Providing Supplying Installation Testing and Commissioning of 30kWP Solar PV On Grid Coonected System at Water Treatment Plant
2026_DMA_1284118_1
TenderNoticeNo.17/2025-26
Open Tender
Solar Power Plants
Percentage
120 days
Pipalnar
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,180
₹33,500
21 Oct 2026
5 Mar 2026
13 Mar 2026
5 Mar 2026
12 Mar 2026
5 Mar 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying and erecting mains with 4x16 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No WG-MA/BW(1-3-10) | 205 | M | 762.3 | ₹1,56,271.5 |
| 2 | Supplying, installing, testing and commissioning of 30 kWp ON-GRID Solar PV System / Plant consisting Solar PV Poly Crystalline Panel (335 Wp X 90 Nos.) and Solar ON-GRID Inverter of similar capacity (THD<3%) with interconnecting wires / cables up to solar ON GRID inverter, proper base plate, canopy box to house Inverter and necessary accessories i.e. ACDB/ DCDB , MCB etc. wiring up to solar Inverter in casing and capping, display board, sign board, two distinct earthing, lightning arrester, liaisoning charges, remote monitoring system with maintaining card / chip for 5 years including net charges for RMS System, complete up to net meter installation and export to the grid with 5 year ON-SITE warranty and fully comprehensive maintenance contract as per Specification no. ESD-RT-ONG. (4-5-6)[{1228770+(5 x 58720)} x 1.1]= 1674607.00 | 1 | Each | 16,74,607 | ₹16,74,607 |
| 3 | Providing & erecting 4 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB (5-5-1) | 2 | Each | 7,007.88 | ₹14,015.76 |
| 4 | Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes panel boards etc. including cutting bending drilling welding riveting treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.(6-1-1) | 670 | kg | 273.9 | ₹1,83,513 |
| 5 | Supplying and erecting iron work sheet metal work consisting of CRCA sheets various sections of iron plates chequered plates rods bars MS pipes etc. for panel board or any other purpose with bending cutting drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears authority.(6-1-19) | 3,250 | kg | 204.6 | ₹6,64,950 |
| 6 | Supplying and erecting self-locking arrangement with keys in duplicate, made of brass of grade 1 compliance to IS 729-1979 duly erected, flush with surface of panel /cupboard(6-1-20) | 30 | Each | 319 | ₹9,570 |
| 7 | Supplying and erecting LT CT multifunction DLMS compliance energy meter of accuracy of class 0.5 3x240V,50 Hz with optical & RS 232 port, backlit LCD, measure & display trivector energy, load survey, TOD, tamper detection & logging, power ON/OFF events, instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box and connected to CTs.(6-3-5) | 1 | Each | 11,804.1 | ₹11,804.1 |
| 8 | Supplying and erecting AC three phase LT CT multifunction net meter DLMS compliance of accuracy class 0.5, 3 x 240V, 50Hz, with backlit LCD display, optical port & RS 232 port (measures import kWh, kVAh, export kWh, kVAh, Net kWh, kVAh, V, I, kW, 6 months history of energy, load survey, TOD, tamper detection & logging, power ON/OFF events, instantaneous parameters of rating 1/5A with display in absence of power) with. wiring connections and mounting hardware on provided panels complete with calibration certificate from manufacturer.(6-3-14) | 1 | Each | 16,282.2 | ₹16,282.2 |
| 9 | Supplying and erecting LT current transformer with bar primary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with test certificates. (6-5-2) | 6 | m | 1,129.7 | ₹6,778.2 |
| 10 | Supplying and erecting LED type indicating pilot lamp with LED colours red / yellow / green, 230/250V on provided box / panel with necessary material, wiring & connections etc.(6-5-5) | 2 | M | 272.8 | ₹545.6 |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.39 MB
BOQ_2208382.xls
BOQ • 0.33 MB
B1-Solar.pdf
Tender Documents • 0.77 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .