SE, ETC, Varanasi
Bhikaripur, DLW, Varanasi
INSTALLATION OF ABT METER ALONG WITH ERECTION OF STRUCTURE/EQUIPMENT AT 132 KV SUBSTATION CHUNAR
2020_UPTCL_514514_3
Short Term E-Tender no. 36/2020-21/ETC/VNS
Open Tender
Electrical Works
Item Wise
15 days
132 KV Substation Chunar
Fee/EMD/PAN/GST Registration and experience for execution of work as per specification
2 documents required · 2 mandatory
₹236
SE, ETC, Varanasi
₹2,000
26 Jun 2021
21 Dec 2020
2 Jan 2021
21 Dec 2020
1 Jan 2021
25 Dec 2020
Amount
Erection of structure / Equipment along with all accessories as per technical specification & instruction manual.
36 KV CT / PT
Main & auxiliary structure
ABT cubical control panel
1.1 KV copper control cable laying including all associated work to complete the job
2C x 2.5 sq. mm
4C x 2.5 sq. mm
Control cable termination including cost of cable glands, ferrules and lugs complete and both end as per site requirement
Making of earthing of above S/S structure, CT, PT junction box by MS Flat provided by the UPPTCL as per actual consumption.
Painting of MS Flat 50 x 6 mm by one coat red oxide and two coat bus green colour enamel paint after cleaning work.
Jumpering work of new CT & PT by ACSR Panther conductor with the help of Clamps
Providing & Fixing of 33 KV Feeder name plate of 2 mm thick aluminium sheet plate size 600 x 400 mm with covering retro reflecting sheet base yellow colour & letter blue colour.
Supply & laying of 50 mm dia GI pipe B class (medium) for conducting of control cable (metering) complete with elbow, Tee, socket reducer as per site requirement in the switchyard.
Providing & fixing of new generation energy & environment friendly long aluminium outdoor beam street light with high power 120 watt LEDs as light source & exclusively designed polycarbonate cover along with electronic driver complete fitting suitable for 220 Volt AC input supply of CGL/Havells/ Surya/Philips/Bajaj etc. Including wiring from junction box to light fitting point and checking of healthiness of LED lights.
Supply and installation of junction box of size 280x225x150 mm made of 16 SWG sheet with grey painting suitable for 2x4x6 C sq mm incoming cable and 2x4x6 C sq mm outgoing cable fitted with 03 Nos. HRC fuse link of 5 Amp. cable glands, nutral link, terminal block etc and fixing of junction box on columns with the help of 50x6 mm GI Clamp.
Dismantling of old & spare pales by cutting Nut & Bolts from unused place
Providing & Fixing of new pale fencing along with required different size of MS angle (along the newly erected structure). Including cost of required grouting & associated work.
Painting of New Pale fencing by one coat red oxide and two coat bus green colour enamel paint(First class Asian/Nerolac/ Burger make) after cleaning of rust, dust of surface including cost of material & TnP.
Supply & fixing of Standard Make (Havells, Bajaj, CGL, Orpat, Usha) Exhaust fan (450mm sweep size) including wiring and switch board
Wiring of Cubical ABT Meter Room situated in Switch yard including all cost of wire, switches, board, flat conduit, 4 nos. LED point with supply of 4 nos. 23W LED Bulb
M/S P B ENTERPRISES
SAI KRIPA LIFT SHIFT COMPANY
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .