SENIOR SUPERINTENDING ENGINEER
OFFICE OF THE SENIOR SUPERINTENDING ENGINEER (P.W.Dte) South-Western Electrical Circle PWD Compound, Midnapore, Paschim Medinipur
Replacement of 8 nos 6 KVA UPS with 12 V 26 Ah battery at OT, Labour Room, Labrotary and SNCU Egra SDH in the district of Purba Medinipur
2025_WBPWD_979105_1
WBPWD/SSE/SWEC/NIQ105/2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
PURBA MEDINIPUR
Please refer Tender documents.
3 documents required · 3 mandatory
₹40,998
OFFICE OF THE SENIOR SUPERINTENDING ENGINEER
9 Feb 2026
24 Dec 2025
16 Jan 2026
24 Dec 2025
14 Jan 2026
6 Jan 2026
5 Jan 2026
SITC of 6 KVA Single phase input & Single phase out put on line UPS systems (Make- Numeric/ APC/ Vertiv) having specification
Topology, IGBT BASED DSP CONTROLED
Input Voltage: 230 VAC, 160 - 270 VAC
Input Frequency: 50 Hz, 47 to 53 Hz
Input PF: > 0.99
Output Voltage: 220 VAC +/- 1%
Output Frequency: 50 Hz +/- 0.1% in Free running & +/- 4% in Sync
Isolation Transformer: Provided Inbuilt (No external tranformer accepted )
Power Factor: 0.8 Lag to Unity
Crest Factor: 3:1
Waveform: Sinusoidal
THD: < 3% on linear load & < 5% on non-linear load
Overload: 110% for 10 minutes, 125% for 1 minutes, 150% for 30 msec
Transient Response : For 0 - 50% & 50% - 100% load change voltage remains within +/- 5%
Ripple: < 2%
Inverter Efficiency: > 93%
Battery : 12 V, Mono Block batteries.
DC Bus : Minimum 240 V
Battery Back UP: 60 mim back up minimum VAH required VAH 12480 Battery Make: Exide, Amar Raja Quanta
Battary Cabine: With power coated MS angle with MS sheet suiteble dimention and gadge,
Protections: Input & Output Over / Under Voltage, Single Phasing DC - High / Under Voltage, Battery Charging Over Current, Output Overload / Short Circuit / Over Temp., UPS auto ON on Mains recovery
Audio Alarm, Mains Fail, Battery Low Pre-alarm, Inverter Trip
Metering: Digital Seven segment - Voltage, Current & Frequency, Battery - Voltage & Current
Indications: Mains - On / Fail / High / Low / Single Phasing DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Current
Switchgear: MCB / MCCB for Input, Battery, Output & Manual Bypass Switch
Termination: Input, Battery, Output & Bypass
Enclosure: IP 20
Operating Temp: 0 to 40 Deg C
Humidity: Upto 95% Rh (non-condensing)
Cooling: Forced Air
Noise: < 55 dB
Charging Current: 5 to 10 Amps. (Site Settable)
Cold Start : Provided
Communication: RS 232
Static Switch: Provided with changeover < 5 msec in sync & < 20msec in non-sync
Certification : ISO 9001: 2015, ISO 14001: 2015, ISO 18001, RoHS and OHSAS 18001
IEC/EN 62040-1-1,IEC/EN50091-1,IEC/EN 60950 (Safety) IEC/EN 50091-2, IEC/EN 62040-2(EMC Emmission),IEC/EN 62040-3(performance & Design)IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design & Manufacture)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.52 MB
Tendernotice_2.pdf
PDF • 1.82 MB
BOQ_2386438.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .