Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.7 LAccepted-AOC 22 1755A KANNANKATTU TEMPLE ROAD EDAKOCHI KOCHI 682010 ERNAKULAM KERALA 682010 | ERNAKULAM | KERALA | 682010 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹39.6 L+₹5.1 L (14.9%)Rejected-Finance | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹39.9 L+₹5.4 L (15.7%)Rejected-Finance | L3 | Rejected-Finance Being L3 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
10 Dec 2024, 6:00 pmClosed
GARRISON ENGINEER (MIS) MHOW
Garrison Engineer (Maint) Infantry School Mhow (MP) - 453441
REPAIR MAINT OF SUB MAIN WIRING AND INTERNAL ELECT ITEMS OF OTM ACCN IN PW DIV MD ACCN MT MECH DEMO COY AMU SARAGRAHI COMPLEX PC WING CHUNNI LAL BLOCK AND FFC AND MORTOR GROUP OF HQ INF SCHOOL MHOW AND MAINT SERVICING OF STANDBY DG SET INSTALLED AT V
2024_MES_683446_1
8747/GE (MIS)/Mhow
Open Tender
Civil Works - Others
Item Rate
270 days
GARRISON ENGINEER (MIS)
All as per Tender document
8 documents required · 8 mandatory
₹500
GE (MIS) Mhow
₹90,000
Yes
4 Jan 2025
12 Nov 2024
12 Dec 2024
12 Nov 2024
10 Dec 2024
26 Nov 2024
Amount
Taking down copper /aluminium point wiring (light, fan, bell,socket or power) complete including fixture and fittings such as switches , ceiling roses , pendent , regulators, sockets, light fitting etc . Removing materials to store for keeping in safe custody or for taking credit ( credit a for above items should be made as per condition seperately ) and making good distrubed surfaces of walls, floors etc.
M & L for Point wiring in repairs with FR LSH PVC insulated PVC unsheathed electric cable 1100V grade single core having multi stranded copper conductor of size 1.5 Sqmm nominal cross sectional area in but in existing conduit & making good the disturbed surface of wall with1.5 sqmm green FR LS PVC insulated unsheathed copper conductor as a earth wire connected to earth dolly by providing lugs including galvanised boxes and bakelite sheet /Modular Boxes for mounting switches, sockets, fan regulators etc for the following:- Make of PVC conduit/Casing Caping:- Plaza/Finolex/Polycab /Kalinga/Jindal/Asian
(a) One light/fan/bell point controlled by one switch
(b) One 5amps socket out let point controlled by one switch on same board with other switches.
(c) One 5amps socket out let point on independent board controlled by one switch.
All as per item 2.00 above but using FR LSH PVC insulated unsheathed 2.5 Sqmm cross sectional area cable for phase /neutral & for earth 2.5 Sq mm green FR LS PVC insulated cable for 15 amps socket point on independent board controlled by one switch.
M & L for stair case point wiring in repairs with FR LSH PVC insulated PVC unsheathed electric cable 1100V grade single core having multi stranded copper conductor of size 1.5 Sqmm nominal cross sectional area in but in existing conduit or in casing caping or in conduit of size not less than 20mm & making good the disturbed surface of wall with1.5 sqmm green FR LS PVC insulated unsheathed copper conductor as a earth wire connected to earth dolly by providing lugs including galvanised boxes and bakelite sheet /Modular Boxes for mounting switches, sockets, fan regulators etc for the following. Make of PVC conduit/Casing Caping:- Plaza/Finolex/Polycab/Kalinga/Jindal/Asian :-
M & L for Point wiring using approved colour coding as as per IS in repairs with FR LSH PVC insulated PVC unsheathed electric cable 1100V grade ISI 694 marked down through single core having multi stranded copper conductor of size 1.5 Sqmm nominal cross sectional area drawn in & including non metallic rigid PVC conduit ISI marked medium grade not less than 20mm dia with all conduit accessories in concealed wiring system by cutting of wall and making good and matching disturbed surface of wall with existing surface of wall (cutting except on ceiling for fan point only, on ceiling instead of PVC conduit surface casing caping will be used) & 1.5 sqmm green FR LS H PVC insulated unsheathed copper conductor as earth wire connected to earth dolly by providing lugs including galvanised boxes and bakelite sheet/Modular Boxes for mounting switches, sockets, fan regulators etc for the following . Make of PVC conduit/Casing Caping:- Plaza/Finolex/Polycab/Kalinga/Jindal/Asian :-
(a) One light point/fan/ Bell point controlled by one switch
(b) One 5amps socket out let point controlled by one switch on same board with other switches.
(c) One 5amps socket out let point on independent board controlled by one switch.
All as per item 5.00 above but using FR LS PVC insulated unsheathed 2.5 sqmm cross sectional area cable for phase /neutral & for earth 2.5 Sq mm green FR LSH PVC insulated cable for 15 amps socket point on independent board controlled by one switch.
M & L for Point wiring using approved colour coding as as per IS in repairs with FR LSH PVC insulated and unsheathed electric cable 1100 volts grade single core having multistranded copper conductor of 1.5 Sqmm nominal cross sectional area for phase & neutral, drawn in and including non metallic rigid PVC casing caping not less than 25mm base size with all fitting and fixing accessories and with 1.5 Sqmm green FR LS PVC insulated unsheathed multistranded copper conductor cable as continuous earth conductor connected to earth dolly by providing suitable lugs including galvanised/wooden boxes of suitable size with white laminated bakelite sheet/Modular Boxes for mounting switches,sockets etc complete for the followings.Make of PVC conduit/Casing Caping:- Plaza/Finolex/Polycab/Kalinga/Jindal/Asian :-
(a) One light/ fan/ bell point controlled by one switch
(b)One 5amps socket out let point controlled by one switch on same board with other switches.
(c) One 5amps socket out let point on independent board controlled by one switch.
All as per item 7.00 above but using FR LS insulated unsheathed 2.5 sqmm cross sectional area cable for phase /neutral & for earth 2.5 Sq mm green FR LSH PVC insulated cable for 15 amps socket point on independent board controlled by one switch.
S&F switch in repairs piano flush button single pole one way 6Amp 240 volt complete as directed.
S&F switch in repairs piano flush button single pole two way 6Amp 240 volt complete as directed.
S&F in repairs socket outlet flush type 5 pin, 6 amps, 230 volts complete all as directed.
S&F in repairs Switch socket combination 2 in 1, 3 pin, 6 and 16 Amp flush type universal with box, 230 volts complete all as directed.
All as per item No 12.00 above but 6 A
S&F in repairs switch piano flush button single pole one way 16 Amp 240 volt complete as directed.
S&F in repairs socket outlet flush type multipurpose 2 in 1, 3 pin 6 and 16 Amp , 230 volts complete as directed.
Supply and fix in repairs bell push single pole, 6 amps, 230 Volts, flush type complete as directed.
S&F in repairs ceiling rose surface bakelite three terminal complete all as directed.
S&F in repairs lamp holder insulated body with back plate for batten fittings complete all as directed.
Supply and fix in repairs Bell, ding dong type, AC 230 Volts,single pole complete.
Supply & fix in repairs electronic Fan regulator step type complete.
S&F in replacement 20W LED batten with inbuilt smart motion sensor, 230 Volt, 50 Each Hz, 4 feet, polycarbonate extruted channel, powder coated with diffuser for glare free light, Inbuilt motion sensor prewired with 25% dimmer illuminous in ideal time with warranty option of 5 years from date of installation with all accessories including two Nos of PVC box of size 75x75x20mm for mounting light fittings complete with following specification. (i) housing-polycarbonate extrusion, diffuser- opal polymer, LED type MID power Light distribition- general Spread, LED efficiency > 130 lumen/Watt, System effieciency-> 100 lumen/Watt, Driver efficiency - more than 85%, power factor-more than 0.95, THD <10%, Mounting/Fixing- Wall/Ceiling, Ingress Protection IP-20, Sensor type- HF inbuilt integral occupancy/movement sensor, sensor range- upto 5 mtrs(cone formation), Dimming operation- default operation at 25% of the is rated value. On detection of motion, light output rises to 100% for upto 20 sec. in absence of motion switches back to default operation, LED life- upto 50,000 Hrs.Surge Protection- not less than 1KV.Model No.-SZSLBMX020 (Make - Shakti)
S&F in replacement 10W LED batten with inbuilt smart motion sensor, 230 Volt, 50 Each Hz, 2 feet, polycarbonate extruted channel, powder coated with diffuser for glare free light, Inbuilt motion sensor prewired with 25% dimmer illuminous in ideal time with warranty option of 5 years from date of installation with all accessories including two Nos of PVC box of size 75x75x20mm for mounting light fittings complete with following specification. (i) housing-polycarbonate extrusion, diffuser- opal polymer, LED type MID power Light distribition- general Spread, LED efficiency > 130 lumen/Watt, System effieciency-> 100 lumen/Watt, Driver efficiency - more than 85%, power factor-more than 0.95, THD <10%, Mounting/Fixing- Wall/Ceiling, Ingress Protection IP-20, Sensor type- HF inbuilt integral occupancy/movement sensor, sensor range- upto 5 mtrs(cone formation), Dimming operation- default operation at 25% of the is rated value. On detection of motion, light output rises to 100% for upto 20 sec. in absence of motion switches back to default operation, LED life- upto 50,000 Hrs.Surge Protection- not less than 1KV.Model No.-SZSLBMX010(Make-Shakti)
S&F in replacement 36 W LED (2feetx 2feet)Serene recess with inbuilt smart motion sensor, 230 Volt, 50 Each Hz, 2 feet x 2feet , polycarbonate extruted channel, powder coated with diffuser for glare free light, Inbuilt motion sensor prewired with 25% dimmer illuminous in ideal time with warranty option of 5 years from date of installation with all accessories for mounting light fittings complete with following specification. (i) housing-polycarbonate extrusion, diffuser- opal polymer, LED type MID power Light distribition- general Spread, LED efficiency > 130 lumen/Watt, System effieciency-> 100 lumen/Watt, Driver efficiency - more than 85%, power factor-more than 0.95, THD <10%, Mounting/Fixing- Wall/Ceiling, Ingress Protection IP-20, Sensor type- HF inbuilt integral occupancy/movement sensor, sensor range- upto 5 mtrs(cone formation), Dimming operation- default operation at 25% of the is rated value. On detection of motion, light output rises to 100% for upto 20 sec. in absence of motion switches back to default operation, LED life- upto 50,000 Hrs.Surge Protection- not less than 1KV.Model No.-SZRSRMX036(Make- Shakti) or other equivalent make as approved by GE
Supply and fix in repairs 1X18/20 W, 6500K V1 LED inverter batten with lithium ion battery charging time 8 hrs to 10 hrs and back up upto 10 hrs high efficiency with warranty option of 5 years from date of installation with and LED Life -Upto 50,000 Hrs all accessories duly connection with three core flexible copper cable duly fixed on two nos of PVC square boxes including taking down the existing complete all as specified and directed. Make:- Havells Cat No. LHEXASP7IN1W020 / Shakti cat Pt No. SZSLBMX018-iBB / other equivalent make as approved by GE
Supply and fix in repairs integrated LED tube light fitting 1x18/20 Watt, white light LED or warm light LED 6000K as per site requirment complete fitting with all accessories duly connection with three core flexible copper cable duly fixed on two nos of PVC square boxes including taking down the existing complete all as specified and directed. Make:- Havells Cat No. LHEXBLP7PN1W018 , Bajaj cat Pt No. BCLSB 18WH or equivalent in Wipro / other equivalent make as approved by GE
Supply and fix in repairs integrated LED tube light fitting 1x9/10 Watt, white light LED or warm light LED 6500K as per site requirment complete fitting with all accessories duly connection with three core flexible copper cable duly fixed on two nos of PVC square box including taking down the existing complete all as specified and directed .Make:- Havells Cat No. LHEXACP7IN1W010 Bajaj Cat Pt No. BCLSB 10 WH or equivalent in Wipro / other equivalent make as approved by GE
Supply and fix in repairs integrated LED tube light fitting 1x5 Watt, white light LED or warm light LED 6500K as per site requirment complete fitting with all accessories duly connection with three core flexible copper cable duly fixed on two nos of PVC square box including taking down the existing complete all as specified and directed .Make:- Havells Cat No. LHEXBLP7IN1W005 Bajaj Cat Pt No. BCLSB 05NW or equivalent in Crompton/Wipro
Supply and fix in repairs retrofit LED tube light T-8 type, 1x20 Watt, 6500K in Polycarbonate body with extruded Al heat sink for efficient heat dissipation including taking down the existing complete all as specified and directed. Make:- Havells Cat No.LHLDDCXCML8Q020 , Bajaj Cat Pt No BLRB20CW LED or equivalent in Wipro.
Supply and fix in repairs batten for retrofit type LED tube T-8 Type upto 1x22 Watt, pre-wired for LED tube complete with all accessories duly connection with three core flexible copper cable and duly fixed on and including two Nos PVC square boxes including taking down the existing complete all as specified and directed. Make:- Havells Cat No. LHFXCENNTN1W020 , Bajaj cat Pt No. BLRB-DB118I,or equivalent inWipro. Note for item Nos. 28 & 29:- Makes of these items should be same and compatible with eath other.
Supply and fix in repairs Wall light fittings suitable for white light or warm light LED bulb 9 watt with & including LED bulb of 9 watt, including connection with all necessary fixing accessories complete all as specified and directed by Engr-in-Charge. Make :- Havells Cat No. LHFOECE1TZ1B014 or equivalent in equivalent in Bajaj, Philips.
Supply & fix in repairs LED Bulk Head luminaire 10W, 6000K pressure die cast housing with IP65 protection complete with electric connection all as specified and directed by Engr-in-Charge. Make:- Havells Cat No. HEXAFT10LED857SSYMBOPC, Crompton Cat No. LBH-10-CDL, Bajaj Cat No. BIBWP 10W LED
Supply and fix in repairs LED street light fittings 30 Watt, 6500K complete fitting having pressure dia cast aluminium housing with heat resistant toughened glass & IP 65 protection fixed on and including sufficient length and appropriate size GI bracket with all accessories duly connection with three core flexible copper cable complete all as specified and directed .Make:- Crompton Cat No. LSTO-25-CDL, Bajaj Cat No. ENXTP30LWHSYPCSD and equivalent in Havells cat No. LHEXAYP7PN6K030 .
S&F in repairs LED round light fitting 12W recess mounting type, white light LED or warm light LED 6500K as per site requirment complete with driver duly connection with copper cable etc. Make, Havells Cat No. LHEBLDP7IZ1W012 Bajaj Cat Pt No. BGSLO SLEEK 15W WH RD, or equivalent in Crompton, Wipro .
S&F in repairs LED round light fitting 12W surface mounting type, white light LED or warm light LED 6500K as per site requirment complete with driver duly connection with copper cable etc. Make, Havells Cat No. LHEAAHP7ILW012 or equivalent inCrompton, Wipro .
S&F in repairs LED round light fitting 15W recess mounting type, white light LED or warm light LED 6500K as per site requirment complete with driver duly connection with copper cable etc. Make, Havells Cat No. LHEBLDP7IN1W015 Bajaj Cat Pt No. BGSLO SLEEK 15W WH RD, or equivalent inCrompton, Wipro . Note :- Ceiling cutout ø 180 mm, height 23 mm ±1 mm for 15 W
S&F in repairs LED round light fitting 18W recess mounting type , white light LED or warm light LED 6000K as per site requirment complete with driver duly connection with copper cable etc. Make, Jaquar LAVRV018XN Bajaj Cat Pt No. BGSLO SLEEK 18W WH RD, or equivalent inCrompton, Wipro Note- All Fittings Should be White/ Warm White as per site Requirement. Note :- Ceiling cutout ø 220 mm, height 23 mm ±1 mm for 18 W.
S&F in repairs recess mounting type 1FTX1 FT LED Luminaire 18W, 5700K in white finish with opal diffuser with electronic driver duly connection with copper cable including taking down the existing etc. Make, Bajaj Cat Pt No. BZRSQL 18L WH, or equivalent in Crompton , Havells and Wipro.
S&F in repairs LED ceiling light fittings 34/36 watt recess mounting type 2x2 luminaire, white light LED or warm light LED 5700K as per site requirment complete with driver duly connection wire etc including taking down the existing. Make Bajaj Cat Pt No. BZRSQL36LLEDGXWH or equivalent in Havells Wipro.
S&F in repairs LED ceiling light fittings 34/36 watt surface mounting type 2x2 luminaire, white light LED or warm light LED 5700K as per site requirment complete with driver duly connection wire etc including taking down the existing. Make Jaguar Cat No. LULT02S036XC, Crompton Cat No. LCTLRN-36-FO-CDL, Bajaj Cat Pt No. BZRSQL 36W GZ1 WH or equivalent in Havells Wipro.
S&F in repairs LED ceiling light fittings recessed mounting of 06 watt 6500K complete with driver duly connection wire etc including taking down the existing. MakeHavells Cat No. LHEEAQPBIB1W006 or equivalent in Bajaj Wipro.
M&L for Sub main wiring in repairs with two runs of single core FR LSH PVC insulated unsheathed cable 1100 volts grade, 6 Sqmm size with multistranded copper conductor, drawn in and including surface non metallic rigid PVC conduit not less than 25mm dia and all fittings like bends, tees, saddles etc including one run of FR LS PVC insulated unsheathed 6.0 sqmm cable with multistranded copper conductor green PVC insulated as continuous earth conductor cable connected to earth dolly complete. Make of PVC conduit/Casing Caping:- Plaza/Finolex/Polycab/Kalinga/Jindal/Asian& Make Of wire - Make - HPL/L&T/HPL/Havells
M&L for Sub main wiring in repairs with two runs of single core FR LSH PVC insulated unsheathed cable 1100 volts grade, 4 Sqmm size with multistranded copper conductor, drawn in and including surface non metallic rigid PVC conduit not less than 25mm dia and all fittings like bends, tees, saddles etcincluding one run of FR LS PVC insulated unsheathed 4 sqmm cable with multistranded copper conductor green PVC insulated as continuous earth conductor cable connected to earth dolly complete. Make of PVC conduit/Casing Caping:- Plaza/Finolex/Polycab/Kalinga/Jindal/Asian & Make Of wire - Make - HPL/L&T/HPL/Havells
M&L for Sub main wiring in repairs with two runs of single core FR LSH PVC insulated unsheathed cable 1100 volts grade, 6 Sqmm size with multistranded copper conductor, drawn in and including non metallic rigid PVC conduit of not less than 25 mm dia concealed in wall by cutting chases of wall and making good the disturbed surface, including PVC insulated unsheathed FR LS 6.0 Sqmm cable with multistranded copper conductor green PVC insulated as contineous earth conductor cable connected to earth dolly from main distribution board complete all as specified and directed by Engr-in-Charge. Make of PVC conduit/Casing Caping:- Plaza/Finolex/Polycab/Kalinga/Jindal/Asian & Make Of wire - Make - HPL/L&T/HPL/Havells
M&L for Sub main wiring in repairs with two runs of single core FR LS H PVC insulated unsheathed cable 1100 volts grade, 4 Sqmm size with multistranded copper conductor, drawn in and including non metallic rigid PVC conduit of not less than 25 mm dia concealed in wall by cutting chases of wall and making good the disturbed surface, including FR LS PVC insulated unsheathed 4.0 Sqmm cable with multistranded copper conductor green PVC insulated as continuous earth conductor cable connected to earth dolly from main distribution board complete all as specified and directed by Engr-in-Charge. Make of PVC conduit/Casing Caping:- Plaza/Finolex/Polycab/Kalinga/Jindal/Asian& Make Of wire - Make - HPL/L&T/HPL/Havells
M&L for Sub main wiring in repairs with Four runs of single core FR LSH PVC insulated unsheathed cable 1100 volts grade, 6 Sqmm size with multistranded copper conductor, drawn in and including non metallic rigid PVC conduit of not less than 25 mm dia concealed or in PVC Conduit as per site requirement in wall by cutting chases of wall and making good the disturbed surface, including FR LS PVC insulated unsheathed 6.0 Sqmm cable with multistranded copper conductor green PVC insulated as continuous earth conductor cable (Two runs of 6 Sq mm cable for earth wire) connected to earth dolly from main distribution board complete all as specified and directed by Engr-in-Charge. Note: Four Run of Single Core FRLSH ( 6Sq mm) Cable and two runs for same size as earth wire(6 Sq mm). 4 X 6 Sqmm ( For R Y B (For Phase) and B (for Neutral) + 2 X 6 Sqmm ( For Earth wire) Make of PVC conduit/Casing Caping:- Plaza/Finolex/Polycab/Kalinga/Jindal/Asian & Make Of wire - Make - HPL/L&T/HPL/Havells
Supply and fix in repairs Modular Switch flush type 6 Amps single pole, one way complete including taking down the existing all as specified. Make: Legrand Mylinc Series, Anchor Roma Plus, Crabtree Athena Series.
Supply and fix in repairs Modular Socket outlet, multi purpose, 2/3 Pin combined 6 Amps flush type complete including taking down the existing all as specified. Make: Legrand Mylinc Series, Anchor Roma Plus, Crabtree Athena Series.
Supply and fix in repairs Modular Bell push flush type,6 Amps complete all as specified. Make: Legrand Mylinc Series, Anchor Roma Plus, Crabtree Athena Series.
Supply and fix in repairs Modular Socket outlet, multi purpose, 2/3 pin combined 16 Amps universal socket complete including taking down the existing all as specified. Make: Legrand Mylinc Series, Anchor Roma Plus, Crabtree Athena Series.
Supply and fix in repairs Modular Switch 16 Amps single pole, one way complete including taking down the existing all as specified. Make: Legrand Mylinc Series, Anchor Roma Plus, Crabtree Athena Series.
Supply & fix in repairs modular fan regulator step type, 2 module type complete including taking down the existing:- Make: Legrand Mylinc Series, Anchor Roma Plus, Crabtree Athena Series.
Supply and fixing in repairs white finished single mounting modular plates suitable for modular accessories of following sizes including taking down the existing:(Make: Legrand Mylinc Series, Anchor Roma Plus, Crabtree Athena Series) :-
(a) suitable for 1/2 modules
(b) suitable for 3 modules
(c) suitable for 4 modules
(c) suitable for 6 modules
(d) suitable for 8 modules
Supply and fix in repairs sheet metal boxes concealed in wall suitable for housing modular accessories of following sizes including taking down the existing:- Make: Legrand Mylinc Series, Anchor Roma Plus, Crabtree Athena Series.
(a) suitable for 1 or 2 modules 50mm.
(b) suitable for 3 modules 50mm.
(c) suitable for 4 modules 50mm.
(d) suitable for 6 or 8 modules 50mm.
Supply and Fix in repairs flush mounting factory made Vertical TPN DB, IP-43 Protection -IK 08, with metal double door with 200 Amps rated copper busbar with 2 neutral bar, earth bar and cables ties for cable management fully insulated bus bar with set of wires and door earthing with provision of sapce for TP/FP 100-125 amps G Frame MCCB as incomer and SP/TP MCBs as out going 4 way complete all as specified and directed by Engr-in-Charge. Make - HPL/L&T/HPL/Havells
Supply and Fix in repairs flush mounting factory made Vertical TPN DB, IP-43 Protection -IK 08, with metal double door with 200 Amps rated copper busbar with 2 neutral bar, earth bar and cables ties for cable management fully insulated bus bar with set of wires and door earthing with provision of sapce for TP/FP 100-125 amps G Frame MCCB as incomer and SP/TP MCBs as out going 8 way complete all as specified and directed by Engr-in-Charge. Make - HPL/L&T/Havells
Supply and fix in repairs double door TPN DBs four way of powder coated DB's suitable for MCB's fitted with bus bar,Neutral link,Earth bar and Din ral complete all as specified and directed by Engr-in-Charge. Make -HPL/L&T/Havells
Supply and fix in repairs double door SPN DBs eight way of powder coated DB's suitable for MCB's fitted with bus bar,Neutral link,Earth bar and Din ral complete all as specified and directed by Engr-in-Charge. Make - HPL/L&T/Havells
Supply and fix in repairs double door SPN DBs four way of powder coated DB's suitable for MCB's fitted with bus bar,Neutral link,Earth bar and Din ral complete all as specified and directed by Engr-in-Charge. Make -HPL/L&T/Havells
S & F in repairs MCCB FP 100 Amps 25 KA including connection with suitable size aluminium / copper lugs complete all as specified and directed by Engr-in-Charge. Make - HPL/L&T/Havells
S & F in repairs MCCB FP 125 Amps 27 KA including connection with suitable size aluminium / copper lugs complete all as specified and directed by Engr-in-Charge. Make - HPL/L&T/Havells
S & F in repairs MCB TPN 50 to 63 amps 10 KA, c-series including connection with suitable size aluminium/copper lugs complete all as specified and directed by Engr-in-Charge. Make - HPL/L&T/Havells
S & F in repairs MCB SPN 6 to 32 amps 10 KA ,C-series including connection with suitable size aluminium / copper lugs complete all as specified and directed by Engr-in-Charge. Make - HPL/L&T/Havells
S&F in repairs MCB SP 240 volts 6 to 32 Amps, 10 KA breaking capacity, 'B' series including connection with suitable size aluminium / copper lugs complete all as specified and directed by Engr-in-Charge. Make - HPL/L&T/Havells
S&F in repairs Single pole and neutral Sheet Metal enclosure with a two pin and earth plug and socket complete with one single pole MCB,20 Amps incl cutting of wall and fixing of AC box in concealed system and making good of disturbed surfaces complete all specified and as directed. Make - HPL/L&T/Havells
M & L for Earthing in repairs complete with galvanized steel earth plate electrode 60cm x 60cmx 6.3 mm thick buried directly in ground ( earth pit not less than 2.25 meter deep below ground level) with the top edge of the earth plate not less than 1.5 meter below normal ground level connected to galvanized earth lead wire 4mm dia by means of bolts, nuts, check nuts and washer of galvanized iron or of steel all as shown in electrical plate No.5 of MES SSR parts-I and including excavation & earth work in any type of soil , disposal of soil , providing alternate layers of charcoal and common salt, construction of PCC earth chamber in mix 1:3:6 type c-1 with 40 mm thick RCC 1:2:4 type B-J cover reinforced with 8mm dia MS bars both ways with lift hook made out of 8 mm dia bar, watering arrangement with funnel and wiremesh and watering pipe of 20mm dia GI light grade and 15mm dia light grade pipe for earth lead protection and testing on completion, complete all as specified and directed.
Supply and fix in repairs Hylem bakelite sheet and providing suitable hole on hylem sheet for fixing of swiches ,sockets and modular plates as per site requirement wall suitable for housing modular accessories of following sizes including taking down the existing:- Make: ISI marked
(a) Hylem bakelite sheet of size ( 5 inch x 5 inch) suitable for 1 or 2 modules 50mm
(b) Hylem bakelite sheet of size ( 8 inch x 5 inch) suitable for 3 modules 50mm.
(c) Hylem bakelite sheet of size ( 6 inch x 9 inch) suitable for 4 modules 50mm.
(d)Hylem bakelite sheet of size ( 9 inch x 11 inch) suitable for 8 modules 50mm.
Note :- Contarcor will provide minimum two nos of electricians and two nos of helper for attending day to day complaints. Contractor's electrician and helper should be available at complaint cell between 9:00 AM to 5:00PM and also provide all T&P for repair/replacement of Lights & point wiring at Wall & ceiling at any Height. No extra cost will be given to contractor for T&P and Ladder etc required for repair/replacent of Lights & point wiring .
Maintenance and servicing to DG set once in a three month including attending faults on call basis for normal repairs including replacement of defective and worn out minor filters gaskets, V- belts, Engine oil, rubber hoses, worm drive clamps, nuts, bolts and cleaning of alternator with vaccum cleaner and attending faults of AMF panels etc, tappet settings if required and greasing of bearings of engine and alternator, checking of batteries, applying petroleum jelly to battery tereminals, adding distilled water checking the oil, coolent levels Auto Manual functions, contact points , timers of capacity 500 KVA DG set installed at Auditoriun Infantry School, Mhow complete all as specified and as directed by Engr- in- Charge.
Note for item No 66.00:- (i) Spares required for maintenance will be measured and paid seprately under relevant items. (ii) Servicing to be carried out as per manufacturer’s specifications/ instructions (iii) The work of maintenance shalll be carried out through respective authorized dealer/ Highly skill operator/ Mechanic and electrician whose certificate shall be produced to Engineer - in - Charge. (iv) Proper record & test results of the same shall be maintained as directed. (v) Work shall be carried out at site at different location
All as per item No 67.00 above but capacity 380 KVA DG set installed at IT DIV.
All as per item No 67.00 above but capacity 320 KVA DG set installed at Auditorium.
All as per item No 67.00 above but capacity 250 KVA DG set installed at MH Mhow.
All as per item No 67.00 above but capacity 200 KVA DG set installed at Filteration plant.
All as per item No 67.00 above but capacity 200 KVA DG set installed at MH City scan.
All as per item No 67.00 above but capacity 180 KVA DG set installed at AMU 10 Mtr Range.
All as per item No 67.00 above but capacity 180KVA DG set installed at HD Enclave.
All as per item No 67.00 above but capacity 160 KVA DG set installed at Kitchen Eqpt YO-Mess.
All as per item No 67.00 above but capacity 160 KVA DG set installed at HD Enclave.
All as per item No 67.00 above but capacity 160 KVA DG set installed at Pump House.
All as per item No 67.00 above but capacity 160 KVA DG set installed at Stn HQ.
All as per item No 67.00 above but capacity 125 KVA DG set installed at Old telephone exchange.
All as per item No 67.00 above but capacity 125 KVA DG set installed at Filteration Plant.
All as per item No 67.00 above but capacity 100 KVA DG set installed at Infantry Library.
All as per item No 67.00 above but capacity 100 KVA DG set installed at KLP Signal centre.
All as per item No 67.00 above but capacity 82.5 KVA DG set at Infantry Museum.
All as per item No 67.00 above but capacity75 KVA DG set at AMU Node-I.
All as per item No 67.00 above but capacity75 KVA DG set at AMU Node-II.
All as per item No 67.00 above but capacity75 KVA DG set at AMU Node-III.
All as per item No 67.00 above but capacity35 KVA DG set at Mhow fort.
All as per item No 67.00 above but capacity 20 KVA DG set installed at Infantry MT.
Supply only Diesel filter element with 'O' ring suitable for 320 KVA to 500 KVA DG set compete all as specified and as directed. Make:- Cummins, Kirloskar, Greaves, Koel (As per DG Set Make).
Supply only Diesel filter element with 'O' ring suitable for 200/ 250 KVA DG set compete all as specified and as directed. Make:- Cummins, Kirloskar, Greaves, Koel (As per DG Set Make).
Supply only Diesel filter element with 'O' ring suitable for 160/180 KVA DG set compete all as specified and as directed.Make:- Cummins, Kirloskar, Greaves, Koel (As per DG Set Make).
Supply only Diesel filter element with 'O' ring suitable for 100/125 KVA DG set compete all as specified and as directed. Make:- Cummins, Kirloskar, Greaves, Koel (As per DG Set Make).
Supply only Diesel filter element with 'O' ring suitable for capacity 82.50/75/35/20 KVA DG set compete all as specified and as directed by Engr-in-Charge. Make:- Cummins, Kirloskar, Greaves, Koel (As per DG Set Make)
Supply only Spin- on filter element for luricanting oil with 'O' ring suitable for 320 KVA to 500 KVA DG set compete all as specified and as directed.Make:- (As per DG Set Make)
Supply only Spin- on filter element for luricanting oil with 'O' ring suitable for 200/ 250 KVA DG set compete all as specified and as directed. Make:- (As per DG Set Make)
Supply only Spin- on filter element for luricanting oil with 'O' ring suitable for 160/180 KVA DG set compete all as specified and as directed.Make:- (As per DG Set Make)
Supply only Spin- on filter element for luricanting oil with 'O' ring suitable for 100/125 KVA DG set compete all as specified and as directed.
Supply only Spin- on filter element for luricanting oil with 'O' ring suitable for capacity 82.50/75/35/20 KVA DG set compete all as specified and as directed by Engr-in- Charge. Make:- (As per DG Set Make)
Supply only by pass filter element with 'O' ring suitable for 380 KVA DG set compete all as specified and as directed.Make:- (As per DG Set Make)
Supply only by pass filter element with 'O' ring suitable for 320 KVA DG set compete all as specified and as directed.Make:- (As per DG Set Make)
Supply only air filter element suitable for 320 to 500 KVA DG set compete all as specified and as directed.Make:- (As per DG Set Make)
Supply only air filter element suitable for 250/200 KVA DG set compete all as specified and as directed. Make:- (As per DG Set Make)
Supply only air filter element suitable for 160/180 KVA DG set compete all as specified and as directed.Make:- (As per DG Set Make)
Supply only air filter element suitable for 125/100 KVA DG set compete all as specified and as directed. Make:- (As per DG Set Make)
Supply only air filter element suitable for capacity 82.50/75/35/20 KVA DG set compete all as specified and as directed by Engr-in-Charge. Make:- (As per DG Set Make)
Supply only Fan Belt complete suitable for 320 to 500 KVA DG set compete all as specified and as directed. Make :- Fenner/Dunlop.
Supply only Fan Belt complete suitable for 250/200 KVA DG set compete all as specified and as directed. Make :- Fenner/Dunlop.
Supply only Fan Belt complete suitable for 160/180 KVA DG set compete all as specified and as directed. Make :- Fenner/Dunlop.
Supply only Fan Belt complete suitable for 125/100 KVA DG set compete all as specified and as directed. Make :- Fenner/Dunlop.
Supply only Fan Belt complete suitable for capacity 82.50/75/35/20 KVA DG set compete all as specified and as directed by Engr-in charge. Make :- Fenner/Dunlop.
Supply only Belt for battery charging alternator complete suitable for 320 to 500 KVA DG set compete all as specified and as directed. Make :- Fenner/Dunlop.
Supply only Belt for battery charging alternator complete suitable for 250/200 KVA DG set compete all as specified and as directed. Make :- Fenner/Dunlop.
Supply only Belt for battery charging alternator complete suitable for 180/160 KVA DG set compete all as specified and as directed. Make :- Fenner/Dunlop.
Supply only Belt for battery charging alternator complete suitable for 125/100 KVA DG set compete all as specified and as directed. Make :- Fenner/Dunlop.
Supply only Belt for battery charging alternator complete suitable for capacity 82.50/75/35/20 KVA DG set compete all as specified and as directed by Engr-in-Charge. Make :- Fenner/Dunlop.
Supply only Rubber Hose pipe set for water circuit with clamps complete suitable for 320 to 500 KVA DG set compete all as specified and as directed.
Supply only Rubber Hose pipe set for water circuit with clamps complete suitable for 250/200 KVA DG set compete all as specified and as directed. Make:- (As per DG Set Make)
Supply only Rubber Hose pipe set for water circuit with clamps complete suitable for 180/160KVA DG set compete all as specified and as directed. Make:- (As per DG Set Make)
Supply only Rubber Hose pipe set for water circuit with clamps complete suitable for 125/100 KVA DG set compete all as specified and as directed. Make:- (As per DG Set Make)
Supply only Rubber Hose pipe set for water circuit with clamps complete suitable for capacity 82.50/75/35/20 KVA DG set compete all as specified and as directed by Engr-in charge. Make:- (As per DG Set Make)
Supply only Engine oil, multi grade premium Genuine oil 20W/ 40 as per manufacturer recommendations in DG sets complete all as specified and as directed. Make :- Indian oil/ Hindustan Petrolium/Castrol/BPCL
Supply and applying Petrolium Jelly (01 Kg plastic sealed container) complete all as specified and as directed. Make :- Indian oil/ Hindustan Petrolium/Castrol/BPCL
Supply and fill distilled water for topping up in lead acid batteries complete all as specified and as directed.
Supply and fill electrolyte of suitable specific gravity for lead acid batteries in sealed container complete all as specified and as directed.
M & L for Battery leads of PVC insulated, multistranded, copper conductor of size 70 sqmm of 1.25 mtr long ach duly fixed with brass clamps, copper lugs suitable for DG set batteries installed at different locations complete including removal of extg unserviceable one complete all as specified and as directed.
M & L for battery teriminal brass clamps including removal of extg unserviceable one compete all as specified and as directed by Engr-in charge.
M & L for disconnecting all electrical connections from DG set charging alternator of any capacity from base plate by opening nuts & bolts keeping aside the alternator for inspection and taking out the to work shop for rewinding including testing & commissioning complete all as specified & directed.
Taking down turbo charger from engine of DG set of any capacity for servicing and replacement of turbo kit complete all as specified and directed.
M & L for water temperature guage including sensor and cable complete as per sample including removal of extg unserviceable one complete all as specified and as directed.
M & L for dismantaling the radiator taking to work shop for overhauling & cleaning, de-scaling with acid, removal of leakage including soldering and welding, brazing as required and renewal of gaskets, nuts, bolts, mounting pads,drain out hoses pipe,clips, etc and refixing its original position for following capacities of DG set complete all as specified and directed.
(a) 20 KVA DG set to 100 KVA DG set
(b) 125 KVA DG set to 200 KVA DG set
(c) 250 KVA DG set to 500 KVA DG set
M & L for repair and calibration of FIP and injectors from authorised dealer for petty repairs to make the FIP functional as per standard calibration procedure and norms including replacement of minor spares, gasket etc for smooth functioning of FIP and refixing its original position including testing at site for following capacities of DG set complete all as specified and as directed. Note :- A certificate to the effect that the calibration and repairs has been carried out by the authorised dealer shall be submitted by the contractor.
(a) 20 KVA DG set to 100 KVA DG set
(b) 125 KVA DG set to 200 KVA DG set
(c) 250 KVA DG set to 500 KVA DG set
M & L for Repair/overhauling of self starting/Exciter system of DG set including replacement of corbon brushes, bearings, bushes, rewinding of armature and field coil etc and varnishing of capacity 24 volts with necessary connections incluing testing and commissioing complete all as specified and as directed.
M & L for Repair/overhauling of self starting system of DG set including replacement of corbon brushes, bearings, bushes, rewinding of armature and field coil etc and varnishing of capacity 12 volts with necessary connections incluing testing and commissioing complete all as specified and as directed.
M & L for repairing of battery charging alternator engine mounted with replacement of any of the unserviceable part such as rectifier with voltage regulator, diode plate, corbon brushes of capacity 24 volts including testing and commissioing complete all as specified and as directed.
M & L for repairing of battery charging alternator engine mounted with replacement of any of the unserviceable part such as rectifier with voltage regulator, diode plate, corbon brushes of capacity 12 volts including testing and commissioing complete all as specified and as directed.
M & L for AVR (automatic voltage regulator) control unit assembly suitable for 20 KVA DG set to 180 KVA DG set including removal of extg unserviceable one compete all as specified and as directed by Engr-in-Carge.
M & L for AVR (automatic voltage regulator) control unit assembly suitable for 200 KVA DG set to 500 KVA DG set including removal of extg unserviceable one compete all as specified and as directed by Engr-in-Charge.
M & L for fuel steel braided pipe with benjo bolts and washers etc of length 30 cm long including removal of extg unserviceable one compete all as specified and as directed by Engr-in-Charge. Make.
M & L for fuel steel braided pipe with benjo bolts and washers etc of length 45 cm long including removal of extg unserviceable one compete all as specified and as directed by Engr-in-Charge.
M & L for fuel steel braided pipe with benjo bolts and washers etc of length 60 cm long including removal of extg unserviceable one compete all as specified and as directed by Engr-in-Charge.
M & L for canopy hinges for auqastic doors with suitable bolts and nuts of DG set including removal of extg unserviceable one compete all as specified and as directed by Engr-in-Charge.
M & L for Anti vibration pads with suitable bolts and washers including removal of extg unserviceable one compete all as specified and as directed by Engr-in-Charge.
M & L for carrying our repairs to AMF panel / Auto and Manual of up to 500 KVA DG set at various instllation inclduing study, tracing out circuit, testing, repalcing all defective parts, rewinding existing power and control wiring with same cables icluding testing and commissioing complete all as specified and as directed. (Note: Spares like Volt meter, CT, power contactor required for repair will be measured and paid under relevant items.
Supply only for digital type frequency meter 96 x 96 mm flush /square pattern including removal of extg unserviceable one compete all as specified and as directed by Engr-in -Charge. Make- L&T/AE or equivalent
Supply only for LED indicator lamps R, Y, B with holder 15 mm screw type including removal of extg unserviceable one compete all as specified and as directed by Engr-in Charge. Make- Rishab/ L&T/AE/Legrand or equivalent
Supply only for CT cast resin type of ratio 400/5 Amps of suitable VA burden including removal of extg unserviceable one compete all as specified and as directed by Engr-in charge. Make:- AE/ L&T/Nutech/Amol
Supply only for CT cast resin type of ratio 200/5 Amps of suitable VA burden including removal of extg unserviceable one compete all as specified and as directed by Engr-in -Charge. Make:- AE/L&T/Nutech/Amol
S & F for CT cast resin type of ratio 100/5 Amps of suitable VA burden including removal of extg unserviceable one compete all as specified and as directed by Engr-in -Charge. Make:- AE/L&T/Nutech/Amol
S & F for Power Contactor 415 Volt, 50 Hz AC suitable for DG set control panel/ AMF panel for following capacity of DG set including removal of extg unserviceable one compete all as specified and as directed. Make:- Simens/L&T/ABB/C&S/ Schneider.
(a) 100 KVA DG set to 250 KVA DG set
(b) 320 KVA DG set to 500 KVA DG set
S & F for Time dealy relay suitable for 20 KVA DG set to 100 KVA DG set including removal of extg unserviceable one compete all as specified and as directed. Make:- Simens/ L&T/ ABB/ C & S
S & F for Time dealy relay suitable for 125 KVA DG set to 500 KVA DG set including removal of extg unserviceable one compete all as specified and as directed. Make:- Simens/L&T/ABB/C & S
M & L for solinoid switch assembly 24 volts suitable up to 500 KVA DG set including removal of extg unserviceable one compete all as specified and as directed by Engr-in charge.
M & L for solinoid switch assembly 12 volts suitable up to 500 KVA DG set including removal of extg unserviceable one compete all as specified and as directed by Engr-in charge.
M & L for self starter assembly 12 volts complete suitable up to 500 KVA DG setincluding removal of extg unserviceable one complete all as specified and as directed. Make:- Lucas/TVS
M & L for self starter assembly 24 volts complete suitable up to 500 KVA DG set including removal of extg unserviceable one complete all as specified and as directed. Make:- Lucas/TVS
M & L for electronic speed control unit assembly 12 volts suitable up to 500 KVA DG set including removal of extg unserviceable one compete all as specified . Make:- Lucas/TVS
M & L for electronic speed control unit assembly 24 volts suitable up to 500 KVA DG set including removal of extg unserviceable one compete all as specified . Make:- Lucas/TVS
M & L for SMPS (system main power supply) type control unit assembly suitable for 12 volts battery charger for including removal of extg unserviceable one compete all as specified .
M & L for SMPS (system main power supply) type control unit assembly suitable for 24 volts battery charger for including removal of extg unserviceable one compete all as specified .
S & F for single phase preventer suitable for operation on 415 Volts 50 Hz AC supply including removal of extg unserviceable one compete all as specified and as directed by Engr-in charge. Make :- L&T/Minilec.
S & F for battery low maintenance lead acid of capacity 12 volts 180 AH with initial charging including removal of extg unserviceable one, all as specified and as directed by Engr-in-Charge. Make:- Exide/AMCO/Amaron
S & F battery low maintenance lead acid of capacity 12 volts 150 AH with initial charging including removal of extg unserviceable one all as specified and as directed by Engr-in-Charge. Make:- Exide/AMCO/Amaron
M & L for welding MS pipe heavy duty 100 mm dia suitable for exhaust manifold of DG set with necessary scraping cutting to size as required and painting with two coats silver paint over a coat of redoxide primer including removal of extg unserviceable one compete all as specified and as directed.
M & L for Engine complete overhauling of DG set capacity upto 500 KVA of Kirloskar/ Crompton Greaves makes by opening the top cover complete including dismatlling the engine head, cylinder liner and piston assembly, crankshaft assembly, radiater fan belt and radiator fan, gear assembly complete removing of engine side for repair/ replacement of parts i.e gasket, washer, 'O' ring all types etc including grinding polishing of crank shaft , head repairing and overhauling valve seat cutting and replacing, valve tapping, head assemble and testing of DG set after necessary repair with and authorised dealer fix at site reassembling of DG set and testing on full load upto entire satisfaction of Engineer in Charge all as directed (Note :- Measure spare parts will be measured and paid seperately under relevent items)
(a) Supply only Piston assembly
(b) Supply only Piston ring set
(c) Supply only full engine gasket
(d) Supply only Main bearing set
(e) Supply only Main cylinder liner
(f) Supply only Main cylinder head copper sleeves
(g) Supply only Lock nut
(h) Supply only Big end bearing
(i) Supply only Timing Belt
(j) Supply only benjo bolt
(k) Supply only Timing belt tension adjuster
(l) Supply only inlet valve
(m) Supply only Exhaust Valve
(n) Supply only head gasket
(o) Supply only oil pump assembly
(p) Supply only Thrust washer
(q) Supply only Crank case gasket
(r) Supply only Head nozzle plug set
S & F for pressure gauge 0 to 7 Kg/ sqcm along with sensor and cables for DG set including removal of extg unserviceable one complete all specified and as directed.
S & F for microprocessor based multifunction controller suitable for DG sets operation of any capacity and showing the various parameters such as volt, ampere, frequency, RPM etc complete as per site requirment including removal of extg unserviceable one complete all specified and as directed.
S & F connecting and testing MCCB in existing DG set Panel of the following capacity, suitable for 415 volts, 50 Hz, with extended terminals type, inter locked to prevent opening when the Switch is in ON Position, connecting and testing complete including removal of exiting unsv all as specified and directed. Make:- L&T/ ABB/ Siemens/ Schneider.
(a) 4 pole 200 Amps with thermal magnetic release breaking capacity 16 KA, Ics=100% Icu
(b) 4 pole 400 Amps with thermal magnetic release breaking capacity 25 KA, Ics=100% Icu
(f) 4 pole 630 Amps with thermal magnetic release breaking capacity 36 KA, Ics=100% Icu
S & F connecting and testing open execution on load change over in existing DG set Panel of the following capacity, suitable for 415 volts, 50 Hz, 630 Amp , 4 pole with extended terminals type, interlocked to prevent opening when the Switch is in ON Position, connecting and testing complete including removal of exiting unsv all as specified and directed. Make:- ABB/ Siemens/ Schneider/Legrand.
Supply and fill genuine coolant in 5 ltrs plastic sealed container for topping up in Radiator of DG set located at different locations as directed by Engr-in-Charge complete all as specified and as directed. Make:- Cummins/Volvoline
M & L for Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron strep 32 x 6 mm as earthing lead by mean of nut/bolt and washer of galvanized iron or steel drawn through 40 mm dia light grade GI pipe as shown in electrical plate no 3 of SSR part I of 2009 including necessary excavation and earth work GI pipe 20mm dia light grade for watering PCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to panel board as indicated including testing complete.
M & L for disconnecting all electrical connections from Coupling and flywheel DG set alternator of any capacity from base plate by opening nuts & bolts keeping aside the alternator for inspection and taking out the to work shop for rewinding including testing & commissioning complete all as specified & directed.
Rewinding of alternator field coil with super enamelled copper winding wire of class 'F' insullation as per existing size and gauge including heating, varnishing and testing of size up to 500 KVA complete all as specified and as directed.
Vinayak Trading House (BID ID -3185827)
Auto Traders (BID ID -3185244)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .