipe ping minimum Thickness 1.15 mm. Liquid pipe 6.35 mm. Gas pipe 15.88 mm.[ Make Royku / Totaline/ Mandeep] and Insulation by nitril rubber of refrigerant Copper Pipeping minimum Thickness 9 mm. Liquid pipe 6.35 mm. Gas pipe 15.88 mm.[ Make Aroflex / Acoflex/ Jeflex] also raping the insulation & Copper wire with GKB Gold raping tape as per direction of EIC.
Supply & drawing 4 core 2.5 sq. mm. P.V.C. insulated sheeted wire for connecting the outdoor to indoor communication supply. (Make Havells / Finolex)
Supply & laying 3/4" heavy type P.V.C. pipe for Water Drainage
Cost of cutting window iron frame & making lock & key arrangements with (1" x 6 mm) M.S flat bar for trouble free service maintenance of split AC outdoor unit.Supply Lock and Key(make-Godrej).
Charges for scaffolding arrangement incl. lifting for outdoor & indoor units.
5 K.V.A (I/P: 1P; O/P: 1P) true on-line double conversion IGBT based UPS System with in -built isolation transformer & 60 mins SMF battery backup. TECHNICAL SPECIFICATION FOR 5 KVA ONLINE UPS Systems Technical Parameters UPS Capacity 5 kVA UPS System Input Voltage Range 160 - 3000 V AC Frequency Range 45 to 55 Hz Power Factor ≥ 0.99 at full load and nominal input Voltage Isolation Transformer Inbuilt at the input side of the UPS Current THD < 5% Output Voltage 230 VAC Voltage Regulation + / - 1% Frequency (Free Running Mode) 50 Hz ± 0.1 Hz Frequency (Synchronisation Mode) 45 to 55 Hz Harmonic Distortion (THD) < 3% (linear load) and < 5% (non-linear load) Output Waveform Sine wave Crest Factor 3:1 Efficiency (AC - AC) >= 92%
Power Factor 0.8 Lagging Overload 105% - 110% for 3 minutes, 111% - 130% for 30 Seconds Battery Battery Type 28AH Sealed Lead Acid Maintenance Free-20 nos Battery Make : Amararaja (Quanta make) / Exide power safe Charger : Built-in solid state float-cum-equalizing charger with automatic boost / trickle charge modes with Current limiting features. VAH Required ≥6720 (for 60 min battery back-up) General Operating Temperature 10 to 45 Deg. C only for UPS Noise level < 50 dB @ 1 meter LCD Display & Indication Input Voltage Output Voltage Input Frequency Output Frequency Battery Charging / Discharging Levl Load Level Input High / Normal / Low / Fail Output Overload Output Short Circuit Output Fault
Audible Alarm Mains Failure alarm; Low Battery Alarm Overload Fault Protections Advanced electronic protection for device safety backed with MCBs, Fast acting fuses, High speed pulse blanking Electronic overvoltage / under voltage Bypass Static Bypass Maintenance Bypass Available Communication Interface RS 232 port for software interface SNMP Provided Certificates ISO 9001 : 2008; ISO 14001 : 2004; OHSAS 18001 : 2007 Make : (Numeric/Emerson/APC) battery rack and linck included.
2 K.V.A (I/P: 1P; O/P: 1P) true on-line double conversion IGBT based UPS System with in -built isolation transformer & 30 mins SMF battery backup.,Battery Make: EXIDE /Amararaja (Quanta make). TECHNICAL SPECIFICATION FOR 2 KVA ONLINE UPS Systems Technical Parameters UPS Capacity 2 kVA UPS System Input Voltage Range 160 - 300 V AC Frequency Range 45 to 55 Hz Power Factor ≥ 0.99 at full load and nominal input Voltage Isolation Transformer Inbuilt at the input side of the UPS Current THD < 5% Output Voltage 230 V AC 1ph Voltage Regulation + / - 1% Frequency (Free Running Mode) 50 Hz ± 0.1 Hz Frequency (Synchronisation Mode) 45 to 55 Hz Harmonic Distortion (THD) < 2% (linear load) and < 5% (non-linear load) Output Waveform Sine wave Crest Factor 3:1 Efficiency (AC - AC) >= 92%
Power Factor 0.8 Lagging Overload 105% - 110% for 3 minutes, 111% - 130% for 30 Seconds Battery Battery Type 28AH Sealed Lead Acid Maintenance Free- 6 nos Battery Make : Amararaja (Quanta make) / Exide power safe Charger : Built-in solid state float-cum-equalizing charger with automatic boost / trickle charge modes with Current limiting features. VAH Required ≥2016 (for 30 min battery back-up) General Operating Temperature 10 to 45 Deg. C only for UPS Noise level < 50 dB @ 1 meter LCD Display & Indication Input Voltage Output Voltage Input Frequency Output Frequency Battery Charging / Discharging Levl Load Level Input High / Normal / Low / Fail Output Overload Output Short Circuit Output Fault
Audible Alarm Mains Failure alarm; Low Battery Alarm Overload or any Fault Protection- Advanced electronic protection for device safety backed with MCBs, Fast acting fuses, High speed pulse blanking Electronic overvoltage / under voltage fast Acting mcb.Electronic Over Current trip. Bypass Static Bypass Maintenance Bypass Available Communication Interface RS 232 port for software interface SNMP Provided Certificates ISO 9001 : 2008; ISO 14001 : 2004; OHSAS 18001 : 2007 Make : (Numeric/Emerson/APC) battery rack and linck included.
Dismantling of the existing two number of TPN DBs, tube lights etc as per direction of EIC and handing over the same to the section office following proper procedure
Terms and Condition
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Rate should be quoted incl. of all taxes and cess.
Defect Liability period : 1 year
GHANASHYAM ELECTRIC STORES
MAHESWAR ELECTRICAL INDUSTRIES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .