Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.9 LAccepted-AOC 2ND FLOOR SHOP NO 303 MARUTI PLAZA RONCHI BANGAR TOWNSHIP MATHURA | MATHURA | UTTAR PRADESH | 281001 | L1 | Accepted-AOC Accept | |
| 2 | L2₹2.0 L+₹4,000 (2.09%)Rejected-AOC GMD ROAD MORADABAD MORADABAD UTTAR PRADESH 244001 | MORADABAD | UTTAR PRADESH | 244001 | L2 | Rejected-AOC Accept | |
| 3 | L3₹2.2 L+₹26,400 (13.8%)Rejected-AOC 19 A DURGA BARI SADAR BAZAR MEERUT MEERUT MEERUT UTTAR PRADESH 250001 | MEERUT | UTTAR PRADESH | 250001 | L3 | Rejected-AOC Accept |
Tender Value
₹1.9 L
EMD Value
₹4,000
Closing Date
26 Nov 2021, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer ETD Etawah
Executive Engineer ETD Etawah
Replacement of defective Vacuum interupter of Diff 36 KV Breaker Poles Under ETD, Etawah
2021_UPTCL_641920_1
T-14/ETD(E)/2021-22
Open Tender
Electrical Works
Item Rate
30 days
Etawah
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Yes
Executive Engineer ETD Etawah
₹4,000
Yes
23 Aug 2022
12 Nov 2021
26 Nov 2021
12 Nov 2021
26 Nov 2021
12 Nov 2021
30 days
Amount
Providing & Fixing of vacuum interupter in defective 33 KV VCB of CGL Make of Auraiya I Feeder of Y Phase which megger value is found less than 100 M ohm at 132 KV S/S Dibiyapur
Providing & Fixing of vacuum interupter in defective 33 KV VCB of Shreem Make of 33 KV Gurapura Feeder of B Phase which megger value is found less than 100 M ohm at 220 KV S/S Bharthana
Providing & Fixing of vacuum interupter in defective 33 KV VCB of Siemens Make of 33 KV Fatehpura Feeder of Y Phase which megger value is found less than 100 M ohm at 220 KV S/S Saifai
Providing & Fixing of vacuum interupter in defective 33 KV VCB of CGL Make of 10MVAR Cap. Bank-I of Y Phase which megger value is found less than 100 M ohm at 132kv s/s Kunera.
After replacement of vaccum interrupter following test & overhauling to be carried out (a)Checking & adjustment of snatch gap,travel of drive insulator rod & tie rod of each pole (b) opening and closing time of breaker of each pole ( c) carrying out contact resistance measurement (CRM Test) of each pole. (d) checking of megger value of breaker poles. (e) checking tripping of breaker at 70% DC Voltage (f) checking the close/open operation of breaker from remote & local and ratification of fault, if any
M/S SATKAR TRADERS
Technocrat Electrical
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .