Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.0 LAccepted-AOC NO 6 NJ BUILDING GANGAMMA TEMPLE ROAD JALAHALLI POST BANGALORE 560 013 | BANGALORE | BANGALORE | KARNATAKA | 560013 | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹4.1 L+₹10,850 (2.71%)Rejected-Finance | L2 | Rejected-Finance BEING NOT LOWEST | |
| 3 | L3₹4.2 L+₹20,850 (5.20%)Rejected-Finance | L3 | Rejected-Finance BEING NOT LOWEST | |
| 4 | L4₹4.3 L+₹26,650 (6.65%)Rejected-Finance | L4 | Rejected-Finance BEING NOT LOWEST | |
| 5 | L5₹4.4 L+₹37,250 (9.29%)Rejected-Finance | L5 | Rejected-Finance BEING NOT LOWEST |
Tender Value
Refer Docs
EMD Value
₹8,000
Closing Date
4 Nov 2022, 5:00 pmClosed
AGE I AF CHIMNEY HILLS BANGALORE
Asst Garrison Engineer I AF Chimney Hills Chikkbanavara Post Bangalore, PIN- 560 090
COMPREHENSIVE MAINTENANCE TO CENTRAL AC PLANT SYSTEM OF CPSS AT NO. 2 AFSB MYSORE UNDER AGE (I) AF STATION CHIMNEY HILLS
2022_MES_557199_1
8569/E8
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
AGE I AF CHIMNEY HILLS BANGALORE
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹300
AGE I AF CHIMNEY HILLS BANGALORE
₹8,000
Yes
12 Jan 2023
14 Oct 2022
5 Nov 2022
14 Oct 2022
4 Nov 2022
28 Oct 2022
14 Oct 2022 - 21 Oct 2022
Amount
Comprehensive Maintenance of CPSS Central A/C plant 2x24 TR capacity, control panel, complete incl material and labour, spares lubricants installed at CPSS bldg, checking of leakage on refrigerant gas, replacement of glands, 'O' ring gaskets, nuts, bolts, washers and routine checks like oil level, V belts, electrical control wires, cleaning of filters, greasing to the motor, replacement of gland packing to pump, indicating lamp to panel etc, but excluding repairs to the plants all as specified and directed
Supply and install in repair MCCB 250 amps, 415 volts , 4 pole, 50 HZ, 36 KA including spreader links on both sides complete all as specified and directed
All as per item no.2 above but fixed type, 3 pole, 25 to 100 A and 16 KA
Supply only in replacement MCB 40 Amps, D Series, 415 volts , 4 pole, 50 HZ, 10 KA complete all as specified and directed
Supply only in replacement of three phase fully automatic Star Delta starter suitable for 12.5 HP Pump/motor 3 Phase, 415 V, 50 Hz, relay range 9-15 Amp, having MN relay is with single phase prevention feature complete all as specified and directed
M & L for leakage arresting with Nitrogen & Vacumailising
M & L for Condensor De-scaling
M & L for AHU full unit servicing
M & L for Chemical cleaning & Servicing of Cooling Tower
Supply only filling/topup R-22 refrigerant gas
Supply only copper harden pipe 5/8x1.1/8
Supply only filter
Supply only drier
M & L for detecting and rectifying leakage of Chiller water AC water pump
Supply only Pressure guage
Supply only room temperature indication guage
Supply only single phase preventor suitable for three phase star delta starter Make : Minilec
M & L for detecting and rectifying leakage of Condensor water pump
M&L earthing complete with galvanised steel plate electrode of size 60x60x6mm thick burried directly in ground verticalIy to a depth not less 2.25rn below ground level with top edge of the rod not less than l.5mtr below normal ground level connected to galvanised earth lead wire 4.0mm dia by means with bolts, check nuts and washers protected by Gl light grade pipe of size 15 mm dia and connecting up with the DB as the case may be upto a maximum distance of 7.5 m away from the earth electrode including test point, excavation, earthwork, PCC Chamber, RCC Cover, watering pipe 20mm dia GI medium grade with funnel and wire mesh, charcoal, salt, etc all as per plate no.3 of SSR 1991 and as directed by Engineer in charge
M&L earthing complete with galvanised steel plate electrode of size 60x60x6mm thick burried directly in ground verticalIy to a depth not less 2.25rn below ground level with top edge of the rod not less than l.5mtr below normal ground level connected to galvanised iron strip 32 X 6mm dia by means with bolts, check nuts and washers protected by Gl light grade pipe of size 40 mm dia and connecting up with panel as the case may be upto a maximum distance of 7.5 m away from the earth electrode including test point, excavation, earthwork, PCC Chamber, RCC Cover, watering pipe 20mm dia GI medium grade with funnel and wire mesh, charcoal, salt, etc all as per plate no.3 of SSR 1991 and as directed by Engineer in charge
eurekaenterprises
M/s A N Kalbhavi
JM Engineering
KUZHIKKAL ENTERPRISES
SAPTHAGIRI CONSTRUCTIONS
SRI LAKSHMI VENKATESHWARA ENTERPRISES
SRI AYYAPPA ENTERPRISES
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .