Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.2 LAccepted-AOC 107 1F TOLLYGUNGE ROAD KOLKATA 700026 | KOLKATA | KOLKATA | WEST BENGAL | 700026 | L1 | Accepted-AOC Accepted | |
| 2 | L2₹40.0 L+₹2.2 L (5.93%)Rejected-Finance 107 1A TOLLYGAUNG ROAD KOLKATA 700026 WB | KOLKATA | WEST BENGAL | 700026 | L2 | Rejected-Finance Being higher bid value | |
| 3 | L3₹41.2 L+₹3.4 L (8.99%)Rejected-Finance 1622 KASTA DANGA ROAD KOLKATA 700061 WB | KOLKATA | WEST BENGAL | 700061 | L3 | Rejected-Finance Being higher bid value | |
| 4 | L4₹41.2 L+₹3.4 L (9.09%)Rejected-Finance 30 SHIVTALLA STREET KOLKATA 700 007 | KOLKATA | KOLKATA | WEST BENGAL | 700007 | L4 | Rejected-Finance Being higher bid value | |
| 5 | L5₹41.8 L+₹4.0 L (10.6%)Rejected-Finance 6A BANAMALI GHOSHAL LANE KOLKATA 700034 | KOLKATA | WEST BENGAL | 700034 | L5 | Rejected-Finance Being higher bid value |
Tender Value
₹38 L
EMD Value
₹76,000
Closing Date
27 Aug 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE ALIPORE KOLKATA
NO 1 NATIONAL LIBRARY AVENUE, ALIPORE, KOLKATA 700027
8879/E8
2020_MES_365132_1
GE/ALP (8879) OF KOLKATA 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
334 days
GE ALIPORE KOLKATA
Class D Category b I
9 documents required · 9 mandatory
₹500
GARRISON ENGINEER ALIPORE
₹76,000
Yes
12 Nov 2020
29 Jul 2020
28 Aug 2020
29 Jul 2020
27 Aug 2020
13 Aug 2020
60 days
Amount
PART - I : E/M - II Maintenance / servicing of APFC panel of 400 KVA ,415 V -50/60 Hz -50kA for auto correction of power factor . complete checking of each capacitor bank, connector and MCB . Cleaning and servicing of all fixed and moving contacts replacement of accessories i.e lockable trip push button,auto /manual switch, indicator , volt meter, ammeter etc after disconneting the APFC for execution of work and re-fixing the same shall be with old serviceable spare parts in existing position and re-connecting all cables and testing on existing load complete all as specified and as directed by the Engr-in-Charge. Make:- L&T. Note:- All new spare parts as required shall be measured and paid seperately.
(a) supply and fix capacitor bank raisin cast box type 20 KVAR 440 volt . Make :- L&T
(b)Supply and fix MOC 25 contactor . Make :- L&T
(c)Supply and fix red and green lamp .
(d)Supply and fix analog amper meter of 0-300A .Make :- L&T
(e)supply and fix 10 sqmm cu cable for panel connection. Make :- L&T/Havells/Mescab
(f) supply and fix MCB 63 Amp three pole 10 KA 'C' Series. Make :- L&T.
Repair to AMF Panel 100 KVA Capacity DG Set by dismantling the following unserviceable items replacing the same by new one, rewiring all internal wiring and replacing relay circuit and the following unserviceable items and complete all as specified and as directed by the Engr-in-Charge. (a) Automatic ON/OF Relay = 01 No (b) Aux Contacts 2NO+2NC = 01 No (c) Auto main failure relay 24 Volts = 01 No (d) Builtin voltage relay for main = 01 (e) Adjustable timer = 01 No (f) Main incomming dalay timer = 01 No (g) HRC Fuse with base 32 Amp = 01 Set (h) CT 400/5. Make : Kappa = 06 Nos (j) Power contactor 3 Pole , 200 Amp, ML 10, 2NO+2NC with aux contact. Make : L&T Cat Part No.SS90921 or equivalent approved make. (k) Push Button = 05 Set (l) DC Volt meter for inbuilt battery charger = 01 No
Maintenance / servicing of LT ACB,1000A,415 V -50/60 Hz,Icu-50 kA Ics-50 kA,Icw-50kA for 1 second of make L & T with Cleaning and servicing of all fixed and moving contacts replacement of accessories i.e lockable trip push button, LIP, LAP, racking, interlock, door interlock, shunt release, under voltage release(UVR) etc after disconneting the ACB for execution of work and re-fixing the same shall be with old serviceable spare parts in existing position and re-connecting all cables and testing on existing load complete all as specified and as directed by the Engr-in-Charge.
Maintenance of HT Vacuum Circuit Breaker, 7.2 KV, 400 Amps, for trouble free operation, opening the incoming/out going HT cables carefully after disconnecting the HT supply, cleaning all terminals, fixed/moving contacts, cleaning vacuume interrupter, insulating coupler, strut, centering ring, all terminal clamp and bolts, drive link, upper/lower post insulators, etc. Special care need to be exercised in removal or insulation of hardware around the bottom, movable contact end of the vacuum interrupter, etc and refixing all HT cable terminals, cover, etc including the following inspection and checking should be carried out : -
(a) Primary power path check (i) Cleanliness check (ii) Inspection of flexible connections (b) Stored energy operator-mechanism checks (i) Maintenance and lubrication (ii) Fastner Check (iii) Manual spring charging check (c) Electric Control Checks (i) Wiring and control check (ii) Secondary disconnect check (iii) Automatic spring charging check (iv) Electrical close and trip check (d) Vacuum Integrity check (e) High potential check (f) Insulation test (g) Contact resistance test (h) Inspection and cleaning of circuit breaker insulation (j) All safety and realay functional tests to be carry out and test report to be submitted to the engr-in-charge
Note : - (i) Any cleaning compounds containing chlorinated hydrocarbons, such as trichlorethylene, perchlorethylene or carbon tetrachloride will not be allowed to use which may be occured to damage the phenylene ether copolymer material used in the barriers and other insulation on the circuit breaker. (ii) Contractor will ensure to provide recommended tools for the maintenance works of the VCB. (iii) Contractor will ensure and take all safety pre-cautions/preventive measures against the mechanic/electrician at his own risk. (iv) The contractor will provide authorised persons to work from the OEM.
Supply only against item No.4 here-in-before as per existing make and size :-
(a) Strut
(b) Upper Connection pad
(c) Lower connection pad
(d) Contact pressure spring
(e) Insulating coupler
Complete servicing to the DG set comprising of the following works for the capacity 320 KVA complete all as specified and as directed by the Engr-in-Charge :- (a) Draining out unserviceable engine oil from engine, refill with new. Note : Engine oil will be measured and piad separately. (b) Cleaning all sludge/deposits in the oil sump and removed off the site (c) Cleaning and replacing the primery, secondary and bi-pass fuel filters (d) Cleaning and replacing oil filters (e) Cleaning of air filters (f) Supply and replace unserviceable hose pipe as required at site (g) Supply and replace PVC fuel indication tube (h) Supply and replacing battery terminals = 02 Set (All new spare parts will be measured and paid separately)
.-Ditto- all as per item No.6 above but capacity 200 KVA DG Set
.-Ditto- all as per item No.6 above but capacity 125 KVA DG Set
.-Ditto- all as per item No.6 above but capacity 110 KVA DG Set
.-Ditto- all as per item No.6 above but capacity 60 KVA DG Set
Supply and fixing push button suitable for existing panel complete all as specified and as directed by the Engr-in-Charge.
Taking down water pump assembly from the existing position, opening into parts overhauling the same with replacement of water pump repair kit, ball bearing (1No) (Make SKF/NBC), water pump, gasket seal, oil seal and re-assembling and refixing on the base for the following capacity of DG sets complete all as specified and as directed by the Engr-in-Charge:-
(b) 110 KVA DG Set
(c) 60 KVA DG set
Taking down the Dynamo 12 Volts (Make LUCAS) from the existing position, shifting to the work shop, opening into parts, cleaning to sort out the unserviceable part, replace by new one, rewinding and warnishing of coil, reassembling and refixing to its base including transportation charge from work shop to the site for the following capacity of DG sets complete all as specified and as directed by the Engr-in-Charge:-
(b) 110 KVA DG Set
(c) 100 KVA DG Set
Maintenance, servicing, tunning of diesel engine by calibration of FIP's adjustment of nozzle pressure and other controls and testing for following capacity of engine complete all as specified and as directed by the Engr-in-Charge :-
(a) 125 KVA DG Set
(b) 110 KVA DG Set
Taking down self starter assembly from the existing position, opening in to parts, sort out the unserviceable items like carbon bush, pinion etc and replace the same with new one including rewinding of field coils, re-assembling and refixing the same in its original position including testing for the following capacity DG Set complete all as specified and as directed by the Engr-in-Charge.
(a) 125 KVA DG Set
(c) 100 KVA DG Set
Dismantling the alternator of DG set 110 KVA, Make Kirloskar, from its base by using chain and pulley after removing the coupling with the engine, removing all nut, bolt with washer and all electrical connections of the alternator, shifting the alternator to work shop, opening the same parts, checking all winding like main stator/rotor winding, exciter stator/rotor winding. Rewinding the main rotor and exciter rotor by using the same insulation and gauge and type of magnet wire that was on the original motor. Refixing the complete including connection to the terminal box of the alternator at work shop and shifting the same to the site. Fixing the alternator to its base carefully by using chain and pulley, connecting it with existing engine including checking the alignment of alternator with the engine, connecting all electrical connections of the alternator and testing the DG set on "OFF/ON LOAD", matching to the existing range of RPM of the engine and all to the satisfaction of the engr-in-charge.
Removing the radiator assembly of DG Set 125 KVA from its base, taken to workshop, opening into parts, sort out the following unserviceable items, cleaning the channels, fins including necessary gas welding works, reassembling and refitting on its base including transportation of the same from work shop to site and replacement of the following unserviceable items complete all as specified and as directed by the Engr-in-Charge (a) Suction Connection = 01 No (b) Main Pipe = 1 No (c) Rubber hose = 02 Nos (d) Stud = 04 Nos (e) Stay for radiator = 01 No (f) Pipe for thermostat to water tank of radiator = 01 No (g) Spacer = 01 Set (h) Coolent as required (All new spare parts will be meaured and paid separately)
.-Ditto- all as per item No. 17 above but 110 KVA DG Set.
.-Ditto- all as per item No.17 above but 60 KVA DG Set.
Taking down unserviceable automatic battery charger including disconnecting of all connection and replacing with new autocut battery charger suitable for charging upto 24 volt 180 AH (2x12Volt) battery complete with provn of necessary connection complete all as specified and as directed by the Engr-in-Charge.
Supply and filling Fleet cool HD heavy duty coolant concentrate ultimate protection for increase engine life for 200 KVA,100KVA complete all as specified and as directed by the Engr-in-Charge. Make : Fleet guard Batch No 16311 or equivalent approved make.
Supply only engine oil of grade 20w 40 brought at sight in sealed container. Complete all as specified and as directed by the Engr-in Charge . Make :- Power oil/ castrol/gulf /servo Note Contractor will submit purchese voucher and manufacturer test certificate in original before any payment.
Supply only fuel filter ( primary, secondary or by pass ) for the following capacity of DG set complete all as specified and as directed
(a) 320 KVA DG set
(b) 200 KVA DG set
(c) 125 KVA DG Set
(d) 110 KVA DG Set
(e) 100 KVA DG Set
(f) 60 KVA DG Set
Supply only oil filter for the following capacity of DG set complete all as specified and as directed
(a) 320 KVA DG set
(b) 200 KVA DG set
(c) 125 KVA DG Set
(d) 110 KVA DG Set
(e) 100 KVA DG Set
(f) 60 KVA DG Set
Supply only suction connection in repair of radiator assembly for the following capacity of DG set complete all as specified and as directed
(a) 320 KVA DG set
(b) 125 KVA DG Set
(c) 100 KVA DG Set
Supply only main pipe in repair of radiator asssembly for the following capacity of DG set complete all as specified and as directed
(b) 125 KVA DG Set
(c) 100 KVA DG Set
Supply only rubber hose in repair of radiator asssembly of DG set complete all as specified and as directed
Supply only stud in repair of radiator asssembly of DG set complete all as specified and as directed
Supply only spacer repair of radiator asssembly of DG set complete all as specified and as directed
Supply only hydraulic fuel pipes for DG set complete as specified and as directed
Supply only pipe from thermostat to water tank in repair of radiator assembly for the following capacity DG set complete as specified and as directed
(a) 125 KVA DG set
(b) 110 KVA DG Set
Repair/maintenance and servicing of oil cooled step down transformer 6 KV/433 Volt of capacity 2000 KVA, Make Kirloskar, comprising following work services :- (a) Disconnection of cable termination of HT & LT ends. (b) Opening of top cover by removing nuts, bolts and all mounting accessories and conservator tanks. (d) Cleaning all sludges from main oil tank and conservator tank and removal off the site. (e) Servicing of tap changing gears by cleaning and polishing tapping contact points. (f) Cleaning, polishing of serviceable bush and stud both HT/LT side and refixing the same. (g) Replacing unserviceable stud and bush as required as directed by Engr-in-Charge. Note : (i) While replacing and refixing the stud and bush all nuts, washers and gaskets are to be replaced with new one against the coated rate (ii) New bushes and studs required for replacement shall be measured and paid separately as 'Supply only'. ih) Refixing all cable terminals HV & LV sides and transformer top cover, conservator tank in position. (j) Cleaning and heating of silica gel in breather and replacing with new silica gel to make up the reduced quantity Note: New silica gel requied for replenishing shall be measured and paid separately as 'Supply only'.(k) Fixing as in repair of buchholz relay. Note: New buchholz relay required for replacement shall be measured and paid separately as 'Supply only'. (l) Connecting HT & LT side with existing incoming and outgoing cables including reconnection of earth strip/lead.Note: (1) HT side cable connection shall be made with new HT tape & M Seal Monoplast. (2) M seal monoplast required for replacement shall be measured and paid for separately as 'Supply only'. (3) The items of work mentioned here-in-after are tentative and may vary as per site requirement as assessed by the representative and the Engn-in-Charge after strip inspection and the contractor shall have no claim on that account. (4) Contractor wiil be very careful and should ensure not to enter any type of moisture in side the transformer during maintenance.
All as per item No 33 here-in-before but for capacity of transformer 315 KVA, Make : Alston
Supply only porcelain transformer bushing LT side as per existng size/Model of following capacity of transformer:-
Supply only porcelain transformer bushing HT side as per existng size/Model of following capacity of transformer:-
Supply only transformer studs of brass for HT as per existng size/Model of following capacity of transformer:-
Supply only transformer studs of brass for LT as per existng size/Model of following capacity of transformer:-
Supply only M seal monoplast kit for Buck/Boost transformer of 2000/400/315 KVA capacity.
Supply only transformer oil temperature gauge dial type range 0 to 100 deg C as per existing type and model.
Supply only Silica gel in existing breather assembly.
Supply only MS bolts, nuts and washer of required size.
Supply only GI bolts, nuts and washer for transformer oil tank, cable end box and at other parts of transformer of required size.
Supply and fixing Auxiliary contact A600 P600, 10A, 690 V Conforms to IEC/EN 60947-5-1, and including taking down old unserviceable one and making good the disturbed surface complete all as specified and as directed by the Engr-in-Charge. Make :L&T/Legrand/C&S or equivalent approved make.
Supply and fix as in repair CT for Amp meter ratio 400/5 Amps (Set of 3 Nos) complete all as specified and as directed by the Engr-in-Charge. Make-AE/Kappa
.-Ditto- all as per item No 45 above but ratio 200/5 Amps.
Filteration and dehydration of old transformer oil and removing of sludge by continuous circulation through transformer oil filtration plant with heater strips to achieve dielectric strength of not less than 50 KV at 2.5 mm gap of electrode, improvement of acidity by minimizing percentage of acidity using chemical reagents complete all as spedified and as directed by the Engn-in-Charge. Note : (i) Filteration of transformer oil shall be carried out as per IS-1866(1983). (ii) Filteration of transformer shall be carried out using filtration plant equipped with circulating pump, series of column filter papers, heater strips and capacity 125 GPH(min). (iii) Transformer oil test before and after dehydration shall be carried out by the contractor and copy of same will be enclosed during claim of payment duly signed by Engr in charge and contractor.
Supply only transformer oil having di-electric strength not less than 50 KV after initial dehydration/filteration conforming to IS 335 and ISI marked to be brought at site in sealed container complete all as specified and as directed by the Engn-in-Charge.
Supply and fixing for Start-stop-reset push button with LED lamp including all necessary incoming and outgoing electric connections after and including taking down old unserviceable one and making good the disturbed surface complete all as specified and as directed by the Engr-in-Charge. Make : L&T Cat No EALTDI or equivalent approved make of Legrand /. ABB/C&S
Supply and fixing for Voltmeter, single phase, class - 1, digital type after and including taking down old unserviceable one complete all as specified and as directed by the Engr-in-Charge. Make : L&T Cat No. WDS101FEV00 or equivalent approved make of Legrand / ABB./C&S
Supply and fixing for Ammeter, single phase, class - 1, 5A digital type after and including taking down old unserviceable one complete all as specified and as directed by the Engr-in-Charge. Make : L&T Cat No. WDS101FCA00 or equivalent approved make of Legrand / ABB/C&S.
Supply and fixing for Current Transformer 160/5 after and including taking down old unserviceable one complete all as specified and as directed by the Engr-in-Charge. Make : Kappa/AE
Supply and fixing for 50 Amp short circuit & over load protection after and including taking down old unserviceable one complete all as specified and as directed by the Engr-in-Charge. Make : L&T Cat No ST41921OOOO or equivalent approved make of Legrand / ABB/C&S
Supply and fixing for SPGD -2 relay with CTs 40 Amp after and including taking down old unserviceable one complete all as specified and as directed by the Engr-in-Charge. Make : Minilac/L&T
Supply and fixing for "On/ off " trip indicatior after and including taking down old unserviceable one complete all as specified and as directed by the Engr-in-Charge. Make : L&T/Vishnu
Supply and fix on load change over switch 630 Amps 415 Volt 4 pole after and including taking down old unservoceable one complete all as specified and as directed by the Engr- in Charge. Make L&T cat no Co CO46300OOOO or equivalent model of schneider/ simence/C&S /ABB
Earthing with Galvanised Iron Earth Plate Electrode 600X600X6.0mm, buried directly in Ground vertically at a depth not less than 2.25 METRE below Ground Level with the Top Edge of Earth Plate at a depth not less than 1.50 METRE below Ground Level connected to GI Strip of size 36x6mm as Earth Lead by means of Bolts, Nuts, Check Nuts and Washers of Galvanised Steel, Earth Plate Electrode surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt in alternate layers of not exc. 150mm thick, GI Strip protected with and including 40mm bore GI Light Grade Pipe upto 1.0METRE above the Floor Level of the Building where Main Switch/DB situated including PCC Pit in Cement Concrete (1:3:6) type C1 (20mm Graded Stone Aggregate) and RCC Cover of size 450X450X50mm in RCC (1:2:4) type B1 (20mm Graded Stone Aggregate) reinforced with and including 8.0mm dia TMT Bars @ 100mm centre to centre both ways, GI Wire Mesh, Funnel, 20mm bore Medium Grade GI Watering Pipe, necessary Excavation in Soft/Loose Soil, returning, filling in and removal of surplus Spoil upto a distance of 50.00 METRE and all as shown in Electrical Plate No. 5 of MES Schedule Part-I and Testing on completion including Taking down unserviceable Earthing ,complete all as specified and directed by the Engineer-in-Charge.
Material and labour in replacement for Galvanised iron strip 32 x 6 mm burried in ground or on wall with clamping arrangement ,complete all as specified and directed by the Engineer-in-Charge.
Material and labour for painting of transformers any capacity with one coat of synthetic enamel paint after and including cleaning of existing surface of all dirts and greasy materials including marking of SM/MES Nos with letters n exc 15cm height at appropriate places complete all as specified and as directed by the Engr-in-Charge. Note: The superficial area for the purpose of painting shall be considered approx 10 Sqm.
Material and labour for painting of panel board any size at various sub stations/locations with two coat of superior quality of synthetic enamel paint after cleaning of existing surface including marking of incoming feeder and outgoing feeder with letters n exc 15cm height complete all as specified and as directed by the Engr-in-Charge. Note : The superficial area for the purpose of painting shall be considered as n exc 15 Sqm.
Supply and fixing for MCCB 100-250 Amp, Four Pole, 415 Volt, AC, 36 kA, type- d sign, DN2-250D with Provision of Thermal Memory : ON/OFF, conform to Conforms to IS/IEC 60947-2 & IEC 60947-2 after and including taking down old unserviceable one and making good the disturbed surface complete all as specified and as directed by the Engr-in-Charge. Make : L&T Cat No. CM92151OOOOX1 or equivalent approved make of Legrand / ABB/C&S
Supply and fixing for MCCB 160 Amps, rapturing capacity 36 KA, FP, 415 Volt fixed thermal and fixed magnetic setting including all necessary incoming and outgoing electric connections after and including taking down old unserviceable one and making good the disturbed surface complete all as specified and as directed by the Engr-in-Charge. Make : L&T Cat No CM98065OOMO or equivalent approved make of Legrand/ABB
Supply and fixing as in replacement MCB 40 Amp SPN 4 pole 'C' curve including all necessary incoming and outgoing electric connections complete all as specified and as directed by the Engr-in-Charge. Make : L&T Cat No BB 40400C or equivalent approved make of Legrand / ABB/C&S
Supply and fixing for SS enclosure suitable to accommodate MCCB 100 Amp and including taking down old unserviceable one and making good the disturbed surface complete all as specified and as directed by the Engr-in-Charge. Make : L&T Cat No. ST29967OOOO or equivalent approved make of Legrand / ABB/C&S
Supply and fixing for MCCB 400 Amp, three Pole, AC, 36 KA, 415 volt with spreader terminals after and including taking down old unserviceable one and making good the disturbed surface complete all as specified and as directed by the Engr-in-Charge. Make : Legrand Cat No 422002 or equivalent approved make of L&T / ABB/C&S
PART - II - E/M - I : Detection of faults by a DG Technician(High Skilled ) as and when required basis or as directed by Engg-in-charge) for Diesel Engine Generator set of:- (a) 750 KVA DG Set No-I (Deffi Tech Accn -01 No) (b)750 KVA DG Set No-II (Deffi Tech Accn -01 No). (c) 200 KVA Dg set(Cath Lab,CMDC,Map Ph-I -03 Nos).(d)320 KVA Dg set( Map Ph-II, - 01 No.(e)100 KVA Dg set(SS-I,SS-2,SS-4, -03 Nos)(f) 1000 KVA DGset (Besement, -01 No) make Kirloskar / Cummins/ Greaves or any other make and alterrnator make Kirloskar/ Cummins/ Crompton Greaves or any other make complete with control/ AMF panel, acoustic enclosure and connected accessories including replacement of oil /lubricant filter to keep the plant in running condition including routine maintenance as per manufacuturer instruction and cleaning the DG sets with its sarroundings, maintaning battery charger complete all as specified and as directed. [Note: (i) Spare parts for maintenence will be measured and paid seperately under relevent items of this schedule as 'Supply Only'] (ii) Details of DG set:- (a)MES No-253/6075-DG/12(Eng),253/6075-DGLT/12 (Alt) near CMDC (EC) (b) MES No 253/6074-DG/11 (Eng), 253/6074-DGALT/11 (Alt) near catheterizetion Lab, CH (EC) and (c) MES No 253/6080/DG/09 (Alt) near Pump House MAP Ph-I. (d) SM No 158739, MES No Eng -T-12540E, Alt -B- 01884E at Sub station 1 (e) MES No 253/6045-Set- (f) SM No 158739, MES No Eng -T-12540E, Alt-B-01884E at Sub Station 1 (g) MES No 253/6045-DG/08 (Eng), 253/6045-DGALT/08 (Alt) at Sub Station 2 and (h) MES No 253/6081-DG/13 (Eng), 253/6081-DG ALT/13 (Alt) at Sub station 4.(j) 750 KVA DG Set No-I (Deffi Tech Accn) (k)750 KVA DG Set No-II (Deffi Tech Accn) (iii) The contractor will have to produce visit reports before claiming of any payment in this regard..( The above work includes detection of major/minor faults, transportation of parts of any volume if required to workshop and after repair to the site and visiting charges of the OEM deputed techincian/high skilled technician etc.)
Supply only following items for maintenance of DG Set 200 kVA and 100 kVA including dismantling of old spares: -
Lubricant oil filter for DG set 200 KVA of make: Kirloskar / Cummins/ Crompton Greaves as required.
Lubricant oil filter for DG set 100 KVA of make: Kirloskar / Cummins/ Crompton Greaves as required complete all as specified and as directed by the Engr-in-Charge. .
Fuel filter (Pre) for DG set 100 KVA of make: Kirloskar / Cummins/ Crompton Greaves as required.
Fuel filter (Micro) for DG set 200 KVA of make: Kirloskar / Cummins/ Crompton Greaves as required.
Fuel filter (Primary Element) for DG set 200 KVA of make: Kirloskar / Cummins/ Crompton Greaves as required.
Fuel filter (Secondary Element) for DG set 200 KVA of make: Kirloskar / Cummins/ Crompton Greaves as required.
Fuel filter (Primary Element) for DG set 100 KVA of make: Kirloskar / Cummins/ Crompton Greaves required.
Fuel filter (Secondary Element) for DG set 100 KVA of make: Kirloskar / Cummins/ Crompton Greaves as required.
Coolant for DG Set of make: Kirloskar, type: KOEL Care Super Genuine Coolant premix or equivalent in Servo in not less than 5 Ltrs non-returnable Can.
Lubricant for DG Set of make: Kirloskar, type: KOEL Care Super Genuine Oil or equivalent in Servo.
Battery Lead acid 12 volt, 150 AH make: TATA GREEN or equivalent in EXIDE/ AMCO
Lub oil pressure sensor for 200 kVA DG Set, make: Kirloskar Code: 2H.092.11.0.00 .
Sensor unit for electrical temperature gauge, make: Kirloskar Code: 4G.085.02.0.00 .
Emergency 'STOP' push button, make: Kirloskar Code: 4H.851.02.0.00 .
Fuse holder including fuse with inbuilt 'fuse blown' indication, make: Kirloskar Code: 4H.865.08.0.00 .
Electric Relay (BAGLI - IN) for sensing and signaling to control circuits, make: Kirloskar Code: 6H.846.35.0.00 .
Channel for mounting of fuse and relays make: Kirloskar .
18 point connector for sensing/ control circuit
Current transformer 300/5 Amp
Relay Board UL 24 volt DC, make: Kirloskar Code: DVO.854.09.0.00
Microprocessor based fully configured DG Set controller model: KG545 of make: Kirloskar Oil Engines Ltd in other OEM approved make for 200 kVA DG Set suitable for 24 volt system with LCD display and control/ monitoring of Engine Speed, Battery Voltage, Coolant Temperature, Lub Oil Pressure, Oil Temperature, Canopy Temperature, Engine Run Hours, Phase to Neutral Generator Voltage, Phase to Phase Generator Voltage, Per Phase Generator Current, Generator frequency, Per phase kW, Total kW, Per phase kVA, Per phase kVAR, Earth fault current, Per phase Power Factor, Total Power Factor, Battery charging condition, Fuel Level with add-on features for converting to AMF and Remote Monitoring in future all as specified and as directed.
Panel box for housing DG Set controller unit make: Kirloskar or equivalent
Internal wiring material for DG Set 200 kVA including single core 1.5 sqmm stranded copper flexible PVC insulated unsheathed wire, lugs, flexible tie clips, adhesive tapes etc of Kirloskar or equivalent
AMF Relay suitable for operating DG set upto 200 kVA in Auto or Manual including facility of running the DG set in Test mode, AMF Controller - EC2 ( Ver 1.10) of make: C&S/L&T/ Schneider
Automatic Voltage Regulator for 100 kVA DG Set of make: Kirloskar or equivalent OEM.
Checking of windings of alternator coils of 100 kVA DG set, carefully dismantling the alternator and transporting to workshop, stripping of faulty winding of excitor coil, armature winding, thorough cleaning with suitable cleaning agent, rewinding of the armature coil, complete baking, heat varnishing and curing of all winding parts, assembling and transporting back the alternator to CH(EC) complex and refitting in original position and testing after completion all as specified and as directed.
Checking of windings of alternator coils of 200 kVA DG set, carefully dismantling the alternator and transporting to workshop, stripping of faulty winding of excitor coil, armature winding, thorough cleaning with suitable cleaning agent, rewinding of the armature coil, complete baking, heat vurnishing and curing of all winding parts, assembling and transporting back the alternator to CH(EC) complex and refitting in original position and testing after completion all as specified and as directed.
Checking,cleaning with suitable cleaning agent of Engine liner,pistions,sleeps and servicing of Nozzle of 200 kVA DG set, carefully dismantling the Engine and transporting to workshop, stripping of faulty , replaced the unsv item carefully,Calivation, reassembling the same and transporting back the Engine to CH(EC) complex and refitting in original position and testing after completion all as specified and as directed. Note : (i) The cost of cleaning materials like kerosine oil cotton waste etc and lubricating item like mobile oil grease etc and patty spare parts required for this job are deemed inclusive in the rates
Supply only following items for maintenance of DG Set 750 kVA including dismantling of old spares: -
Element pre-air cleaner, make: Cummins code: 4020552
Element air cleaner fine, make: Cummins code: 4020551
Kit super BYP filter element, make: Cummins code: KIT3879488
Kit Fuel filter and 'O' ring, make: Cummins code: KIT3238493
Element lubricating oil filter, make: Cummins code: KIT3238204
Inhibitor corrosion, make: Cummins code: 3167224
Engine oil Valvoline Premium Blue 7600, in non returnable container make:Cummins code: 500255
Battery 12 volt 180 Ah model: Pulse lite, code: AX1012845 oe eqv in AMCO/EXIDE
Coolant for DG Set in 5 Ltrs non-returnable Can.
Supply only following items for maintenance of DG Set 1000 kVA including dismantling of old spares: -
Element pre-air cleaner, make: Cummins
Element air cleaner fine, make: Cummins
Kit super BYP filter element, make: Cummins
Kit Fuel filter and 'O' ring, make: Cummins
Element lubricating oil filter, make: Cummins
Inhibitor corrosion, make: Cummins
Engine oil Valvoline Premium Blue 7600, 210 ltr in non returnable container make:Cummins code: 500255
Battery 12 volt 180 Ah model: Pulse lite, code: AX1012845 oer eqv in AMCO/EXIDE
Coolant for DG Set in 5 Ltrs non-returnable Can
Distile water for Battery
Material and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised strip of size 32 x 6 mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion all as specified and as directed by the Engr-in-Charge.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/ loose soil
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. in any type of soil
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point in any type of soil
Material and Labour for dry river Sand filling in trenches including punning down consolidation in soft/ loose soil
Material and Labour for tubes, 'light grade', galvanised, with all fitting; laid in trenches for cable protection of the following sizes: -
(a) 80 mm dia nominal bore
(b) 50 mm dia nominal bore
Material and labour for brick protection of cables in trenches with old size sub-class 'B' bricks
Material and labour for cutting of existing bituminous metal road for laying of cables including demolition of road surface, excavation from bottom level of road upto a depth of 0.55 m from road surface and returning filling of excavated earth and making good the road surface with PCC type C2 (1:3:6) with 40 mm graded aggregate upto a depth of 10 cm from road surface and removing of excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point in any type of soil all as specified and as directed. [Note: Laying of cable/ protection pipe will be measured and paid under separate item of this schedule]
Supply, laying and testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, including taking out of old cables all as specified and as directed of following sizes: -
(a) Cross-sectional area 240 sq mm 3.5 core
(b) Cross-sectional area 185 sq mm 3.5 core
(c) Cross-sectional area 120 sq mm 3.5 core
Taking out of existing LT UG cable and re-laying/ shifting the same all as specified and as directed for the following size of cables: -
(a) 95 to 120 sqmm 3.5 core
(b) 50 to 70 sqmm 3.5 core
(b) 25 to 30 sqmm 3.5 core
(d) 10 to 16 sqmm 2/4 core
Taking out of damage canopy of 200 KVA DG set and fixing the new canopy, silencer, door lock of existing size and model of DG set all us directed by engineer-in-charge. All the unserviceable canopy are deposited at MES store yard.
Taking out FIP from engine assembly shifting of FIP to work shop overhauling of FIP complete after repalcment of unserviceable parts callibration of FIP returning from workshop refixing to engine assembly including replacement of nozzles and cleaning of nozzle pipes complete all as specified and directed for 100/200 KVA capacity by DG set. Note : (i) The cost of cleaning materials like kerosine oil cotton waste etc and lubricating item like mobile oil grease etc and patty spare parts required for this job are deemed inclusive in the rates. (ii) Nozzles and 'O' rings are to be measued and paid separatly as " Supply only" Items below. (iii) Insurance policy for requisit value if directed by Engr-in-Charge shall be submitted before taking over the FIP to workshop by the contractor. Quoted rate shall deemed to be included for insurance.
Supply and fix battery lead copper flexible cable PVC insulated 650W 25 sqmm single core of length 1.5 Metre long with one side connected (welded/soldered) with male type batery terminal and other end connected with female type terminal complete ass as specified and directed including taking down unserviceable one.
All as per item No 84 here before but length 1.00 mtr all as specified and as directed by Engr-In-Charge.
Taking out alternator dynamo from the 100 KVA DG set, dismantling all the parts cleaning and serviceing complete including replacement of petty spare parts , reclosing and refixing to its original position complete all as specified and directed by Engr-In-Charge.
Cleaning of diesel tank by opening out of diesel pipe line taking out of diesel removal of all the sludge cleaning with caustic soda solution, then with fresh water drying up and refitting resetting of the tank to its original position of 200 KVA DG set complete all as specified and directed by Engineer-In-Charge.
Cleaning of diesel tank by opening out of diesel pipe line taking out of diesel removal of all the sludge cleaning with caustic soda solution, then with fresh water drying up and refitting resetting of the tank to its original position of 300 KVA DG set complete all as specified and directed by Engineer-In-Charge.
Supply and fixing radiator hose complete set as per existing shape and size of 125 KVA DG set including taking out old unserviceable items complete all as specified and directed by Engineer-In-Charge.
Scrapping out existing paint, cleaning of surface fresh spray painting with two coat of approved colour synthetic enamel paint to the 100 KVA DG set including diesel tank complete all as specified and directed .
All as per item No 90 here-in before but of capacity 200 KVA DG Set.
All as per item No 90 here-in before but of capacity 300 KVA DG Set.
ARJUN DAS VALECHA
NICE INFOTECH
SUDHA ENTERPRISES
AUTO ELECTRICALS
Tractors Machinary Components
dutta and dutta
M/S J S ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .