| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹92.0 LAccepted-AOC | L1 | Accepted-AOC WORK AWARDED | |
| 2 | L2₹94.8 L+₹1.5 L (1.56%)Rejected-Finance NO 1 2 BIG STREET SAKKARAMALLUR VILLAGE POST ARCOT TALUK RANIPET DISTRICT 632 511 | TIRUVANNAMALAI | TAMIL NADU | 632511 | L2 | Rejected-Finance SECOND LOWEST | |
| 3 | Rejected-Technical SFNO 73 UTHUKULI ROAD MANNARAI TIRUPUR | TIRUPPUR | TAMIL NADU | 638051 | - | Rejected-Technical EA Licence not produced |
Tender Value
₹92 L
EMD Value
₹56,000
Closing Date
9 Apr 2025, 3:00 pmClosed
SUPERINTENDING ENGINEER
OFFICE OF THE SE., PWD BUILDINGS CIRCLE VELLORE
Provision of RMG Panel (HT Line), Transformer and MVC Panel arrangements to the 250 Bedded Muthamizh Arignar Kalaignar Centenary Hostel building at Perumugai in Vellore District
2025_PWD_537721_1
27/VLR-CLE/24-25-1/18.03.2025
Open Tender
Electrical Works
Lump-sum
120 days
PERUMUGAI IN VELLORE DISTRICT
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹56,000
24 Jul 2025
3 Apr 2025
9 Apr 2025
3 Apr 2025
9 Apr 2025
3 Apr 2025
Amount
6.TP ND IDMT 2OC + 1 EF Relay similar like Megawin type MCDG 31 Master trip Relay Megawin MVAJH 13 (Incom-1No & Out-1 No), 7. Breaker ON/OFF/Auto Trip/Healthy/Spring Charged Indication Lamp LED Type, 8. Phase Indication Lamps R,Y,B(Incomings 3Nos), 9.Control Wiring, 10.800Amps Copper Bus bar PVC Sleeved and required panel copper earthing., 11.Control switch TNC (Incoming-1 No, Outgoing -1No), 12.Trip Circuit healthy Push Button(Incoming-1 No, Outgoing -1No), 13.Common for Switch gear, MCB's for AC DC Control, Heater ON/OF Switch with space Heater and thermostat Single phase switch socket, cubicle illumination lamp, Disconnecting type terminal Block.etc., 14.MS Sheet enclosure for Indoor Installations Powder.
Type ONAN type Transformer: Supply, erection, testing and Commissioning of 630 KVA 22KV/ 433V,copper wound off load tap changing copper wound Indoor type distribution transformer ONAN type of cooling conforming to relevant IS 1180- Level 2 and fitted with the following and standard accessories. (A) HV cable end box suitable for connecting 3 core 300 sq.mm11KVXLPE HT cable., (B) LT Cable end box suitable for connection 4 runs of 3 ½ x 300 sq.mm LTUG cables., (C) Tapping on primary winding for voltage variation +5%to -5% steps 2.5%., (D)Neutral on L.V. side, (E)The transformer should be supplied with first filling of oil All removable covers shall be provided with weather proof, hot oil resistant, resistance gasket to prevent leakage of water into core and oil from the tank (Make: Voltech/ CREL or equivalent).
Design, Supply, erection, testing and commissioning of 1250A MV panel board suitable for operation on 415 V 3 phase, 50 Hz A.C supply, dust and vermin proof and accommodating the following ACB as Incomer unit with the following items of work complete to satisfy the latest IE rules and CEIG guidelines with Bus bar chambers, Main switches chambers and cable entry chambers. Bus bar chamber: Supply and fixing of suitable bus bar chamber made up of 16SWG MS sheet steel(1.8mm) with 3” X 1/2” tinned copper bus bar for 3 phases and neutral (75mm x 12mm) and 2 Nos. of earth bus of size 1” X 1/4 tinned copper bus(25mm x 6mm) on suitable bus bar insulator(Epoxy insulator) with maximum creepage distance and supported on MS Base channel frame work of size 18*3*2–1Set. Main Switches Chamber: Incoming (1)Supply and fixing of 1 No. 1250A 4pole Draw out ACB of Microprocessor board EDO Type ( Cat. no:SL96074) basic rating 4 pole 433V LT ACB confirming to IS13947–2 IEC 60947–2 with suitable capacity and breaking capacity of drawout 65 KA breaking capacity with all accessories for standard horizontal manual draw out type ACB equipped with auxiliary contacts and all accessories for closing and opening operation with Microprocessor Based SR 18 G relay, over current trip device adjustable to LTD, STD and release for over current protection UV release with time delay, EF release short circuit protection, Mains CTs for 3 phases lockout, features, separate mold base for each pole for easy maintenance all relevant protection safety accessories as per CEIG, IE rules in force with inter connection and terminations as required in specification.
Outgoing (1)Supply and fixing of 800A TPN Double break switch with HRC Fuse—1 Nos, (2) Supply and fixing of 630A TPN Double break switch with HRC Fuse—3Nos, (3) Supply and fixing of 400A TPN Double break switch with HRC Fuse—3 Nos, (4)Supply and fixing of 250A TPN Double break switch with HRC Fuse—4 Nos. Inter connecting the all LT ACB’s and Switches to bus bar with suitable insulated tinned copper flats and painting/PVC sleeve color coding of phases and neutral indication. Double Earth connection of the switches and ACB’s to earth bus using suitable tinned copper flats by 2 runs of 1” X 1/4”. Supply and fixing of RYB LED lamp arrangements with toggle switches to control each phases and with rigid connection in suitable separate compartments within the cubicle as per CEIG rules with 1set, supply and fixing Electronic Trivector meter EC,300N class 0.5 flush mounting L&T or equivalent make–ModelER300N. Supply and fixing of danger board with Siemens grey powder coating with super scribing the names of places to which supply is fed feeder sizes of cables direction of cables etc. Erection of panel board complete with suitable foundation bolts and nuts including suitable M.S Channel, concreting ,testing and commissioning (L&T,C&S,SIEMENS,ABB)
Design, Supply, erection, testing and commissioning of 800A 4 pole Draw out ACB of Microprocessor board EDO Type panel board suitable for operation on 415 V 3 phase, 50 Hz A.C supply, dust and vermin proof and accommodating the following ACB as Incomer unit with the following items of work complete to satisfy the latest IE rules and CEIG guidelines with Bus bar chambers, Main switches chambers and cable entry chambers. Bus bar chamber: Supply and fixing of suitable bus bar chamber made up of 16SWG MS sheet steel(1.8mm) with 2” X 1/2” tinned copper bus bar for 3 phases and neutral (50mm x 12mm) and 2 Nos. of earth bus of size 1” X 1/4 tinned copper bus(25mm x 6mm) on suitable bus bar insulator(Epoxy insulator) with maximum creepage distance and supported on MS Base channel frame work of size 10*3*2–1Set. Main Switches Chamber: Incoming (1)Supply and fixing of 1 No. 800A 4pole Draw out ACB of Microprocessor board EDO Type ( Cat. no:SL96072), basic rating 4 pole 433V LT ACB confirming to IS13947–2 IEC 60947–2 with suitable capacity and breaking capacity of drawout 65 KA breaking capacity with all accessories for standard horizontal manual draw out type ACB equipped with auxiliary contacts and all accessories for closing and opening operation with Microprocessor Based SR 18 G relay, over current trip device adjustable to LTD, STD and release for over current protection UV release with time delay, EF release short circuit protection, Mains CTs for 3 phases lockout, features, separate mold base for each pole for easy maintenance all relevant protection safety accessories as per CEIG, IE rules in force with inter connection and terminations as required in specification.
Outgoing : (1)Supply and fixing of 630A TPN Double break switch with HRC Fuse—2 Nos, (2) Supply and fixing of 400A TPN Double break switch with HRC Fuse—3 Nos. Inter connecting the all LT ACB’s and Switches to bus bar with suitable insulated tinned copper flats and painting/PVC sleeve color coding of phases and neutral indication. Double Earth connection of the switches and ACB’s to earth bus using suitable tinned copper flats by 2 runs of 1” X 1/4”. Supply and fixing of RYB LED lamp arrangements with toggle switches to control each phases and with rigid connection in suitable separate compartments within the cubicle as per CEIG rules with 1set, supply and fixing Electronic Trivector meter EC,300N class 0.5 flush mounting L&T or equivalent make–ModelER300N., Supply and fixing of danger board with Siemens grey powder coating with super scribing the names of places to which supply is fed feeder sizes of cables direction of cables etc. Erection of panel board complete with suitable foundation bolts and nuts including suitable M.S Channel, concreting ,testing and commissioning (L&T,C&S,SIEMENS,ABB)
Supply and Clamping of 3C x 240 Sq.mm. 11 KV HT XLPE cable in a suitable 6" duro pipe to be excavated at a depth of 0.75 metre and covering the cable completely and refiling the earth to make good.(Make Gloster/Havells/ Polycab). (From 2 Pole Str. to VCB Panel)
Supply and Laying of 3C x 240 Sq.mm. 11 KV HT XLPE PVC cable with aluminium conductors on wall with MS clamp with necessary supports or in a existing trench including removing and relaying the cement slab. (From VCB To Tr. 1) (Make Gloster/Havells/ Polycab)
Supply and Providing cable end termination for 11KV 3 core 240 Sqmm XLPE HTUG cable with necessary Indoor type heat shrinkable joint kit and accessories (Make: Raychem or Equivalent)
Supply and Providing cable end termination for 11KV 3 core 240 Sqmm XLPE HTUG cable with necessary Outdoor type heat shrinkable joint kit and accessories (Make: Raychem or Equivalent)
Supply and laying of 4 runs of 31/2 x 300 sqmm size of PVC armoured LTUG cable in a trench tobe excavated at a depth of 0.75 Mtr. And puttin 0.15 mtr. layer of sand and covering the cable completely with concrete trough and sand and refilling the earth to make good. ( From transformer to MV panel)
Supply and clamping of 4 runs of 31/2 x 300 sqmm of PVC armoured LTUG cable on post on wall with MS clamp.
Supply and fixing of brass cable gland for 3 1/2 x 300 sqmm PVC LTUG cable with eart connection.
Supply and providing cable end termination of 3 1/2 x 240 sqmm PVC LTUG Aluminum armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection
Supply and laying of 2 runs of 31/2 x 300 sqmm size of PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 Mtr. And puttin 0.15 mtr. layer of sand and covering the cable completely with concrete trough and sand and refilling the earth to make good. ( From MV panel to Essenal & Non Essenal Panel at 'B' Block and for ATS to MV Panel))
Supply and clamping of 2 runs of 31/2 x 300 sqmm of PVC armoured LTUG cable on post on wall with MS clamp..
Supply and frxing of brass cable gland for 3 1/2x185 sqmm PVC armoured LTUG cable with earth connection
Supply and clarnping of 3.5x185sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps. ( From Main Panel to Laundry)
Supply and laying of 3.5x185sq.mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt. Layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good.
Supply and providing cable end termination of 3-1/2x185 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and run of 1" x 1/8" (25mmx3mm) tinned copper flat with necessary clamps/supports on all / floor/ ground for earth connection.
Supply and run of 1" x 1/4" (25mmx6mm)copper flat for earth connection.
Supply and run of 1 of No. 8 SWG hard drawn copper conductor for earth connection.
Earthing as per ISI specification with an earth electrode of 2.1 metre Class "B" GI pipe of dia not less than 40 mm with copper earth plate of 125 mm x 50 mm x 6 mm with necessary funneling arrangements with necessary masonry work and with 38 mm RCC cover slab for the brick masonry.
Supply and erection of 200 KVAR 415/440Volts 50Hz 3 Ph automatic power factor correction panel, 8 stage, (at 0.95 lag), made up of powder coated, 14/16 SWG CRCA sheet steel enclosure with 1 1/2" x 1 1 1/2" x 1/2" AI Frame work with RCC concreting foundation and bolted to masonry pedestal with 400A triple pole MCCB as incoming (L&T/Siemens/C&S) with Delta Connected capacitors (BCH/EPCOS) MOO Type operating in multiple stage with 3 current and Voltage Transducers (CVT) at the phases simultaneously to activate the desired power factor switching time between steps 120 seconds, switching off time in case of fault 3 seconds with a LCD display to show the following Parameters. (A)Vr – R phase Line Voltage, (B)Vy – Y phase Line Voltage, (C)Vb – B phase Line Voltage, (D)Ir – R phase Line current, (E)Iy – Y phase line current, (F)Ib – B phase Line Current, (G)KW – Present Kilo Watts, (H)RKVA – Present KVAR Demand, (I)KVA – Present KVA, (j)PF – Present Power Factor, (K)Number of Capacitor bank ON/OFF, (L)Provision to indicate the imbalanced load, Provision to indicate the change in phase Sequence The APFC Panel Should also with built in protection For high Voltage/Low Voltage cut off, single phase Preventer in current line surge line surges, Current Limiters, Current Sensor, etc., with connection complete and as per the relevant IE Rules. Eight Stages of Automatic Power Factor control panel is necessary connection.
Provision towards preparation of site plan, physical layout, electrical line schematic diagram HT side ,5 sets getting drawing approval from C E I G authority (Measures safety to electricity) regulation, preparation of completion report ,Rectification report, preparation of one set approved drawing and copy of safety certificate in a neat frame work and payment of CEIG 's inspection fees including supporting staff for availing service connection.
Towards charges for safety accessories, measuring instruments and tools. Safety Accessories for 11 KV-substation First Aid Box-3 Nos, 4 Fire Bucket with stand -3 Set. Rubber Mat 1m X 2m - 10 Nos. Fire Extinguisher-DCP- 5 Kg’s - 6 Nos. Hand Gloves in glass frame- 4 Nos. (2 pair) First Aid Chart Tamil and English - 3 Nos. Earth Discharge Rod-1 No Danger Board -6Nos.
SURESHBABU (BID ID -1286015)
GUNASEKARAN (BID ID -1286588)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .