| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAdmitted-Finance B1 114 CHAND BIHARI NAGAR KHATIPURA ROAD JAIPUR RAJASTHAN 302012 | JAIPUR | RAJASTHAN | 302012 | ₹1.2 Cr | L1 | Admitted-Finance |
| Sl No | Description | Qty | Unit | TAPANUKULA PRIVATE LIMITED L1 |
|---|---|---|---|---|
| 1.00Supply, installation, testing and commissioning of factory fabricated Double Skinned DX Coil Air- handling unit fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm polished SS sheet inside complete with supply & exhaust blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters for both supply & exhaust fan motor, power control panel with necessary switchgears incoming & outgoing for VFD, HRW & humidifier, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 8 row cooling & 2 row heating coil made of Aluminium finned Copper tube, Copper header with coil section, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame in both the supply & exhaust side of AHU, fine filter section with MERV 13 filters in extruded aluminium frame in supply after fan, (Hepa filters shall be at terminals along with laminar flow plenum & not to be included in the cost), Heat Recovery Wheel with HRW Section, mixing chamber, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers, coilotron UV section only of 600 mm in length in floor mounted AHU (Coilotron UV System quantified separately). The AHU panels shall be insulated with 48mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. These AHUs shall have air inlet / outlet connection made of aluminium 20 G & all fixing arrangement / blank off shall be of SS The complete AHU shall conform to standard specication. The face velocity across cooling / heating coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows: | ||||
| 1.10 | 2400 CFM (6.0 TR ) ESP - 120 mm | 3 | Nos. | 2,13,000 ₹6,39,000 Lowest |
| 1.20 | 2000 CFM (5.0 TR ) ESP - 120 mm | 2 | Nos. | 1,73,000 ₹3,46,000 Lowest |
Tender Value
₹1.2 Cr
EMD Value
₹2.4 L
Closing Date
8 Aug 2026, 6:00 pmClosed
Executive Engineer, Medical and Health Ajmer
Office of The Executive Engineer, Medical and Health Ajmer
Construction work of Sub District Hospital Bijaynagar Distt. Beawar (H.V.A.C. Work)
2026_MEDIC_579421_10
NIT 12 of 2026-27 (EE MH Ajmer)
Open Tender
Electrical Works
Percentage
180 days
Beawar
Please refer Tender documents.
4 documents required · 4 mandatory
₹2,000
EE MH Ajmer Through NEFT/RTGS/IMPS
₹2.4 L
14 Aug 2026
30 Jul 2026
10 Aug 2026
30 Jul 2026
8 Aug 2026
30 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, installation, testing and commissioning of factory fabricated Double Skinned DX Coil Air- handling unit fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm polished SS sheet inside complete with supply & exhaust blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters for both supply & exhaust fan motor, power control panel with necessary switchgears incoming & outgoing for VFD, HRW & humidifier, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 8 row cooling & 2 row heating coil made of Aluminium finned Copper tube, Copper header with coil section, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame in both the supply & exhaust side of AHU, fine filter section with MERV 13 filters in extruded aluminium frame in supply after fan, (Hepa filters shall be at terminals along with laminar flow plenum & not to be included in the cost), Heat Recovery Wheel with HRW Section, mixing chamber, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers, coilotron UV section only of 600 mm in length in floor mounted AHU (Coilotron UV System quantified separately). The AHU panels shall be insulated with 48mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. These AHUs shall have air inlet / outlet connection made of aluminium 20 G & all fixing arrangement / blank off shall be of SS The complete AHU shall conform to standard specication. The face velocity across cooling / heating coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows: | |||||
| 1.1 | 2400 CFM (6.0 TR ) ESP - 120 mm | - | Nos. | - | - |
| 1.2 | 2000 CFM (5.0 TR ) ESP - 120 mm | - | Nos. | - | - |
stage.html
html • 0.02 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
Tendernotice_2.pdf
PDF • 2.03 MB
Tendernotice_3.pdf
PDF • 10.81 MB
Tendernotice_4.pdf
PDF • 9.16 MB
BOQ_1030018.xls
BOQ • 0.41 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .