Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance LANE REGAL CHOWK RESIDENCY ROAD RAMBAN JAMMU KASHMIR 182144 UDYAM JK 21 0008336 01ALQPN9565N2Z9 B R | RAMBAN | JAMMU AND KASHMIR | 182144 | Admitted-Finance |
| 2 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹57 L
EMD Value
₹2.9 L
Closing Date
18 Dec 2023, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer JSD PHE Mech Rural Division Sgr
Executive Engineer JSD PHE Mech Rural Division Sgr
Electro-mechanical works to be carried out at WSS Migrant colony Baba-daryadin, Ganderbal
2023_PHE_239866_1
PHE/MRD/TS/124of 12/2023
Open Tender
Miscellaneous Works
Item Rate
60 days
Srinagar
Please refer Tender documents.
2 documents required · 2 mandatory
₹200
Yes
Executive Engineer JSD PHE Mech Rural Division Sgr
₹2.9 L
Yes
20 Dec 2023
11 Dec 2023
18 Dec 2023
11 Dec 2023
18 Dec 2023
11 Dec 2023
Amount
Supply, Installation, Testing & Commissioning of Submersible Pumping Unit at an altitude of 1711m (AMSL). The specifications are as under. PUMP: - Make = Reputed make as per IS 8034(2002) Discharge = 4500 GPH. Head Range = 230 meter Type of pump = Mixed flow. Type of fluid to be handled = Raw Water. Rest specifications as per Item No. 1 of Annexure "A"
Providing and installation of MS Liner fabricated out of 12’’MS Pipe of thickness 8mm, length 8 meters or as per the depth of the sump which shall be ascertained after construction of sump by the civil counterpart (weight approximately 480kgs each). The liner shall have symmetrically drilled holes for smooth inflow of water to the pumping units. The liners shall be provided with vibration dampers (05 nos for each liner) at an equidistance to prevent the pumping unit from vibration during operation. The liner shall be fitted with collar fabricated out of 20mm thick MS Plate with Outer diameter of 14’’ which shall bolted to the wedge of the sump openings..(02 jobs)
Fabrication, providing, fitting of delivery manifold system for 02 no Submersible pumping units out of 10 m of Heavy duty, 4.60 mm thick, 100 mm Dia MS pipe at site and suitable no of bends / pipe Spacer of 100 mm nominal dia, reducers / increasers with – 20 mm thick flange, gaskets, fasteners as per pump diffuser size & other parameters as per site requirement. The system is to be designed to with stand pressure of 25 Kg. / cm2.The job shall include fabrication of washout as per site requirement for the manifold.
Providing and fitting of, Ductile iron double flanged, non-rising spindle soft seated glandless gate/ sluice valves as per IS14846 for regulating the water supply outside the pumping units. The body and bonnet of the valve shall be of ductile iron, wedge with fully vulcanized EPDM rubber (Approved for drinking water) with NBR seal. The Gate/Sluice valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions. Nominal Dia= 80 mm. Rating – PN 16. Type – Rising Spindle Nature of Operation – Horizontal / Vertical The job includes cost of of Fabrication, P/F of tail pieces of 5.4 mm thick 100 mm Dia MS pipe with table flanges of 20 mm thickness if required as per site requirement in delivery system and wash out system.
Providing and fitting of 80 mm NB Non-Return valve (NRV) in the delivery manifold with specifications Nominal Dia 80 mm. Pressure Rating – PN 16. The valve Shall poses high speed closing characteristics and be designed for minimum slam condition while closing. External counterweight is not acceptable. Perfect interchangeability of components, parallelism between side flanges shall assured. Surface Protection-- Electro static epoxy powder coated Parameter: - Type – Single plate. Nature of Operation – Automatic All tests shall conform to Code – IS 5312
Providing, fitting, testing, and commissioning of 50mm Dia ARV (Air Release valve) as per IS 14845 to be fitted to 80 mm G.I rising Main pipe of NB 80 mm. the ARV Shall have the following specifications: - i. Valve type - single chamber, single orifice. ii. End connection– flanged/welded ends as per relevant IScode iii. Working temperature - -10ºc to 50º c iv. Test pressure - body / seat 1.5 x PN rating v. Sealing ring - EPDM vi. Construction -ductile iron with stainless steel floats vii. Coating - epoxy with corrosion resistance Besides the above works, the job also includes cost on account of providing and fitting of R.I gasket, nuts and bolts required for installation of ARV and arrangement of gas cutter/ welding set at site.
Fabrication& Erection of channel iron column to act as support for resting monorail crane as per following details: - Vertical Posts: - ISMC 150 No. of Vertical posts:- 02 Nos. Vertical channel section each post:- 02 Nos. Vertical post bracing:- ISMC 100 Sole/Matching plates: - 500x300x12mm (Thick) Height of Vertical Post:-6M Size of vertical post concrete blocks:- 600x600x1200mm(depth) Concrete Grade:- M20 Welding Electrode :- Reputed makes as per relevant IS Code Monorail Section:- ISMB 200 Length of monorail:-3.5M Steel Details i. ISMC 150 6Mx2x2 = 24 M@ 16.8Kgs/M= 403.2Kgs. ii. ISMC 100 0.25Mx8x2x2 = 8M@ 9.56Kg/m= 76.48 Kgs. iii. Plate 0.500x0.300x60 (12mm thk) = 0.90M²(12thk)=84.7 Kgs iv. iv Monorail ISMB200 3.5M @24.2 kgs/m = 84.7Kgs v Bolts/Nuts (L.S) = 20 Kgs. Vi The job includes welding of ISA 50x50x5 each 1’ In length to the vertical post so as act as ladder 15 steps=17.50 Kgs Total :- 686.66 Kgs say=690 kgs. The job also includes painting of single coat of metal primer followed by two coats of silver or yellow paint. The quantity of the steel may vary as per site requirement as it is conditional to civil structures being constructed. Structural steel shall be procured by the contractor conforming to relevant IS codes.
Providing, installation and testing of manual type triple spur gear chain pulley block having following features Gears: - The hoist shall have precision machine case Hardened alloy steel gear mounted on bearings and housed in a dust proof gear box. The lubrication of gears should be of high viscosity and temperature for longer life of gears. Load Chain: - The load chain be made of high tensile alloy steel having wear resistance and greatest mobility. The chain should be accurately collaborated, tested and have adequate in built factor of safety for safer operation. Load chain wheel: - the load chain well should be double ball bearing supported and Specially designed, perfectly machined wheel providing correct grip of load chain to makes the hoist most safe and reliable against any failure. The main specifications of C.P Block are given below: i.) Make =Indef,Pull lift or of equivalent standard ii) Capacity= 2MT iii) No. Of load chain falls = 2 or above iv) Min. Height of lift = 6 M The Test certificate from the OEM of the equipment is to be appended.
Rising Main for Submersible pumping unit: Providing, shifting, loading, unloading, stacking, fabrication, fitting, laying, testing, commissioning of 80 mm (conforming to IS 1239) Dia GI 4.80 mm thick C-Class (Heavy duty) with permissible tolerance open ended, finished neatly, well galvanized on both inner and outer surfaces, and shall be free from cracks, surface flaws, laminations, and other defects for laying of rising main from pump house to storage reservoir at Migrant colony Babadaryadin Ganderbal. Length: 5-6 meter. Make-Jindal, Tata, Electro steel, Suyra Prakash or any equivalent make. Test certificate – From OEM of the pipe according to relevant IS code Rest specifications as per Item No. 10 of Annexure "A"
Providing, fitting, testing, and commissioning of 75 Kva voltage controller as per specifications below Type of voltage controller: Manually operated copper wound, 3-phase, and AC power supply multi-step. Type of Regulators: Double plate type with electrolytic copper contacts. Input voltage: 140-420 AC volts. Output voltage: 410 ± 05% volts. Frequency: 50± 3 C/S. Rest specifications as per Item No. 11 of Annexure "A"
Design, manufacture, Supply, installation, Testing and commissioning and Creation of pole mounted, outdoor type 100 KVA (11/0.440 KV)Level-2Electric Sub Station as per the IS 1180 (Part I-2014) with latest amendments. Technical specifications given here under:- Type: HT/LT Transformer Type of cooling: ONAN. Operating conditions: Input=11000 volts Output =440 volts AC supply in 3- phase. Terminals: Input=3 No. HT bush rods with insulators, washer, nuts etc. Output=4 No. LT bush rods switch insulators, washers, nuts etc. Core: The core shall be of high permeability to reduce core losses and the strips shall be of suitable size and gauge. Transformer Coils: - Suitable number of HT and LT coils in each leg of the core. The transformer coils shall be fabricated out of superior quality aluminium wire/strips properly wound. Rest specifications as per Item No. 12 of Annexure "A"
Supply, installation, errection of MS Tubular Poles-SP33, ISI mark HTL-IS 1161 or IS 2713 of 9mtrs long H.T pole having reduced 4”x5’’x6” from top to bottom and shall be anti-corrosive painted. The job includes providing/laying of cement concrete block in 1:2:4 mix/M15 (Cement concrete, sand aggregate block(s) (of size 3ft deepx1ft above the ground) for grouting of each pole, further includes drilling of holes for installation of various accessories. wherever required the job further includes G.I wire earthing of pole as per REC standard. The two numbers of HT Poles required for erection of 02 pole structure for sub-station are included in the job.
Supply and fitting of 11 KV polymeric composite insulators (polymer Type-5KV)
Supply, laying, installation, testing & commissioning of 0.05 ACSR 11 KV HT Conductor.
Supply, Installation, Testing and commissioning of 11KV G-O set polymer insulator type complete in every respect with all allied accessories 01 No. for tapping point and 01 No. for substation along with disc insulator sets complete (polymer Type -5KN).
Supply, Installation, Testing and commissioning of Drop out Fuse set polymer insulator type for 11KV power supply.
Providing & fixing of 9KA lightning arrestor set station/post type complete with fittings
Providing & fixing of sign plates fabricated out of MS sheets of size1ftx1ft to be fixed on each pole. The job includes letter writing as 11KV Danger in red colour on the sign plates
Providing & fixing of anti-climbing Devices
Providing & fitting of ISMC75, 9ft long (02 No’s) for resting of 100KVA HV Power transformer with suitable dia. Size hole along with D-Clamps, nuts and bolts etc for fitting on 02 pole structure. The job includes providing and fitting of 02 nos. of 50x50x6mm ISC (09 ft) along with Studs & nuts of appropriate size for holding of HT Transformer.
Providing & fitting of ISMC 75X40,9ft long, for with suitable dia. Size hole for installation of link set, G.O.set and lightning arrestor along with D-Clamps/Mukhi clamps, nuts and bolts etc. for fitting on poles as per site requirement.
Providing & fitting of 4ft long, ISA 40X40X5mm for bracing/cross arm with suitable dia., size, and hole along with D-Clamp/Mukhi clamps, nuts& bolts etc.for fitting on poles.
Providing & fitting of ISMC 75X40,9ft long, for with suitable dia. Size hole for accommodating pin insulators along with D-Clamps/Mukhi clamps, nuts and bolts etc for fitting on poles.
Providing, installation, testing of power cable for working voltage up to and including 1100 volts; 120 mm².armored aluminium 3.5 core cable as service line from Sub-station to main cubical panel. Cost includes laying of cable over cable trays, GI hooks as per site requirement, termination of ends with suitable Aluminium tube terminals dully crimpled & taped. Make: Finolex. Havells, Polycab or as per IS Code -IS 7098(part-1)/ IS 1554(part-1).
Providing and fitting of 16mm² 3-Core flat submersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964 from FASD Starter to Submersible Pumping Unit. The cable connections terminal shall be fitted with copper thimbles of required size. Make: Finolex, Gloster, Legend. Polycab or of equivalent standards. as per IS- 694:1990.
Providing and Fitting of 3 core, XLPE, 1.1KV and 11KV grade Aluminium Cable of size 75mm² conforming to IS: 7098 part 1st as internal cabling from Voltage Stabilizer to Change Main control Panel including necessary thimbling, crimping, taping etc. Make:- Reputed & as per latest relevant IS Codes.
Fabrication, installation of perforated ladder type pre-painted MS cable trays with perforations not more than 17.5% in convenient sections joined with connector, with ventilated flanged cover, suspended on MS suspenders included are accessories like vertical bends, horizontal bends, inside bends, outside bends, tees, cable clamps, cable cleats, bolts & nuts, painting of the suspenders etc. as required. As per IS 1255 Tray Thickness - 3mm Cover Thickness – 3mm Dimensions- 100mm width x 100mm depth Quantity –40 m Rest specifications as per Item No. 28 of Annexure "A"
Providing and Installation of earthing station for various electrical gadgets comprising of company fabricated earthling electrode as per IS: 3043. The job includes Auguring of bore of required dia/depth for installation of electrode along with backfill compound mixed with soil and all other items required thereof for achieving the best result. The job includes connecting of electric gadgets through GI strip from earthing station to all the installed equipment’s, pit covers after making of surface structure in brick/cement concrete material as per site requirement, Safe earthling electrode size 80mm dia., included is installation of required sized Aluminium strips from earthing station to all the installed equipment’s, pit covers with all desired items required Length – 2000 mm Back fill compound. -30 kg Model/make – JVM -393, Ashlok, Recons or of equivalent make. The total installation shall be effectively earthed and shall conform to IS: 3043
Fitting, Installation, testing and commissioning of Star Delta Starter Panel /Electric control panel cum starter floor mounted in cubical shape, dust & vermin proof the enclosures of which shall be of sheet metal construction using 16 SWG thick steel sheets with corrosion resistant coat. Fabrication shall be done using seam or spot welding and finish shall be elegant and workmanship of high quality. The interiors of cubicles shall be finished with gloss white paint. The cubicle exterior shall be finished to cream colour. All cut- outs and holes to be drilled in the panel shall be carried out before rust proofing. Rest specifications as per Item No. 30 of Annexure "A"
Tool kit in a suitable box comprising of following tools (Taparia / Jeelani or of equivalent make) Pipe wrench 18” -01 No. Pipe wrench 24” – 01 No. Ring spanner set of 12 pieces. - 01 set. Open ended spanner set of 12 pieces -01 set. Pliers 8” -01 No. Adjustable wrench -01 No. L.T. Line tester -01 No. Clamp meter -01 No. Screw driver set starter type 01 set Chisel type Screw driver set -01 set. Hammer -01 No. Hex saw frame with set of 6 blades. -01 No. 5 kg handy gas filled with burner. – 01 No Bamboo Ladder 16 feet long. Link disconnecting rod 12 feet long.
Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen due to possible leakage of current & short circuit. The floor surface shall be made good & shall be free from dust, grease, foreign material & moisture free. The mats shall be as per IS 15652:2006 & shall have the following specifications: -Composition: Rubber (synthetic mats for electrical purpose) Thickness: - 2.5mm Size: - 1M wide. Make: - Safe Volt/Jyoti or of equivalent Make
a) 02 No. durable and long lasting Blankets made from wool. b) 02 No. good quality mattress, quilts, pillows with covers for complete bedding. c) 10’x12’ and 2x (6’x5’) excel & 12mm thick thermo Cole for same dimensions (size may vary as per site requirement). e) Heavy duty 3-watt chargeable torch. g) 02 No. pressure cookers of 5 litters capacity, 01 No. tea pan, 4 No. glass,4 cups, plates, spoons, 2 jugs, 02 No. buckets ,Electric cooking heater infrared type, 03 No. plastic chairs ,01 No. Plastic table required for three no operational staff All the items shall be purchased under the presence of person in charge as per his choice.
Illumination of pump house which involves:- providing & fitting of lighting points involves: a) Wiring to lighting points with main wire as 1.5 mm sq. and for branches 1 mm sq. PVC single core multistranded copper conductor insulted, unsheathed 1.1 KV grade ISI marked with length as required. b) Recessed pvc conduit/ channel 1.5” and 1” as required. c) 6 Ampere flush type switches ISI marked. d) Switch board frame fabricated out of wooden/ iron included flushing ways for above frames on walls as per site requirement. e) Phenolic / phylum laminated sheet cover for fitting of switches over the above frame. f) Ceiling roses, square blocks, angle holders, PVC corner/ending points accessories, washers, star screws, cement nails ,rawl plugs as per site requirement.
Providing and fitting of 10 watt LED lamps for holders of item no 1.
Providing and fitting indicator points ISI marked.
Providing and fitting Fan regulating points with 02 No 400 mm sweep wall fan and 02 no 150 mm exhaust fans ISI marked
Providing and fitting 03 pin flash type socket 6 Ampere ISI marked
Providing and fitting of heating/stabilizer input and output points involves: a) Wiring for 5 pin 16 Ampere power plug point with 2.5 mm sq. PVC single core Multistranded copper conductor insulted, unsheathed 1.1 KV grade ISI marked with length as required length as required. b) Recessed pvc conduit/ channel 1.5” and 1” length as required. c) 16 Ampere 5 pin flush type switches and 16 Ampere flash type socketed modules ISI marked. of equivalent Make d) Switch board frame fabricated out of wooden/ iron included flushing ways for above frames on walls as per site requirement. e) phenolic / phylum laminated sheet cover for fitting of switches over the above frame. f) PVC corner/ending points accessories, washers, star screws, cement nails ,rawl plugs as per site requirement
Providing, fitting of Distribution Board of Indo Asian, S K or of equivalent make 6-way S P N single door powder coated sheet steel enclosure for surface mounting fitted with bus bar, DIN channel, neutral link and incoming contact. The above DB is to be provided /fitted with double pole 63 amp MCB for heating circuit & rests five of 16 amps each for lighting, fans/exhaust fans, premises luminary, and auxiliary circuit of Indo Asian, Havells or of equivalent make. The job further includes providing and fitting of 4 mm² multi stranded single core 1100 volts, PVC insulated copper conductor through pvc conduit as main line from main panel to required power points at site.
Supply, installation, Testing & commissioning of 1000VA Full Sine wave power inverter (Make: Microtek/Luminous or of equivalent Make) including Providing / Installation of 12V, 180AH Tubular inverter Battery with trolley and cover. (Make: Amaron /Exide or any equivalent make) with 2-core 6mm2Cu wiring as per site requirement along with other accessories like SS-Combine (02 No’s), 3-pin plugs etc of reputed make for proper fitment and installation of the item
Illumination of the pump house premises Providing and erection of 9 Mtr long Hot Dip Galvanized octagonal pole (single Section) with bottom 11, top 75mm vile, thickness 3nim with 70 Microns Zinc coating having inside arrangement for providing of power connection along with following items. 3 Way Terminal Connector 20 Amp. 2 No. MCB 8Amp.
Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light type) on top of octagonal pole Having following specs: input: 90-240 V 50 Hz Power Factor: >0.9 Colour Temperature: 4K - 6.5K Bean Angle: 120"-170" Lumens: >12000 Operating Temperature: -20°C to 60 C
S/I/T/C of three phase LT prodigy meter on the service line at the Sub-stationas per the following specifications: Connection type: Direct Wiring : three phase, 4wire Voltage Rating : 230/240V( L-N) Current Rating : 40 to 200 A Accuracy : Class 1 Frequency : 50Hz + 5% Burden voltage circuit :<1.0W, 1.5VA per phase Insulation class Protection class II Impulse withstand 10KV Weight 4.5 kg (approx) Enclosure Double insulated glass filled polycarbonate Terminals Thread through design suitable for current up to 200 A Sealing 95% non-condensing The job shall include cabling, thimbling if required as per site requirement.
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .