Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.0 LAccepted-AOC 1 OPP NAGAR NIGAM KATNI MAIN ROAD KATNI MADHYA PRADESH 483501 | KATNI | MADHYA PRADESH | 483501 | L1 | Accepted-AOC Being lowest tenderer | |
| 2 | L2₹16.4 L+₹1.7 L (11.2%)Rejected-Finance | L2 | Rejected-Finance Being not lowest tenderer | |
| 3 | L3₹16.9 L+₹2.2 L (14.8%)Rejected-Finance | L3 | Rejected-Finance Being not lowest tenderer | |
| 4 | L4₹21.0 L+₹6.2 L (42.1%)Rejected-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NORTH | DELHI | 110006 | L4 | Rejected-Finance Being not lowest tenderer |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
11 Jul 2023, 6:00 pmClosed
CWE AF TUGHLAKABAD
HQ CWE AF TUGHLAKABAD AF STATION, TUGHLAKABAD PO SANGAM VIHAR NEWDELHI-110080
REPAIR/MAINT TO CENTRAL AC PLANTS INCLD MAINT OF LT PANELS AHU, COOLING TOWER AND OTHER MISC WORKS AT BRD AF STN UNDER GE (AF) TUGHLAKABAD
2023_MES_603036_1
CWE/TKD/TOKEN-25 OF 2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE(AF) Tughlakabad
As per NIT conditions
8 documents required · 8 mandatory
₹500
GE (AF) Tughlakabad
₹60,000
Yes
4 Aug 2023
13 Jun 2023
13 Jul 2023
13 Jun 2023
11 Jul 2023
27 Jun 2023
Amount
M&L for checking the leakage in both low and high side of the system by feeding dry nitrogen to maintain adequate pressure in the system, plugging the leaks including S&F replacement of Teflon sealing of all refrigerant line valves like liquid lines valves/suction/ discharge valves of compressors, gland packages of all angle valves flaring of all connections framing welding etc complete for the following plants:- Note:1. Entire work is to be carried out by OEM i.e Bluestar for following plants.
AC plant of capacity 3 x 37.5 TR-Plant for RSBN. OEM- Bluestar
AC plant of capacity 3x15TR-Plant for Signal Section.OEM- Bluestar
AC plant of capacity 2 x 30 TR-Plant for ESCT. OEM-Bluestar
AC plant of Capacity 3x66 TR plant for PW-VI. OEM-Bluestar
AC plant of Capacity 1x37.5 TR plant for PW-III. OEM-Voltas
AC plant of Cap 2x5.5TR-Plant for New signal centre.OEM-Bluestar
AC plant of Capacity 3 x 26 TR plant for Spyder. OEM-Bluestar
Opening the upper sheet and side sheet of AHU’s of the following plants for access to cooling coil, including M&L for washing/cleaning of cooling coil externally with mild acid (or caustic soda hot water solution) followed by water jet including cleaning/washing of air filters and descaling of cooling coil of AHU, re-fixing and changing of necessary fitting, T&P for mounting and all connections framing welding as specified and directed. Note:1. Entire work is to be carried out by OEM i.e Bluestar for following plants.
AC plant of capacity 3x37.5 TR-Plant for RSBN. Make-Bluestar
AC plant of capacity 3x15 TR-Plant for Signal Sec. Make-Bluestar
AC plant of capacity 2x30 TR-Plant for ESCT. Make-Bluestar
AC plant of capacity 3x26 TR-Plant for spyder. Make-Bluestar
M&L for repair of AHU motor suitable for AC plants with following capacity by dismounting it from weather making unit of AHU, rewinding of 10/12.5HP motor same gauge with super enamelled copper wire including removing burnt winding cleaning of slotes sepration of rotor and startor making insulation to all joint all as specified and directed. Note: UNSV part shall be measured and paid seperately under the below items of BoQ, accept scope covered under this item.
Supply only in replacement of following defective spare parts of AHU motor of any description/make and capacity 10/12.5 Hp and in any positioin :-
Replacement of ball bearing.
Replacement of cooling fan.
Replacement of capacitor of suitable mfd
Replacement of seal, bush
Turning and polishing of motor shaft including lathe work
M&L for fixing in replacement of gun metal gate valve butterfly type of 15 mm dia complete all as specified and directed.
M&L for fixing in replacement of gun metal gate valve butterfly type of 20 mm dia complete all as specified and directed.
M&L for fixing in replacement of gun metal gate valve butterfly type of 25 mm dia complete all as specified and directed.
M&L in replacement of Y type strainer 65mm dia CI body flanged ends with stainless stell strainer type as per existing omplete all as specified and directed.
M&L in replacement of Y type strainer 80mm dia CI body flanged ends with stainless stell strainer type as per existing omplete all as specified and directed.
M&L for opening the outer sheets of package unit to access cooling coil, washing / cleaning of cooling coil externally with mild acid (or caustic soda hot water solution) followed by water jet including cleaning / washing of air filter and re-fixing, complete all as specified and directed . Note- Entire work is to be carried out by OEM only i.e Bluestar/Voltas/Fedders Lloyd
AC Plant of capacity 1 x 37.5 TR Plant for PW-IV. OEM-Voltas
AC Plant of capacity 3 x 66 TR Plant for PW-VI. OEM- Bluestar
AC Plant of capacity 2 x 5.5 TR Plant for signal Sec. OEM- Bluestar
AC plant of Capacity 2x5.5TR-Plant for New signal centre.OEM-Bluestar
Cleaning of existing choked fins of existing cooling towers with chemical, removing the sludge and replace of defective fins,repair leakage base plate ,cleaning and two coat of epoxy paints required complete all as specified and directed.
AC plant of capacity 3x37.5 TR-Plant for RSBN . Make-Bluestar
AC plant of capacity 3x15 TR-Plant for Signal Sec. Make-Bluestar
AC plant of capacity 2x30 TR-Plant for ESCT. Make-Bluestar
AC plant of capacity 3x26 TR-Plant for spyder. Make-Bluestar
AC plant of Capacity 3x66 TR plant for PW-VI. OEM-Bluestar
AC plant of Capacity 1x37.5 TR plant for PW-IV. OEM-Voltas
M&L for evacuation of gas from the system into the empty cylinder provided by department/pumping down to the system, descaling condenser unit of the following capacity plants after bypassing the cooling tower, pumps & supply and circulation of the descalling solution (ANTI SCALENE SCALE FOEE-100) with pump brushing the tubes and where required drilling the stubbon scalling without damaging the tube, replacement of deshed end gasket and unserviceable nuts and bolts assembling back complete testing and commissioning including removing air lock, recharging the gas taken out of the system complete all as specified and directed . Notes: Descaling pumps, nylon brush, acid including storage containers, drill and drill bits to be arranged by contractor and cost of the same deemed to be included in the rate quoted for the following:-
AC plant of capacity 3x37.5 TR-Plant for RSBN. No of compressors are 9(OEM- Bluestar)
AC plant of capacity 3x15 TR-Plant for Signal Sec (OEM- Bluestar). No of compressors are 3
AC plant of capacity 2x30 TR-Plant for ESCT (OEM-Bluestar). No of compressors are 4
AC plant of capacity 3x26 TR-Plant for spyder (OEM- Bluestar. No of compressors are 6
AC plant of Capacity 3x66 TR plant for PW-VI. OEM-Bluestar no of compressor are12
AC plant of Capacity 1x37.5 TR plant for PW-IV. OEM-Voltas No. of compressor are 9
M & L for Vacuum the system and after maintaining vacuum for 24 hours supply and charge refrigerant gas HCFC 22 complete all as specified and directed . Make:-Mafron/Refron
M & L for Vacuum the system and after maintaining vacuum for 24 hours supply and charge refrigerant gas R-407/410 C complete all as specified and directed . Make:-Mafron/Refron
M&L in replacement for EWT/LWT sensor suitable for tripping for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR ESCT, 3x7.5 TR PW-VI, 3x7.5 TR PW-III AC plant as required and specified by OEM i.e Bluestar. Complete all as specified and as directed.
M&L in replacement for digital temperature humidity display assembly as per existing sample for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR ESCT, 3x66 TR PW-VI, 3x37.5 TR PW-IV AC plant as required and specified complete all as specified and as directed .
M&L in replacement for Thermometer gauge with thermowell complete with fittings etc as reqd capacity 0-50 degree celcius placed on pipe line as per existing for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR ESCT, 3x66 TR PW-VI, 3x37.5 TR PW-IV AC plant as required and specified. Complete all as specified and as directed.
M&L in replacement pressure gauge complete with fittings ,cock valve ,syphon and pressure gauge etc Range 0-10.6 KG/cm2 (low/high) as per existing for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR 3x66 TR PW-VI, 3x37.5 TR PW-IV AC plant as required and specified complete all as specified and as directed
Taking down defective /unserviceable AC compressor of capacity 5.5/7.5 TR package type AC, and repair of the same compressor at company authorized outlet including replacemnet of bearing -02 Nos, rewinding of same gauge with super enamelled copper wire including removing burnt winding cleaning of slotes sepration of rotor and startor making insulation to all joint pressure testing, oiling, lathe work, piston rings, shaft seal, bush & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge. NOTE- Compressor maintenance cost for next 6 months is deemed to be included in qouted rates.
Taking down existing water softener and supply and fixing water treatment system 440 LPM capacity non chemical online electrostatic type including control panel, outer casing made of SS 304 both ends flanged including necessary nut, bolts and rubber packing and cutting welding required at site all specified and directed by Engr-in-Charge. Make: Model no 302 of M/s Weldon Engineers or equivalent of Ion Exchange/Pristine water
Supply and fixing in replacement PVC insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sq mm 3 core all as specified and as directed.
Supply and fixing in replacement PVC insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sq mm 3.5 core all as specified and as directed.
M&L for painting of AC Plant as per existing colour including Compressor, condenser, motor, chiller pump, AHU, cooling tower, Plant LT panel including base and all pipe lines & connected valve etc complete all as specified and directed for following:-
AC plant of capacity 3x37.5 TR-Plant for RSBN
AC plant of capacity 3x15 TR-Plant for Signal Sec
AC plant of capacity 2x30 TR-Plant for ESCT
AC plant of capacity 2x26 TR-Plant for Spyder
AC plant of Capacity 3x66 TR plant for PW-VI. OEM-Bluestar
AC plant of Capacity 1x37.5 TR plant for PW-IV. OEM-Voltas
M&L in replacement of control panel suitable for upto 7.5 TR package unit incl display unit, PCB model No -12.8412K10, contactor model No 3TF30100A-02 Nos, relay NO+NC, wiring complete all as specified and directed Make:-Blue Star package model No DPUA5475 & equivalent
M&L in replacement of Single phase preventor VSP 2 auto/manual reset of any size , 415V, complete all as specified and directed
M&L in replacement MCCB (AC 415 V) with adjustable thermal & fixed magnetic setting Four pole 400 Amp 36 KA complete all as specified and directed .
M&L in replacement MCCB (AC 415 V) with adjustable thermal & fixed magnetic setting Four pole 630 Amp 36 KA complete all as specified and directed .
M&L in replacement MCCB 200 Amp, 4 Pole, 415 V, 36 KA Breaking capacity, with adjustable thermal & fixed magnetic release complete all as specified and directed .
M&L in replacement MCCB 100 Amp, 4 Pole, 415 V, 35 KA Breaking capacity, with fixed thermal magnetic release complete all as specified and directed .
M&L in replacement for MCCB 3 pole 63 amps, 25 KA, complete all as specified and directed .
M&L in replacement of Electronic overload relay (Manual reset) relay range 9-16 amp suitable for direct mountimg complete all as specified and directed
M&L in replacement of Electronic overload relay (Manual reset) relay frame size 4 inch relay range 24-40 amp suitable for contactor frame size CH 1 to CH 2 Type MPR200Nx complete all as specified and directed.
S&F in replacement of flare nuts (5/8, 3/8)" for connecting copper pipe for indoor & outdoor unit complete all as specified and directed .
M & L welding/brazing rod copper for fluxing to ac plant equipments complete all as specified and directed.
Supply only Butane gas cane of 225 gms for brazing complete all as specified and directed .
S&F in replacement Power contactor 3 pole Type MNX 18 AC 3 rating 18 Amp with auxiliary contact 1 NO + 1 NC complete all as specified and directed
M&L in replacement Power contactor 3 pole Type MNX 70 AC 3 rating 70 Amp with auxiliary contact 2 NO + 2 NC complete all as specified and directed
M&L in replacement Power contactor 3 pole Type 2 M 50 AC 3 rating 50Amp, coil capacity 240VAC. complete all as specified and directed
S&F in replacement Power contactor 3 pole Type 3 ML AC 3 rating 40/45 Amp with auxiliary contact 2NO + 2NC, complete all as specified and directed
S&F in replacement Power contactor 3 pole Type MNX 25 A AC 3 rating 25 Amp with auxilary contact 2NO + 2NC, complete all as specified and directed.
S&F in replacement Power contactor 3 pole Type 1.5 ML AC 3 rating 25 Amp with auxilary contact 2 NO + 2 NC,complete all as specified and directed.
M&L in replacement Power contactor 3 pole Type MNX 12 AC 3 rating 32 Amp with auxilary contact 2NO + 2NC. complete all as specified and directed
M&L for thermal insulation for ducts with 13mm thick nitrile rubber insulation, complete all as specified and directed .
Supply and installation in replacement of aluminium powder coated grills / diffusers for supply air/return air and size 400x 400mm, square type with MS volume control dampers complete all as specified and directed .
M&L in replacement of supply/return air ducting fabricated out of GI Sheet of thickness 22 guage complete all specified and directed .
M&L in replacement of supply/return air ducting fabricated out of GI Sheet of thickness 24 guage complete all specified and directed .
S&F in replacement of high pressure cutout for R-22. complete all specified and directed.
S&F in replacement of Low pressure cutout for R-22. complete all specified and directed.
S&F in replacement of Oil pressure cutout for R-22. complete all specified and directed.
S&F in replacement of Solonoid Valve for AC plant of Cap upto 80 TR complete all specified and directed
S&F in replacement of Safety relief Valve for AC plant of Cap upto 80 TR complete all specified and directed.
M&L in replacment of PUF Insulation 36 mm thick, density 36kg/cm and 26 gauge GI cladding complete with necessry mounting arrangement like clamps nut bolt etc suitable for existing AC plant cap upto 100 TR all as specified and as directed.
M&L in replacement of PCB contoller panel with display unit complete with necessary mounting, contactor, wiring kit, thimble, contact complete suitable for existing AC Plant cap upto 100 TR, PCB model No WCUS1015A complete all as specified and as directed .
Repair of PCB contoller panel with display unit complete with necessary mounting, contactor, wiring kit, thimble, contact complete suitable for existing AC Plant cap upto 100 TR, complete all as specified and as directed .
M&L in replacement Duct filter with ss material filter media capacity shall capable 5 microns as per existing, suitable for AC plant of capacity upto 75 TR, package units as per site requirement. Complete all as specified and directed .
M&L in replacement Strip heating element of cap 3KW (3000 W) 240 Volt Ac 50 Hz single phase complete all as specified and directed .
M&L in replacement compressor Strip heaters of cap 1.5KW, 240 Volt Ac 50 Hz single phase complete all as specified and directed.
M&L in replacement Aluminium sprinkler 4 way 3" (63mm) with necessary mounting complete suitable for existing cooling towers,complete all as specified and as directed .
M&L in replacement rigid PVC (drift size 600 MM X 600 MM X 125 MM) elemator for distribution of water over fills with necessary mounting complete suitable for existing cooling towers cap upto 100 TR,complete all as specified and as directed by Engr-in-Charge
Taking out the U/S motor and rewinding of motor capacity 7.5 HP with same gauge with super enameled copper wire including removing burnt winding cleaning of slots separation of rotor and starter making insulation to all joint and replacement of the following items. All as specified and directed . (a) Replacement of ball bearing. Make: SKF-02 Nos (b) Replacement of bush (c) Replacement of cooling fan - 01 Nos.
Taking out the U/S motor and rewinding of motor capacity 5 HP with same gauge with super enameled copper wire including removing burnt winding cleaning of slots separation of rotor and starter making insulation to all joint and replacement of the following items. All as specified and directed . (a) Replacement of ball bearing. Make: SKF-02 Nos (b) Replacement of bush (c) Replacement of cooling fan - 01 Nos.
Taking out the U/S motor and rewinding of motor capacity 3 HP with same gauge with super enameled copper wire including removing burnt winding cleaning of slots separation of rotor and starter making insulation to all joint and replacement of the following items. All as specified and directed . (a) Replacement of ball bearing. Make: SKF-02 Nos (b) Replacement of bush (c) Replacement of cooling fan - 01 Nos.
Taking out the U/S motor and rewinding of motor capacity 2 HP with same gauge with super enameled copper wire including removing burnt winding cleaning of slots separation of rotor and starter making insulation to all joint and replacement of the following items. All as specified and directed . (a) Replacement of ball bearing. Make: SKF-02 Nos (b) Replacement of bush (c) Replacement of cooling fan - 01 Nos.
Opening of pump 7.5 HP centrifugal for repair and re-fixing of all the same and testing and commissioning complete all as directed. Note: Unsv spair parts shall be measured and paid under the respetive items of BoQ.
Opening of pump 5 HP centrifugal for repair and replacement of following u/s parts including re-fixing of all the same and testing and commissioning complete all as directed. Note: Unsv spair parts shall be measured and paid under the respetive items of BoQ.
Opening of pump 3 HP centrifugal for repair and replacement of following u/s parts including re-fixing of all the same and testing and commissioning complete all as directed. Note: Unsv spair parts shall be measured and paid under the respetive items of BoQ.
Supply only in replacement of following defective spare parts of motor of any description/make and capacity 5/7.5 Hp and in any positioin :-
Replacement of gun metal impeller.
Replacement of gun metal bush
Replacement of ball bearing.
Replacement of oil seal
Replacement of gland
Replacement of gun metal impeller for 03 HP
M&L in replacement of fasteners made of aluminium with suitable size for fixing of cooling tower fan blades including nut, bolts etc complete all as specified and directed .
Cleaning of Y type strainer by opening of all nut bolts and removing filter under strainer cleaning the accumulated mud, cooling tower of any capacity, choked nozzles, valves etc complete all as specified and directed .
M&L for fixing cooling tower FRP Type forced draft suitable for AC plant capacity 60 TR along with high speed fan motor and mounting and connection frame along with nut bolt, washer, sprinkler.Complete all as specified and directed .
M&L in replacment MCB TP 63 Amp, 415V, 10 kA complete all as specified and directed .
M&L in replacement of Rotational moulded polyethylene water storage tank capacity 2000 L (cylindrical vertical with closed top) hoisted and fixed in position all as specified and as directed .
M&L in replacment of MCB SP 'C' Curve 6-32 Amp 10 kA complete all as specified and directed .
M&L in replacemenbr of filter dryer strainer suitable for central AC plant of various capacities for installation in suction/chiller/liquid line complete all as specified and directed.
Repairing and overhauling, commissioning and testing of AC compressor suitable for 15 TR at various location of AC plants, comprising of dismantling replacement of unserviceable components including, metaling grinding, polishing and reflux nuts, bolts, washers, assembling the compressor testing on load complete all as specified and directed. Note:-Spare parts/Component will be measured & paid seperately under respective item of BoQ. Model No SM185S4RC of Danfoss or equivalent of Blue Star/Voltas
Supply only under mentioned spare parts for AC plants for maintenance of repair to compressor
Connecting rod
Cylinder liner
Piston
Piston ring
Gajan pin
Suction plates
Suction read and discharge read
Oil pump
Loder assembly
Gasket sets complete
Tyre coupling with lock
Oil filter
Spring section
Spring ducting
Oil seal
Main Bearing
M&L in replacement of fabrication and designing for motor and pump mounting made up of channel MS angle iron, Ms channel, Ms sheet and ensuring the allignment of pump and motor thickness not less than 7 mm Framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc. n exc 10 kg each brackets, conforming to Fe.290.Gde-E-165 (Brackets over 10 kg each to be measured under 'Structural Steel') complete all as specified and directed .
M & L in replacement of Pre - insulated MS pipe dia 65 mm , Class 'C' having thickness of PUF insulation 36 mm of density 36 Kg/Cum and 26 gauge GI claddingcomplete suitable for above ground with all mounting arrangements like clamps with nut bolt , brazing etc. Complete all as specified and as directed.
M & Lin replacement of Pre - insulated MS pipe dia 80 mm , Class 'C' having thickness of PUF insulation 40 mm of density 36 Kg/Cum and 26 gauge GI cladding complete suitable for above ground with all mounting arrangements like clamps with nut bolt , brazing etc. Complete all as specified and as directed.
M & L in replacement of Pre - insulated MS pipe dia 50 mm , Class 'C' having thickness of PUF insulation 36 mm of density 36 Kg/Cum and 26 gauge GI claddingcomplete suitable for above ground with all mounting arrangements like clamps with nut bolt ,brazing etc. Complete all as specified and as directed.
M&L in replacement of inner copper tubing of chiller of capacity 37.5 TR including necessary brazing, welding work complete all as specified and directed. Note:-Dismantling of existing pipeline and miscellineous work required at site, refixing of all water lines, insulation, check leakage, testing and sensors is deemed to be included in quoted rate by Contractor . Make-Bluestar or equivalent ISI Marked.
Supply and fix the following unserviceable accessories of complete central/package type AC plant of capacity upto 100 TR including connecting testing complete all as directed:-
out door unit condensing/AHU motor's fan blade
V Belt of AHU
canvas cloth for linkage as per existing
Phase sequence corrector
Expansion valve as per existing
Anti freeze thermosat
MS Nuts, bolts and washers of various sizes as required.
Compressor oil No-90
S & F in repairs indicator lamps suitable for 3 phase LT panel board/as per sample complete all as specified and directed
M&L in replacement of ampere meter digital type, 415V suitable for existing panel CT operated of range 0-100 as required complete all as specified and directed
M&L in replacement of voltmeter digital type, 415V suitable for existing panel CT operated of range 0-500 complete all as specified and directed
M&L in replacement of MNX/MCX front block 2NO and 2NC complete all as specified & directed complete all as specified and directed
M&L in replacement of terminal block single way suitable for mounting unit complete all as specified & directed.
M&L in replacement of panel mounted ON/OFF push button with contact block. complete all as specified and directed
M&L in replacement of CT 50/5 complete all as specified and directed
M&L for fixing in replacement of butterfly valve 50mm dia with CI body ,SS Disc ,nitrile rubber seal & O ring ,PN 1.6 Pressure rating comlete all as specified by Engr-in-Charge against replacement of the existing one, complete all as specified and as directed.
M&L for fixing in replacement of butterfly valve 65mm dia with CI body ,SS Disc ,nitrile rubber seal & O ring ,PN 1.6 Pressure rating comlete all as specified by Engr-in-Charge against replacement of the existing one, complete all as specified and as directed.
M&L for fixing in replacement of butterfly valve 80mm dia with CI body ,SS Disc ,nitrile rubber seal & O ring ,PN 1.6 Pressure rating comlete all as specified by Engr-in-Charge against replacement of the existing one, complete all as specified and as directed.
M & L in replacement of Earthing complete with galvanised steel earth plate electrode, 600x600x6mm thick, buried directly in ground vertically to depth not less than 1.5 meters below normal ground level, connected to galvanised iron earthing strip 25x4mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, CGI watering pipe 15 mm bore light grade with funnel and wire mesh, PCC chamber in cement concrete 1:3:6 type c1, 80mm thick pre-cast RCC 1:2:4, type B-1 cover reinforced earth plate surrounded by alternate layers of packed charcoal, salt oacked which shall not be less than 15cm in all side of earth plate complete all as shown in electrical plate No 3 of MES schedule Part-I.specified and directed by Engr-in-charge .
supply ,Fixing and testing of MS pipe of size 50mm class 'C ' complete all as specified and directed.
supply ,Fixing and testing of MS pipe of size 65mm class 'C ' complete all as specified and directed.
S&F submain wiring with unsheathed multi-stranded copper conductor cable 1100 V grade drawn through in and including PVC Rigid conduit medium grade of size not less than 20 mm dia with conduit accessories and concealed in wall /surface of ceiling for two runs of 4 Sqmm single core FRLS Grade and one run of 4 Sqmm PVC insulated copper conductor for earth continuity between Main DB to Submain DB/AC plug pints complete all as specified and directed. Note: (i) Two Run of Single core with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasses in wall complete. (ii)Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit and making good the disturbed surface with existing treatment.
M&L for detecting the fault of LT Panel board of AC Plants by providing skilled tradesmen & helper with necessary safety and working equipment such as multimeter ,speedometer and other required tools and rectified the defects including replacement of copper wiring of existing size cable and testing of interlocking system complete all as specified and directed by Engr-in-Charge Note :If the Contractor fail/delay to rectify and replacement of defective parts same day ,they shall fine @1% per day of the quoted rate
Pressure testing for entire system of the following AC plant of all three set of condenser, compressor and circulating system with CO2/Nitroge n gas and retain to allow the pressure for three days. If any leakage in found or reduction in the scale of pressure shall be located and arrest the leakage immediately by soldering or an appropriate measure are to be taken to stop the leakage permanently for the AC plant of the following capacity complete all as specified and directed
S&F in replacment PVC eliminator and PVC fins (honey comb) from cooling tower of capacity complete all as as specified and directed for following capacity:-
Schedule of Credit
M/S S.K.Electricals
M/s Prakash Enterprises
M/S Anand Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .