Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
13 Oct 2021, 6:00 pmClosed
GE (WEST) PATHANKOT
GE (WEST) PATHANKOT
REPAIR/REPLACEMENT/IMPROVEMENT OF LT FEEDER PILLAR BOX/RMU PANELS/MCCBS AND ALLIED WORKS UNDER GE (WEST) PATHANKOT
2021_MES_475353_1
GE/PKT-46/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (WEST) PATHANKOT
Please refer tender documents
9 documents required · 9 mandatory
₹500
GE (WEST) PATHANKOT
₹40,000
Yes
25 Nov 2021
15 Sept 2021
15 Oct 2021
15 Sept 2021
13 Oct 2021
30 Sept 2021
16 Sept 2021 - 25 Sept 2021
Amount
Taking down the unserviceable MCCBs and supply and fixing of MCCB 630 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 50 KA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 50 KA RMS at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer, complete all as specified and directed. Make: Havells cat part no IHLLNFCF0630 or equivalent in any make mentioned in list of product.
Taking down the unserviceable MCCBs and supply & fixing of MCCB 400 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 50 kA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 50 kA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer, complete all as specified and directed. Make: Havells cat part no IHLLNFCF0400 or equivalent in any make mentioned in list of product.
Taking down the unserviceable MCCBs and supply & fixing of MCCB 250 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 36 kA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 100% Icu for short circuit breaking capacity of minimum 36 kA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer, complete all as specified and directed. make: Havells cat part no IHLLSECF0250 or equivalent in any make mentioned in list of product.
Taking down the unserviceable MCCBs and supply & fixing of MCCB 200 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 36 kA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 100% Icu for short circuit breaking capacity of minimum 36 kA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer, complete all as specified and directed. Make: Havells cat part no IHLLSECF0200 or equivalent in any make mentioned in list of product.
Taking down the unserviceable MCCBs and supply & fixing of MCCB 160 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 25 kA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 25 kA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer complete all as specified and directed. Make: Havells cat part no IHLANDCF0160 or equivalent in any make mentioned in list of product.
Taking down the unserviceable MCCBs and supply & fixing of MCCB 125 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 25 kA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 25 kA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer, complete all as specified and directed. Make: Havells cat part no IHLANDCF0125 or equivalent in any make mentioned in list of product.
Taking down the unserviceable MCCBs and supply & fixing of MCCB 100 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 25 kA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 25 kA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer, complete all as specified and directed. Make: Havells cat part no IHLANDCF0100 or equivalent in any make mentioned in list of product.
Taking down the unserviceable MCCBs and supply & fixing of MCCB 63 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 25 kA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 25 kA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer, complete all as specified and directed. Make: Havells cat part no IHLASF0063 or equivalent in any make mentioned in list of product. Note :- (i) For item No 1 to 9 all MCCBs should be of suitable for unbalanced load.
Supply and fixing in replacement of Digital Ammeter 0 - 500 Amp suitable range of CTs complete all as specified and directed. Make: Schneider , cat part no : 30002385 or equivalent in any make mentioned in list of product.
Supply and fixing in replacement of Digital Voltmeter 0 - 500 V, complete all as specified and directed. Make: Schneider , cat part no : 30002386 or equivalent in any make mentioned in list of product.
Taking down the unserviceable ACB and supply & fixing of ACB 630 amp ,4 pole 415 volts ,3 phase ,50 Hz AC fixed type manual operated with microprocessor release IPR E+ (4Pole) & 50 kA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The ACB shall have spreader links and barriers as standard feature of manufacturer with MS enclosure grounted with PCC, make: Havells cat part no IHAFE1E060**or equivalent in any make mentioned in list of product.
Material and labour for painting of LT panels/feeder pillar boxes outdoor /indoor type of any sizes or rating installed at varoius location under GE (wset) Pathankot with preparing the surface ,one coat of red oxide primer & one coat of synthetic enamelled paint of approved colour with spray painting after cleaning the surface and preparing the same for painting complete all as specified and directed.
M&L for cross arms bracing supports clamps, back plates fabricated from steel section incuding nuts,bolts and washers welding,drilling hole complete with two coats of aluminium paint over and including one coat of red oxide primer complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thickness not less than 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below the normal ground level ) with top edge of plate not less than 1.5 mtr below the normal ground level connected to galvanized iron strip 32X6 mm by means of nuts bolts,washers, check nuts of GI steel all as shown in electric plate no 3 all as specified and indicated complete and including 15 cm thick layer of charcoal dust,salt etc alround the plate and GI protection pipe ,medium grade 40mm dia and GI watering pipe 20mm ,medium grade with funnel and wire mesh and 40mm thick pre-cast RCC M-15 (nominal mix) cover reinforced with XPM weight not less than 4 kg /sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover ,PCC M-15 (nominal Mix) for pit,excavation and earth work in any type of soil and connected and testing complete all as specified and as directed.
Supply,installation, commissioning & testing of bus bar chamber of size 600 x 400 x 250 mm made up of MS Sheet 3.15 mm ,powder quoted with RAL 7032 code ( Siemens Grey) and aluminum strip of size 50 x 6 mm -04 Nos (300mm long ) with 100 amps 25 kA FP MCCB along with spreaded Link for conection with 45 cm long legs made out of 50x50x6mm angle iron grouted in PCC (1:3:6) blocks of size 30cmx30cmx60cm complete all as specfied and directed as per site requirment.
Supply,installation, commissioning & testing of bus bar chamber of size 600 x 400 x 250 mm made up of MS Sheet 3.15 mm ,powder quoted with RAL 7032 code ( Siemens Grey) and aluminum strip of size 50 x 6 mm -04 Nos (300mm long ) with 200 amps 25 kA FP MCCB along with spreaded Link for conection with 45 cm long legs made out of 50x50x6mm angle iron grouted in PCC (1:3:6) blocks of size 30cmx30cmx60cm complete all as specified and directed as per site requirment.
Supply, fixing and testing of 25 sq mm 4 core, XLPE insulated, armoured, heavy duty electric cable with aluminum conductor, 1100 volts grade, including taking down of old UNSV cable complete all as specified and directed. NOTE : Earth work including excavation ,returning Filling,removing,sand coushioning,brick covering for mechanical protection of cable etc will be measured and paid separately under respective items of schedule)
All as per ser item No 19 here-in-before but 50 sq mm 3.5 Core
All as per ser item No 19 here-in-before but 70 sq mm 3.5 Core
All as per ser item No 19 here-in-before but 95 sq mm 3.5 Core
All as per ser item No 19 here-in-before but 120 sq mm 3.5 Core
Supply and fixing of 50 mm bore, GI tubing light grade for cable protection laid in trenches in road crossing or fixed to wall/Pole of complete all as specified and directed.
All as per ser Item No 24 here-in-before but 80mm bore
M&L for Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in soft/loose soil for laying of cable ,pole foundation,stay,laying of pipe etc complete all as specified and directed.
M&L for Returning filling in, including spreading ,leveling ,watering and well ramming in layers not exc 25 cm thick complete all as specified and directed.
M&L for sand cushioning to under ground cables with a layer of sand 8 cm before laying the cable and 15 cm after laying the cable and punned down to 18 cm thick complete all as specified and directed. Note :- Punned thickness 18 cm will be measured for payment.
S&F of Brick covering with equal to length of brick as mechanical protection to cable with well burnt sub class 'B' bricks laid complete all as specified and directed.
M&L for Removing excavated soil to a distance not exceeding 50 mtr and deposting where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
Notes :- (a) The contract sum shall be arrived at after deduction of amount of Schedule of Credit. (41,300.00). (b) PERFORMANCE SECURITY :- (Refer condition 19 of IAFW-2249) The performance security for an amount equivalent to 3% (Three percent) of the accepted contract sum shall be delivered by the successful bidder immediately after the date of intimation letter of acceptance and all provisions shall be applicable as per condition 19 of IAFW 2249
M/S SHAKTI ELECTRIC WORKS
Substantial Const. Co.
JAI DURGA CONSTRUCTION CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .