Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.0 LAccepted-AOC 307 SADAR BAZAR LUCKNOW UP 226002 | LUCKNOW | UTTAR PRADESH | 226002 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹38.3 L+₹3.7 L (10.5%)Rejected-Finance | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹45.4 L+₹10.7 L (30.9%)Rejected-Finance | L3 | Rejected-Finance Being L3 | |
| 4 | L4₹49.2 L+₹14.5 L (41.8%)Rejected-Finance | L4 | Rejected-Finance Being L4 |
| Sl No | Description | Qty | Unit | M/s Vatsh Raj and co L1 | M I & CO. L2 | GYAN ENTERPRISES L4 | OM NAMAH SHIVAY ENTERPRISES L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | Taking down existing ACSR conductor from pole, including disconnection, from LT Overhead electric line, after taking proper written shut down permission, all as specified and directed by Engr-in-Charge. | 8 | Qtl | 100 ₹800 | 500 ₹4,000 | 700 ₹5,600 | 1 ₹8 Lowest |
| 2.00 | Dismantling taking down old cross arms, clamps, braces etc of any section from LT electric pole including nuts, bolts, washers complete all as specified and as directed by Engineer-in-Charge. | 6 | Qtl | 150 ₹900 | 500 ₹3,000 | 1,000 ₹6,000 | 1 ₹6 Lowest |
| 3.00 | Dismantling of GI wire any type and any size from LT electric pole complete all as specified and as directed by Engineer-in-Charge. | 1.2 | Qtl | 2.5 ₹3 | 3,400 ₹4,080 | 1,000 ₹1,200 | 1 ₹1.2 Lowest |
| 4.00 | Dismantling of existing insulators any types and any size from LT electric pole all as specified and directed by Engr-in-Charge | 240 | Each | 1 ₹240 Lowest | 25 ₹6,000 | 15 ₹3,600 | 1 ₹240 Lowest |
| 5.00 | Dismantling of stay assembly any type and any size complete all as specified and as directed by Engineer-in-Charge. | 4 | Each | 10 ₹40 | 120 ₹480 | 900 ₹3,600 | 1 ₹4 Lowest |
| 6.00 | Excavation in trenches not exc. 1.5 m wide and not exc 1.5 metre deep in soft / loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom surface to required level all as specified and directed by Engineer-in-Charge. | 1,070 | Cum | 90 ₹96,300 | 70 ₹74,900 Lowest | 170 ₹1,81,900 | 150 ₹1,60,500 |
| 7.00 | Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick using excavated soil complete all as specified and as directed. | 623 | Cum | 55 ₹34,265 Lowest | 65 ₹40,495 | 70 ₹43,610 | 126 ₹78,498 |
| 8.00 | Removing excavated soil n.exc 50 m and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and as directed. | 446 | Cum | 65 ₹28,990 | 60 ₹26,760 Lowest | 65 ₹28,990 | 125 ₹55,750 |
| 9.00 | M & L for dry Sand cushioning in trenches for protection of cable including watering and consolidation all as specified and directed.
Note: Punned thickness (18 cm) shall be consider for measurement purpose | 321 | Cum | 450 ₹1,44,450 | 260 ₹83,460 Lowest | 425 ₹1,36,425 | 450 ₹1,44,450 |
| 10.00 | M&L laying well burnt old size bricks, sub class "B" bricks, straight or curved on plan, laid flat with width equal to length of brick, laid dry over electric cable for protection complete all as specified & directed by Engr-in-Charge. | 30 | Per thousand Nos | 5,500 ₹1,65,000 | 4,500 ₹1,35,000 Lowest | 5,300 ₹1,59,000 | 5,200 ₹1,56,000 |
Tender Value
₹44.6 L
EMD Value
₹89,180
Closing Date
18 Oct 2025, 6:00 pmClosed
GE E/M Lucknow
Garrison Engineer E/M, 36 LBS Marg, Lucknow Cantt, Lucknow (U.P.) PIN 226002
SPL REPAIR FOR CONVERSION OF OH CONDUCTOR WITH UNDERGROUND CABLE INCL CONNECTED ITEMS AT 1806 PNR UNIT AND HQ CC RVS AND PROVN OF 8 X 1.5 TON HOT AND COOL TYPE SPLIT AC WITH VOLTAGE STAILIZER ELECTRICAL WIRING FOR RADIATION ONCOLOGY DEPT OF CH (CC)
2025_MES_733002_1
GE/EM/LKO/EXT(ELECT)/T-40 OF 2025-2026
Open Tender
Miscellaneous Works
Item Rate
180 days
Lucknow
As per NIT
8 documents required · 8 mandatory
₹500
GE E/M Lucknow
₹89,180
Yes
3 Dec 2025
27 Sept 2025
20 Oct 2025
27 Sept 2025
18 Oct 2025
11 Oct 2025
Amount
Taking down existing ACSR conductor from pole, including disconnection, from LT Overhead electric line, after taking proper written shut down permission, all as specified and directed by Engr-in-Charge.
Dismantling taking down old cross arms, clamps, braces etc of any section from LT electric pole including nuts, bolts, washers complete all as specified and as directed by Engineer-in-Charge.
Dismantling of GI wire any type and any size from LT electric pole complete all as specified and as directed by Engineer-in-Charge.
Dismantling of existing insulators any types and any size from LT electric pole all as specified and directed by Engr-in-Charge
Dismantling of stay assembly any type and any size complete all as specified and as directed by Engineer-in-Charge.
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 metre deep in soft / loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom surface to required level all as specified and directed by Engineer-in-Charge.
Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick using excavated soil complete all as specified and as directed.
Removing excavated soil n.exc 50 m and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and as directed.
M & L for dry Sand cushioning in trenches for protection of cable including watering and consolidation all as specified and directed. Note: Punned thickness (18 cm) shall be consider for measurement purpose
M&L laying well burnt old size bricks, sub class "B" bricks, straight or curved on plan, laid flat with width equal to length of brick, laid dry over electric cable for protection complete all as specified & directed by Engr-in-Charge.
All as per item No 10 here-in-before but using old bricks obtained under serial item No 6 here in before.
Deployment of tools & manpower for Boring /drilling (Horizontal) manually / mechanically under existing road max 10 M in width) suitable for passing pipe of any description of dia 40 to 100 mm complete all as specified and directed by Engineer in Charge
M&L for 40 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable complete all as specified and directed by Engr-in-Charge.
M&L for 50 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable complete all as specified and directed by Engr-in-Charge.
Material & Laying, jointing and testing of LT under ground electric power cable crossed linked polyethylene (XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 95 sqmm cross sectional area, 3.5 core, complete all as specified laid in trenches / laid under floor or fixed naked with walls / on poles/ in ducts / in GI pipes etc. with and including MS Clamps, nuts, bolts, washers complete all as specified and directed. Note :- Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items.
All as per item No 15 above but LT under ground cable of size 70 Sqmm 3.5 core
All as per item No 15 above but LT under ground cable of size 50 Sqmm 3.5 core
All as per item No 15 above but LT under ground cable of size 25 Sqmm 4 core
All as per item No 15 above but LT under ground cable of size 35 Sqmm 3.5 core
All as per item No 15 above but LT under ground cable of size 16 Sqmm 4 core
All as per item No 15 above but LT under ground cable of size 10 Sqmm 4 core
S&F Factory made RCC cable route marker with mix of concrete 1:2:4, size 750 mm x 300 mm x 75 mm (length x width x thickness), dully engraved "LT Cable" including applying two coat synthetic enamel paint in brown colour, over one coat primer, and engraved letter painted with black synthetic enamel paint, fixed in ground including excavation, earthwork, and removal of surplus soil complete all as specified & directed By Engineer-in-Charge.
S&F Cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 6 to 16 Sqmm 3.5 / 4 core, XLPE armoured aluminium conductor LT cable.
S&F Cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core 25 to 50 Sqmm XLPE armoured aluminium conductor LT cable.
Material and labour for plain cement concrete 1:2:4, type B-2, using 40 mm graded stone aggregates for filling of cutting of roads / path / hardstanding etc complete all as specified and as directed by Engineer-in-Charge.
M&L for cutting of PCC / Hard standing / WBM road not exceeding 20 cm in width not exceeding 30 cm in depth for passing of LT cable complete all as specified and directed .
S&F of weather proof pole mounting PVC junction box, base and door of junction box made out of SMC having outside dimension 333 x 233 x 120 mm, inside dimention 300 x 200 x 105 mm, single door front openable provided with hinged cover and locking arrangements with 4 Nos aluminium bas bar 63 Amps, mounted on porcelin insulator including M&L for MCB SP 6 Amp -1No, fixed on box in Din rail complete with electrical connection fixed to pole with suitable size FI clamp nut bolts and washer including embossing / painting of danger notice of size not less than 10 cm x 7.5 cm with letters, figures and conventional skull and bones in signal red colour on front face of junction box body Complete all as directed by Engr-in-Charge.
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by mean of GI wire 4 mm dia by means of bolts, nuts check nuts and washers of GI or steel and connecting to earthing test point, main switch board, testing on completion..........
Item no 28 contd..... .......... including PCC cover and frame, PCC (1:3:6) type C-2 as in earthing pit, MS funnel with wire mesh GI pipe 20 mm dia light grade for watering and GI pipe 15 mm dia light grade for the protection of GI wire from earth pit to earth point complete including necessary excavation and earth work in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50 m all as specified as shown in electrical plate No 3 SSR Part-I. PCC chamber shall be constructed at least one metre away from the earth pit and GI pipe fittings for watering shall be provided up to chamber and cost of the same is deemed to be included in the rate of earthing. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by mean of GI strip of size 32 x 6 mm by means of bolts, nuts check nuts and washers of GI or steel and connecting to earthing test point, main switch board, testing on completion including PCC cover and frame, PCC (1:3:6) type C-2 as in earthing pit, MS funnel with wire mesh GI pipe 20 mm dia light grade for watering and GI pipe 40 mm dia light grade for the protection of strip from earth pit to earth point complete.............
Item no 29 contd..... .......... including necessary excavation and earth work in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50 m all as specified as shown in electrical plate No 3 SSR Part-I. PCC chamber shall be constructed at least one metre away from the earth pit and GI pipe fittings for watering shall be provided up to chamber and cost of the same is deemed to be included in the rate of earthing. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
Supply, installing, testing and commissioning of factory made, tested, CPRI approved overall powder coated, LT Panel boards as per the standards IEC 61439-1 &2 ,cubical compartmentalized, out door type double door, plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain / SMC insulator. The panel shall be dust and vermin proof IP-54 class protection and outer shell made of (not less than 3.00 mm) CRCA MS sheet, inner shell made of (not less than 1.6 mm thick) CRCA MS sheet , 50 x 50 x 6 mm thick MS angle iron frame work, the cubical have bottom channel of size 75 x 40mm duly, front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size and comprising of the following:-
(a) Incoming :- (i) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii) Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTs ratio 250/5 A ,class 1, ISI marked -01 sets of three (iv) Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators.
(b) Outgoing (i) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 36 KA thermal magnetic release - 03 Nos (ii) MCCB 4 pole , 63 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 01Nos (iii) MCCB 4 pole , 40 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 01 Nos (iv) MCCB 4 pole , 35 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 01 Nos
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii)The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer.
Note - (iv) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site. A - Construction Requirement: (a) Strength of material and parts (b) Degree of protection of enclosures (c) Clearances (d) Creepage distances (e) Protection against electric shock and integrity of protective circuits (f) Incorporation of switching devices and components (g) Internal electrical circuits and connections (h) Terminals for external conductors B - Performance Requirement: (a) Di-electric properties (b) Verification of temperature rise (c) Short circuit withstand strength (d) Electromagnetic compatibility (e) Mechanical operations
All as per item No 30 above but LT Panel board comprising following in coming & outgoing switchgear:-
(a) Incoming :- (i) MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 25 KA, with thermal magnetic release - 01 Nos (ii) Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTs ratio 125/5 A ,class 1, ISI marked -01 sets of three (iv) Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 250 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 63 Amps,50 Hz,415 Volts, 25 KA, with thermal magnetic release - 02 Nos (ii) MCCB 4 pole , 40 Amps,50 Hz,415 Volts, 25 KA, with thermal magnetic release - 02Nos
All as per item No 30 above but LT Panel board comprising following in coming & outgoing switchgear:-
(a) Incoming :- (i) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii) Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTs ratio 160/5 A ,class 1, ISI marked -01 sets of three (iv) Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 300 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 25 KA, with thermal magnetic release - 01 Nos (ii) MCCB 4 pole , 63 Amps,50 Hz,415 Volts, 25 KA, with thermal magnetic release - 01 Nos (iii) MCCB 4 pole , 40 Amps,50 Hz,415 Volts, 25 KA, with thermal magnetic release - 02 Nos
All as per item No 30 above but LT Panel board comprising following in coming & outgoing switchgear:-
(a) Incoming :- (i) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 25 KA, with adjustable thermal magnetic release - 01 Nos (ii) Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTs ratio 100/5 A ,class 1, ISI marked -01 sets of three (iv) Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 250 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 63 Amps,50 Hz,415 Volts, 25 KA fixed thermal magnetic release - 02 Nos (ii) MCCB 4 pole , 40 Amps,50 Hz,415 Volts, 25 KA fixed thermal magnetic release - 01 Nos
Supply, installing, testing and commissioning of factory made, tested, CPRI approved overall powder coated, out door type busbar panel board (Dimention of Cubical / enclosure not less than 600 mm x 450 mm x 450 mm) made out of ( not less than 3.00 mm thick) MS sheet and MS angle section 50 x 50 x 6 mm suitable for 3 phase 4 wire 415 Volt, 50 Hz, powder coat painted comprising of the following:- (a) FP, Aluminium bus bar 250 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Incoming MCCB 125 Amps 25 KA, 415 Vots, 50 Hz, FP. – 1 No (c) LED Indicator lamp RYB - 01 set of three. d) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
All as per item No 34 above but Busbar Panel comprising following in coming & outgoing switchgear:- (a) FP, Aluminium bus bar of suitable size insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Incoming MCCB 100 Amps 25 KA, 415 Vots, 50 Hz, FP. – 1 No (c) LED Indicator lamp RYB - 01 set of three.
Supply and fix of MCCB FP 100 Amps, 25 kA, 415 Volt AC, 50 Hz, complete with sheet metal enclosure of 1.6 mm thick MS sheet factory made with powder coat paint including connecting with existing system with existing cablling network including making good disturbed surfaces complete all as specified and directed. Note : The cost of suitable size fastner/Nut bolts required at site for fixing of cubical is deemed to be included in the quoted rate by the contractor.
Supply and fix MCCB FP 63 Amps, 25 kA, 415 Volt AC, 50 Hz, complete with sheet metal enclosure of 1.6 mm thick MS sheet factory made with powder coat paint including connecting with existing system with existing cablling network including making good disturbed surfaces complete all as specified and directed. Note : The cost of suitable size fastner/Nut bolts required at site for fixing of cubical is deemed to be included in the quoted rate by the contractor.
Supply & fix of nature switch (using Infrared Sensor based technology) based automatic street light contol panel. Panel should be suitable enough to take 3 - Phase load of 8 KW. Nature switch operation should be based on LUX level of natural light. Required illuminance for switching ON is < 60 Lux and for switching OFF > 10 Lux level. The Sensor along with suitable Power Contactor(s) and Incoming - Outgoing MCBs should be enclosed in a pole / wall mountable Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Enclosure conforming to IP54 including mounting bracket, cable glands, openable doors with lock complete all as specified & directed by Engr-in-Charge.
M&L for Preparation of old painted surfaces of LT steel tubular pole 9 mtrs long and applying one coat aluminium paint from bottom to top and painting up to 1.5 mtr height from top of PCC coping with synthetic enamel paint one coat in black and Yellow / white alternate strip including re writing pole numbering in 8 cm height with one coat synthetic enamel paint complete all as specified & directed by Engineer –in-Charge.
Supplying, transporting, erecting Steel tubular swaged poles type 410 SP-31 ( 9.0 metres long) complete with cast iron base plate, finial, taper plug, bolts, nuts and screws as specified, including necessary excavation and earth work, PCC 1:4:8 type D2 in foundations below pole, PCC 1:3:6 type C2 around poles and PCC 1:3:6 type C1 as in plinth block, disposal of surplus soil to a distance not exceeding 50 m and depositing where directed, the exposed surface of steel tubular poles shall be painted with two coat of aluminum paint over a coat of red oxide, embaded portion of the pole shall be painted with one coat of bituminous paint. 05 Nos black and Yellow alternate strip with two coat of synthetic enamel paint shall be painted up to the the height of 1.5 M from copping of the pole including numbering on pole in black colour synthetic enamel paint complete all as specified and directed.
All as per Item No 40 above but fixing of Steel tubular swaged poles type 410 SP-31 ( 9.0 metres long) after taking down old pole:-
Supply & fix GI brackets made of 40 mm nominal bore GI pipe medium grade of required length not less than 1.5 M long, mounting brackets made out of Mild steel FI 40 x 6 mm of required shape ( two Nos) duly fitted with Mild steel nuts, bolts and washers and painting with two coats of synthetic enamelled paint over one coat of red oxide primer and fixed to pole / walls etc complete all as specified & directed by Engr-in-Charge.
All as per Item No 40 above but fixing of GI bracket after taking down old bracket.
Supply and fix of 60 W LED street light fitting with mandatory driver set having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embaded PC cover / IP lens, street light should have IP 66 protection, impact resistance of IK 07 , Lumen efficiency of LED not less than 110 lumen per watt system efficency ,power factor >0.95, THD<10% at Full load CRI> 70% ,street light should have built in potted electronic LED driver with, lower THD, open circuit protection, over voltage protection, surge voltage protection, and provided with company LOGO ingraved on housing of the street light complete all as specified and directed by Engr -in-Charge. Note :-The contractor should take approval of techincal specification of luminaries and driver from department before procurement .
All as per Item No 44 above but fixing of street light fitting after taking down old light fitting.
Supply drawing, connecting and testing of 3 core, 1.5 Sqmm PVC insulated and PVC round sheathed` copper conductor (flexible ) industurial cable, 1100 Volts conforming to IS 694 in steel tubular poles from Junction box to street light fitting including providing suitable copper lugs all as specified and directed by Engr-in-charge.
Supply, installation, commissioning and testing, Hot and Cool, inverter type, high wall split Air Conditioner of capacity 1.5 TR with digital invertor rotary compressor, filter, auto clean function, indoor sound level 32 db., front panel display, wireless LCD remote, precoated aluminium fins, 477 cfm air circulation, auto fan speed, 3 star rated, electric driven suitable for working on 230 volts, single phase 50 Hz supply with cardless remote complete including cutting of wall, providing stand for out door unit and making good disturbed surface of wall etc complete, all as specified and directed and details as under.
(a) Fixing the indoor unit on wall with grouting nuts, cutting groove/ hole to wall for gas pipe & water drainage pipe. (b) S&F cutting, bent to shape copper refrigerant pipe (up to 6 meter length ) of appropriate size with insulation from outdoor unit to indoor unit by cutting holes to wall including brazing to copper pipe fixing union including making good disturbed surfaces as existing. (c) S&F PVC pipe 20 mm Dia transparent flexible heavy duty for water drainage pipe up to 06 RM length. (d) Insulation of both the copper pipes with insulating material. (e) Charging of correct qty of refrigerant gas after necessary / fixing of both the outdoor/ indoor unit and testing complete. (f) All other connected civil work, like hole cutting & other misc. work reqd for split AC for proper functioning as directed by EIC. (g) Outdoor unit Shall be fixed wall mounted stand and quoted rates shall be deem to include cost of same (h) Plug to provided by contractor with wire.
Material & Labour for sub main wiring with 2 run single core multistranded copper conductor cable, of size 4 Sqmm, PVC insulated, unsheathed, fire retardant, low smoke (FRLS) 1100 Volts grade, drawn through and including PVC casing & caping not less than 20 mm wide with all necessary fitting and including one run single core multistranded copper conductor cable, of size 4 Sqmm, PVC insulated, unsheathed, fire retardant low smoke (FRLS) 1100 Volts grade, as earth wire, fixed on wall / ceiling complete. Note: (i) 2 Runs of main cable and one run earth wire with casing & caping conduit will be measured as one RM for payment. (ii) Extra length of cables / wire required for connection to MCBs shall be deem to include in rate quoted by contractor for per unit.
S&F sheet metal enclosures with socket plug top and MCBs with a two pin and earth plug and socket complete with including one single pole MCB 20 Amps C curve complete all as per specified and directed
S&F Voltage stabilizer for automatic operation single phase naturally air cooled indoor type and designed for input variation between 170 volts to 270 volts, 4 Kva capacity and time delay 3 minutes + 20 sec, with output voltage stabilize at 230 volts with accuracy of ± 2.5% complete all as specified & directed.
M I & CO. (BID ID -3459240)
OM NAMAH SHIVAY ENTERPRISES (BID ID -3458073)
GYAN ENTERPRISES (BID ID -3458839)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.33 MB
BOQ_820722.xls
BOQ • 0.42 MB
Tender40.pdf
Tender Documents • 1.11 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .