Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹21.8 CrAccepted-AOC SITANI BUILDING DINBAZAR JALPAIGURI 735101 | JALPAIGURI | JALPAIGURI | WEST BENGAL | 735101 | ₹21.8 Cr | L-1 | Accepted-AOC L-1 Bidder. |
| 2 | L-2₹23.6 CrRejected-Finance HOUSE OF RAJ KUMAR GOEL PO MATELLI MATELLI BAZAR JALPAIGURI | MATELLI BAZAR | JALPAIGURI | WEST BENGAL | ₹23.6 Cr | L-2 | Rejected-Finance Rejected. Other than L-1. |
| 3 | L-3₹26.2 CrRejected-Finance | ₹26.2 Cr | L-3 | Rejected-Finance Rejected. Other than L-1. |
| 4 | Rejected-Technical | - | - | Rejected-Technical Rejected. Being the firm has not executed similar work as per list of work submitted and not submitted details of works completed and under progress in MES. |
Tender Value
₹20.3 Cr
EMD Value
₹15 L
Closing Date
14 Jan 2025, 6:00 pmClosed
CE SILIGURI ZONE
HQ CE SILIGURI ZONE, MES, SEVOKE ROAD, PO SALUGARA, DIST JALPAIGURI, PIN 734 008 (WB)
PROVN OF OFFRS MD ACCN AT BENGDUBI MIL STATION UNDER GE (P) SILIGURI
2024_MES_685770_1
98792/BENG/SZ/E8
Open Tender
Civil Works
750 days
Bengdubi
Please refer Tender documents.
8 documents required · 8 mandatory
₹3,000
GE (P) SILIGURI
₹15 L
Yes
HQ CE SILIGURI ZONE, MES, SEVOKE ROAD, PO SALUGARA
4 Apr 2025
26 Nov 2024
21 Jan 2025
26 Nov 2024
14 Jan 2025
31 Dec 2024
26 Nov 2024 - 4 Dec 2024
6 Dec 2024
Amount
BUILDINGS & STRUCTURE (Sch 'A' PART-I)
Lump sum price worked out by the Contractor for “BUILDINGS & STRUCTURE” as listed in Schedule ‘A’ Part-I. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 20,35,50,000.00 inserted by the MES in Schedule ‘A’ Part-I.
EARTHWORK, SITE CLEARANCE AND SITE DEVELOPMENT (Sch 'A' PART-II)
Lump sum price worked out by the Contractor for “EARTHWORK, SITE CLEARANCE AND SITE DEVELOPMENT” as listed in Schedule ‘A’ Part-II. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 15,99,306.61 inserted by the MES in Schedule ‘A’ Part-II.
INTERNAL WATER SUPPLY (Sch 'A' PART-III)
Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part-III. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 14,28,216.34 inserted by the MES in Schedule ‘A’ Part-III.
INTERNAL ELECTRIFICATION (Sch 'A' PART-IV)
Lump sum price worked out by the Contractor for “INTERNAL ELECTRIFICATION” as listed in Schedule ‘A’ Part-IV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 61,18,427.31 inserted by the MES in Schedule ‘A’ Part-IV.
ROAD, PATH, CULVERT & HARDSTANDING (Sch 'A' PART-V)
Lump sum price worked out by the Contractor for “ROAD, PATH, CULVERT & HARDSTANDING” as listed in Schedule ‘A’ Part-V. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 78,63,894.93 inserted by the MES in Schedule ‘A’ Part-V.
SEWAGE DISPOSAL (Sch 'A' PART-VI)
Lump sum price worked out by the Contractor for “SEWAGE DISPOSAL” as listed in Schedule ‘A’ Part-VI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 3,92,548.04 inserted by the MES in Schedule ‘A’ Part-VI.
AREA DRAINAGE (Sch 'A' Part-VII)
Lump sum price worked out by the Contractor for “AREA DRAINAGE” as listed in Schedule ‘A’ Part-VII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 27,12,948.52 inserted by the MES in Schedule ‘A’ Part-VII.
CHAIN LINK FENCING AND STEEL GATE (Sch 'A' PART-VIII)
Lump sum price worked out by the Contractor for “CHAIN LINK FENCING AND STEEL GATE” as listed in Schedule ‘A’ Part-VIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 16,26,551.87 inserted by the MES in Schedule ‘A’ Part-VIII.
EXTERNAL WATER SUPPLY (Sch 'A' PART-IX)
Lump sum price worked out by the Contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part-IX. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 1,60,485.96 inserted by the MES in Schedule ‘A’ Part-IX.
EXTERNAL ELECTRIFICATION (Sch 'A' PART-X)
Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIFICATION” as listed in Schedule ‘A’ Part-X. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 12,78,702.22 inserted by the MES in Schedule ‘A’ Part-X.
FIRE FIGHTING & FIRE ALARM SYSTEM (Sch 'A' PART-XI)
Lump sum price worked out by the Contractor for “FIRE FIGHTING & FIRE ALARM SYSTEM” as listed in Schedule ‘A’ Part-XI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 13,34,183.00 inserted by the MES in Schedule ‘A’ Part-XI.
STP (Sch 'A' PART-XII)
Lump sum price worked out by the Contractor for “STP” as listed in Schedule ‘A’ Part-XII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 2,29,673.74 inserted by the MES in Schedule ‘A’ Part-XII.
LIGHTNING PROTECTION (Sch 'A' PART-XIII)
Lump sum price worked out by the Contractor for “LIGHTNING PROTECTION” as listed in Schedule ‘A’ Part-XIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 3,96,960.60 inserted by the MES in Schedule ‘A’ Part-XIII.
DG SET (Sch 'A' PART-XIV)
Lump sum price worked out by the Contractor for “DG SET” as listed in Schedule ‘A’ Part-XIV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 1,01,086.50 inserted by the MES in Schedule ‘A’ Part-XIV.
SOLAR HOT WATER (Sch 'A' PART-XV)
Lump sum price worked out by the Contractor for “SOLAR HOT WATER” as listed in Schedule ‘A’ Part-XV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 15,81,393.58 inserted by the MES in Schedule ‘A’ Part-XV.
LIFT (Sch 'A' PART-XVl)
Lump sum price worked out by the Contractor for “LIFT” as listed in Schedule ‘A’ Part-XVl. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 90,874.80 inserted by the MES in Schedule ‘A’ Part-XV.
MISCELLANEOUS ITEMS REQUIRED FOR B/R & E/M SERVICES (Sch 'A' Part-XVI)
SITE CLEARANCE AND SITE DEVELOPMENT Bringing approved earth (as approved by Garrison Engineer) from sources outside defence land including all cost such as royalty if any, transportation, taxes if any etc. complete all as specified and directed. NOTE :- (a) Earth required for the item shall be supplied by contractor from outside of MOD land of any lead, at his own arrangement. (b) All cost of procurement of earth including cost of transportation, compaction royalties, tax etc shall be deemed to be included in the unit rate quoted by the contractor. (c) With reference to Clause 3.6 of MES Schedule Part-II on Serial Page No. 21, it is clarified that measurement of the above item shall be of finished embankment / traverse of filled earth after consolidation / compaction and 10% deduction shall be made from measured and calculated volume to allow for increase in bulk. (d) Total quantitiy / partial quantity of earth may not be available in Bengdubi Area. The contractor shall bring the earth outside area and it is advised to quote the rate considering available of soil and its lead involved.
INTERNAL WATER SUPPLY S & F two way bib cock, chromium plated, with all flange quarter (Low-flow) 16 mm bore complete all as specified and directed.
S&F 16 mm bore chromium plated mixer (wall / table mounted) complete all as specified and directed.
S&F bib cock, chromium plated, with all flange quarter turn (Low-flow) 16 mm bore complete all as specified and directed.
S&F hand shower (health faucet) with 1 meter long easy flex tube in chrome finish and wall hook with NRV (Back flow preventor) complete all as specified and directed.
S&F angular stop cock 15 mm bore of pipe (16 mm outer dia) with wall flange chromium plated stop valves complete all as specified and directed.
S&F overhead shower 140 mm round shape single flow with air effect (ABS & face plate chrome plated) with rubit cleaning system 16 mm dia, with shower Arm Casted 120 mm long heavy body round shape for wall mounted showers with wall flange complete all as specified and directed.
S&F wall mixer with provision for overhead shower, chromium plated, with 115 mm long bend pipe on upper side, connecting legs & wall flanges complete all as specified and directed.
INTERNAL ELECTRIFICATION S & F modular type 3/5 pin socket outlet incl plug top 16A controlled by switch 16A including sheet metal enclosure suitable for Geyser point complete all as specified and directed.
Supplying and fixing of Modular type RJ-11 telephone socket outlet in the modular metal flush box and cover plate including concealed 25 mm PVC conduit in wall/ceiling/fixed to roof, connections etc complete all as specified and directed.
Supplying and fixing of Modular type TV socket Co-axial outlet 1 Module in the modular metal flush box and cover plate including concealed 25 mm PVC conduit in wall/ceiling/fixed to roof, connections etc complete all as specified and directed.
S & F Decorative wall light fixture made up of Polycarbonate, suitable for 9 W retrofit LED Lamp B22 base with LED lamp of 9W, 950 lm, 6500K including connecting up with three core twisted flexible copper conductor cable with complete all as specified and directed.
S & F 2-star (EEL) LED lamp 5W capable to output 501 lm with lamp holder B22 type complete all as specified and directed.
S & F Wall mounted fan, oscillating and tilting type, speed not less than 1350 RPM, AC , single Phase 230V of size 400mm sweep complete all as specified and directed.
S & F TPN DB 6 way (Vertical type) , double door, metallic distribution board, conforming to IEC 61439-3, suitable for flush / surface mounting with provision for FP RCCB / RCBO /MCCB as incomer and SP/TPN MCBs as outgoing, reversible metal door, 100 A copper busbar, fully shrouded neutral bar, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified and directed.
S & F SPN DB with sheet metal enclosure 240 volts, 6 way, Single phase, double door with copper bus bar neutral link, earth link, earthing studs, without MCBs complete all as specified and directed.
S & F MCCB 80Amp, 4P, 415V, 25KA complete all as specified and directed.
Supply and fix Hot Press Molded SMC meter box of size not less than 380mm x 225mm x 140mm for accommodating 01 No of three phase pre-paid energy meters including cutting the wall surfaces for flush mounting of meter box and making good to match with the existing surface all as specified and directed.
Supply, fixing, commissioning and Design verified as per IS /IEC-61439-1&2 LT Panel, indoor type LT Panel Box by CPRI Approved manufacturers with comprising of the following :- Fabrication Details : Main frame 2 mm thick CRCA sheet, partition sheets / covers / doors of 2 mm thick CRCA sheet, base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom for installation, seperate chambers for Main Bus Bars, switch Gears and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for doors and locking arrangements with Aldrops at front and Back complete all as specified and directed. Bus bar details : Material shall be Copper bus bar 600Amp rated (3P+N), sleeving heat shrinkable type, with bus bar sizes for phase of rated capacity and bus bar shall extended type be support of epoxy type insulators for connection , earthing of 40x6 mm GI Flat complete all as specified and directed. Painting Detais : Painting shall be 7 tank processed powder coated shall be a dry finishing process that uses finely ground particles of pigment and resin based polymer that are electrostatically charged and sprayed onto electrically grounded parts complete all as specified and directed. Item Continued as Srl No. 17.20
Wiring : Pannel wiring shall be of 2.5 sq mm copper standard with 5A MCB wiring for control wiring and indication lamps complete all as specified and directed. Accessories for Panel Box : Digital Multifunctional Meters CT/PT programmable with RS 485 communication port CL 0.5 with direct acess to basic power and Energy parameters and Three phase Indication Lamps (LED) - 01 Set No. make: L&T or equivalent in Secure /Elmeasure complete all as specified and directed. Incoming :- (a) MCCB 400 Amps rating 415 Volts ,4 pole ,36 kA (Ics=100%icu) with adjustable thermal & magnetic release (80-100%) & earth fault protection-01 No (I/C) (b) Indicating lamp RYB -01 Set (Set of three) Outgoing:- (a) MCCB TP, 80 Amp, 415 Volts , 25 kA (Ics=100%icu) with adjustable thermal & magnetic release (80-100%) & earth fault protection - 07 Nos (O/G) : (01 No for each floor & 01 No spare) (b) MCB SPN 16 Amps, 10 kA -05Nos (For gound floor DB-04 Nos, 01 No spare ) (For ground floor) NOTE : Rate quoted includes for necessary PCC foundation / steel angulars/ channels to LT pannel and includes the cost of all Accessories and switch gears, necessary cable connections with Lugs, washers nut bolts and cable glands as per site requirement complete all as specified and directed.
ROAD, PATH, CULVERT & HARDSTANDING M&L for 3.00 mm thick painting to road surfaces as in lines, dashes, arrows, letters, zebra cross etc, in white/yellow color, on roads, pavements and the like etc with reflactive thermoplastic road marking paint @ 5 Kg/Sqmm and applying glass grit @300 gms/sqm over opainted surfaces while the painting surfaces are hot including cleaning surfaces complete all as specified and directed. NOTE : Painting to road surface shall be carried out through mechanical application by the approved applicator of manufacturers instruction.
Supply and installation of Raised Pavement Marker (RPM) with polycarbonate lens electronically welded with the RPM body. The marker shall be scratch proof and abrasion resistant microprismatic polycarbonate lens with polycarbonate reflective panels with dual prismatic cubescapable providing total internal reflection. Dimension:- The dimension of the marker is height 15.88mm, width 101.6mm, length 89.2mm. The marker conforms to ASTM D4280 and is in accordance with MOSRTH circular reference No. RW/NH 33023/10/97-DO III dated 11 June 1997. Marker shall be fixed with adhesive and no nails shall be used to affix the marker and shall be marked with manufacturer name complete all as specified and directed.
SEWAGE DISPOSAL M&L for 150 mm bore DWCPE (SN-8) pipes with all fittings and laid in trenches and jointed complete all as specified and directed.
EXTERNAL WATER SUPPLY Supply & Laying duclite iron (DI) pipe SS class K-7 laid in trenches under floor / walls / columns etc. of bore size 100 mm, including rubber gasket push on joints complete all as specified and as directed.
S&F ductile iron fitting/flange/SS/bend/reducer 80 to 200 mm dia of different size as required at site and directed.
M&L for construction of brick masonary valve pit of intemal dimensions 900mm x 900 mm x 900 mm complete and fabrication of 3.15 mm thick MS Sheet cover and angle iron frame made out of 40mm x 40mm x 6 mm MS angle iron and one side provided with hinge with locking arrangement & duly painted with two coats of black bituminous paint over a coat of red oxide primer induding necessary earth work and PCC work complete all as specified and as directed.
M&L for construction of brick masonary valve pit of intemal dimensions 600mm x 600 mm x 600 mm complete and fabrication of 3.15 mm thick MS Sheet cover and angle iron frame made out of 40mm x 40mm x 6 mm MS angle iron and one side provided with hinge with locking arrangement & duly painted with two coats of black bituminous paint over a coat of red oxide primer induding necessary earth work and PCC work complete all as specified and as directed. Note:- 02 Nos for External water supply and 03 Nos for STP work.
Supply and install testing and commissioning of horizontal monoblock centrifugal pumping Set with suitable capacity motor with copper winding, voltage range 350 to 440 volts, AC 3 Phase, IP 55 Protection, Insulation class 'F', Mechanical sealing, CI motor and Pump body, SS Pump Shaft, cast Impellar mounted on heavy duty bearing alongwith suitable for continuous operation with non-over loading power characteristics for frequent start/stop operation minimum head 36 Mtr and having capacity to discharge water minimum 450 LPM complete with suction and discharge duly mounted on MS frame on foundation / platform grouted with MS bolts, nuts of required size properly connected with suction and delivery water line complete all as specified and as directed including GI Suction pipe medium grade of dia as per suction size of Pump - 04 RM (not exc) for each Pump. The pump and motor shall comply to all the requirements of relevant IS (1W +1S) complete all as specified and as directed.
Supply, install, testing & commissioning of Air release valve, Cast iron, double air outlet, flanged ends,conforming to IS- 14845, 100 mm bore connected to the main line including all jointing materials as required complete all as specified and as directed.
Supply, installation, testing & commissioning CI Foot Valve conforming to IS 4038, 65 mm dia all as specified and directed.
Supply and fixing Strainer Y type conforming to IS, size 65 mm dia all as specified and directed.
Supply, install, testing and commissioning of indoor cubical type LT Control Board, factory fabricated CPRI type tested with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-43 & general construction confirming to IS-13947, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & tinned copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB rating. The panel board shall be fabricated out of 2.0 mm thick CRCA sheet duly pre-treated & powder coated, supporting frame made out of 50 x 50 x 6 mm angle iron suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl PCC platform/plinth of suitable size complete all as specified & as directed with & incl the following accessories :- (Pump House panel) BUSBAR AND INTERNAL CONNECTION : The busbar shall be made up of 04 Nos Copper busbar 100A rated duly insulated with 1100 V grade standard colour coated PVC sleeves and rigidly mounted on suitable sized 'F'class insulators of non hygrosopic, all internal connections from main busbar to switch gear etc. PROVISION FOR CABLE ENTRY; The provision for cable entry/exit shall be provide in the bottom for both incoming and outgoing cables. Item Continued as Srl No. 17.33
EXTERNAL ELECTRIC SUPPLY Supply, installation, testing and commissioning Compact Sub Station (CSS) complete all as specified comprising of the following equipments :- (A) OUTDOOR ENCLOSURE: Outdoor type enclosure having construction of galvanized steel sheet of thickness 2mm. The enclosure shall have IP 54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for transformer compartment. The enclosure shall be powder coated as per approved colour. Each compartment will be provided with door and pad locking arrangement. The compartment illumination lamp with door operated switch shall be provided in each compartment. (B) HT SWITCHGEAR: (i) HT 11 kV, 630 Amps, 350 MVA, 21 kA for 3 secs, SF6 insulated Non-extensible Compact Switchgear consisting of 01 No. fixed manual Vacuum Circuit breaker as Incomer and 01 No. manual load break switch as Outgoing and 01 No. fixed manual Vacuum Circuit Breaker as Outgoing with microprocessor based self powered relay in SF6 insulated stainless steel enclosure, with series trip, self powered microprocessor based numerical over current relay (IDMT + Inst) protection along with Class 1.0 Metering with interconnection between HT switchgear and transformer with Cable 95 sqmm 3 Core aluminium unarmoured XLPE cable - 01 Set Item Continued as Srl No. 17.35 to 17.38
(ii) 11 kV single phase indoor resin cast PT of ratio 11 kV/rt 3/110 V/rt3, lass 0.5-3, Burden 5VA - 50VA, insulation level 28/75 kV, voltage factor 1.2 const and 1.9 for 30 sec, conforming to IS-3156 - 01 Set. (iii) 11 kV single phase indoor resin cast CT of appropriate ratio as per manufactrurer's design, based on load, class 0.5, 5P10, Burden as per manufacturer's design, insulation level 28/75 KV, as per IS-2705 - 01 Set. (C) TRANSFORMER: (i) 200 KVA, 11 kV/433 V, Dyn11, 3 phase, copper wound insulation class 'F', Natural Air Cooling Cast Resin Dry Type Transformer with off circuit link +5% to -5% @ 2.5 % on HT side of transformer with WTI scanner with Alarm and trip contact and other standard accessories - 01 No.
(D) LT PANEL: 600 Amps rated aluminium bus bar for three phase and neutral with PVC sleeves supported on insulators - 04 Nos INCOMING :- (i) MCCB FP, 400 Amps rating, Ics=100%Icu, 50 kA breaking capacity, adjustable thermal magnetic release - 01 No OUTGOING :- (i) MCCB FP, 320 Amps rating, Ics=100%Icu, 36 kA breaking capacity, adjustable thermal magnetic release - 02 Nos ( 01 No Spare) (ii) MCCB FP, 160 Amps rating, Ics=100%Icu, 25 kA breaking capacity, adjustable thermal magnetic release - 02 No. ( 01 No Spare)
Supply and fixing 8.0 Mtr Long Hot Dip Galvanised Street Light Octagonal Pole with Foundation type Base Plate and Foundation Bolts and additional structural steel as reqd, dimentions of Pole as Top Diameter - 70 mm, Bottom Diameter- 130 mm, Section Length - 8000 mm, Thickness - 3 mm, Foundation type Base Plate (200 x 200 x 16 mm), Foundation Bolts - 4 Nos 20 mm dia, pitch circle dia 200 mm, bolt length 600 mm, projects bolt length 100 mm , with Single type arm bracket 1500 mm long , top dia 70 mm , suitable for LED Street Light fitting. The Pole shaft shall have octagonal cross section and continuously tapered with single longitudinal welding all as specified and as directed.
OUTGOING :- (a) MCCB 4P of capacity 25 to 63 Amp 16 KA breaking capacity, Ics=100%Icu, adjustable thermal magnetic release- 04 Nos( 1 No spare), 415 Volts, 50 Hz, 3 phase (b) MCB TPN , 415 VOLTS 6 to 32 Amps -02 Nos (c) MCB SPN 10KA , 230 VOLTS 6 Amps -2 Nos (d) Astronomical Time switch with MCCB/MCB and suitable capacity contactor for auto/manual operation- 01 Set. (e) Danger notice plate of size25 x 20 cm of 1.6 mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal-red color and fixed with MS clamp and bolt and nuts of approved size for LT conforming to lS:2551 complete-02 Nos
Supply and Fixing Aviation obstruction light, Integral LED Aviation light comprising of Aluminium housing with Red Polycarbonate dome, integral driver, ingress protection IP-65, inbuild surge protection, 60 Watts, input voltage range 100-270 Volts AC all as specified and as directed.
M&L for cable route marker made up of PCC block (1:3:6) type. C-1 using 20mm graded stone aggregated of size 900 mm x 300mm x 100 mm thick (45 Cm burried in ground) and properly painted as per approved colour Brown/Blue (HT/LT) and written both side with signed red colour paint ( HT cable 11/33 KV or LT cable 1100 Volts) on route marker including necessary excavation and earthwork complete all as specified and as directed. NOTE : (i) The spacing between two consecutive cable route indicators shall not be more than 50 meters & also shall be provided at each & every bend or corner. (ii) PCC will be measured and paid separately
M&L Horizontal boring ultrasound technic /any other suitable mechanical means at approx 1 mtr bellow the raw/pavement /hard standing etc without dammaging the existing surface geting out and disposal of soil to a distance not exceeding 50 mtrs from the site of work complete all as specified and directed.
FIRE FIGHTING & FIRE ALARM SYSTEM Supply, install, testing and commissioning of " Out door type" LT Distribution Board of suitable size factory fabricated CPRI type tested with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 and general construction , front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB rating. The panel board shall be fabricated out of 3.15 mm thick CRCA sheet duly pre-treated & powder coated, supporting frame angle iron suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring incl cable glands of suitable sizes incl PCC platform/plinth of suitable size complete all as specified & as directed with & incl the following accessories : (Fire Panel) BUSBAR AND INTERNAL WIRING : The busbar shall be made up of 04 Nos Copper busbar 100A rated duly insulated with 1100 V grade standard colour coated PVC sleeves and rigidly mounted on suitable sized 'F'class insulators of non hygrosopic, all internal connections from main busbar to switch gear etc. PROVISION FOR CABLE ENTRY: The provision for cable entry/exit shall be provide in the bottom for both incoming and outgoing cables. Item Continued as Srl No. 17.48
Supply, install, testing & commissioning of Air release valve, Cast iron, double air outlet, flanged ends,conforming to IS- 14845, 100 mm bore connected to the main line including all jointing materials as required complete all as specified and as directed.
Supply and fixing fire extingusiher, Dry Chemical Powder, ABC type 6.00 kg Capacity complete with initial charge and wall bracket BIS and BSEN standard complete.
S&F for CO2 fire extinguisher consisting of welded MS cylindrical body, squeeze lever discharge valve fitted with internal discharge tube, 30 cm long high pressure discharge hose, discharge nozzle, suspension bracket, confirming to IS:934 finished externally with red enamel paint and fixed to wall with bracketswith rawl plug/dash fasteners complete with internal charge capacity 4.5 Kg ISI marked 4.5 litres capacity complete all as specified and directed.
Supply and fixing Fire Extinguisher Water Stored Pressure Type 9.0 Ltr capacity BIS standard complete.
Supply and fixing Fire Extinguisher Mechanical Foam Type 9.0 Ltrs capacity BIS standard complete.
S&F auto-illuminated (glow-in-dark) exit sign board with red colour background with appropriate symbol, made up of acrylic sheet for fire escape in minimum 10 cm x 30 cm size to be pasted on wall with high quality adhesive or to be hanged with s.s. hook-chain system all as specified.
Supply and fixing rechargeable type ceiling/wall mounted Escape lighting showing exit sign in green colour provided with in-built battery suitable to provide minimum 90 min contineous lighting after power cut all as specified..
Supply and fixing Fire Bucket 09 Ltrs made of iron with high functionality, able to withstand very high temperature with ring handle all as speified.
Supply and fixing XLPE insulated heavy duty FRLSH copper ammoured conductor 2.5 Sqmm 6 Core, with working voltage 1100 volts conforming to IS: 1554 part -I, all as specified and as directed. (From Control panel to Jockey pump)
STP Design,supply, Install,Testing and commissioning of MBBR technology Package Sewage Treatment Plant of capacity 50 KLD with FRP underground packege sewage treatment plant along with the followings incl all connecting piping network, required valves,pressure gauge and sensors, gates,drains, pathways sludge dry bed and all other accessories as per OEM, all necessary civil work for installation complete as per relevant IS & WHO norms as applicable including spare parts for 2 years of operation, etc. complete as turnkey job with all duties and taxes complete. The STP should achieved the desired parameters. (i) Bar Screen Chamber and Bar Screen - 01 No (ii) Raw Sewage Pump of required Cap - 02 Nos (01 W + 01 S) (iii) MBBR Tank with MBBR media - 02 Nos (iv) Tube settler (v) Filter Feed Pump of required Cap - 02 Nos (01 W + 01 S) (vi) Treated Water Pump of required Cap - 02 Nos (01 W + 01 S) (vii) Air Blower of required Cap with Air piping - 02 Nos (01 W + 01 S) (viii) RCC Collection Tank 17 KL Cap (ix) Settling Tank Cap 11 KL (x) Intermediate Tank Cap 15 KL (xi) RCC Treated Water Tank Cap 15 KL (xii) Blower Room 03 Mtr x 03 Mtr x 03 mtr (xiii) Activated Carbor Filter, FRP - 01 no (xiv) Pressure sand Filter, FRP - 01 No (xv) Disinfectant dosing System (xvi) Centrifuge - 02 Nos (01 W + 01 S) (xvii) Back wash Pump- 02 Nos (01 W + 01 S) Item Continued as Srl No. 17.59 to 17.61
(a) Inlet parameter (i) PH : 6.5-8.5 (ii) BOD : < = 200-250 mg/Lit (iii) COD : <= 350 mg/Lit (iv) TSS : < 250 -300 mg/Lit (v) Total Nitrogen : 50 mg/Lit (vi) Phosphorus (Total) : 7.0 mg/ltr (vii) Temperature : Ambient (viii) Coliforms (Faecal) : 10 5-10 6 /100 ml (ix) Oil and Grease : 20-30 ml /Ltr (x) Chlorides and Sulphates : As per water sample (xi) Heavy Metals : Nil (xii) Colour and odour : Actual (xiii) TDS : As per water sample (xiv) Turbidity : As per water sample (xv) Residual Chlorine : As per water sample (xvi) Odour : As per water sample
(b) Outlet Parameter (i) PH : 6.5-8.5 (ii) BOD : <10 mg/Lit (iii) COD : <As arrising (iv) TSS : <10 mg/Lit (v) Total Nitrogen : < 10 mg/Lit (vi) Phosphorus (Total) : 2.0 mg/Ltr (vii) Temperature : Ambient (viii) Coliforms (Faecal) : Nil (ix) Oil and Grease : 10 mg /Ltr (x) Chlorides and Sulphates : As arising (xi) Heavy Metals : Nil (xii) Colour : Colourless (xiii) TDS : 2100 mg/Ltr (xiv) Turbidity : Less than 2 NTU (xv) Residual Chlorine : Greater Than 1 PPM (xvi) Odour : No foul odour (xvii) Nitrate Nitrogen as N : 10 mg/Ltr (xviii) Acidity : As arising (Also refer imp notes below).
Supply and install Pumping sets, centrifugal, electric driven complete 210 LPM, 37 mtr Head, electric driven 415 volts,50 Hz inclusive duly mounted on MS frame on foundation / platform grouted with MS bolts, nuts of required size properly connected with suction and delivery water line complete all as specified and as directed.The pump and motor shall comply to all the requirements of relevant IS (1W +1S) (Treated water pump)
Supply, installation, testing & commissioning Foot Valve conforming to IS 4038, 50 mm (2”) dia all as specified and directed.
Supply and installation of nonclog submersible pump set with electric driven motor complete of capacity upto 5/5.5 HP, 415 Volts, 3 Phase, 50 Hz, 2900 RPM Head 9-18.5 Mtr, LPM 1200 at 9 mtr head and 400 at 18.5 Mtr head delivery pipe size 100 mm complete all as specified as directed.
S & F flat submersible cable 3 core multi standard copper conductor PVC insulated, water proof, ISI marked of size 6 sqmm for connecting from starter to bore well submersible pump sets complete all as specified and as directed.
Supply, Installation and commissioning CPRI type tested factory made LT panel board cubical outdoor type, dust and vermin proof pedestal type suitable for AC 500 V fabricated out of 3.15 mm thick CRCA sheet and supported by 50mmx50mmx6mm MS angle iron frame work including front and back hinged door shutter with locking arrangement including embedded in PCC (1:3:6) and suitable opening with cable gland for incoming and outgoing cables, prewired by approved quality copper wires and copper bus bars proper ratings and cables lugs of suitable size including two coats synthetic enamel paint over one coat red oxide primer to accommodate the following accessories complete all as specified and as directed. (Panel E) Item Continued as 17.68
(a) Copper bus bar TPN 150A for phase and neutral for main bus bar and incoming cable entry bus. (b) MCCB-63 Amp current rating AC 415 Volt, 3 Phase 4 pole, 50 Hz with adjustable thermal magnetic release setting 80% -100% and breaking capacity 25 KA-01 Nos (As Incomer). (c) MCB 32A-415 Volt 50 Hz TP-02 Nos. (As outgoing) (d) Star Delta Starter fully Automatic suitable for 5/5.5 HP submersible pump 415 Volt, 50 Hz-02 Nos (e) 3 Phase digital voltmeter-01 Nos (f) 3 Phase digital type ammeter 0-30A with CTS-01 No. (g) Single Phase preventer-02 Nos (h) LED Type indicator lamp (Red, Yellow and Blue)
DG SET Supply install testing and commissioning Silent type built in within an acoustic enclosure Diesel Engine driven Generating set water cooled including AMF panel for standby power supply 415 volts, 3 Phase, 4 wire, 50 cycles / sec,0.8 power factor, 82.5 KVA (66 KW) or next higher standard size available KVA,1500 RPM. Self exicited self regulated brushless AC generator installed. The alternator directly coupled to diesel engine, mounted on common base frame & complete with self starter 24/12 volt. Acoustic enclosure suitable for ambient condition at Siliguri area and confirming to condition under IS 10002, 13364 Part I 1992, BS 5514/5000 to meet exhaust emission test as per revised MoEF norms/as per CPCB -IV plus or as per latest. Fuel tank capacity not less than 08 hours fuel requirement & battery as reccommended by OEM battery leads, sound proof canopy etc. with features for automatic shutdown in the event of a circuit failure condition arising from low oil pressure, high coolant temperature, over speed etc. & microprocessor based gen-set controller governor with the following under-mentioned features & all as specified & as directed :- Note :- The capacity of Generator set shall be net after all due derating factors as per relevant IS/BS Standards design. Item Continued as Srl No. 17.70 to 17.81
(A) Alternator :- Standard design alternator rated at 82.5 KVA/ nearest higher available capacity at 0.8 (lag) power factor AC, 3 - phase 4 - wire, 415 volts, 50 Hz, 1500 RPM, self exicited self regulated screen protected drip proof brushless design with winding in pole faces, insulating class 'H' and voltage regulation of + 1% at rated voltage from no load to full load. The alternator shall be confirming to BS 5000, IS: 13364 Part I (1992) and shall be in position to generate supply with frequecy regulation with in + 1% tolerance. The alternator will be suitable for tropical climate and shall generally confirm to BS - 2613/5000/ IS - 4722. (i) Insulation class - 'H' (ii) Temperature rise Class - 'H' (iii) Excitation : Self Excited (iv) Regulation performance: The voltage is kept constant with + 1%. (v) Frequency regulation + 1%
(B) Diesel Engine: - Adequate capacity of Diesel engine water cooled to drive independently above alternator and after considering de-rating as per site conditons after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant IS/BS complete, with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under:- (i) Fly wheel with housing (ii) Cooling system :- Moulded radiator with fan & belts. (iii) Cooling Water pump : - Centrifugal type belt driven.
(iv) Exhaust System :- Exhaust System complete with exhaust piping of suitable dia with MS pipe medium grade. MS Exhaust pipe with bends/flanges and all accessories to be supplied and erected as per OEM recommendation. The Exhaust Pipe shall be insulated with low resin bounded wool of min 75 mm thickness min 144 Kg/m density. The dia/thickness and Stack height of the Exhaust pipe shall be as per OEM recommendation and CPCB norms. The minimum height of Stack to be provided with each gererator set shall be worked out as per CPCB norms. Turbo charger type Exhaust manifold Silencer : Residential type
(v) Fuel System :- Diesel Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by governer electronic operated/ (as recommended by OEM) for 1% speed /frequency regulation. Comprising with Fuel Filters and Fuel Hoses. (vi) Lub oil System :- Comprising of Lubricating oil filter, Lubricating oil pump etc. (vii) Air Intake System :- Air intake Manifold, Air cleaner dry type etc (viii) Governer Electronic type (ix) Starting System :- Electric Self starter with and including battery charging alternator 24 Volts DC. (x) Batteries :- Batteries of maintenance free of capacity 12 V, 180 AH- 01 No complete with copper conductor multistranded leads of suitable length from self starter to the battery terminals complete with initial charge and initial fill of electrolyte all as specified.
Start and stop push button Ignition key / Switch Radiator with blower fan & first fill of coolant oil Corrosion inhibitor coolant (xi) Generator Monitoring Panel : - Comprising of all standard items as per standard manufacturing, iginiton key switch and start / stop arrangement, indications for Engine parametes, hour run meter, RPM meter, Engine oil pressure indicator, water/coolant temperature indicator, Battery volt display. (xii) Safety Controls : - Engine low lube oil pressure, high water temperature and over speeding of engine. (xiii) Coupling arrangement : - Flexible coupling
(xiv) Accessories :- AVM Pads built- in or separtely mounted to manufactrer base frames. (xv) Base Frame : - Made out of ISMC of sturdy design made of MS channel with necessary reinforcement and predetermined holes as per manufacturer. (xvi) Fuel Tank :- Daily service fuel tank made complete on a common base inside the acoustic enclosure as per manufacturer guidelines for min 8 hrs continuous operation. (xvii) MS/Steel flexible pipe line to and from the fuel tank to the DG Set. (xviii) Battery Charger shall be provided as per manufacturer guidelines (xix) The DG Set shall comply to the emission limits requirement as per Govt of India, CPCV-IV plus or as per latest. The DG Set shall be complied with all test requirements as stipulated in the gazette notification. All relevant test results from NABL accredited lab shall be produced.
(b) Digital Volt meter with slector switch of 0 to 500 volts - 1 Set (c) Digital Frequency meter - 1 No (d) Digital KW meter - 1 No (e) Digital KWH meter panel mounted type - 1 No (f) Digital PF meter - 1 No (g) Annuciation with indication lamps for : (i) Low lub oil pressure. (ii) High Water Temparature. (iii) Engine over speed. (iv) Battery low voltage. (v) Over voltage, under voltage and over current (vi) Display shall be alphanumeric LCD display with LED backlight.
Controls and Records:- (a) Load on Indication (b) Load off indication (c) Engine start push button (d) Engine stop push button (e) Fault accept / reset push button (f) Battery Charger shall be provided as per manufacturer guidelines (g) Suitable to provide a record of most recent fault conditions & fault history. (h) Complete alternator data viz, voltage ph - ph, ph - neutral, KVA , frequency etc. (j) Complete engine data viz, starting battery voltage, engine temp, engine runnning hours, engine oil pressure etc. (k) Control incl provn of service adjustment & calibration of DG control functions.
(D) Civil Works :- All civil works including PCC platform and related foundations including for panel and equipments including making good of distrubed area during installation and commissioning of genset. The depth and size of the foundation and PCC as recommended by the manufacturer. Note:- The contractor shall arrange for artificial load for testing of DG Set at site and the cost is deemed to be included in the above offer. (E) Acoustic Enclosure:- Manufactured by OEM suitable for 82.5 KVA DG Set. (i) Tested by NABL approved lab as per CPCB (ii) It Should be as per latest rules and regulations of Ministry of Environment and Forest and Pollution control board. (iii) The generating set battery should be inside the enclosure.
(iv) Fuel tank should be inside the enclosure, however, the fuel storage shall be enough for 8 hrs continuous operation. If required contractor may arrange outside fuel storage capacity to achieve this (v) Construction Details/specification are as follows : - (a) Outer body :- CRCA Sheet of 1.6mm thick. (b) Doors :- CRCA sheet of 1.6 mm thick (c) Sound Insulation :- 100 mm thick rock wool (minimum density 64kg/Cum)/ fire resistance foam/puff as per OEM/ as per standard manufacturing to achieve desired decibel level (vi) The acoustic should be composite in construction and fully assembled integral unit. (vii) The DG Set should be provided with external Emergency stop push button. (viii) The enclosure should be suitably internally illuminated by CFL/FTL Lamp fittings. (ix) The noise level should be 75 dB at 1m under free field conditions. (x) The acoustic enclosure parts shall be of powder coated after pre treatment process. The base frame should be painted with epoxy based black shade.
Design, supply, install, testing & commissioning 13 passengers (884 Kg) lift at a speed of 1.0 M/sec, lift with single speed motor 415 volts, 3 phase, AC 50 Hz supply conforming to IS 14665, suitable to serve S+6 floors with AC Variable Voltage & Variable Frequency drive(VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive(electric motor driven mechanism), sliding stainless steel doors,automatic rescue device(ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set (04 Nos,one each in car, Machine room & near Ground floor landing door) complete all as specified (Passenger cum Luggage Lift)
Design, supply, install, testing & commissioning 8 passengers(544 Kg) lift, speed 1.0 metre/sec, lift with single speed motor 415 volts, 3 phase, AC 50 Hz supply conforming to IS 14665, suitable to serve S+6 floors with AC Variable Voltage & Variable Frequency drive(VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive(electric motor driven mechanism), sliding stainless steel doors,automatic rescue device(ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set (04 Nos,one each in car, Machine room & near Ground floor landing door) complete all as specified.(01 No Passanger Lift and 1 Nos Fire Lift)
SOLAR PV GENERATION SYSTEM M&L for Supply, Install, Testing and Commissioning of 50 KWp MNRE approved roof top on grid Solar power plant consisting of accessories shall be as under:- (a) Design, supply, fixing on grid solar panel (roof to system) with anodized aluminium structure for 50 KWP. Height of aluminium structure shall not be 1.0 meter with concrete foundation as per manufacturer's design/OEM. Aluminium structure shall be rest on roof top. Make of solar panels ADANI/WAAREE/SATVIK or as MNRE approved. (b) Design, installation 3 phase 50 KWP solar ongrid inverter with inbuild MPPT changer controller and remote monitor system. Grid inverter shall be installed in closed vicinity of solar PV modules connected to the inverter in the forms of strings through a DC distribution box. Make of inverter : GROWATT or equivalent of GODWE/SUN POWER or as MNRE approved. (c) Supply and fixing of 375 watt/380 watt 24 volts monocrystaline PERC technology solar photovolatic panel. The panel shall be installed on a solar mounting structure at an angle similar to the solar mounting structure with the help of mounting clamps. Make of solar panels ADANI/WAAREE/SATVIK or as MNRE approved. Item Continued as Srl No. 17.85
ANUGRAH CONSTRUCTION PVT. LTD. (BID ID -3208006)
CHHABINDRA KUMAR PRADHAN (BID ID -3208359)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid