| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.0 LAccepted-AOC 25 A RR SAMY LANE KATTOOR COIMBATORE 641009 | COIMBATORE | COIMBATORE | TAMIL NADU | 641009 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹39.4 L+₹3.3 L (9.01%)Rejected-Finance | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹39.7 L+₹3.6 L (9.91%)Rejected-Finance 121004 | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | L4₹39.7 L+₹3.6 L (10.0%)Rejected-Finance NO 1A 1 SHALOM VALLUVAR STREET SIVANANDHA COLONY COIMBATORE TAMIL NADU 641 012 | COIMBATORE | TAMIL NADU | 641012 | L4 | Rejected-Finance Other than lowest bidder | |
| 5 | L5₹40.0 L+₹3.9 L (10.9%)Rejected-Finance NO 6 1 ALAGAR PERUMAL KOIL MAIN STREET VADAPALANI CHENNAI 600 026 | CHENNAI | CHENNAI | TAMIL NADU | 600026 | L5 | Rejected-Finance Other than lowest bidder |
| Sl No | Description | Qty | Unit | shalom constructions L4 | Neptune Engineers and Builders L3 | rvelectricals L1 | KUMAR AGENCIES L6 | eurekaenterprises L2 | LAKSHMI ELECTRICAL ENTERPRISES L7 | Veera Electrical L5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply installation, testing and commissioning of transformer, outdoor type step down 11/0.433 KV, HT with 3 phase and LT with 3 Phase, 4-wire system double copper wound with Off Circuit Tap Changer arrangement on HT side for a variation of secondary voltagewith tapping range + 5% to -10% in steps of 2.5 % continious rating of 500 KVA (Energy efiicent not less than Level-II) confirming to IS: 1180 (Part 1):2014 & other latest IS codes, Oil - IS: 335: 1993 including first fill of Oil,making incoming and outgoing connection to Transformer with copper conductor with lugs & glands complete, mounting on exisitng plinth complete all as specified and directed. Make ESSENAR/CG/ABB/Scheindier or any technco commercial equivalent make listed Ein C/HQ SC approved list
The quoted rates shall deemed to include the following :- | 1 | Each | 21,49,000 ₹21,49,000 | 24,00,000 ₹24,00,000 | 21,30,499 ₹21,30,499 | 23,90,000 ₹23,90,000 | 22,96,000 ₹22,96,000 | 23,70,000 ₹23,70,000 | 19,62,000 ₹19,62,000 Lowest |
| 1.10Temp. Rise in Oil [Degree C.] : as per IS, By Resistance [Degree C.] : as per IS, Ambient temperature : as per IS, Winding Material : Double wound Copper Type of Cooling : ONAN, Class of Insulation : Class “A”, Vector Group : Dyn11, Frequency [Hz.] : 50, Phase : 3, Insulation Level [kV/Kvp] H.V. : 28kV,L.V. : 3kV, Primary Connection [HV] : Delta, Primary Volts : 11000V,Primary Phases : 3 Primary Wires : 3,Primary rated current : Approx 26 Amps, Secondary Connection [LV] : Star,Secondary Volts : 433V,Secondary Phases : 3, Secondary Wires : 4, Secondary rated current : Approx 666 , Taps on Primary /Secondary Winding for : +7.5% to –7.5% in steps of 2.5%, Primary /Secondary Voltage Variation Off Circuit Tap Changer, No. of switch positions : 7 Terminal Arrangement H.V. : Bare Bushings/Cable box, L.V : Bare bushings /Cable Box, Load Losses (Level-II) At 50% Loading : As per IS in Watts (Max.) At 100% Loading : As per IS in Watts (Max.) Impedance (Z) [Percentage], HV - LV : not more than 5% No Load Current (% of Rated Current) :As per IS | ||||||||||
| 1.20Weights & Dimensions (Approx.) 1) Core & Windings with clamps (Untanking Weight) : As per IS Specifications 2) Tank & Fittings :As per IS Specifications 3) Oil :As per IS Specifications 4) Total Weight : .As per IS Specifications Overall dimensions of the transformer (mm) Length :width :As per IS Specifications Height : As per IS Specifications HV - LV Orientation : 180 deg. Bushing - as per latest IS Porcelain Bushings HV : 3 Epoxy Bushing LV : 4 Painting [Finish] : PU Light Grey Shade No. 631 – IS: 5 | ||||||||||
| 1.30TESTS - Routine Tests as per IS: 1180 (Part 1):2014 1) Ratio test 2) Polarity 3) Phase angle error measurement 4) I R Values 5) Winding resistance 6) Open circuit test 7) Short circuit & Impedance test 8) Separate source voltage test 9) Induced over voltage test 10) Vector group test 11) BDV of Oil like etc.. | ||||||||||
| 1.40STANDARD FITTINGS AND ACCESSORIES: 1) Rating & Terminal Marking Plate - One 2) Earthing Terminals- Two 3) Lifting Lugs -Two 4) Drain Valve with blanking plate - One 5) Filter Valve with blanking plate - One 6) Conservator - One 7) Conservator Oil filling hole with cap - One 8) Oil Level indicator with min. marking - One 9) Dehydrating Breather filled with silica gel- One 10) Conservator Drain Plug - One 11) Air Release Device - One 12) Thermometer Pocket - One 13) Pressure relief valve - One 14) Roller Uni directional - Four 15) Radiators As per IS 16) Bare Bushings/Cable box HV -As per IS 17) Bare Bushings/Cable box LV - As per IS 18) Separate Neutral Terminal -One 19) Off Circuit Tap Changer - One 20) thermometer - One 21) Buchholz relay-One | ||||||||||
| 1.50Note:- (i) The Studs for neutral & body shall be sufficeiently long to fix 2 Nos GI strip for earthing. (ii) Cost of Cable entry boxes/Bare bushing on both sides shall be deemed to be included in quoted rates. | ||||||||||
| 2.00 | Supply,install,commissioning and testing the following vaccum circuit breakers 11kV,3-ph 50hz,totally enclosed metal clad switch gear type tested compisite panel confirming to IS,factory made powder coated board with vaccum circuit breaker floor mounted with common bus buar complete all as specifed | 1 | Each | 7,38,000 ₹7,38,000 | 5,00,000 ₹5,00,000 Lowest | 5,65,000 ₹5,65,000 | 6,25,000 ₹6,25,000 | 6,80,000 ₹6,80,000 | 6,84,500 ₹6,84,500 | 8,10,000 ₹8,10,000 |
| 2.10(A) Incoming VCB panel eachconsisting of the following quipment-01 Nos:- (a) One No 800 Amps capacity tripple pole metal clad HT control panel totally enclosed pattern air insulated metal clad housing,floor mounting vertically isolated ,vermin proof,fully interlocked horizontal draw out type having double isolation features & control device with grounded neutral system and equipped with the following accessories. (i) One set of 3-ph 800Amps air insulated bus bar with insulated colour coating. (ii) One set of side frame for housing for circuit breakercarriege. (iii)06 Nos 800Amps isolator plugs. (iv) one 800 Amps,3 pole 350MVA repturing capacity VCB with automatic drop out and manually charged and motor operated spring closed mechanism complete with auxilary switches draw out,vaccum circuit breaker incorporating mechanical as well electricall on/off indication, mechnaical indication ON push button for emergency trip & OEM recommended trip coil shall be provided. (v) One cable box suitable for reception for cable size up to 300sqmm of 2 runs,11kv,XLPE. (vi) one set in all phases of Dual core CT of recommended capacity and ratio for metering and protection as recommended by OEM. (vii)One set of indicating LED lampsto indicate ON/OFF/Trip/Charging. (viii) one set in all phases of Dual core PT of recommended capacity and ratio for metering and protection as recommended by OEM. (ix)CT operated Ditial Ammeter,PT operated digital Volt meter scaling as recommended by OEM, Three on/off roraty selector swtich. | ||||||||||
| 2.20(x) Volt coil to trip the VCB on failure of electric supply (xi) One nurical processor relay for Over Current & Earth fault relay power, under/over voltage, directional over current ,under/over frequency,CB fault detection, VT/CT supervision, all rms measurment as recommed by OEM. (xii) Master trip electro mechanical relay, Single element high speed tripping relay with hand rest contacts. (xiii) Strip heater,thermo stator with swtich for space heating (xiv) Proviosn AC/DC voltage source required for tripping system with suitable power back up including provision of siren/horon alaram and accept switch as recommeded by OEM. (xv) Provision for charging of spring charge motor with operated voltage as recommended by OEM. (xvi) Annuiceator complete with showing type of fault,accept and reset button with OEM recommended windows. (xvii) quoted rated deemed to be inclusive of pcc foundation , coping and wahite wash etc. | ||||||||||
| 3.00 | Supply and laying in trenches/through pipes or bare in road crossings/paths/ drains/ ducts/ floors/along poles/equipments/trenches etc. Cable Under ground, cross linked poly-ethylene (XLPE) insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables with aluminium conductor, earthed,11 KV grade, of cross sectional area 185 Sqmm x 3 core laid including all necessary end terminations,all cable glands, nuts bolts as required complete all as specified. | 370 | RM | 1,735 ₹6,41,950 | 1,500 ₹5,55,000 | 1,475 ₹5,45,750 | 1,725 ₹6,38,250 | 1,300 ₹4,81,000 Lowest | 1,815 ₹6,71,550 | 1,980 ₹7,32,600 |
Tender Value
₹42.9 L
EMD Value
₹86,000
Closing Date
13 Oct 2025, 6:00 pmClosed
CWE(AF)Trivandrum
CWE AF TRIVANDRUM HQ SAC IAF Complex Akkulam Thruvikkal Post Trivandrum 11
82602/E8 Special Repair / Replacement to BER Transformers and connected E/M works at Af stn Sulur (Phase-l)
2025_MES_730927_1
82602/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Sulur
Class D Category b(ii)
7 documents required · 7 mandatory
₹500
GE (AF) Sulur
₹86,000
Yes
13 Nov 2025
15 Sept 2025
15 Oct 2025
15 Sept 2025
13 Oct 2025
29 Sept 2025
15 Sept 2025 - 23 Sept 2025
Amount
Supply installation, testing and commissioning of transformer, outdoor type step down 11/0.433 KV, HT with 3 phase and LT with 3 Phase, 4-wire system double copper wound with Off Circuit Tap Changer arrangement on HT side for a variation of secondary voltagewith tapping range + 5% to -10% in steps of 2.5 % continious rating of 500 KVA (Energy efiicent not less than Level-II) confirming to IS: 1180 (Part 1):2014 & other latest IS codes, Oil - IS: 335: 1993 including first fill of Oil,making incoming and outgoing connection to Transformer with copper conductor with lugs & glands complete, mounting on exisitng plinth complete all as specified and directed. Make ESSENAR/CG/ABB/Scheindier or any technco commercial equivalent make listed Ein C/HQ SC approved list The quoted rates shall deemed to include the following :-
Temp. Rise in Oil [Degree C.] : as per IS, By Resistance [Degree C.] : as per IS, Ambient temperature : as per IS, Winding Material : Double wound Copper Type of Cooling : ONAN, Class of Insulation : Class “A”, Vector Group : Dyn11, Frequency [Hz.] : 50, Phase : 3, Insulation Level [kV/Kvp] H.V. : 28kV,L.V. : 3kV, Primary Connection [HV] : Delta, Primary Volts : 11000V,Primary Phases : 3 Primary Wires : 3,Primary rated current : Approx 26 Amps, Secondary Connection [LV] : Star,Secondary Volts : 433V,Secondary Phases : 3, Secondary Wires : 4, Secondary rated current : Approx 666 , Taps on Primary /Secondary Winding for : +7.5% to –7.5% in steps of 2.5%, Primary /Secondary Voltage Variation Off Circuit Tap Changer, No. of switch positions : 7 Terminal Arrangement H.V. : Bare Bushings/Cable box, L.V : Bare bushings /Cable Box, Load Losses (Level-II) At 50% Loading : As per IS in Watts (Max.) At 100% Loading : As per IS in Watts (Max.) Impedance (Z) [Percentage], HV - LV : not more than 5% No Load Current (% of Rated Current) :As per IS
Weights & Dimensions (Approx.) 1) Core & Windings with clamps (Untanking Weight) : As per IS Specifications 2) Tank & Fittings :As per IS Specifications 3) Oil :As per IS Specifications 4) Total Weight : .As per IS Specifications Overall dimensions of the transformer (mm) Length :width :As per IS Specifications Height : As per IS Specifications HV - LV Orientation : 180 deg. Bushing - as per latest IS Porcelain Bushings HV : 3 Epoxy Bushing LV : 4 Painting [Finish] : PU Light Grey Shade No. 631 – IS: 5
TESTS - Routine Tests as per IS: 1180 (Part 1):2014 1) Ratio test 2) Polarity 3) Phase angle error measurement 4) I R Values 5) Winding resistance 6) Open circuit test 7) Short circuit & Impedance test 8) Separate source voltage test 9) Induced over voltage test 10) Vector group test 11) BDV of Oil like etc..
STANDARD FITTINGS AND ACCESSORIES: 1) Rating & Terminal Marking Plate - One 2) Earthing Terminals- Two 3) Lifting Lugs -Two 4) Drain Valve with blanking plate - One 5) Filter Valve with blanking plate - One 6) Conservator - One 7) Conservator Oil filling hole with cap - One 8) Oil Level indicator with min. marking - One 9) Dehydrating Breather filled with silica gel- One 10) Conservator Drain Plug - One 11) Air Release Device - One 12) Thermometer Pocket - One 13) Pressure relief valve - One 14) Roller Uni directional - Four 15) Radiators As per IS 16) Bare Bushings/Cable box HV -As per IS 17) Bare Bushings/Cable box LV - As per IS 18) Separate Neutral Terminal -One 19) Off Circuit Tap Changer - One 20) thermometer - One 21) Buchholz relay-One
Note:- (i) The Studs for neutral & body shall be sufficeiently long to fix 2 Nos GI strip for earthing. (ii) Cost of Cable entry boxes/Bare bushing on both sides shall be deemed to be included in quoted rates.
Supply,install,commissioning and testing the following vaccum circuit breakers 11kV,3-ph 50hz,totally enclosed metal clad switch gear type tested compisite panel confirming to IS,factory made powder coated board with vaccum circuit breaker floor mounted with common bus buar complete all as specifed
(x) Volt coil to trip the VCB on failure of electric supply (xi) One nurical processor relay for Over Current & Earth fault relay power, under/over voltage, directional over current ,under/over frequency,CB fault detection, VT/CT supervision, all rms measurment as recommed by OEM. (xii) Master trip electro mechanical relay, Single element high speed tripping relay with hand rest contacts. (xiii) Strip heater,thermo stator with swtich for space heating (xiv) Proviosn AC/DC voltage source required for tripping system with suitable power back up including provision of siren/horon alaram and accept switch as recommeded by OEM. (xv) Provision for charging of spring charge motor with operated voltage as recommended by OEM. (xvi) Annuiceator complete with showing type of fault,accept and reset button with OEM recommended windows. (xvii) quoted rated deemed to be inclusive of pcc foundation , coping and wahite wash etc.
Supply and laying in trenches/through pipes or bare in road crossings/paths/ drains/ ducts/ floors/along poles/equipments/trenches etc. Cable Under ground, cross linked poly-ethylene (XLPE) insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables with aluminium conductor, earthed,11 KV grade, of cross sectional area 185 Sqmm x 3 core laid including all necessary end terminations,all cable glands, nuts bolts as required complete all as specified.
Supply and laying in trenches/through pipes or bare in road crossings/paths/ drains/ ducts/ floors/along poles/equipments/trenches etc. Cable Under ground, cross linked poly-ethylene (XLPE) insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables with aluminium conductor, earthed,1.1 KV grade, of cross sectional area 240 Sqmm x 3.5 core laid including all necessary end terminations,all cable glands, nuts bolts as required complete all as specified.
Supply and installation of Earthing with Galvanised Earth Plate Electrode 600x600x 6mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, connected with Galvanised Earth Strip of size 32x6 mm (upto 7.50mm length) by means of Bolts, Nuts, Check Nuts and Washers of GI or Steel and connected Earthing Testing Point/Bus-bar including GI 40mm bore light grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt, Magneisum Sulphate (1 : 1 : 0.5) in alternate layers of not exc 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50 mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, Funnel with GI Watering Pipe 20mm bore medium grade including necessary Excavation in any type of soil, Returning, Filling and Removal of surplus Spoil disposal to out side MD land and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including taking down old unserviceable one, complete all as specified and as directed.
Note for Item No 5:- (a) All Joints should be joined by tight nut/bolts. (b) After completion of work earthing shall be tested by the contractor in presence of JE/ Engineer-in-Charge, User and proper record shall be maintained duly signed by all concerned. (c) Earth resistance tester shall be provided by the contractor. It should be caliberated from authorised company/ lab. (d) After testing if desired earth resistance of less than 5 Ohm is not obtained, the earthing will be redone at no extra cost to Govt till desired result is obtained.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop[ earthing of GI strip 32x6mm
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure
M&L Out door cable end jointing kit (Heat shrinkable) suitable for XLPE under ground aluminium conductor cable, 11 KV (Earthed) grade, of cross sectional area 185 Sqmm 3 core complete all as specified and as directed.
M&L for disconnecting all electrical mechnical connections of existing trasnformer and deposit to store yard GE AF sulur
M&L for disconnecting all electrical mechnical connections of existing VCB and deposit to store yard GE AF sulur
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr depth for foundation, laying of poles in trenches and getting out in hard/dense soil complete all as specified
Returning, filling including spreading, levelling, watering and well ramming in layers not exceeding 25 cms thick complete all as directed by Engineer-in-Charge.
Removal of surplus soil to a distance no exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtrs above from the starting point complete all as directed by Engineer-in-charge.
Riddling Sand obtained from excavation for cable protection 8cm under the cable and 15cm above the cable in trench and get the thick layer of 18cm after ramming complete all as specified and as directed.
M&L in Un-reinforced precast concrete cable cover class HV Type 1, flat size 300mm x 180 mm x 40 mm thick complete all as specified and as directed.
M&L in Un-reinforced precast concrete cable cover class Class LV, Type I, flat, size 250 mm x 150mm x 40mm thick complete all as specified and as directed.
eurekaenterprises (BID ID -3444173)
Neptune Engineers and Builders (BID ID -3442995)
shalom constructions (BID ID -3442150)
Veera Electrical (BID ID -3443697)
KUMAR AGENCIES (BID ID -3443893)
LAKSHMI ELECTRICAL ENTERPRISES (BID ID -3449437)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .