Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.8 LAccepted-AOC | L1 | Accepted-AOC Being (L1) | |
| 2 | L2₹32.4 L+₹3.5 L (12.1%)Rejected-Finance | L2 | Rejected-Finance Other than (L1) | |
| 3 | L3₹32.5 L+₹3.5 L (12.2%)Rejected-Finance 212 B 8 PARDEWANPUR LAL BANGLA KANPUR 208007 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208007 | L3 | Rejected-Finance Other than (L1) | |
| 4 | L4₹32.7 L+₹3.7 L (12.9%)Rejected-Finance 11 82 GROUND FLOOR BLOCK 11 KALYANPURI EAST DELHI DELHI 110091 | EAST DELHI | DELHI | 110091 | L4 | Rejected-Finance Other than (L1) | |
| 5 | L5₹36.3 L+₹7.4 L (25.6%)Rejected-Finance | L5 | Rejected-Finance Other than (L1) |
Tender Value
₹39 L
EMD Value
₹78,000
Closing Date
2 Aug 2023, 6:00 pmClosed
GE (AF) E/M CHAKERI KANPUR
GE(AF)EM Chakeri, Kanpur
Repair Maint Replacement and Improvement works of LT cable joints LT OH distribution system various connections and distribution system in domestic area at AFS Kanpur
2023_MES_606063_1
8630/E8
Open Tender
Civil Works
Item Rate
180 days
Area under GE(AF) EM Chakeri
As per tender documents
9 documents required · 9 mandatory
₹500
Yes
GE (AF) E/M CHAKERI
₹78,000
Yes
25 Sept 2023
27 Jun 2023
7 Aug 2023
28 Jun 2023
2 Aug 2023
20 Jul 2023
Amount
Excavation in trenches by mechanical means, not exceeding 1.5 m wide and n. exc 1.5 m in depth for laying of cable for soft/ loose soil and getting out all as specified and directed.
Returning, filling in and including spreading, leveling, watering and well ramming in layers n. exc 25 cm in for soft/loose soil all as specified and directed.
M & L for dry Ganga Sand cushioning in trenches for protection of cable including watering and consolidation all as specified and directed. Note: Punned thickness shall be considerd for measurment purpose
M & L for well burnt brick sub class B old size laying in trenches for cable protection with width equal to length of whole brick complete all as specified and directed.
Supplying and laying un-reinforced precast concrete cable cover, class HV type- 1, flat, size 300 mm x 180 mm x 40 mm complete all as specified and as directed.
Removing of excavated surplus soil to a distance n. exc 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
M & L for cutting of PCC/Hard standing/WBM road not exceeding 45 cm in width & not exceeding 90 cm in depth for passing of cable and making good of disturbed surface to match with the existing surface complete all as specified and directed .
M & L for making horizontal boring not exe 90 cm deep below road crossing for passing of cable in GI pipe all as specified and directed.
Taking out from trenches/duct/floor/wall/roof/under road/drain or hardstanding etc. old existing underground XLPE aluminium conductor LT cable for checking the serviceability of cables and making good the disturbed surface to original position complete all as specified and directed:- Size of cable - 2 to 4 core x 10 sqmm to 16 sqmm
All as per item no. 9 above but of size 3.5/4 core x 25 sqmm to 50 sqmm.
All as per item no. 9 above but of size 3.5 core x 70 sqmm to 120 sqmm.
All as per item no. 9 above but of size 3.5 core x 150 sqmm to 240 sqmm.
All as per item no. 9 above but of size 3.5 core x 400 sqmm to 630 sqmm.
Re-laying only or fixing or passing through pipe, in Pole/duct/trench/under road/hardstanding/wall/roof etc. 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanized steel wire or tape and overall PVC sheathed old serviceable cable after rectifying of any type of faults (if any) by inspection / using equipment / meggering as required complete all as specified and directed by providing lugs/thimbles/glands by compression arrangement. Size of cable - 2 to 4 core x 10 sqmm to 16 sqmm
All as per item no. 14 above but of size 3.5/4 core x 25 sqmm to 50 sqmm.
All as per item no. 14 above but of size 3.5 core x 70 sqmm to 120 sqmm.
All as per item no. 14 above but of size 3.5 core x 150 sqmm to 240 sqmm.
All as per item no. 14 above but of size 3.5 core x 400 sqmm to 630 sqmm.
Supply Laying, testing and commissioning of LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 sq mm 2 core laid in trenches/duct / laid on wall etc. incl. suitable size lugs ,thimbles, glands, GI Nuts and bolts, washers, insulation tape etc. complete all as directed. Make :- Havells / Grandlay / Gloster
All as per item No 19 above but size 16 Sqmm 4 core
All as per item No 19 above but size 25 Sqmm 3.5 core
All as per item No 19 above but size 35 Sqmm 3.5 core
All as per item No 19 above but size 50 Sqmm 3.5 core
All as per item No 19 above but size 70 Sqmm 3.5 core
All as per item No 19 above but size 95 Sqmm 3.5 core
All as per item No 19 above but size 120 Sqmm 3.5 core
All as per item No 19 above but size 150 Sqmm 3.5 core
All as per item No 19 above but size 185 Sqmm 3.5 core
All as per item No 19 above but size 240 Sqmm 3.5 core
All as per item No 19 above but size 400 Sqmm 3.5 core
All as per item No 19 above but size 630 Sqmm 3.5 core Note for SL 19 to 31: The cable at various location shall be of varying lengths i.e. in pieces of different lengths as per requirement at site and are not necessarily to be laid in one go.
Supply and laying in trenches/Floor or fixed to Pole/Wall in replacement 40 mm bore GI pipe light grade with fitting for protection of cable including dismantling existing pipe complete all as directed. Make :- Jindal / Tata / Prakash Surya
All as per item No. 32 above but of size 50 mm bore.
All as per item No. 32 above but of size 80 mm bore.
All as per item No. 32 above but of size 100 mm bore.
M & L for detection of fault through fault locating high voltage mobile machine to locate the fault in cable by giving high voltage surge and to find out exact location of fault all as directed at site. (Note : The Item includes transportation, fuel charges, charging of machine etc. for full functioning of machine upto detecting fault at a time. It is solely bidder's responsibility to arrange fault locating machine & he should'nt expect facilitation from the dept. for the same.)
M & L for replacement of Straight through joint kit Heat shrinkable type suitable for XLPE under ground cable of size 25-50 sqmm 3.5 core all as directed. Make: Raychem / 3M / Denson
All as per item No. 37 above but of size 70-150 sqmm 3.5 core.
All as per item No. 37 above but of size 185-240 sqmm 3.5 core.
All as per item No. 37 above but of size 400-630 sqmm 3.5 core.
Earthing complete with copper earth plate electrode of size 600 mm x 600 mm x 3.15 mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.5 Mtr below normal ground level connected to copper strip 32 x 6 mm size as earthing lead incl. GI pipe of 40 mm bore complete with filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to copper strip by means of nuts, bolts and washers including chamber PCC 1 : 3 : 6 type C1 alongwith lifting handle and providing earthing indentification plate fabricated out of 1.6mm thick MS plate , duly black ground painted with two coat of black paint and writting with white paint about Earthing No.XX, Copper Earthing & Earthing test results in Ohm in appropriate letter font size. MS Plate shall be of size 0.05Sqm (Triangular / Rectangular / Ovel shape) welded with 600mm long angle iron of size 25x25x3mm , embedded in ground with PCC block (1:3:6) type C2 using 40mm graded stone aggregate, size 300x300x300mm complete all as directed. (Copper strip upto 7.5 m length and earth identification plate including grouting in ground shall be included in unit rate quoted by contractor).
Surface dressing 15 cm deep and getting out including cleaning away all grass vegetation saplings, brush wood under grouting, roots & tree and not exceeding 30 cm girth and removing rubbish to a distance of 50 mtr outside the periphery of area as directed.
Dismantling of ACSR conductor of any sizes & length and removing the same from the site all as specified and directed.
Dismantling of Earth wire of any sizes & length and removing the same from the site all as specified and directed.
Dismantling of insulators of any type, any sizes and at any location complete and removing the same from the site all as specified and directed.
Restriging of exisiting ACSR conductor / GI wire of any size / any no. conductor including opening of winding wire of ACSR conductor with insulator and winding with aluminium wire and repair of old jumper wires complete all as specified and directed.
M & L for Aluminium conductor, steel rainforced (ACSR) of existing size & length as per site requirement all as specified and as directed.
M & L for Galvanised steel wire 4 mm dia earth wire of existing size & length as per site requirement all as specified and as directed.
M & L for Pin type, porcelain, vitreous, white, brown or green insulator including galvanized mild steel spindle, two galvanazed iron washer and one galvanazed nut, 100mm height, 65mm dia 1100 Volts grade all as specified and as directed.
M & L for Shackle type, porcelain, vitreous, white, brown or green insulator including galvanized mild steel straps 31x3 mm , washers, insulator bolts 12 mm dia, 75 mm height, 90 mm dia & working pressure in 1100 volts all as specified and as directed.
M & L for erection and replacement of stay assembly (wire size 7/4 mm) with stay rod 16 mm dia & insulator loop type with nuts, bolts and washers stay wires size 7/4 mm , Flat iron clamps, Nuts, bolts and washers complete as shown on electrical plate no. 1 of SSR Part-1(1991)including necessary excavation, removal of soil, refilling of soil, PCC 1:3:6 , type C2 using 40mm graded stone aggregate work complete all as directed.
M & L for replacement of PVC Line separator suitable for 02 / 03 nos over conductor with nuts, bolts and washers all as directed.
M & L for replacement of PVC Line separator suitable for 04 / 05 nos over conductor with nuts, bolts and washers all as directed.
Cutting / trimming of tree branches and creepers which are touching of overhead lines / pole and disposal of timber complete without dismantling of ACSR conductor all as directed.
Dehydration/filteration of transformer oil of Voltage Stablizer (Servo) to achive dielectrci strength 50-70KV using centrifuging machine complete all as directed by Engineer in Charge. Note: Conducting of testing of dielectric strength of oil before and after filteration shall be done and report shall also be submitted, unit rate quoted by the contractor shall be deemed to be inclusive of this activities. Topping of oil if required shall be measured and paid seperately under respective item. While measurement of this items, SM/MES Number of Voltage Stablizer shall be entered in MB as record purpose by the concerned JE executive.
Shifting of Panel / Transformer / HT Switchgear / RMU / VCB to a distance not more than 5 Kms from power house/substation / any place to the required place, including disconnecting and necessary connection and testing after shifting complete all as directed. Note: Details of equipement shifted under this items with location from & to shall be entered in MB.
Supply and toping up transfomrer oil conforming to IS:335-1993 for Voltage stablizer (Servo) and mentaining dielectric strength to 50-70KV complete all as directed by Engineer in Charge. Note: Breakup details of top up of transformer oil with respect to capacity of oil required for transformer of voltage stablizer along with SM/MES number of Voltage stabizer shall be mentioned in MB. Make of Oil : - Power Oil/ HP/BPL/IOCL/SAVITA.
Attending complaints from Complaint Section / JE / Engr-in-charge by any mode of communication & attending the same within 4 hours like opening of connections, checking for supply, transportation of necessary tools and labour, assessing the nature of complaints, rectifying minor issues, removing carbon deposits (if any), cleaning of lugs/glands etc., meggering of cables, making temporary connections (as required), and restoring back the power supply all as directed at site. Note:- The occurance of fault if any, will be communicated to the contractor and he shall rectify the same within 4 hrs of reporting, failing to which a recovery @ Rs 500/= per complaint per day and maximum of Rs. 10,000 /= per day shall be recovered from contractor's payment. A proper date wise record of complaint attended by the contractor shall be mentained and submitted duly signed by him for verfifcation & signing of Engineer in Charge and shall submit along with claim for payments.
Supply, laying, testing and commissioning in replacement of unarmoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor twin core of size 10 sq mm laid on wall/pole etc. incl. suitable size lugs, glands, nuts and bolts, washers, insulation tape etc. complete all as directed.
M & L for replacement of Street Light Auto Timer Panel including. testing and commissioning of NATURE Switch for outdoor lighting automation using space grade sensors, micro controller suitable for outdoor use IP 55 having features Automatic Switching ON at Sunset, Automatic Switching OFF at dawn, No clock setting and time settings wide operating voltage range, high voltage trip and auto reset having specification 230 Volts, 50 Hz with all connected accessories suitable for 3 phase , 0.80KW complete all as specified and directed. Make: - Kakatiya Energy System Pvt Ltd / Bajaj / Healer.
M & L in replacement for new tubular poles 9 mtr long swaged type, 410SP-31, conforming to IS:2713(Part 1 to 3) 1980 complete with cast iron base plate, final taper plug, bolts, nuts & screws etc. including providing two coats of aluminium paint over a coat of factory applied red oxide primer and writing pole number with paint and making connections complete all as specified and directed. Note:- Excavation, earth work, concrete shall be measured and paid separately. Make of Pole along with allotted Pole number with location shall be entered in MB.
M & L for plain cement concrete (1:4:8) type D2 using 40 mm graded stone aggregate as in foundation, filling and mass concrete complete all as specified and directed.
M & L for plain cement concrete (1:2:4) type B1 using 20 mm graded stone aggregate as in coping of pole complete all as specified and directed.
S B ENTERPRISES
santosh electronics
Bharat Sales Corporation
Bluemax Associate
M/s Sohanil Construction
PAWAN COOL CORPORATION
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .