Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.7 LAccepted-Finance 49 1 ISWAR GUPTA ROAD KOLKATA 700 028 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700028 | L1 | Accepted-Finance Offer lowest bid therefore Provisional order issued | |
| 2 | L2₹14.9 L+₹1.1 L (8.14%)Rejected-Finance 28 DOCTOR LANE | L2 | Rejected-Finance that the bid is not L1 | |
| 3 | L3₹15.2 L+₹1.4 L (10.5%)Rejected-Finance 24C GOABAGAN LANE KOLKATA 700 006 | KOLKATA | KOLKATA | WEST BENGAL | 700006 | L3 | Rejected-Finance that the bid is not L1 |
Tender Value
Refer Docs
EMD Value
₹34,000
Closing Date
27 Dec 2023, 1:00 pmClosed
EEI,KNHED, PW Dte
KIT Building Annex, 4thFloor,P-16, India Exch. Place Extn., Kolkata -700073
Repair and renovation of electrical installation work for the proposed modification of seminar hall and for Air conditioning work and Other electrical installation work at IBTMIH ,Kolkata- EI Work
2023_WBPWD_603831_1
WBPWD/EE/KNHED/NIQ-103/23-24
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
Kolkata
Please refer Tender documents.
5 documents required · 5 mandatory
₹34,000
21 Mar 2024
10 Nov 2023
29 Dec 2023
21 Nov 2023
27 Dec 2023
21 Nov 2023
Amount
Dismnatling the existing LT panel and making necessary temporarry arrangement to cater electrical supply to all utilities. If required co may need to hire temporary panel,cables etc.
S & Installation of Wall mounter SMDB with MCCB as incomer with outgoing in Enclosure:SMDB 16 way Make: L & T ,TN400D, Cat:DA40AD1164CZZ0 or equivallent of ABB,Havells- 1 nos Incomer: 415 V ,4 Pole MCCB of 320A suitable for fixing in the enclosure( make: L & T D-SINE -CM94105OOQ10G or equivallent of ABB,Havells) -1 nos Spreader terminal 400 4P-1 nos (make- L &T-ST98066OOOO, equivalent ABB,Havells) Out going- a) 415 V ,3 Pole MCCB of 63A suitable for fixing in the enclosure( make: L & T -CM91612OOHOOG or equivallent of ABB,Havells) -16 nos Metering Extension Box- -1 nos (Make: L & T -CM90439OOPO, equivallent ABB, Havells) Bottom Cabling Box--1 nos (Make: L & T ,ABB Havells) Corner Box-4 nos (Make: L & T ,ABB Havells)
Supplying and fixing 415V, 63A AL Busbar in sheet steel (16SWG) enclosure with nuts bolts etc incl. powder coated painting.
Supply and providing of hiring based soundproof 75 KVA Diesel Generator with attendent
Supplying and pouring of diesel to hiring based DG time to time including carrying and storation charges.
Supplying and fixing 415V, 200 A FP, TPN on load front operated changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc [Make: L&T/ Havells/ Seimens] {1st floor}
Supplying and fixing 415V, 320A TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc [Make: L&T/ Havells/ Standard] { on New LT Panel}
Supply and installation of net guard and door arrangement with 20 mm angle iron frame of height approx. (6x4) ft. for covering of existing panel
Supplying and delivery of 1.1 KV grade armoured Alminium XLPE cable. (Make: Gloster/Havells/Polycab) 4 core 120 sqmm (For dual source arrangement to 1st floor)
4 core 240 sqmm (For DG Bypass arrangement)
Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting 4 core 120 sqmm
4 core 240 sqmm
Supply and fixing compression type glandcomplete with brass gland brass ring and rubber ring for dust and moisture proof entry of XLPE/PVC armoured cable. 4 core 120 sqmm
4 core 240 sqmm
Finishing the end of following XLPE/PVC armoured cables bycrimping method incl. supplying and fixing solderless socket(Dowels make), tapes, anticorrosive paste & jointing materials 4 core 120 sqmm
4 core 240 sqmm
Cost of labour charges for dismantling the existing E1 & mending good the damages as to GS
Cost of Refixing the existing El goods as to G.S.
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Havells/Polycab/R R Kabel) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for horizontal run & above false ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed] Avg lenght 8 Mtr.
Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Havells/Polycab/R R Kabel) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 6A 3 pin Modular type plug socket & switch (Brand approved by EIC) on 4 Module GI switch board with 3/4 Module top cover plate on wall incl. necy. connection making earthing attachment, painting and mending good damages to building works. On Board
Supply & Fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Anchor/Legrand-Myrius/Schneider), 16A Modular switch type MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.[Make: Legrand- Myrius/ Arteor]
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket with 20/25A Modular switch (Anchor/Legrand-Myrius/Schneider) type SP MCB (C-Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Anchor/Legrand-Myrius/Schneider) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Anchor/Legrand-Myrius/Schneider)with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V, 3 nos. 16 A, 3 pin Modular type plug socket with 3 nos. 16A Modular type switch (Anchor/Legrand-Myrius/Schneider), 20A Modular switch type SP MCB (C-Curve) and Indicator without plug top on 2 row 12 Module GI Modular type switch board with 2 row 12 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supplying and fixing double door 6 way Vertical TPN MCB Distribution board for 100 A MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment, including Supplying and fixing double door sheet steel (16SWG), powder coated top and bottom end box for TPN DB vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment (Make: Legrand/L&T/Siemens) Incoming: 100A, 415V, 25KA FP MCCB-1nos Out going 32A, 415V, 10KA & C curve TP MCB-6nos
Supply & foxing of 415V, 6 way Horizontal TPN Double Door MCB Power DB complete with the following accessories and two number matching cable end box inside it and the same to be fitted after concealing the wall and mending good the damages as far as praticable as to G.S (Make: Legrand/L&T/Siemens) Incoming 63A 415V, 10KA FP MCB type isolator 1nos Out going (6-32A), 240V, 10KA & C curve SP MCB-18 nos
Supplying and fixing double-doer 2+10 way SPN MCB Distribution Board with P 4243 protection fitted with 1 nos 40 A capacity DP isolator and 10 nos 6/10A capacity class curve 10KA SP MCB, concealed in wall after cutting the wall & mending good the damages to original finish inct, Inter connection with suitable sice of copper wire and neutral link & provision for earthing attachment (Make: Legrand/L&T/Siemens)
Supply & fixing of 36 watt LED full Glow High efficiency light fittings (2 ft x 2 ft) with necessary chain arrangement (Make- Philips, Cat No RC370B LED36S-6500 G6 L60W60 PSU OD S6/CG/Havells/Wipro)
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.(Legrand -Mynus/Arteor)
Supply & fixing of Single LED Tube light fitting [Make- Philips cat no. TMC 501 P 1 x T-LED Crompton cat no IGP161 LT8-16/wipro] complete with 18/20 Watt LED tube lamp Make-Philips Master LED tube model no 18W 865 T8 I 2100lm/Crompton cat no. LTTB-20/wipro) making connection as to GS
Supply and Delivery of 220V 75Watt 1200mm sweep 380 rpm ceiling fan with safety steel wire complete with all accessories (Canopy- 2 sets, shakle accessories, down rod, blades) without fan regulator. (Make:Crompton Rivera /equivalent Orient/equivalent Usha)
Supply & fixing 230V 50Hz 400mm ( 16 inch) sweep heavy duty full metal body with canopy /Decorative type wall bracket fan with all accessorieswith necy. bolts & nuts. ( Make- EPC/CG/havells )
Supply & fixing of Exhaust fans complete with all accessories having the following Model/Cat No. (Make-EPC/CG/Havells) 9'', Speed 1420 RPM
Supply & Delivery of 4 Core XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes (Make: Polycab/Habells/Gloster) 4Core 70 Sq mm
Laying of 4 core 70 sqmm XLPE cable on wall surface including S&F MS saddles with earthing attachment in 2 x 10 SWG G (Hot Dip) Wire, making hole etc as necy mending good damages and painting
Supply and fixing compression type gland For 70 sqmm 4core complete with brass gland brass ring and rubber ring for dust and moisture proof entry of XLPE/PVC armoured cable
Finishing the end of following XLPE/PVC armoured cables bycrimping method incl supplying and fixing solderless socket(Dowels make), tapes, anticorrosive paste & jointing materials For 70 sqmm 4core
Distn Wiring in 1.1 Kv gr Single core stranded FRLSH PVC insulated & unsheathed cu wire (make- Havells/Polycab/RR Kable) in 20/32/40 mm size PVC rigid conduit 'FR (precession) incl. necy Fitting as reqd. a) 2 x1.5 sqmm+ 1x 1.5sqmm for ECC for 18W LED circuler light
b) 2 x2.5 sqmm 1x 1.5sqmm for ECC
c) 2 x 4 sqmm+1x2.5 sqmm for ECC
d) 2x6 sqmm+1x4sqmm for ECC
e) 4 x16 sqmm+ 2 x 10 sqmm for ECC
f) 4x10 sqmm+ 2 x 6 sqmm for ECC
Finishing end of copper wire and PVC/AI cable of the folowing sizes by crimping 16 sqmm
Supply of 3 ph timer for controlling 1 no 3-ph AC. MC(consealed split) of size 8.5 Tr. Consisting of the following a) 14 inch X 12 inch x 6 inch -double door MS Box b) Digital Timer - (make-Siemens/L&T)- 1nos, C) 4P MCB 415V/63A-1 NO (make-Siemens/L&T). Cat no STL44327RC, e) 4 pole power cotactor of 40A rating 2 no (make-Siemens/L&T) type 1) DB locking arrangement must be there. g) 6A MCB, h) Push bottom ON/OFF switch indivisual outer side of DB (There must be bypass mechanism and indication for ON/OFF by indicating lamp of the AC m/c unit attached to it )(For double Air-Conditioner Machine)
Supply of Single-Phase timer for controlling 1 No. single-ph AC M/C (concealed split) of size 1 5/2 Tr. Consisting of the following: a) 8 way SPN DB-1 No.-Double Door(Make L&T/ Simence), b) Digital Timer, (Make) L&T)-1 nos, c) DP MCB 250V/32A-1No (Make: L&T), d) 3-pole power contactor of 40A rating-1No (Make L&T), e) DB Locking arrangement must be there of Push Bottom ON/OFF switch individual outer side of DB (There must be bypass mechanism and indication for ON/OFF by indicating Lamp of the AC m/c unit attached to it )(For Single Air Conditioner Machine)
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket ((Legrand, Myrius cat no. 3145/Crabtree), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. [for AC point)
Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (C Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. (Make: Legrand/crabtree)
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections. (make- Legrand / North-West)
Supply & fixing of indoor 18 Watt Round type LED Fittings complete on false celing with necy. Connetion asper direction of EIC.(Make: Philips cat no-DN395BLED200S-3000PSRWH/ equivalent product of Crompton/ Wipro having similar specification in all respect.)
Extra for suspension exceeding 25 cm with S&F additional 2 no 20 mm dia EI conduit (14 SWG) supports & necy PVC insulated wire and painting etc as required by 2x24/0.20 mm (1.5sqmm) flexible copper wire of 1.10 mt length.
Supplying & Fixing of RC type fan clamp of 150mm dia & 80mm depth made of 16 SWG CRCA sheet with one end duly sealed by cover, properly welded, incl. S&F 12mm dia 600mm long MS rod duly bent by heat treatment at the centre position of rod to grip fan bobbin properly, incl. binding the rod and fan box with reinforcement by 22 SWG steel binding wire, incl. supplying & covering the box with alkathene sheet, placed in order to prevent concrete from entering the box.
Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment [4 way]
S&F of 240/415 V, 63 A 4pole MCB on din rail of existing DBs & necessary connection (make- Legrand/L&T/ Seimens)
S&F SMC Loop box of dimension(280 x 170 x 130) mm with IP 67 protection ( Sintex/Hensel) make with 1no channel for 4 pole MCB installation on wall including necessary interconnection complete. (for AC ODU)
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level by ISI Medium GI pipe as to GS
Excavation of soil for installation of Earth Electrode and filling & ramming for For Morrum Soil
Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Extra for treatment of soil by using salt and charcoal for earth electrode.
Supplying & fixing of ACSR conductor for DG body and neutral earthing with necessary GI bolts, nuts, washers, spacing insulators etc. as required.
Supply and installation of DG AMF panel outer frame with GI sheet steel and 25 mm C channel angle iron frame of height approx. (8x5) ft. including in CC foundation (Proportion and dimension indicated below), having 600x600x150 mm thick CC (4:2:1) base block below sole plate/pole with hard jhama metal including CC (6:3:1) muffing 10 x 6 ft 0.30 mts. and above ground level including 3 mm thick neat cemented finish
Supplying and fixing of Isolator on din rail of existing DBs and necessary connection {Make: Legrand/L&T/Seimens/ Havells} 415V, 125A FP MCB Isolator {for relacement of existing MCBs}
Supply & Fixing of 4 module 240 V, 25A, plug socket with separate C-curve 25 A DPMCB on sheet metal switch board embedded in wall incl. S & F 4 module MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required [Make: Havells HAVELLS DBOXX PROTECTED SOCKET DHDMCSN0251025-Pk1 MCB/ equivalent make of Legrand/ Anchor/ North-West]
(Rate should be quotated including all taxes and duties and GST)
K. C. BYSACK AND SONS
ALPHA ELECTRICALS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .